- Home
- Modbus register maps
- Neptronic
- EFCB-OE1 Series networkable fan coil controller (Modbus RTU)
Thermostat / fan coil controller · Modbus register map
Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU) Modbus register map
Updated 19 November 2026
The EFCB-OE1 is the OE1 variant of Neptronic's networkable fan coil controller, used with a TFL/TDF digital room sensor on Modbus RTU (RS-485). Its holding-register map follows the EFCB layout but adds a Fan system mode, a selector-switch input option and a few extra option bits, and from 40079 on the configuration block sits one register later. The map covers readings, demands, output states, mode/fan/setpoint control and the configuration registers.
This page lists 172 Modbus registers for the Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU) — 136 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Neptronic’s own free documentation (linked below) and checked against it.
- Manufacturer
- Neptronic
- Model
- EFCB-OE1 Series networkable fan coil controller (Modbus RTU)
- Equipment type
- Thermostat / fan coil controller
- Registers
- 172 (136 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- EFCB10T-OE1, EFCB12T-OE1, EFCB10TU2-OE1, EFCB10TU4-OE1, EFCB12TU2-OE1, EFCB12TU4-OE1, EFCB1x-OE1
Integration notes: Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU)
Read holding registers with function 03 at the wire address shown in the guide's Protocol Address column (Modicon 40001 = address 0). Set the temperature unit for Modbus first, then use the mode, fan and setpoint registers for control.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 11 | Internal temperature sensor reading | UINT16 | Internal (room) temperature x100 | Read |
| HR 14 | Control temperature reading | UINT16 | Control temperature x100 | Read/write |
| HR 45 | System mode status | UINT16 | System mode | Read/write |
| HR 46 | Fan speed selection by user | UINT16 | Fan speed | Read/write |
| HR 47 | Temperature setpoint in occupancy or day mode | INT16 | Occupied setpoint x10 | Read/write |
| HR 24 | Actual heating demand | UINT16 | Heating demand | Read |
| HR 26 | Actual cooling demand | UINT16 | Cooling demand | Read |
| HR 9 | System Status 1 | BITMAP16 | Status 1 (fault, filter, changeover) | Read |
| HR 10 | System Status 2 | BITMAP16 | Status 2 (alarms) | Read |
| HR 48 | System options 1 | BITMAP16 | System options 1 (bit 1 = Modbus temp unit) | Read/write |
Enable Modbus control & writes
Modbus is the controller's native protocol; set the address (1-246) and, if needed, a fixed baud rate and parity from the device menu or registers 0-2.
Byte order & addressing
- The guide prints both the 0-based protocol address and the 40001-style notation, so there is no off-by-one guesswork.
- Baud register holds baud/100 (384 = 38400); 0 means automatic baud detection.
Network setup
- RS-485 two-wire, RTU. Supported baud rates 9600, 19200, 38400 and 57600; automatic baud detection is the default.
- Parity/stop bits come from the communication-port register: 1 = none + 2 stop, 2 = even + 1 stop, 3 = odd + 1 stop.
Watch out for
- Changing the Modbus temperature-unit bit changes the meaning of every temperature register at once.
- Some registers only apply to models with a humidity, CO2 or other optional sensor.
Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Address - Neptronic ID and Modbus address of current device | UINT16 | Read/write | |||||
| HR | 1doc 40002 | Baud rate (baud / 100) | 0 = automatic detection. | UINT16 | × 100 | Read/write | |||
| HR | 2doc 40003 | Communication port configuration | UINT16 | Read/write | 1 = No parity, 2 Stop bits; 2 = Even parity, 1 Stop bit; 3 = Odd parity, 1 Stop bit | ||||
| HR | 7doc 40008 | Product actual firmware version | UINT16 | Read | |||||
| HR | 8doc 40009 | Product actual EEPROM version | UINT16 | Read | |||||
| HR | 9doc 40010 | System Status 1 | BITMAP16 | Read | bit 0 = System operation (0 = Normal, 1 = Fault); bit 2 = System override by NSB (0 = Normal, 1 = OFF); bit 3 = Change Over Mode (0 = Cooling, 1 = Heating); bit 4 = Flow Switch Alarm (0 = No alarm,1 = Alarm activated); bit 6 = Dirty Filter Alarm (0 = No alarm,1 = Alarm activated); bit 12 = Analog Input 3 Mode (0 = Temp 10kΩ, 1 = 0-10Vdc); bit 13 = Analog Input 4 Mode (0 = Temp 10kΩ, 1 = 0-10Vdc); bit 14 = Analog Input 5 mode (0 = Temp 10kΩ, 1 = 0-10Vdc); bit 15 = Analog Input 6 Mode (0 = Temp 10kΩ, 1 = 0-10Vdc) | ||||
| HR | 10doc 40011 | System Status 2 | BITMAP16 | Read | bit 7 = Override Alarm (0 = Off, 1 = On); bit 8 = Window Opened Alarm (0 = Off, 1 = On); bit 9 = Door Opened Alarm (0 = Off, 1 = On); bit 10 = DI1 Alarm (0 = Off, 1 = On); bit 11 = DI2 Alarm (0 = Off, 1 = On); bit 13 = DI4 Alarm (0 = Off, 1 = On); bit 15 = Overheat Alarm (0 = Off, 1 = On) | ||||
