Air handler (in-row self-contained DX cooling unit) · Modbus register map

APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit Modbus register map

Updated 19 November 2026

Short answer

The InRow SC (ACSC 100 series) is a self-contained DX in-row cooling unit. It answers Modbus RTU and Modbus TCP with all data in holding registers, readable with function 03 or 04. This map covers unit start/stop, setpoints, air and refrigerant temperatures and pressures, fan speeds, run hours, group settings and the one-register fault flags.

This page lists 119 Modbus registers for the APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit — 32 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from APC (Schneider Electric)’s own free documentation (linked below) and checked against it.

Manufacturer
APC (Schneider Electric)
Model
InRow ACSC 100 Series self-contained DX cooling unit
Equipment type
Air handler (in-row self-contained DX cooling unit)
Registers
119 (32 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
ACSC100, InRow SC, InRow ACSC
Source document
Modbus Register Map: InRow ACSC 100 Series · 990-3027D
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit

Integration in brief

Poll holding registers with function 03 or 04: OVERALL_STATUS and OPERATE_MODE at 0 and 87, then the 32-bit temperatures from 88 upward in tenths of a degree F, and the fault flags from 256 to 299. Write UNIT_CTRL at 7 to start or stop the unit.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Overall statusUINT16Overall alarm severityRead
HR 87Operate modeUINT16Unit operating modeRead
HR 7Unit ctrlUINT16Unit on / standby commandRead/write
HR 1Cool setpointINT32 ABCDCooling setpointRead/write
HR 92Rack inlet tempINT32 ABCDRack inlet temperatureRead
HR 94Supply tempINT32 ABCDSupply air temperatureRead
HR 96Return tempINT32 ABCDReturn air temperatureRead
HR 259Cool failUINT16Cooling failure alarmRead
HR 272Water detectedUINT16Water detected alarmRead

Enable Modbus control & writes

The register map does not describe how to enable Modbus or set the network parameters.

