Thermostat / fan coil controller · Modbus register map

Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The EFCB-OE1 is the OE1 variant of Neptronic's networkable fan coil controller, used with a TFL/TDF digital room sensor on Modbus RTU (RS-485). Its holding-register map follows the EFCB layout but adds a Fan system mode, a selector-switch input option and a few extra option bits, and from 40079 on the configuration block sits one register later. The map covers readings, demands, output states, mode/fan/setpoint control and the configuration registers.

This page lists 172 Modbus registers for the Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU) — 136 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Neptronic’s own free documentation (linked below) and checked against it.

Manufacturer
Neptronic
Model
EFCB-OE1 Series networkable fan coil controller (Modbus RTU)
Equipment type
Thermostat / fan coil controller
Registers
172 (136 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
EFCB10T-OE1, EFCB12T-OE1, EFCB10TU2-OE1, EFCB10TU4-OE1, EFCB12TU2-OE1, EFCB12TU4-OE1, EFCB1x-OE1
Source document
EFCB-OE1 Series Modbus Communication Module User Guide · EFCB1x-OE1-Modbus Guide (V2.16)-260626
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU)

Integration in brief

Read holding registers with function 03 at the wire address shown in the guide's Protocol Address column (Modicon 40001 = address 0). Set the temperature unit for Modbus first, then use the mode, fan and setpoint registers for control.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 11Internal temperature sensor readingUINT16Internal (room) temperature x100Read
HR 14Control temperature readingUINT16Control temperature x100Read/write
HR 45System mode statusUINT16System modeRead/write
HR 46Fan speed selection by userUINT16Fan speedRead/write
HR 47Temperature setpoint in occupancy or day modeINT16Occupied setpoint x10Read/write
HR 24Actual heating demandUINT16Heating demandRead
HR 26Actual cooling demandUINT16Cooling demandRead
HR 9System Status 1BITMAP16Status 1 (fault, filter, changeover)Read
HR 10System Status 2BITMAP16Status 2 (alarms)Read
HR 48System options 1BITMAP16System options 1 (bit 1 = Modbus temp unit)Read/write

Enable Modbus control & writes

Modbus is the controller's native protocol; set the address (1-246) and, if needed, a fixed baud rate and parity from the device menu or registers 0-2.