| HR | 11doc 40012 | Internal temperature sensor reading | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.01 | °C / °F | Read | ||
| HR | 12doc 40013 | External temperature sensor reading | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.01 | °C / °F | Read | ||
| HR | 13doc 40014 | Changeover temperature sensor reading | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.01 | °C / °F | Read | ||
| HR | 14doc 40015 | Control temperature reading | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.01 | °C / °F | Read/write | ||
| HR | 15doc 40016 | Internal humidity sensor reading | Not on every model. | UINT16 | × 0.1 | %RH | Read | ||
| HR | 16doc 40017 | External Humidity sensor reading | Not on every model. | UINT16 | × 0.1 | %RH | Read | ||
| HR | 17doc 40018 | Analog input 3 reading | Volts or temperature, depending on how the input is configured. | INT16 | × 0.01 | V / °C / °F | Read | ||
| HR | 18doc 40019 | Analog input 4 reading | Volts or temperature, depending on how the input is configured. | INT16 | × 0.01 | V / °C / °F | Read | ||
| HR | 19doc 40020 | Analog input 5 reading | Volts or temperature, depending on how the input is configured. | INT16 | × 0.01 | V / °C / °F | Read | ||
| HR | 20doc 40021 | Analog input 6 reading | Volts or temperature, depending on how the input is configured. | INT16 | × 0.01 | V / °C / °F | Read | ||
| HR | 21doc 40022 | Digital input status of 8 digital inputs | BITMAP16 | Read | bit 0 = Digital input 1 (0 = Open, 1 = Close); bit 1 = Digital input 2 (0 = Open, 1 = Close); bit 2 = Digital input 3 (0 = Open, 1 = Close); bit 3 = Digital input 4 (0 = Open, 1 = Close); bit 4 = AI3 Digital input (0 = Open, 1 = Close); bit 5 = AI4 Digital input (0 = Open, 1 = Close); bit 6 = AI5 Digital input (0 = Open, 1 = Close); bit 7 = AI6 Digital input (0 = Open, 1 = Close) | ||||
| HR | 22doc 40023 | Actual system occupancy state | UINT16 | Read | 1 = NoOccupancy; 2 = Occupancy; 3 = Override | ||||
| HR | 23doc 40024 | Actual night setback state of the system | Not on every model. | UINT16 | Read | 1 = Day; 2 = Night; 3 = Override | |||
| HR | 24doc 40025 | Actual heating demand | UINT16 | × 0.1 | % | Read | |||
| HR | 25doc 40026 | Actual local reheat demand | UINT16 | × 0.1 | % | Read | |||
| HR | 26doc 40027 | Actual cooling demand | UINT16 | × 0.1 | % | Read | |||
| HR | 27doc 40028 | Actual changeover demand | UINT16 | × 0.1 | % | Read | |||
| HR | 28doc 40029 | Actual fan demand | UINT16 | × 0.1 | % | Read | |||
| HR | 29doc 40030 | Actual dehumidification demand | Not on every model. | UINT16 | × 0.1 | % | Read | ||
| HR | 30doc 40031 | Actual humidification demand | Not on every model. | UINT16 | × 0.1 | % | Read | ||
| HR | 31doc 40032 | Switch timer countdown until the system is able to swap the demand | UINT16 | min | Read | ||||
| HR | 32doc 40033 | Analog output 1 value | UINT16 | × 0.1 | % | Read/write | |||
| HR | 33doc 40034 | Analog output 2 value | UINT16 | × 0.1 | % | Read/write | |||
| HR | 34doc 40035 | Analog output 3 value | UINT16 | × 0.1 | % | Read/write | |||
| HR | 35doc 40036 | Analog output 4 value | UINT16 | × 0.1 | % | Read/write | |||
| HR | 36doc 40037 | Floating output 1 value | UINT16 | × 0.1 | % | Read | |||
| HR | 37doc 40038 | Floating output 2 value | UINT16 | × 0.1 | % | Read | |||
| HR | 38doc 40039 | Pulsing output 1 value | UINT16 | × 0.1 | % | Read | |||
| HR | 39doc 40040 | Pulsing output 2 value | UINT16 | × 0.1 | % | Read | |||
| HR | 40doc 40041 | Pulsing output 3 value | INT16 | × 0.1 | % | Read | |||
| HR | 41doc 40042 | Pulsing output 4 value | INT16 | × 0.1 | % | Read | |||
| HR | 42doc 40043 | TRIAC output on-off mode status | BITMAP16 | Read/write | bit 0 = On Off output 1 (0 = Off, 1 = On); bit 1 = On Off output 2 (0 = Off, 1 = On); bit 2 = On Off output 3 (0 = Off, 1 = On); bit 3 = On Off output 4 (0 = Off, 1 = On) | ||||
| HR | 43doc 40044 | Digital output - 7 relays output status | BITMAP16 | Read/write | bit 0 = Digital output 1 (0 = Open, 1 = Close); bit 1 = Digital output 2 (0 = Open, 1 = Close); bit 2 = Digital output 3 (0 = Open, 1 = Close); bit 3 = Digital output 4 (0 = Open, 1 = Close); bit 4 = FAN Output High (0 = Open, 1 = Close); bit 5 = FAN Output Med (0 = Open, 1 = Close); bit 6 = FAN Output Low (0 = Open, 1 = Close) | ||||
| HR | 44doc 40045 | System command | BITMAP16 | Read/write | bit 0 = Service Display Address (0 = Off, 1 = Display address on LCD); bit 1 = Cooling Ramp Lock (0 = Off, 1 = On); bit 2 = Condensation Alarm (0 = Off, 1 = On); bit 3 = Heating Ramp Lock (0 = Off, 1 = On); bit 4 = Reheat Ramp Lock (0 = Off, 1 = On); bit 5 = Changeover Ramp Lock (0 = Off, 1 = On); bit 7 = Humidify Ramp Lock (0 = Off, 1 = On); bit 8 = Dehumidify Ramp Lock (0 = Off, 1 = On) | ||||