Byte order & addressing

Network setup

Watch out for

APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

119 of 119 shown
APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 0000h (0)Overall statusWorst active alarm severity for the unit.UINT16Read0 = No Alarm; 2 = Informational; 4 = Warning; 8 = Critical
HR1doc 0001h (1)Cool setpointCooling setpoint for this unit.INT32ABCD× 0.1°FRead/write
HR3doc 0003h (3)Supply air setpointSupply air temperature setpoint.INT32ABCD× 0.1°FRead/write
HR5doc 0005h (5)Configuration typeUINT16Read/write0 = RACS; 1 = Spot; 2 = In-Row
HR6doc 0006h (6)Fan speed preferenceUINT16Read/write0 = Low; 1 = Med-Low; 2 = Med; 3 = Med-High; 4 = High
HR7doc 0007h (7)Unit ctrlStart (On) or stop (Standby) the unit.UINT16Read/write0 = Standby; 1 = On
HR8doc 0008h (8)Capacity ctrlCompressor capacity control method.UINT16Read/write0 = Discrete (Disc); 1 = Proportional (Prop)
HR9doc 0009h (9)Cool deadbandINT32ABCD× 0.1°FRead/write
HR11doc 000Bh (11)Unit nameSTRING[42]Read/write
HR32doc 0020h (32)Unit locationSTRING[42]Read/write
HR53doc 0035h (53)Model numSTRING[20]Read
HR63doc 003Fh (63)Serial numSTRING[20]Read
HR73doc 0049h (73)Firmware revSTRING[8]Read
HR77doc 004Dh (77)Hardware revSTRING[8]Read
HR81doc 0051h (81)Date of manufactureSTRING[12]Read
HR87doc 0057h (87)Operate modeCurrent unit state.UINT16Read0 = Standby; 1 = On; 2 = Idle
HR88doc 0058h (88)Unit cool outputCooling delivered by this unit.INT32ABCD× 0.1kWRead
HR90doc 005Ah (90)Unit cool demandCooling requested from this unit.INT32ABCD× 0.1kWRead
HR92doc 005Ch (92)Rack inlet tempRack inlet air temperature.INT32ABCD× 0.1°FRead
HR94doc 005Eh (94)Supply tempAir temperature leaving the unit.INT32ABCD× 0.1°FRead
HR96doc 0060h (96)Return tempAir temperature entering the unit.INT32ABCD× 0.1°FRead
HR98doc 0062h (98)Cond outlet tempCondenser air outlet temperature.INT32ABCD× 0.1°FRead
HR100doc 0064h (100)Cond inlet tempCondenser air inlet temperature.INT32ABCD× 0.1°FRead
HR102doc 0066h (102)Unit air flowINT32ABCDCFMRead
HR104doc 0068h (104)Evaporator fan speedINT32ABCD× 0.1%Read
HR106doc 006Ah (106)Suction tempINT32ABCD× 0.1°FRead
HR108doc 006Ch (108)SuperheatSuction superheat.INT32ABCD× 0.1°FRead
HR110doc 006Eh (110)Condenser fan speedINT32ABCD× 0.1%Read
HR112doc 0070h (112)Filter dpINT32ABCD× 0.01in W.C.Read
HR114doc 0072h (114)Containment dpINT32ABCD× 0.01in W.C.Read
HR116doc 0074h (116)Suction pressureRefrigerant suction pressure.INT32ABCDpsiRead
HR118doc 0076h (118)Discharge pressureRefrigerant discharge pressure.INT32ABCDpsiRead
HR120doc 0078h (120)Air filter runhourINT32ABCDhRead
HR122doc 007Ah (122)Evaporator fan 1 runhourINT32ABCDhRead
HR124doc 007Ch (124)Evaporator fan 2 runhourINT32ABCDhRead
HR126doc 007Eh (126)Evaporator fan 3 runhourINT32ABCDhRead
HR128doc 0080h (128)Compressor runhourINT32ABCDhRead
HR130doc 0082h (130)Condenser fan runhourCondenser fan run hours (first of three rows with this name).INT32ABCDhRead
HR136doc 0088h (136)Fan left pwrsp runhourINT32ABCDhRead
HR138doc 008Ah (138)Fan right pwrsp runhourINT32ABCDhRead
HR140doc 008Ch (140)Conds pump runhourINT32ABCDhRead
HR142doc 008Eh (142)Air filter serv intINT32ABCDweeksRead/write
HR144doc 0090h (144)Air filter serv int alarmUINT16Read/write0 = Enable; 1 = Disable
HR145doc 0091h (145)Rack temp high threshINT32ABCD× 0.1°FRead/write
HR147doc 0093h (147)Sply air temp high threshINT32ABCD× 0.1°FRead/write
HR149doc 0095h (149)Rtn air temp high threshINT32ABCD× 0.1°FRead/write