Byte order & addressing

Network setup

Watch out for

Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

172 of 172 shown
Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001Address - Neptronic ID and Modbus address of current deviceUINT16Read/write
HR1doc 40002Baud rate (baud / 100)0 = automatic detection.UINT16× 100Read/write
HR2doc 40003Communication port configurationUINT16Read/write1 = No parity, 2 Stop bits; 2 = Even parity, 1 Stop bit; 3 = Odd parity, 1 Stop bit
HR7doc 40008Product actual firmware versionUINT16Read
HR8doc 40009Product actual EEPROM versionUINT16Read
HR9doc 40010System Status 1BITMAP16Readbit 0 = System operation (0 = Normal, 1 = Fault); bit 2 = System override by NSB (0 = Normal, 1 = OFF); bit 3 = Change Over Mode (0 = Cooling, 1 = Heating); bit 4 = Flow Switch Alarm (0 = No alarm,1 = Alarm activated); bit 6 = Dirty Filter Alarm (0 = No alarm,1 = Alarm activated); bit 12 = Analog Input 3 Mode (0 = Temp 10kΩ, 1 = 0-10Vdc); bit 13 = Analog Input 4 Mode (0 = Temp 10kΩ, 1 = 0-10Vdc); bit 14 = Analog Input 5 mode (0 = Temp 10kΩ, 1 = 0-10Vdc); bit 15 = Analog Input 6 Mode (0 = Temp 10kΩ, 1 = 0-10Vdc)
HR10doc 40011System Status 2BITMAP16Readbit 7 = Override Alarm (0 = Off, 1 = On); bit 8 = Window Opened Alarm (0 = Off, 1 = On); bit 9 = Door Opened Alarm (0 = Off, 1 = On); bit 10 = DI1 Alarm (0 = Off, 1 = On); bit 11 = DI2 Alarm (0 = Off, 1 = On); bit 13 = DI4 Alarm (0 = Off, 1 = On); bit 15 = Overheat Alarm (0 = Off, 1 = On)
HR11doc 40012Internal temperature sensor readingUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.01°C / °FRead
HR12doc 40013External temperature sensor readingUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.01°C / °FRead
HR13doc 40014Changeover temperature sensor readingUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.01°C / °FRead
HR14doc 40015Control temperature readingUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.01°C / °FRead/write
HR15doc 40016Internal humidity sensor readingNot on every model.UINT16× 0.1%RHRead
HR16doc 40017External Humidity sensor readingNot on every model.UINT16× 0.1%RHRead
HR17doc 40018Analog input 3 readingVolts or temperature, depending on how the input is configured.INT16× 0.01V / °C / °FRead
HR18doc 40019Analog input 4 readingVolts or temperature, depending on how the input is configured.INT16× 0.01V / °C / °FRead
HR19doc 40020Analog input 5 readingVolts or temperature, depending on how the input is configured.INT16× 0.01V / °C / °FRead
HR20doc 40021Analog input 6 readingVolts or temperature, depending on how the input is configured.INT16× 0.01V / °C / °FRead
HR21doc 40022Digital input status of 8 digital inputsBITMAP16Readbit 0 = Digital input 1 (0 = Open, 1 = Close); bit 1 = Digital input 2 (0 = Open, 1 = Close); bit 2 = Digital input 3 (0 = Open, 1 = Close); bit 3 = Digital input 4 (0 = Open, 1 = Close); bit 4 = AI3 Digital input (0 = Open, 1 = Close); bit 5 = AI4 Digital input (0 = Open, 1 = Close); bit 6 = AI5 Digital input (0 = Open, 1 = Close); bit 7 = AI6 Digital input (0 = Open, 1 = Close)
HR22doc 40023Actual system occupancy stateUINT16Read1 = NoOccupancy; 2 = Occupancy; 3 = Override
HR23doc 40024Actual night setback state of the systemNot on every model.UINT16Read1 = Day; 2 = Night; 3 = Override
HR24doc 40025Actual heating demandUINT16× 0.1%Read
HR25doc 40026Actual local reheat demandUINT16× 0.1%Read
HR26doc 40027Actual cooling demandUINT16× 0.1%Read
HR27doc 40028Actual changeover demandUINT16× 0.1%Read
HR28doc 40029Actual fan demandUINT16× 0.1%Read
HR29doc 40030Actual dehumidification demandNot on every model.UINT16× 0.1%Read
HR30doc 40031Actual humidification demandNot on every model.UINT16× 0.1%Read
HR31doc 40032Switch timer countdown until the system is able to swap the demandUINT16minRead
HR32doc 40033Analog output 1 valueUINT16× 0.1%Read/write
HR33doc 40034Analog output 2 valueUINT16× 0.1%Read/write
HR34doc 40035Analog output 3 valueUINT16× 0.1%Read/write
HR35doc 40036Analog output 4 valueUINT16× 0.1%Read/write
HR36doc 40037Floating output 1 valueUINT16× 0.1%Read
HR37doc 40038Floating output 2 valueUINT16× 0.1%Read
HR38doc 40039Pulsing output 1 valueUINT16× 0.1%Read
HR39doc 40040Pulsing output 2 valueUINT16× 0.1%Read