| HR | 45doc 40046 | System mode status | UINT16 | Read/write | 1 = Auto; 2 = Heat; 3 = Cool; 4 = Fan; 5 = Off | ||||
| HR | 46doc 40047 | Fan speed selection by user | UINT16 | Read/write | 1 = Auto; 2 = Low; 3 = Med; 4 = High | ||||
| HR | 47doc 40048 | Temperature setpoint in occupancy or day mode | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 48doc 40049 | System options 1 | BITMAP16 | Read/write | bit 0 = Temp unit displayed on digital room sensor (0 = °C, 1 = °F); bit 1 = Temp unit displayed in Modbus (0 = °C, 1 = °F); bit 2 = Temp SetPoint Lock (0 = Off, 1 = On); bit 3 = Humidity SetPoint Lock (0 = Off, 1 = On); bit 4 = Program Mode Lock (0 = Off, 1 = On); bit 5 = Floating TO1/TO2 Direction (0 = Direct, 1 = Reverse); bit 6 = Floating TO3/TO4 Direction (0 = Direct, 1 = Reverse); bit 7 = Freeze Protection Alarm (0 = Off, 1 = On); bit 8 = User System Off Modes (0 = Enable, 1 = Disable); bit 9 = Keypad Bottom Left Lock (0 = Off, 1 = On); bit 10 = Keypad Upper Left Lock (0 = Off, 1 = On); bit 11 = Keypad Arrows Lock (0 = Off, 1 = On); bit 12 = User Fan Auto Mode (0 = Enable, 1 = Disable); bit 13 = Night SetBack Mode* (0 = Setpoint, 1 = OFF * Also applies to No Occupancy Mode); bit 14 = Humidity Control Source (0 = Intern Sensor, 1 = Extern Sensor); bit 15 = Time Mode (0 = 24h, 1 = 12h) | ||||
| HR | 49doc 40050 | System options 2 | BITMAP16 | Read/write | bit 2 = Baud Rate (0 = Auto, 1 = Manual); bit 3 = Schedule On or Off (0 = Off, 1 = On); bit 4 = Analog Output 1 Direction (0 = Direct, 1 = Reverse); bit 5 = Analog Output 2 Direction (0 = Direct, 1 = Reverse); bit 6 = Analog Output 3 Direction (0 = Direct, 1 = Reverse); bit 7 = Analog Output 4 Direction (0 = Direct, 1 = Reverse); bit 8 = TO1 Direction (0 = Direct, 1 = Reverse); bit 9 = TO2 Direction (0 = Direct, 1 = Reverse); bit 10 = TO3 Direction (0 = Direct, 1 = Reverse); bit 11 = TO4 Direction (0 = Direct, 1 = Reverse); bit 12 = Digital Output 1 Direction (0 = Direct, 1 = Reverse); bit 13 = Digital Output 2 Direction (0 = Direct, 1 = Reverse); bit 14 = Digital Output 3 Direction (0 = Direct, 1 = Reverse); bit 15 = Digital Output 4 Direction (0 = Direct, 1 = Reverse) | ||||
| HR | 50doc 40051 | System option 3 | BITMAP16 | Read/write | bit 1 = ECM Fan Enable (0 = Off, 1 = On); bit 3 = Display CO2 (0 = Off, 1 = On); bit 4 = CO2 Source Select (0 = TFL, 1 = Analog); bit 7 = Occupancy Control Source (0 = DigitalInput3, 1 = InternSensor); bit 9 = Display RH (0 = Off, 1 = On); bit 10 = User system Fan Mode (0 = Disable, 1 = Enable) | ||||
| HR | 52doc 40053 | TFL/TDF display information | UINT16 | Read/write | 1 = Temperature and Demand; 2 = Setpoint and Demand; 3 = Temperature Only; 4 = Setpoint Only; 5 = Off | ||||
| HR | 53doc 40054 | Temperature control source | UINT16 | Read/write | 1 = Network Temp; 2 = Intern Temp; 3 = Extern Temp | ||||
| HR | 54doc 40055 | Network fallback timeout Present Value | UINT16 | min | Read/write | ||||
| HR | 55doc 40056 | Minimum occupancy/day setpoint | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 56doc 40057 | Maximum occupancy/day setpoint | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 57doc 40058 | Cooling temperature setpoint in unoccupied or night mode | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 58doc 40059 | Heating temperature setpoint in unoccupied or night mode | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 59doc 40060 | Heating proportional band | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 60doc 40061 | Local reheat proportional band | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 61doc 40062 | Cooling proportional band | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 62doc 40063 | Change over proportional band | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 63doc 40064 | Heating dead band | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 64doc 40065 | Local reheat dead band | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 65doc 40066 | Cooling dead band | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 66doc 40067 | Change over dead band | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 67doc 40068 | Change over setpoint | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 68doc 40069 | Fan time out in seconds | UINT16 | s | Read/write | ||||
| HR | 69doc 40070 | Fan damping factor in seconds | UINT16 | s | Read/write | ||||
| HR | 70doc 40071 | Heating integral time factor in seconds | UINT16 | s | Read/write | ||||
