Air handler (in-row self-contained DX cooling unit) · Modbus register map
APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit Modbus register map
Updated 19 November 2026
The InRow SC (ACSC 100 series) is a self-contained DX in-row cooling unit. It answers Modbus RTU and Modbus TCP with all data in holding registers, readable with function 03 or 04. This map covers unit start/stop, setpoints, air and refrigerant temperatures and pressures, fan speeds, run hours, group settings and the one-register fault flags.
This page lists 119 Modbus registers for the APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit — 32 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from APC (Schneider Electric)’s own free documentation (linked below) and checked against it.
- Manufacturer
- APC (Schneider Electric)
- Model
- InRow ACSC 100 Series self-contained DX cooling unit
- Equipment type
- Air handler (in-row self-contained DX cooling unit)
- Registers
- 119 (32 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- ACSC100, InRow SC, InRow ACSC
- Source document
- Modbus Register Map: InRow ACSC 100 Series · 990-3027D
Integration notes: APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit
Poll holding registers with function 03 or 04: OVERALL_STATUS and OPERATE_MODE at 0 and 87, then the 32-bit temperatures from 88 upward in tenths of a degree F, and the fault flags from 256 to 299. Write UNIT_CTRL at 7 to start or stop the unit.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Overall status | UINT16 | Overall alarm severity | Read |
| HR 87 | Operate mode | UINT16 | Unit operating mode | Read |
| HR 7 | Unit ctrl | UINT16 | Unit on / standby command | Read/write |
| HR 1 | Cool setpoint | INT32 ABCD | Cooling setpoint | Read/write |
| HR 92 | Rack inlet temp | INT32 ABCD | Rack inlet temperature | Read |
| HR 94 | Supply temp | INT32 ABCD | Supply air temperature | Read |
| HR 96 | Return temp | INT32 ABCD | Return air temperature | Read |
| HR 259 | Cool fail | UINT16 | Cooling failure alarm | Read |
| HR 272 | Water detected | UINT16 | Water detected alarm | Read |
Enable Modbus control & writes
The register map does not describe how to enable Modbus or set the network parameters.
Byte order & addressing
- 32-bit values are high word first (ABCD).
- Temperatures are tenths of a degree Fahrenheit.
- OVERALL_STATUS uses 0, 2, 4 and 8 rather than 0-3.
Network setup
- Modbus RTU and Modbus TCP are supported; serial settings and unit ID are not in this map.
Watch out for
- Reading an item before the controller has data for it returns an invalid-address error, so retry later.
- Large block reads may take 2 seconds or more.
APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 0000h (0) | Overall status | Worst active alarm severity for the unit. | UINT16 | Read | 0 = No Alarm; 2 = Informational; 4 = Warning; 8 = Critical | |||
| HR | 1doc 0001h (1) | Cool setpoint | Cooling setpoint for this unit. | INT32 | ABCD | × 0.1 | °F | Read/write | |
| HR | 3doc 0003h (3) | Supply air setpoint | Supply air temperature setpoint. | INT32 | ABCD | × 0.1 | °F | Read/write | |
| HR | 5doc 0005h (5) | Configuration type | UINT16 | Read/write | 0 = RACS; 1 = Spot; 2 = In-Row | ||||
| HR | 6doc 0006h (6) | Fan speed preference | UINT16 | Read/write | 0 = Low; 1 = Med-Low; 2 = Med; 3 = Med-High; 4 = High | ||||
| HR | 7doc 0007h (7) | Unit ctrl | Start (On) or stop (Standby) the unit. | UINT16 | Read/write | 0 = Standby; 1 = On | |||
| HR | 8doc 0008h (8) | Capacity ctrl | Compressor capacity control method. | UINT16 | Read/write | 0 = Discrete (Disc); 1 = Proportional (Prop) | |||
| HR | 9doc 0009h (9) | Cool deadband | INT32 | ABCD | × 0.1 | °F | Read/write | ||
| HR | 11doc 000Bh (11) | Unit name | STRING[42] | Read/write | |||||
| HR | 32doc 0020h (32) | Unit location | STRING[42] | Read/write | |||||
| HR | 53doc 0035h (53) | Model num | STRING[20] | Read | |||||