HR40doc 40041Pulsing output 3 valueINT16× 0.1%Read
HR41doc 40042Pulsing output 4 valueINT16× 0.1%Read
HR42doc 40043TRIAC output on-off mode statusBITMAP16Read/writebit 0 = On Off output 1 (0 = Off, 1 = On); bit 1 = On Off output 2 (0 = Off, 1 = On); bit 2 = On Off output 3 (0 = Off, 1 = On); bit 3 = On Off output 4 (0 = Off, 1 = On)
HR43doc 40044Digital output - 7 relays output statusBITMAP16Read/writebit 0 = Digital output 1 (0 = Open, 1 = Close); bit 1 = Digital output 2 (0 = Open, 1 = Close); bit 2 = Digital output 3 (0 = Open, 1 = Close); bit 3 = Digital output 4 (0 = Open, 1 = Close); bit 4 = FAN Output High (0 = Open, 1 = Close); bit 5 = FAN Output Med (0 = Open, 1 = Close); bit 6 = FAN Output Low (0 = Open, 1 = Close)
HR44doc 40045System commandBITMAP16Read/writebit 0 = Service Display Address (0 = Off, 1 = Display address on LCD); bit 1 = Cooling Ramp Lock (0 = Off, 1 = On); bit 2 = Condensation Alarm (0 = Off, 1 = On); bit 3 = Heating Ramp Lock (0 = Off, 1 = On); bit 4 = Reheat Ramp Lock (0 = Off, 1 = On); bit 5 = Changeover Ramp Lock (0 = Off, 1 = On); bit 7 = Humidify Ramp Lock (0 = Off, 1 = On); bit 8 = Dehumidify Ramp Lock (0 = Off, 1 = On)
HR45doc 40046System mode statusUINT16Read/write1 = Auto; 2 = Heat; 3 = Cool; 4 = Fan; 5 = Off
HR46doc 40047Fan speed selection by userUINT16Read/write1 = Auto; 2 = Low; 3 = Med; 4 = High
HR47doc 40048Temperature setpoint in occupancy or day modeUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR48doc 40049System options 1BITMAP16Read/writebit 0 = Temp unit displayed on digital room sensor (0 = °C, 1 = °F); bit 1 = Temp unit displayed in Modbus (0 = °C, 1 = °F); bit 2 = Temp SetPoint Lock (0 = Off, 1 = On); bit 3 = Humidity SetPoint Lock (0 = Off, 1 = On); bit 4 = Program Mode Lock (0 = Off, 1 = On); bit 5 = Floating TO1/TO2 Direction (0 = Direct, 1 = Reverse); bit 6 = Floating TO3/TO4 Direction (0 = Direct, 1 = Reverse); bit 7 = Freeze Protection Alarm (0 = Off, 1 = On); bit 8 = User System Off Modes (0 = Enable, 1 = Disable); bit 9 = Keypad Bottom Left Lock (0 = Off, 1 = On); bit 10 = Keypad Upper Left Lock (0 = Off, 1 = On); bit 11 = Keypad Arrows Lock (0 = Off, 1 = On); bit 12 = User Fan Auto Mode (0 = Enable, 1 = Disable); bit 13 = Night SetBack Mode* (0 = Setpoint, 1 = OFF * Also applies to No Occupancy Mode); bit 14 = Humidity Control Source (0 = Intern Sensor, 1 = Extern Sensor); bit 15 = Time Mode (0 = 24h, 1 = 12h)
HR49doc 40050System options 2BITMAP16Read/writebit 2 = Baud Rate (0 = Auto, 1 = Manual); bit 3 = Schedule On or Off (0 = Off, 1 = On); bit 4 = Analog Output 1 Direction (0 = Direct, 1 = Reverse); bit 5 = Analog Output 2 Direction (0 = Direct, 1 = Reverse); bit 6 = Analog Output 3 Direction (0 = Direct, 1 = Reverse); bit 7 = Analog Output 4 Direction (0 = Direct, 1 = Reverse); bit 8 = TO1 Direction (0 = Direct, 1 = Reverse); bit 9 = TO2 Direction (0 = Direct, 1 = Reverse); bit 10 = TO3 Direction (0 = Direct, 1 = Reverse); bit 11 = TO4 Direction (0 = Direct, 1 = Reverse); bit 12 = Digital Output 1 Direction (0 = Direct, 1 = Reverse); bit 13 = Digital Output 2 Direction (0 = Direct, 1 = Reverse); bit 14 = Digital Output 3 Direction (0 = Direct, 1 = Reverse); bit 15 = Digital Output 4 Direction (0 = Direct, 1 = Reverse)
HR50doc 40051System option 3BITMAP16Read/writebit 1 = ECM Fan Enable (0 = Off, 1 = On); bit 3 = Display CO2 (0 = Off, 1 = On); bit 4 = CO2 Source Select (0 = TFL, 1 = Analog); bit 7 = Occupancy Control Source (0 = DigitalInput3, 1 = InternSensor); bit 9 = Display RH (0 = Off, 1 = On); bit 10 = User system Fan Mode (0 = Disable, 1 = Enable)
HR52doc 40053TFL/TDF display informationUINT16Read/write1 = Temperature and Demand; 2 = Setpoint and Demand; 3 = Temperature Only; 4 = Setpoint Only; 5 = Off
HR53doc 40054Temperature control sourceUINT16Read/write1 = Network Temp; 2 = Intern Temp; 3 = Extern Temp
HR54doc 40055Network fallback timeout Present ValueUINT16minRead/write