| HR | 71doc 40072 | Cooling integral time factor in seconds | UINT16 | s | Read/write | ||||
| HR | 72doc 40073 | Delay between cooling and heating or vice versa | UINT16 | min | Read/write | ||||
| HR | 73doc 40074 | Cooling anticycle delay in minutes | UINT16 | min | Read/write | ||||
| HR | 74doc 40075 | NSB override delay in minutes | UINT16 | min | Read/write | ||||
| HR | 75doc 40076 | Unoccupied override delay in minutes | UINT16 | min | Read/write | ||||
| HR | 76doc 40077 | Occupancy minimum time in minutes | UINT16 | min | Read/write | ||||
| HR | 77doc 40078 | Unoccupied override delay count down in minutes | UINT16 | min | Read/write | ||||
| HR | 78doc 40079 | Fan mode (speed) in unoccupied or NSB mode | UINT16 | Read/write | 1 = Low; 2 = Med; 3 = High; 4 = Auto | ||||
| HR | 79doc 40080 | System Control mode | UINT16 | Read/write | 1 = Auto; 2 = Heat; 3 = Cool; 4 = Heat or Cool; 5 = Auto Lock | ||||
| HR | 80doc 40081 | Digital input 3 mode | UINT16 | Read/write | 1 = Off; 2 = Occupancy normally open; 3 = Occupancy normally close; 4 = NSB normally open; 5 = NSB normally close | ||||
| HR | 81doc 40082 | Override system occupancy or NSB mode | Options available depend on the DI3 mode (register 40081). | UINT16 | Read/write | 1 = Locally; 2 = OFF; 3 = Occupied; 4 = Unoccupied; 5 = Day; 6 = Night | |||
| HR | 82doc 40083 | Internal temperature sensor offset correction | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.01 | °C / °F | Read/write | ||
| HR | 83doc 40084 | External temperature sensor offset correction | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.01 | °C / °F | Read/write | ||
| HR | 84doc 40085 | Change over analog input signal | UINT16 | Read/write | 3 = Sensor; 4 = Normally Cool; 5 = Normally Heat | ||||
| HR | 85doc 40086 | Change over control mode | UINT16 | Read/write | 1 = Local; 2 = Cool; 3 = Heat | ||||
| HR | 86doc 40087 | External temperature 0-10V input on analog input | UINT16 | Read/write | 1 = Off; 2 = 2-10V; 3 = 0-10V | ||||
| HR | 87doc 40088 | Minimum analog input external temperature reading | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 88doc 40089 | Maximum analog input external temperature reading | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 89doc 40090 | Fan output signal | UINT16 | Read/write | 1 = 1 speed; 2 = 2 speeds; 3 = 3 speeds; 4 = Analog | ||||
| HR | 90doc 40091 | Ramp to control analog output 1 | UINT16 | Read/write | 1 = Off; 2 = Alarm; 3 = Changeover with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat; 8 = Humidify with fan (needs a TFLH/TDF humidity room sensor); 9 = Reserved; 10 = Cooling or Heating | ||||
| HR | 91doc 40092 | Minimum voltage for analog output 1 (volt) | UINT16 | × 0.1 | V | Read/write | |||
| HR | 92doc 40093 | Maximum voltage for analog output 1 (volt) | UINT16 | × 0.1 | V | Read/write | |||
| HR | 93doc 40094 | Ramp to control analog output 2 | UINT16 | Read/write | 1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat; 8 = Humidify with fan (needs a TFLH/TDF humidity room sensor); 9 = Reserved; 10 = Cooling or Heating | ||||
| HR | 94doc 40095 | Minimum voltage for analog output 2 (volt) | UINT16 | × 0.1 | V | Read/write | |||
| HR | 95doc 40096 | Maximum voltage for analog output 2 (volt) | UINT16 | × 0.1 | V | Read/write | |||
| HR | 96doc 40097 | Ramp to control analog output 3 | UINT16 | Read/write | 1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat; 8 = Humidify with fan (needs a TFLH/TDF humidity room sensor); 9 = Reserved; 10 = Cooling or Heating | ||||
| HR | 97doc 40098 | Minimum voltage for analog output 3 (volt) | UINT16 | × 0.1 | V | Read/write | |||
| HR | 98doc 40099 | Maximum voltage for analog output 3 (volt) | UINT16 | × 0.1 | V | Read/write | |||
| HR | 99doc 40100 | Ramp to control analog output 4 | UINT16 | Read/write | 1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat; 8 = Humidify with fan (needs a TFLH/TDF humidity room sensor); 9 = Fan; 10 = Cooling or Heating | ||||
| HR | 100doc 40101 | Minimum voltage for analog output 4 (volt) | UINT16 | × 0.1 | V | Read/write | |||
| HR | 101doc 40102 | Maximum voltage for analog output 4 (volt) | UINT16 | × 0.1 | V | Read/write | |||
| HR | 102doc 40103 | Timing of floating motor TO1-TO2 in seconds | UINT16 | s | Read/write | ||||
| HR | 103doc 40104 | Timing of floating motor TO3-TO4 in seconds | UINT16 | s | Read/write | ||||
| HR | 104doc 40105 | Ramp to control TRIAC output 1 | UINT16 | Read/write | 1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat | ||||
| HR | 105doc 40106 | Signal output configuration for TRIAC output 1 | UINT16 | Read/write | 1 = Pulsing mode; 2 = On/Off mode; 3 = Floating mode | ||||