| HR | 63doc 003Fh (63) | Serial num | STRING[20] | Read | |||||
| HR | 73doc 0049h (73) | Firmware rev | STRING[8] | Read | |||||
| HR | 77doc 004Dh (77) | Hardware rev | STRING[8] | Read | |||||
| HR | 81doc 0051h (81) | Date of manufacture | STRING[12] | Read | |||||
| HR | 87doc 0057h (87) | Operate mode | Current unit state. | UINT16 | Read | 0 = Standby; 1 = On; 2 = Idle | |||
| HR | 88doc 0058h (88) | Unit cool output | Cooling delivered by this unit. | INT32 | ABCD | × 0.1 | kW | Read | |
| HR | 90doc 005Ah (90) | Unit cool demand | Cooling requested from this unit. | INT32 | ABCD | × 0.1 | kW | Read | |
| HR | 92doc 005Ch (92) | Rack inlet temp | Rack inlet air temperature. | INT32 | ABCD | × 0.1 | °F | Read | |
| HR | 94doc 005Eh (94) | Supply temp | Air temperature leaving the unit. | INT32 | ABCD | × 0.1 | °F | Read | |
| HR | 96doc 0060h (96) | Return temp | Air temperature entering the unit. | INT32 | ABCD | × 0.1 | °F | Read | |
| HR | 98doc 0062h (98) | Cond outlet temp | Condenser air outlet temperature. | INT32 | ABCD | × 0.1 | °F | Read | |
| HR | 100doc 0064h (100) | Cond inlet temp | Condenser air inlet temperature. | INT32 | ABCD | × 0.1 | °F | Read | |
| HR | 102doc 0066h (102) | Unit air flow | INT32 | ABCD | CFM | Read | |||
| HR | 104doc 0068h (104) | Evaporator fan speed | INT32 | ABCD | × 0.1 | % | Read | ||
| HR | 106doc 006Ah (106) | Suction temp | INT32 | ABCD | × 0.1 | °F | Read | ||
| HR | 108doc 006Ch (108) | Superheat | Suction superheat. | INT32 | ABCD | × 0.1 | °F | Read | |
| HR | 110doc 006Eh (110) | Condenser fan speed | INT32 | ABCD | × 0.1 | % | Read | ||
| HR | 112doc 0070h (112) | Filter dp | INT32 | ABCD | × 0.01 | in W.C. | Read | ||
| HR | 114doc 0072h (114) | Containment dp | INT32 | ABCD | × 0.01 | in W.C. | Read | ||
| HR | 116doc 0074h (116) | Suction pressure | Refrigerant suction pressure. | INT32 | ABCD | psi | Read | ||
| HR | 118doc 0076h (118) | Discharge pressure | Refrigerant discharge pressure. | INT32 | ABCD | psi | Read | ||
| HR | 120doc 0078h (120) | Air filter runhour | INT32 | ABCD | h | Read | |||
| HR | 122doc 007Ah (122) | Evaporator fan 1 runhour | INT32 | ABCD | h | Read | |||
| HR | 124doc 007Ch (124) | Evaporator fan 2 runhour | INT32 | ABCD | h | Read | |||
| HR | 126doc 007Eh (126) | Evaporator fan 3 runhour | INT32 | ABCD | h | Read | |||
| HR | 128doc 0080h (128) | Compressor runhour | INT32 | ABCD | h | Read | |||
| HR | 130doc 0082h (130) | Condenser fan runhour | Condenser fan run hours (first of three rows with this name). | INT32 | ABCD | h | Read | ||
| HR | 136doc 0088h (136) | Fan left pwrsp runhour | INT32 | ABCD | h | Read | |||
| HR | 138doc 008Ah (138) | Fan right pwrsp runhour | INT32 | ABCD | h | Read | |||
| HR | 140doc 008Ch (140) | Conds pump runhour | INT32 | ABCD | h | Read | |||
| HR | 142doc 008Eh (142) | Air filter serv int | INT32 | ABCD | weeks | Read/write | |||
| HR | 144doc 0090h (144) | Air filter serv int alarm | UINT16 | Read/write | 0 = Enable; 1 = Disable | ||||
| HR | 145doc 0091h (145) | Rack temp high thresh | INT32 | ABCD | × 0.1 | °F | Read/write | ||
| HR | 147doc 0093h (147) | Sply air temp high thresh | INT32 | ABCD | × 0.1 | °F | Read/write | ||
| HR | 149doc 0095h (149) | Rtn air temp high thresh | INT32 | ABCD | × 0.1 | °F | Read/write | ||
| HR | 151doc 0097h (151) | Altitude | INT32 | ABCD | ft | Read/write | |||
| HR | 153doc 0099h (153) | Startup delay | INT32 | ABCD | s | Read/write | |||
| HR | 155doc 009Bh (155) | Idle on leak | UINT16 | Read/write | 0 = Yes; 1 = No | ||||
| HR | 156doc 009Ch (156) | Input normal | UINT16 | Read/write | 0 = Open; 1 = Closed | ||||
| HR | 157doc 009Dh (157) | Input state | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| HR | 158doc 009Eh (158) | Output normal | UINT16 | Read/write | 0 = Open; 1 = Closed | ||||
| HR | 159doc 009Fh (159) | Output state | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| HR | 160doc 00A0h (160) | Output source | Which alarms drive the output relay. | UINT16 | Read/write | 0 = Any Alarm; 1 = Only Critical Alarms | |||