HR55doc 40056Minimum occupancy/day setpointUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR56doc 40057Maximum occupancy/day setpointUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR57doc 40058Cooling temperature setpoint in unoccupied or night modeUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR58doc 40059Heating temperature setpoint in unoccupied or night modeUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR59doc 40060Heating proportional bandUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR60doc 40061Local reheat proportional bandUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR61doc 40062Cooling proportional bandUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR62doc 40063Change over proportional bandUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR63doc 40064Heating dead bandUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR64doc 40065Local reheat dead bandUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR65doc 40066Cooling dead bandUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR66doc 40067Change over dead bandUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR67doc 40068Change over setpointUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR68doc 40069Fan time out in secondsUINT16sRead/write
HR69doc 40070Fan damping factor in secondsUINT16sRead/write
HR70doc 40071Heating integral time factor in secondsUINT16sRead/write
HR71doc 40072Cooling integral time factor in secondsUINT16sRead/write
HR72doc 40073Delay between cooling and heating or vice versaUINT16minRead/write
HR73doc 40074Cooling anticycle delay in minutesUINT16minRead/write
HR74doc 40075NSB override delay in minutesUINT16minRead/write
HR75doc 40076Unoccupied override delay in minutesUINT16minRead/write
HR76doc 40077Occupancy minimum time in minutesUINT16minRead/write
HR77doc 40078Unoccupied override delay count down in minutesUINT16minRead/write
HR78doc 40079Fan mode (speed) in unoccupied or NSB modeUINT16Read/write1 = Low; 2 = Med; 3 = High; 4 = Auto
HR79doc 40080System Control modeUINT16Read/write1 = Auto; 2 = Heat; 3 = Cool; 4 = Heat or Cool; 5 = Auto Lock
HR80doc 40081Digital input 3 modeUINT16Read/write1 = Off; 2 = Occupancy normally open; 3 = Occupancy normally close; 4 = NSB normally open; 5 = NSB normally close
HR81doc 40082Override system occupancy or NSB modeOptions available depend on the DI3 mode (register 40081).UINT16Read/write1 = Locally; 2 = OFF; 3 = Occupied; 4 = Unoccupied; 5 = Day; 6 = Night
HR82doc 40083Internal temperature sensor offset correctionUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.01°C / °FRead/write
HR83doc 40084External temperature sensor offset correctionUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.01°C / °FRead/write
HR84doc 40085Change over analog input signalUINT16Read/write3 = Sensor; 4 = Normally Cool; 5 = Normally Heat
HR85doc 40086Change over control modeUINT16Read/write1 = Local; 2 = Cool; 3 = Heat
HR86doc 40087External temperature 0-10V input on analog inputUINT16Read/write1 = Off; 2 = 2-10V; 3 = 0-10V
HR87doc 40088Minimum analog input external temperature readingUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR88doc 40089Maximum analog input external temperature readingUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR89doc 40090Fan output signalUINT16Read/write1 = 1 speed; 2 = 2 speeds; 3 = 3 speeds; 4 = Analog
HR90doc 40091Ramp to control analog output 1UINT16Read/write1 = Off; 2 = Alarm; 3 = Changeover with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat; 8 = Humidify with fan (needs a TFLH/TDF humidity room sensor); 9 = Reserved; 10 = Cooling or Heating
HR91doc 40092Minimum voltage for analog output 1 (volt)UINT16× 0.1VRead/write
HR92doc 40093Maximum voltage for analog output 1 (volt)UINT16× 0.1VRead/write
HR93doc 40094Ramp to control analog output 2UINT16Read/write1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat; 8 = Humidify with fan (needs a TFLH/TDF humidity room sensor); 9 = Reserved; 10 = Cooling or Heating
HR94doc 40095Minimum voltage for analog output 2 (volt)UINT16× 0.1VRead/write
HR95doc 40096Maximum voltage for analog output 2 (volt)UINT16× 0.1VRead/write
HR96doc 40097Ramp to control analog output 3UINT16Read/write1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat; 8 = Humidify with fan (needs a TFLH/TDF humidity room sensor); 9 = Reserved; 10 = Cooling or Heating
HR97doc 40098Minimum voltage for analog output 3 (volt)UINT16× 0.1VRead/write