| HR | 106doc 40107 | TRIAC output 1 when set to close | UINT16 | % | Read/write | ||||
| HR | 107doc 40108 | TRIAC output 1 when set to open | UINT16 | % | Read/write | ||||
| HR | 108doc 40109 | Ramp to control TRIAC output 2 | UINT16 | Read/write | 1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat | ||||
| HR | 109doc 40110 | Signal output configuration for TRIAC output 2 | UINT16 | Read/write | 1 = Pulsing mode; 2 = On/Off mode; 3 = Floating mode | ||||
| HR | 110doc 40111 | TRIAC output 2 when set to close | UINT16 | % | Read/write | ||||
| HR | 111doc 40112 | TRIAC output 2 when set to open | UINT16 | % | Read/write | ||||
| HR | 112doc 40113 | Ramp to control TRIAC output 3 | UINT16 | Read/write | 1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat | ||||
| HR | 113doc 40114 | Signal output configuration for TRIAC output 3 | UINT16 | Read/write | 1 = Pulsing mode; 2 = On/Off mode; 3 = Floating mode | ||||
| HR | 114doc 40115 | TRIAC output 3 when set to close | UINT16 | % | Read/write | ||||
| HR | 115doc 40116 | TRIAC output 3 when set to open | UINT16 | % | Read/write | ||||
| HR | 116doc 40117 | Ramp to control TRIAC output 4 | UINT16 | Read/write | 1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat | ||||
| HR | 117doc 40118 | Signal output configuration for TRIAC output 4 | UINT16 | Read/write | 1 = Pulsing mode; 2 = On/Off mode; 3 = Floating mode | ||||
| HR | 118doc 40119 | TRIAC output 4 when set to close | UINT16 | % | Read/write | ||||
| HR | 119doc 40120 | TRIAC output 4 when set to open | UINT16 | % | Read/write | ||||
| HR | 120doc 40121 | Configuration of DO1 mode | UINT16 | Read/write | 1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat; 8 = Humidify with fan (needs a TFLH/TDF humidity room sensor) | ||||
| HR | 121doc 40122 | Delay before activation of DO1 in minutes | UINT16 | min | Read/write | ||||
| HR | 122doc 40123 | Close position percentage for contact DO1 | UINT16 | % | Read/write | ||||
| HR | 123doc 40124 | Open position percentage for contact DO1 | UINT16 | % | Read/write | ||||
| HR | 124doc 40125 | Configuration of DO2 mode | UINT16 | Read/write | 1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat; 8 = Humidify with fan (needs a TFLH/TDF humidity room sensor) | ||||
| HR | 125doc 40126 | Activation delay for contact DO2 in minutes | UINT16 | min | Read/write | ||||
| HR | 126doc 40127 | Close position percentage for contact DO2 | UINT16 | % | Read/write | ||||
| HR | 127doc 40128 | Open position percentage for contact DO2 | UINT16 | % | Read/write | ||||
| HR | 128doc 40129 | Configuration of DO3 mode | UINT16 | Read/write | 1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat; 8 = Humidify with fan (needs a TFLH/TDF humidity room sensor) | ||||
| HR | 129doc 40130 | Activation delay for contact DO3 in minutes | UINT16 | min | Read/write | ||||
| HR | 130doc 40131 | Close position percentage for contact DO3 | UINT16 | % | Read/write | ||||
| HR | 131doc 40132 | Open position percentage for contact DO3 | UINT16 | % | Read/write | ||||
| HR | 132doc 40133 | Configuration of DO4 mode | UINT16 | Read/write | 1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat; 8 = Humidify with fan (needs a TFLH/TDF humidity room sensor) | ||||
| HR | 133doc 40134 | Activation delay for contact DO4 in minutes | UINT16 | min | Read/write | ||||
| HR | 134doc 40135 | Close position percentage for contact DO4 | UINT16 | % | Read/write | ||||
| HR | 135doc 40136 | Open position percentage for contact DO4 | UINT16 | % | Read/write | ||||
| HR | 136doc 40137 | Digital input contact of DI1 to DI4 | BITMAP16 | Read/write | bit 0 = Digital input 1 (0 = Normally Open, 1 = Normally Close); bit 1 = Digital input 2 (0 = Normally Open,1 = Normally Close); bit 2 = Digital input 3 (0 = Normally Open,1 = Normally Close); bit 4 = Digital input 4 (0 = Normally Open,1 = Normally Close) | ||||
| HR | 137doc 40138 | Configuration of DI1 mode | UINT16 | Read/write | 1 = OFF; 2 = Override; 3 = Window; 4 = Door; 5 = DirtyFilter; 6 = FlowSwitch; 7 = OverHeat; 8 = Selector switch (use together with a flow switch; fan stays off in local mode) | ||||
| HR | 138doc 40139 | Delay before activation of DI1 in minutes | UINT16 | min | Read/write | ||||
| HR | 139doc 40140 | Configuration of DI2 mode | UINT16 | Read/write | 1 = OFF; 2 = Override; 3 = Window; 4 = Door; 5 = DirtyFilter; 6 = FlowSwitch; 7 = OverHeat; 8 = Selector switch (use together with a flow switch; fan stays off in local mode) | ||||
| HR | 140doc 40141 | Delay before activation of DI2 in minutes | UINT16 | min | Read/write | ||||
| HR | 141doc 40142 | Configuration of DI4 mode | UINT16 | Read/write | 1 = OFF; 2 = Override; 3 = Window; 4 = Door; 5 = DirtyFilter; 6 = FlowSwitch; 7 = OverHeat; 8 = Selector switch (use together with a flow switch; fan stays off in local mode) | ||||