HR151doc 0097h (151)AltitudeINT32ABCDftRead/write
HR153doc 0099h (153)Startup delayINT32ABCDsRead/write
HR155doc 009Bh (155)Idle on leakUINT16Read/write0 = Yes; 1 = No
HR156doc 009Ch (156)Input normalUINT16Read/write0 = Open; 1 = Closed
HR157doc 009Dh (157)Input stateUINT16Read0 = Open; 1 = Closed
HR158doc 009Eh (158)Output normalUINT16Read/write0 = Open; 1 = Closed
HR159doc 009Fh (159)Output stateUINT16Read0 = Open; 1 = Closed
HR160doc 00A0h (160)Output sourceWhich alarms drive the output relay.UINT16Read/write0 = Any Alarm; 1 = Only Critical Alarms
HR161doc 00A1h (161)Compressor stateCompressor running or not.UINT16Read0 = Off; 1 = On
HR200doc 00C8h (200)Number of cooling unitsINT32ABCDRead/write
HR202doc 00CAh (202)Group cool setpointINT32ABCD× 0.1°FRead/write
HR204doc 00CCh (204)Group supply air setpointINT32ABCD× 0.1°FRead/write
HR206doc 00CEh (206)Group configuration typeUINT16Read/write0 = RACS; 1 = Spot; 2 = In-Row
HR207doc 00CFh (207)Group fan speed preferenceUINT16Read/write0 = Low; 1 = Med-Low; 2 = Med; 3 = Med-High; 4 = High
HR208doc 00D0h (208)Group capacity ctrlUINT16Read/write0 = Discrete (Disc); 1 = Proportional (Prop)
HR209doc 00D1h (209)Group fan speed ctrlUINT16Read/write0 = Automatic; 1 = Manual
HR210doc 00D2h (210)Group cool deadbandINT32ABCD× 0.1°FRead/write
HR212doc 00D4h (212)Group altitudeINT32ABCDftRead/write
HR214doc 00D6h (214)Group rack inlet max tempINT32ABCD× 0.1°FRead
HR216doc 00D8h (216)Group rack inlet min tempINT32ABCD× 0.1°FRead
HR218doc 00DAh (218)Group return air max tempINT32ABCD× 0.1°FRead
HR220doc 00DCh (220)Group return air min tempINT32ABCD× 0.1°FRead
HR222doc 00DEh (222)Group cooling demandINT32ABCD× 0.1kWRead
HR224doc 00E0h (224)Group cooling actualINT32ABCD× 0.1kWRead
HR226doc 00E2h (226)Group airflow demandINT32ABCDCFMRead
HR228doc 00E4h (228)Num active flow controllersINT32ABCDRead/write
HR230doc 00E6h (230)Active flow control biasUINT16Read/write0 = Positive; 1 = Slightly Positive; 2 = Zero; 3 = Slightly Negative; 4 = Negative
HR231doc 00E7h (231)Active flow control statusUINT16Read0 = Under; 1 = Okay; 2 = Over; 3 = N/A
HR232doc 00E8h (232)Active flow control lamp testUINT16Read/write0 = Disable; 1 = Enable
HR256doc 0100h (256)Internal comm faultUINT16Read0 = Clear; 1 = Alarm
HR257doc 0101h (257)Alink isolation relay faultUINT16Read0 = Clear; 1 = Alarm
HR258doc 0102h (258)External communication faultUINT16Read0 = Clear; 1 = Alarm
HR259doc 0103h (259)Cool failUINT16Read0 = Clear; 1 = Alarm
HR260doc 0104h (260)High rack tempUINT16Read0 = Clear; 1 = Alarm
HR261doc 0105h (261)Air filter cloggedUINT16Read0 = Clear; 1 = Alarm
HR262doc 0106h (262)Rtn air sensor faultUINT16Read0 = Clear; 1 = Alarm
HR263doc 0107h (263)Upper rtn air sensor faultUINT16Read0 = Clear; 1 = Alarm
HR264doc 0108h (264)Sply air sensor faultUINT16Read0 = Clear; 1 = Alarm
HR265doc 0109h (265)Upper sply air sensor faultUINT16Read0 = Clear; 1 = Alarm
HR266doc 010Ah (266)Rack temp sensor faultUINT16Read0 = Clear; 1 = Alarm
HR267doc 010Bh (267)High discharge pressureUINT16Read0 = Clear; 1 = Alarm
HR268doc 010Ch (268)Low suction pressureUINT16Read0 = Clear; 1 = Alarm
HR269doc 010Dh (269)Evaporator fan 1 faultUINT16Read0 = Clear; 1 = Alarm
HR270doc 010Eh (270)Evaporator fan 2 faultUINT16Read0 = Clear; 1 = Alarm
HR271doc 010Fh (271)Evaporator fan 3 faultUINT16Read0 = Clear; 1 = Alarm
HR272doc 0110h (272)Water detectedUINT16Read0 = Clear; 1 = Alarm