| HR | 161doc 00A1h (161) | Compressor state | Compressor running or not. | UINT16 | Read | 0 = Off; 1 = On | |||
| HR | 200doc 00C8h (200) | Number of cooling units | INT32 | ABCD | Read/write | ||||
| HR | 202doc 00CAh (202) | Group cool setpoint | INT32 | ABCD | × 0.1 | °F | Read/write | ||
| HR | 204doc 00CCh (204) | Group supply air setpoint | INT32 | ABCD | × 0.1 | °F | Read/write | ||
| HR | 206doc 00CEh (206) | Group configuration type | UINT16 | Read/write | 0 = RACS; 1 = Spot; 2 = In-Row | ||||
| HR | 207doc 00CFh (207) | Group fan speed preference | UINT16 | Read/write | 0 = Low; 1 = Med-Low; 2 = Med; 3 = Med-High; 4 = High | ||||
| HR | 208doc 00D0h (208) | Group capacity ctrl | UINT16 | Read/write | 0 = Discrete (Disc); 1 = Proportional (Prop) | ||||
| HR | 209doc 00D1h (209) | Group fan speed ctrl | UINT16 | Read/write | 0 = Automatic; 1 = Manual | ||||
| HR | 210doc 00D2h (210) | Group cool deadband | INT32 | ABCD | × 0.1 | °F | Read/write | ||
| HR | 212doc 00D4h (212) | Group altitude | INT32 | ABCD | ft | Read/write | |||
| HR | 214doc 00D6h (214) | Group rack inlet max temp | INT32 | ABCD | × 0.1 | °F | Read | ||
| HR | 216doc 00D8h (216) | Group rack inlet min temp | INT32 | ABCD | × 0.1 | °F | Read | ||
| HR | 218doc 00DAh (218) | Group return air max temp | INT32 | ABCD | × 0.1 | °F | Read | ||
| HR | 220doc 00DCh (220) | Group return air min temp | INT32 | ABCD | × 0.1 | °F | Read | ||
| HR | 222doc 00DEh (222) | Group cooling demand | INT32 | ABCD | × 0.1 | kW | Read | ||
| HR | 224doc 00E0h (224) | Group cooling actual | INT32 | ABCD | × 0.1 | kW | Read | ||
| HR | 226doc 00E2h (226) | Group airflow demand | INT32 | ABCD | CFM | Read | |||
| HR | 228doc 00E4h (228) | Num active flow controllers | INT32 | ABCD | Read/write | ||||
| HR | 230doc 00E6h (230) | Active flow control bias | UINT16 | Read/write | 0 = Positive; 1 = Slightly Positive; 2 = Zero; 3 = Slightly Negative; 4 = Negative | ||||
| HR | 231doc 00E7h (231) | Active flow control status | UINT16 | Read | 0 = Under; 1 = Okay; 2 = Over; 3 = N/A | ||||
| HR | 232doc 00E8h (232) | Active flow control lamp test | UINT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 256doc 0100h (256) | Internal comm fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 257doc 0101h (257) | Alink isolation relay fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 258doc 0102h (258) | External communication fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 259doc 0103h (259) | Cool fail | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 260doc 0104h (260) | High rack temp | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 261doc 0105h (261) | Air filter clogged | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 262doc 0106h (262) | Rtn air sensor fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 263doc 0107h (263) | Upper rtn air sensor fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 264doc 0108h (264) | Sply air sensor fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 265doc 0109h (265) | Upper sply air sensor fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 266doc 010Ah (266) | Rack temp sensor fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 267doc 010Bh (267) | High discharge pressure | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 268doc 010Ch (268) | Low suction pressure | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 269doc 010Dh (269) | Evaporator fan 1 fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 270doc 010Eh (270) | Evaporator fan 2 fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 271doc 010Fh (271) | Evaporator fan 3 fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 272doc 0110h (272) | Water detected | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 273doc 0111h (273) | Check condensate management fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 274doc 0112h (274) | Conds pan full | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 275doc 0113h (275) | Fan pwrsp left fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 276doc 0114h (276) | Fan pwrsp right fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 277doc 0115h (277) | Air filter runhour violation | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 278doc 0116h (278) | Condenser fan 1 fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 279doc 0117h (279) | Condenser fan 2 fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 280doc 0118h (280) | Condenser fan 3 fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 281doc 0119h (281) | Supply high temp fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 282doc 011Ah (282) | Return high temp fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 283doc 011Bh (283) | Filter dp sensor fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 284doc 011Ch (284) | Containment dp sensor fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 285doc 011Dh (285) | Suction temp sensor fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 286doc 011Eh (286) | Suction pressure sensor fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 287doc 011Fh (287) | Disch press sensor fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 288doc 0120h (288) | Containment dp high fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 289doc 0121h (289) | Input contact fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 290doc 0122h (290) | High discharge pressure fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 291doc 0123h (291) | Low suction pressure fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 292doc 0124h (292) | Start low suction pressure | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 293doc 0125h (293) | Start line pressure imbalance | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 294doc 0126h (294) | Group comm fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 295doc 0127h (295) | Leak detected shutdown | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 296doc 0128h (296) | Ecoaisle door open fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 297doc 0129h (297) | Num of active flow controllers fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 298doc 012Ah (298) | Insufficient airflow fault | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 299doc 012Bh (299) | Active flow controller sensor fault | UINT16 | Read | 0 = Clear; 1 = Alarm |
Notes on this map
- Word order: note 2 says 32-bit values keep the most significant word at n+0 (ABCD). The table labels them LONG; they are listed here as signed 32-bit, since note 5 says signed values are two's complement and temperatures can go below zero.
- Scale comes from the units column: '(Tenths)' is 0.1 and '(Hundredths)' is 0.01. Temperatures are in tenths of a degree Fahrenheit.
- Function codes 3 and 4 read the same registers; writes use function 16, or function 6 for one-register items.
- Left out: the rows at 132 and 134, which repeat the name CONDENSER_FAN_RUNHOUR of the row at 130 so their meaning is not stated; the reserved blocks; and the APC serial diagnostic counters at 0xFFEE-0xFFFE.
- The source prints the bias enum as '3 = Slightly Neg4 = Negative'; it is split here into 3 = Slightly Negative and 4 = Negative.
- Data points that a unit does not support read as 0 rather than raising an error.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit
What Modbus registers does the APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit have?
This map lists 119 registers: 119 holding registers. 32 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table gives absolute addresses in hex and decimal. Note 11 says absolute address 0 equals Modicon register 40001 and is address zero on the wire, so the decimal column is the wire address as printed.