| HR | 142doc 40143 | Delay before activation of DI4 in minutes | UINT16 | min | Read/write | ||||
| HR | 143doc 40144 | Humidity control mode status | Not on every model. | UINT16 | Read/write | 1 = Auto; 2 = Dehumidification; 3 = Humidification; 4 = Off | |||
| HR | 144doc 40145 | Humidity setpoint (%RH) in occupancy or day mode | Not on every model. | UINT16 | × 0.1 | %RH | Read/write | ||
| HR | 145doc 40146 | Dehumidification setpoint (%RH) in unoccupied or night mode | Not on every model. | UINT16 | × 0.1 | %RH | Read/write | ||
| HR | 146doc 40147 | Humidification setpoint (%RH) in unoccupied or night mode | Not on every model. | UINT16 | × 0.1 | %RH | Read/write | ||
| HR | 147doc 40148 | Minimum user setpoint | Not on every model. | UINT16 | × 0.1 | %RH | Read/write | ||
| HR | 148doc 40149 | Maximum user setpoint | Not on every model. | UINT16 | × 0.1 | %RH | Read/write | ||
| HR | 149doc 40150 | Humidity proportional band | Not on every model. | UINT16 | × 0.1 | %RH | Read/write | ||
| HR | 150doc 40151 | Humidity deadband | Not on every model. | UINT16 | × 0.1 | %RH | Read/write | ||
| HR | 151doc 40152 | Internal humidity sensor offset correction | Not on every model. | INT16 | × 0.1 | %RH | Read/write | ||
| HR | 152doc 40153 | External humidity sensor offset correction | Not on every model. | INT16 | × 0.1 | %RH | Read/write | ||
| HR | 153doc 40154 | Internal CO2 sensor reading | Not on every model. | UINT16 | ppm | Read | |||
| HR | 154doc 40155 | Maximum limit of CO2 concentration | Not on every model. | UINT16 | × 0.1 | ppm | Read/write | ||
| HR | 155doc 40156 | System status 3 | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 156doc 40157 | Maximum range for the CO2 sensor | Not on every model. | UINT16 | × 0.02 | ppm | Read/write | ||
| HR | 157doc 40158 | External CO2 sensor reading | Not on every model. | UINT16 | ppm | Read | |||
| HR | 158doc 40159 | Internal light sensor reading in Luxes | Not on every model. | UINT16 | lx | Read | |||
| HR | 159doc 40160 | Internal PIR sensor reading | Not on every model. | UINT16 | Read | 0 = No Occupancy; 1 = Occupancy | |||
| HR | 160doc 40161 | Internal VOC sensor reading in ppb | Not on every model. | UINT16 | ppb | Read | |||
| HR | 161doc 40162 | Configuration of AI3 mode | UINT16 | Read/write | 1 = Off; 2 = Temperature; 3 = CO2; 4 = Humidity | ||||
| HR | 162doc 40163 | Configuration of AI4 mode | UINT16 | Read/write | 1 = Off; 2 = Temperature; 3 = CO2; 4 = Humidity | ||||
| HR | 163doc 40164 | Configuration of AI5 mode | UINT16 | Read/write | 1 = Off; 2 = Temperature; 3 = CO2; 4 = Humidity | ||||
| HR | 164doc 40165 | Configuration of AI6 mode | UINT16 | Read/write | 1 = Off; 2 = Temperature; 3 = CO2; 4 = Humidity | ||||
| HR | 165doc 40166 | Configuration of TO1 alarm source | UINT16 | Read/write | 1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2 | ||||
| HR | 166doc 40167 | Configuration of TO2 alarm source | UINT16 | Read/write | 1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2 | ||||
| HR | 167doc 40168 | Configuration of TO3 alarm source | UINT16 | Read/write | 1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2 | ||||
| HR | 168doc 40169 | Configuration of TO4 alarm source | UINT16 | Read/write | 1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2 | ||||
| HR | 169doc 40170 | Configuration of AO1 alarm source | UINT16 | Read/write | 1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2 | ||||
| HR | 170doc 40171 | Configuration of AO2 alarm source | UINT16 | Read/write | 1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2 | ||||
| HR | 171doc 40172 | Configuration of AO3 alarm source | UINT16 | Read/write | 1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2 | ||||
| HR | 172doc 40173 | Configuration of AO4 alarm source | UINT16 | Read/write | 1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2 | ||||
| HR | 173doc 40174 | Configuration of DO1 alarm source | UINT16 | Read/write | 1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2 | ||||
| HR | 174doc 40175 | Configuration of DO2 alarm source | UINT16 | Read/write | 1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2 | ||||
| HR | 175doc 40176 | Configuration of DO3 alarm source | UINT16 | Read/write | 1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2 | ||||
| HR | 176doc 40177 | Configuration of DO4 alarm source | UINT16 | Read/write | 1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2 |
Notes on this map
- Every register is a 16-bit holding register (function 03 to read, 06 or 16 to write); there are no 32-bit values.