HR98doc 40099Maximum voltage for analog output 3 (volt)UINT16× 0.1VRead/write
HR99doc 40100Ramp to control analog output 4UINT16Read/write1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat; 8 = Humidify with fan (needs a TFLH/TDF humidity room sensor); 9 = Fan; 10 = Cooling or Heating
HR100doc 40101Minimum voltage for analog output 4 (volt)UINT16× 0.1VRead/write
HR101doc 40102Maximum voltage for analog output 4 (volt)UINT16× 0.1VRead/write
HR102doc 40103Timing of floating motor TO1-TO2 in secondsUINT16sRead/write
HR103doc 40104Timing of floating motor TO3-TO4 in secondsUINT16sRead/write
HR104doc 40105Ramp to control TRIAC output 1UINT16Read/write1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat
HR105doc 40106Signal output configuration for TRIAC output 1UINT16Read/write1 = Pulsing mode; 2 = On/Off mode; 3 = Floating mode
HR106doc 40107TRIAC output 1 when set to closeUINT16%Read/write
HR107doc 40108TRIAC output 1 when set to openUINT16%Read/write
HR108doc 40109Ramp to control TRIAC output 2UINT16Read/write1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat
HR109doc 40110Signal output configuration for TRIAC output 2UINT16Read/write1 = Pulsing mode; 2 = On/Off mode; 3 = Floating mode
HR110doc 40111TRIAC output 2 when set to closeUINT16%Read/write
HR111doc 40112TRIAC output 2 when set to openUINT16%Read/write
HR112doc 40113Ramp to control TRIAC output 3UINT16Read/write1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat
HR113doc 40114Signal output configuration for TRIAC output 3UINT16Read/write1 = Pulsing mode; 2 = On/Off mode; 3 = Floating mode
HR114doc 40115TRIAC output 3 when set to closeUINT16%Read/write
HR115doc 40116TRIAC output 3 when set to openUINT16%Read/write
HR116doc 40117Ramp to control TRIAC output 4UINT16Read/write1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat
HR117doc 40118Signal output configuration for TRIAC output 4UINT16Read/write1 = Pulsing mode; 2 = On/Off mode; 3 = Floating mode
HR118doc 40119TRIAC output 4 when set to closeUINT16%Read/write
HR119doc 40120TRIAC output 4 when set to openUINT16%Read/write
HR120doc 40121Configuration of DO1 modeUINT16Read/write1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat; 8 = Humidify with fan (needs a TFLH/TDF humidity room sensor)
HR121doc 40122Delay before activation of DO1 in minutesUINT16minRead/write
HR122doc 40123Close position percentage for contact DO1UINT16%Read/write
HR123doc 40124Open position percentage for contact DO1UINT16%Read/write
HR124doc 40125Configuration of DO2 modeUINT16Read/write1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat; 8 = Humidify with fan (needs a TFLH/TDF humidity room sensor)
HR125doc 40126Activation delay for contact DO2 in minutesUINT16minRead/write
HR126doc 40127Close position percentage for contact DO2UINT16%Read/write
HR127doc 40128Open position percentage for contact DO2UINT16%Read/write
HR128doc 40129Configuration of DO3 modeUINT16Read/write1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat; 8 = Humidify with fan (needs a TFLH/TDF humidity room sensor)
HR129doc 40130Activation delay for contact DO3 in minutesUINT16minRead/write
HR130doc 40131Close position percentage for contact DO3UINT16%Read/write
HR131doc 40132Open position percentage for contact DO3UINT16%Read/write
HR132doc 40133Configuration of DO4 modeUINT16Read/write1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat; 8 = Humidify with fan (needs a TFLH/TDF humidity room sensor)
HR133doc 40134Activation delay for contact DO4 in minutesUINT16minRead/write
HR134doc 40135Close position percentage for contact DO4UINT16%Read/write
HR135doc 40136Open position percentage for contact DO4UINT16%Read/write
HR136doc 40137Digital input contact of DI1 to DI4BITMAP16Read/writebit 0 = Digital input 1 (0 = Normally Open, 1 = Normally Close); bit 1 = Digital input 2 (0 = Normally Open,1 = Normally Close); bit 2 = Digital input 3 (0 = Normally Open,1 = Normally Close); bit 4 = Digital input 4 (0 = Normally Open,1 = Normally Close)
HR137doc 40138Configuration of DI1 modeUINT16Read/write1 = OFF; 2 = Override; 3 = Window; 4 = Door; 5 = DirtyFilter; 6 = FlowSwitch; 7 = OverHeat; 8 = Selector switch (use together with a flow switch; fan stays off in local mode)