HR273doc 0111h (273)Check condensate management faultUINT16Read0 = Clear; 1 = Alarm
HR274doc 0112h (274)Conds pan fullUINT16Read0 = Clear; 1 = Alarm
HR275doc 0113h (275)Fan pwrsp left faultUINT16Read0 = Clear; 1 = Alarm
HR276doc 0114h (276)Fan pwrsp right faultUINT16Read0 = Clear; 1 = Alarm
HR277doc 0115h (277)Air filter runhour violationUINT16Read0 = Clear; 1 = Alarm
HR278doc 0116h (278)Condenser fan 1 faultUINT16Read0 = Clear; 1 = Alarm
HR279doc 0117h (279)Condenser fan 2 faultUINT16Read0 = Clear; 1 = Alarm
HR280doc 0118h (280)Condenser fan 3 faultUINT16Read0 = Clear; 1 = Alarm
HR281doc 0119h (281)Supply high temp faultUINT16Read0 = Clear; 1 = Alarm
HR282doc 011Ah (282)Return high temp faultUINT16Read0 = Clear; 1 = Alarm
HR283doc 011Bh (283)Filter dp sensor faultUINT16Read0 = Clear; 1 = Alarm
HR284doc 011Ch (284)Containment dp sensor faultUINT16Read0 = Clear; 1 = Alarm
HR285doc 011Dh (285)Suction temp sensor faultUINT16Read0 = Clear; 1 = Alarm
HR286doc 011Eh (286)Suction pressure sensor faultUINT16Read0 = Clear; 1 = Alarm
HR287doc 011Fh (287)Disch press sensor faultUINT16Read0 = Clear; 1 = Alarm
HR288doc 0120h (288)Containment dp high faultUINT16Read0 = Clear; 1 = Alarm
HR289doc 0121h (289)Input contact faultUINT16Read0 = Clear; 1 = Alarm
HR290doc 0122h (290)High discharge pressure faultUINT16Read0 = Clear; 1 = Alarm
HR291doc 0123h (291)Low suction pressure faultUINT16Read0 = Clear; 1 = Alarm
HR292doc 0124h (292)Start low suction pressureUINT16Read0 = Clear; 1 = Alarm
HR293doc 0125h (293)Start line pressure imbalanceUINT16Read0 = Clear; 1 = Alarm
HR294doc 0126h (294)Group comm faultUINT16Read0 = Clear; 1 = Alarm
HR295doc 0127h (295)Leak detected shutdownUINT16Read0 = Clear; 1 = Alarm
HR296doc 0128h (296)Ecoaisle door open faultUINT16Read0 = Clear; 1 = Alarm
HR297doc 0129h (297)Num of active flow controllers faultUINT16Read0 = Clear; 1 = Alarm
HR298doc 012Ah (298)Insufficient airflow faultUINT16Read0 = Clear; 1 = Alarm
HR299doc 012Bh (299)Active flow controller sensor faultUINT16Read0 = Clear; 1 = Alarm

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit

What Modbus registers does the APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit have?

This map lists 119 registers: 119 holding registers. 32 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table gives absolute addresses in hex and decimal. Note 11 says absolute address 0 equals Modicon register 40001 and is address zero on the wire, so the decimal column is the wire address as printed.

What byte order does the APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit?

Start with HR 0 Overall status (Overall alarm severity); HR 87 Operate mode (Unit operating mode); HR 7 Unit ctrl (Unit on / standby command); HR 1 Cool setpoint (Cooling setpoint); HR 92 Rack inlet temp (Rack inlet temperature); HR 94 Supply temp (Supply air temperature); HR 96 Return temp (Return air temperature); HR 259 Cool fail (Cooling failure alarm); HR 272 Water detected (Water detected alarm).

How do I enable Modbus control of the APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit?

The register map does not describe how to enable Modbus or set the network parameters.

Where is the official APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit Modbus documentation?

The source is Modbus Register Map: InRow ACSC 100 Series (990-3027D), published free by APC (Schneider Electric) at https://download.se.com/files?p_Doc_Ref=Modbus_Register_Map_InRow_ACS.