- Temperatures, setpoints, bands and offsets are reported in °C or °F according to the "temperature unit in Modbus" bit of the system-options register; scaling is x100 for sensor readings and offsets and x10 for setpoints and bands, as listed per register.
- Register 0 packs the Neptronic product ID in the high byte and the Modbus address in the low byte.
- Left out: the four product-name registers (two ASCII characters each, byte order not spelled out) and every register the guide marks Reserved.
- Do not reuse an EFCB (non-OE1) register list on this unit: from 40079 onward the two maps are offset by one register.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU)
What Modbus registers does the Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU) have?
This map lists 172 registers: 172 holding registers. 136 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row prints both the protocol (wire) address, starting at 0, and the 40001-style notation; e.g. 40046 is protocol address 45. The documented field holds the 4xxxx notation.
What are the minimum Modbus registers to integrate the Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU)?
Start with HR 11 Internal temperature sensor reading (Internal (room) temperature x100); HR 14 Control temperature reading (Control temperature x100); HR 45 System mode status (System mode); HR 46 Fan speed selection by user (Fan speed); HR 47 Temperature setpoint in occupancy or day mode (Occupied setpoint x10); HR 24 Actual heating demand (Heating demand); HR 26 Actual cooling demand (Cooling demand); HR 9 System Status 1 (Status 1 (fault, filter, changeover)); HR 10 System Status 2 (Status 2 (alarms)); HR 48 System options 1 (System options 1 (bit 1 = Modbus temp unit)).
How do I enable Modbus control of the Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU)?
Modbus is the controller's native protocol; set the address (1-246) and, if needed, a fixed baud rate and parity from the device menu or registers 0-2.
Where is the official Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU) Modbus documentation?
The source is EFCB-OE1 Series Modbus Communication Module User Guide (EFCB1x-OE1-Modbus Guide (V2.16)-260626), published free by Neptronic at https://www.neptronic.com/controls/PDF/2026/EFCB1x-OE1-Modbus%20Guide%20(V2.16)-260626.pdf.
More Neptronic Modbus register maps
- Thermostat / room controller (temperature, humidity, CO2, VOC)
Neptronic AROB series universal room controller (Modbus communication module)
Neptronic AROB24T / AROB24TH / AROB24TGH / AROB24TGVH universal room controllers with the Modbus module, ARO Modbus Guide_170824.
Also known as: AROB, AROB24T, AROB24TH, AROB24TGH, AROB24TGVH, ARO - Air handler (compact make-up air unit)
Neptronic CMU compact make-up air unit (Modbus communication module)
Neptronic CMU compact make-up air units with the Modbus communication module, guide CMU-Modbus Guide-211125.
Also known as: Compact Make-up Air Unit, Neptronic CMU, CMU Series - Thermostat / fan coil controller
Neptronic EFCB Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB Series fan coil controllers (24, 120 and 240 Vac; 2 or 4 relays) with the Modbus communication module, guide EFCB-Modbus Guide-260626.
Also known as: EFCB10TU2, EFCB10TU4, EFCB11TU2, EFCB11TU4, EFCB12TU2, EFCB12TU4, EFCB fan coil controller - Air handler terminal (dual-duct VAV controller)
Neptronic EVCBM dual-duct VAV controller (Modbus communication module)
Neptronic EVCBM dual-duct VAV controllers (master + slave airflow) with the Modbus module, guide EVCBM Dual Duct-V500-Modbus Guide-180927-ESA.
Also known as: EVCBM Dual Duct, EVCB, Neptronic EVCBM Modbus - Air handler humidifier (electric steam)
Neptronic SKE4 electric steam humidifier (Modbus communication module)
Neptronic SKE4 series electric steam humidifiers with the Modbus communication module, guide SKE4-Modbus Guide-240531 (V2.07).
Also known as: SKE4-E, SKE4-N, SKE4 Steam Humidifier, Neptronic SKE4 Modbus - Air handler humidifier (gas-fired steam)
Neptronic SKG4 gas-fired steam humidifier (Modbus communication module)
Neptronic SKG4 series gas-fired steam humidifiers (one to four burner modules) with the Modbus communication module, guide SKG4-Modbus Guide-221114 (V2.04).