HR138doc 40139Delay before activation of DI1 in minutesUINT16minRead/write
HR139doc 40140Configuration of DI2 modeUINT16Read/write1 = OFF; 2 = Override; 3 = Window; 4 = Door; 5 = DirtyFilter; 6 = FlowSwitch; 7 = OverHeat; 8 = Selector switch (use together with a flow switch; fan stays off in local mode)
HR140doc 40141Delay before activation of DI2 in minutesUINT16minRead/write
HR141doc 40142Configuration of DI4 modeUINT16Read/write1 = OFF; 2 = Override; 3 = Window; 4 = Door; 5 = DirtyFilter; 6 = FlowSwitch; 7 = OverHeat; 8 = Selector switch (use together with a flow switch; fan stays off in local mode)
HR142doc 40143Delay before activation of DI4 in minutesUINT16minRead/write
HR143doc 40144Humidity control mode statusNot on every model.UINT16Read/write1 = Auto; 2 = Dehumidification; 3 = Humidification; 4 = Off
HR144doc 40145Humidity setpoint (%RH) in occupancy or day modeNot on every model.UINT16× 0.1%RHRead/write
HR145doc 40146Dehumidification setpoint (%RH) in unoccupied or night modeNot on every model.UINT16× 0.1%RHRead/write
HR146doc 40147Humidification setpoint (%RH) in unoccupied or night modeNot on every model.UINT16× 0.1%RHRead/write
HR147doc 40148Minimum user setpointNot on every model.UINT16× 0.1%RHRead/write
HR148doc 40149Maximum user setpointNot on every model.UINT16× 0.1%RHRead/write
HR149doc 40150Humidity proportional bandNot on every model.UINT16× 0.1%RHRead/write
HR150doc 40151Humidity deadbandNot on every model.UINT16× 0.1%RHRead/write
HR151doc 40152Internal humidity sensor offset correctionNot on every model.INT16× 0.1%RHRead/write
HR152doc 40153External humidity sensor offset correctionNot on every model.INT16× 0.1%RHRead/write
HR153doc 40154Internal CO2 sensor readingNot on every model.UINT16ppmRead
HR154doc 40155Maximum limit of CO2 concentrationNot on every model.UINT16× 0.1ppmRead/write
HR155doc 40156System status 3UINT16Read0 = Off; 1 = On
HR156doc 40157Maximum range for the CO2 sensorNot on every model.UINT16× 0.02ppmRead/write
HR157doc 40158External CO2 sensor readingNot on every model.UINT16ppmRead
HR158doc 40159Internal light sensor reading in LuxesNot on every model.UINT16lxRead
HR159doc 40160Internal PIR sensor readingNot on every model.UINT16Read0 = No Occupancy; 1 = Occupancy
HR160doc 40161Internal VOC sensor reading in ppbNot on every model.UINT16ppbRead
HR161doc 40162Configuration of AI3 modeUINT16Read/write1 = Off; 2 = Temperature; 3 = CO2; 4 = Humidity
HR162doc 40163Configuration of AI4 modeUINT16Read/write1 = Off; 2 = Temperature; 3 = CO2; 4 = Humidity
HR163doc 40164Configuration of AI5 modeUINT16Read/write1 = Off; 2 = Temperature; 3 = CO2; 4 = Humidity
HR164doc 40165Configuration of AI6 modeUINT16Read/write1 = Off; 2 = Temperature; 3 = CO2; 4 = Humidity
HR165doc 40166Configuration of TO1 alarm sourceUINT16Read/write1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2
HR166doc 40167Configuration of TO2 alarm sourceUINT16Read/write1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2
HR167doc 40168Configuration of TO3 alarm sourceUINT16Read/write1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2
HR168doc 40169Configuration of TO4 alarm sourceUINT16Read/write1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2
HR169doc 40170Configuration of AO1 alarm sourceUINT16Read/write1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2
HR170doc 40171Configuration of AO2 alarm sourceUINT16Read/write1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2
HR171doc 40172Configuration of AO3 alarm sourceUINT16Read/write1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2
HR172doc 40173Configuration of AO4 alarm sourceUINT16Read/write1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2
HR173doc 40174Configuration of DO1 alarm sourceUINT16Read/write1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2
HR174doc 40175Configuration of DO2 alarm sourceUINT16Read/write1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2
HR175doc 40176Configuration of DO3 alarm sourceUINT16Read/write1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2
HR176doc 40177Configuration of DO4 alarm sourceUINT16Read/write1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU)

What Modbus registers does the Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU) have?

This map lists 172 registers: 172 holding registers. 136 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row prints both the protocol (wire) address, starting at 0, and the 40001-style notation; e.g. 40046 is protocol address 45. The documented field holds the 4xxxx notation.

What are the minimum Modbus registers to integrate the Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU)?

Start with HR 11 Internal temperature sensor reading (Internal (room) temperature x100); HR 14 Control temperature reading (Control temperature x100); HR 45 System mode status (System mode); HR 46 Fan speed selection by user (Fan speed); HR 47 Temperature setpoint in occupancy or day mode (Occupied setpoint x10); HR 24 Actual heating demand (Heating demand); HR 26 Actual cooling demand (Cooling demand); HR 9 System Status 1 (Status 1 (fault, filter, changeover)); HR 10 System Status 2 (Status 2 (alarms)); HR 48 System options 1 (System options 1 (bit 1 = Modbus temp unit)).

How do I enable Modbus control of the Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU)?

Modbus is the controller's native protocol; set the address (1-246) and, if needed, a fixed baud rate and parity from the device menu or registers 0-2.

Where is the official Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU) Modbus documentation?

The source is EFCB-OE1 Series Modbus Communication Module User Guide (EFCB1x-OE1-Modbus Guide (V2.16)-260626), published free by Neptronic at https://www.neptronic.com/controls/PDF/2026/EFCB1x-OE1-Modbus%20Guide%20(V2.16)-260626.pdf.