Also known as: SKG4-E, SKG4-N, SKG4 Gas Fired Humidifier, Neptronic SKG4 Modbus - Air handler humidifier (high-pressure atomizer)
Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module)
Neptronic SKH4 high-pressure atomizers with the Modbus communication module, guide SKH4-Modbus Guide-240126 (V.1.00).
Also known as: SKH4, SKH4 High-Pressure Atomizer, Neptronic SKH4 Modbus - Pump / water treatment unit (reverse osmosis for humidifiers)
Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module)
Neptronic SKRO reverse osmosis water treatment units with the Modbus communication module, guide SKRO-Modbus Guide-250913 (V1.0).
Also known as: SKRO, SKRO Water Treatment Unit, Neptronic SKRO Modbus - Air handler humidifier (steam-to-steam)
Neptronic SKS4 steam-to-steam humidifier (Modbus communication module)
Neptronic SKS4 series steam-to-steam humidifiers with the Modbus communication module, guide SKS4-Modbus Guide-220509 (V2.03).
Also known as: SKS4-E, SKS4-N, SKS4 Steam to Steam Humidifier, Neptronic SKS4 Modbus - Air handler evaporative cooler (adiabatic cooling / humidification)
Neptronic SKVF evaporative cooler / humidifier (Modbus communication module)
Neptronic SKVF series evaporative coolers with the Modbus communication module, guide SKVF-Modbus Guide-211025.
Also known as: SKVF Evaporative Cooler, SKVF Series, Neptronic SKVF Modbus - Thermostat / fan coil and unitary controller
Neptronic TSUB Series universal wall-mount controller (Modbus RTU)
Neptronic TSUB Series universal wall-mount controllers with Modbus, guide TSUB-Modbus Guide-250829 (V1.13).
Also known as: TSUB Series, TSUB universal wall-mount controller - Thermostat / heat pump and unitary controller
Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU)
Neptronic TUCB24C6X2 (temperature) and TUHB24C6X2 (temperature and humidity) universal wall-mount controllers with 6 binary and 2 analog outputs, guide TUXB-Modbus Guide-190515.
Also known as: TUCB24C6X2, TUHB24C6X2, TUCB, TUHB, TUXB - Thermostat / heat pump and unitary controller
Neptronic TUUB Series universal wall-mount controller (Modbus RTU)
Neptronic TUUB Series universal wall-mount controllers with Modbus, guide TUUB-Modbus Guide-250829 (V1.13).
Also known as: TUUB Series, TUUB universal wall-mount controller
Other hvac equipment register maps
- Thermostat / room controller (chilled beam with supply and extract air dampers)
Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU)
Swegon CONDUCTOR W3 room controller, software 1.38 and later (technical manual updated 2015-06-15).
Also known as: CONDUCTOR RE W3, Conductor W3 - Air handler (in-row computer room cooling unit)
Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus)
Liebert CRV row-based cooling units (DX and chilled water) on the iCOM v4 controller with a Liebert IntelliSlot Modbus 485 or Modbus IP card.
Also known as: Liebert CRV, CRV, Liebert CRV iCOM - Air handler (in-row self-contained DX cooling unit)
APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit
APC by Schneider Electric InRow SC (ACSC 100 series) self-contained cooling units, per register map part number 990-3027D.
Also known as: ACSC100, InRow SC, InRow ACSC - Rooftop unit
Daikin Applied Rebel / Rebel Applied rooftop (MicroTech 4 controller)
Daikin Applied Rebel Applied (DPSA, R-410A/R-32) and Rebel (DPS, R-32) packaged rooftops with MicroTech 4 controller and Modbus RTU module, per ED 19133-2 (Oct 2025).
Also known as: DPSA, DPS, Rebel Applied, Rebel, MicroTech 4 rooftop, ED 19133-2 - Air handler
Flexit Nordic residential air handling unit (Flexit GO, built-in Modbus)
Flexit NORDIC series residential ventilation units with Flexit GO control and built-in Modbus RTU (cable harness 116405), per the 'Modbus Nordic Basic' register sheet and instruction 117989-01 (2020-01). Not EcoNordic, which has its own register sheet.
Also known as: Nordic S2, Nordic S3, Nordic S4, Nordic CL2, Nordic CL3, Nordic CL4, Flexit GO, Modbus Nordic Basic, 117989 - Thermostat (fan coil)
Johnson Controls T7000 series fan coil thermostat (Modbus RTU)
Johnson Controls T7000 series Modbus thermostats listed in the data table: T7600-TF21, T7601-TF20 (ECM fan), T7600-TF20 (relay), T7603-T000 (single-stage heating) and T7600-TB21 (with AI); data table revision 2.4 (2019-12-23).
Also known as: T7600-TF21-9JS0, T7601-TF20-9JS0, T7600-TF20-9JS0, T7603-T000-9JF0, T7600-TF21-1JS0, T7601-TF20-1JS0, T7600-TF20-1JS0, T7603-T000-1JF0, T7600-TB21-9JA0, T7600, T7601, T7603
All hvac equipment Modbus register maps →
Source: EFCB-OE1 Series Modbus Communication Module User Guide · EFCB1x-OE1-Modbus Guide (V2.16)-260626. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.