What byte order does the APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit?
Start with HR 0 Overall status (Overall alarm severity); HR 87 Operate mode (Unit operating mode); HR 7 Unit ctrl (Unit on / standby command); HR 1 Cool setpoint (Cooling setpoint); HR 92 Rack inlet temp (Rack inlet temperature); HR 94 Supply temp (Supply air temperature); HR 96 Return temp (Return air temperature); HR 259 Cool fail (Cooling failure alarm); HR 272 Water detected (Water detected alarm).
How do I enable Modbus control of the APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit?
The register map does not describe how to enable Modbus or set the network parameters.
Where is the official APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit Modbus documentation?
The source is Modbus Register Map: InRow ACSC 100 Series (990-3027D), published free by APC (Schneider Electric) at https://download.se.com/files?p_Doc_Ref=Modbus_Register_Map_InRow_ACS.
More APC (Schneider Electric) Modbus register maps
- UPS
APC (Schneider Electric) Galaxy VL 200-500 kW three-phase UPS
Schneider Electric Galaxy VL 200-500 kW UPS with firmware 7.23 or later, per register map 990-6447.
Also known as: Galaxy VL, GVL, Galaxy VL 200 kW, Galaxy VL 500 kW - Air handler (in-row chilled-water cooling unit)
APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm)
APC by Schneider Electric InRow ACRC30x (300 mm chilled water) units, per register map part number 990-4742B.
Also known as: ACRC30x, ACRC300, ACRC301, InRow RC 300 mm - Air handler (in-row data-centre cooling unit)
APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786)
APC / Schneider Electric InRow ACRD60x and ACRC60x in-row cooling units, register map part number 990-5786A.
Also known as: ACRD60x, ACRC60x, InRow ACRD60x, InRow ACRC60x, 990-5786 - Air handler (in-row data-centre DX cooling unit)
APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B)
APC / Schneider Electric InRow RD cooling units, register map part number 990-3576B (08/2015).
Also known as: InRow RD, 990-3576B, Schneider Electric InRow RD - UPS
APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702)
APC Smart-UPS (excluding SMT, SMX, SURTD and SRT prefixes), Smart-UPS VT and MGE Galaxy 3500 through Network Management Card AP9630/AP9631/AP9635 (TCP) or AP9635 (RTU), part number 990-5702.
Also known as: 990-5702, AP9630, AP9631, AP9635, Smart-UPS VT, MGE Galaxy 3500, Schneider Electric APC Smart-UPS - UPS
APC Symmetra PX 250/500 kW
APC Symmetra PX 250/500 kW three-phase UPS via Network Management Card AP9635, register map 990-3936D (firmware sypx510 to sypx516 changes listed in the source).
Also known as: 990-3936D, Symmetra PX 250 kW, Symmetra PX 500 kW, SYPX
Other hvac equipment register maps
- Rooftop unit
Daikin Applied Rebel / Rebel Applied rooftop (MicroTech 4 controller)
Daikin Applied Rebel Applied (DPSA, R-410A/R-32) and Rebel (DPS, R-32) packaged rooftops with MicroTech 4 controller and Modbus RTU module, per ED 19133-2 (Oct 2025).
Also known as: DPSA, DPS, Rebel Applied, Rebel, MicroTech 4 rooftop, ED 19133-2 - Air handler
Flexit Nordic residential air handling unit (Flexit GO, built-in Modbus)
Flexit NORDIC series residential ventilation units with Flexit GO control and built-in Modbus RTU (cable harness 116405), per the 'Modbus Nordic Basic' register sheet and instruction 117989-01 (2020-01). Not EcoNordic, which has its own register sheet.
Also known as: Nordic S2, Nordic S3, Nordic S4, Nordic CL2, Nordic CL3, Nordic CL4, Flexit GO, Modbus Nordic Basic, 117989 - Thermostat (fan coil)
Johnson Controls T7000 series fan coil thermostat (Modbus RTU)
Johnson Controls T7000 series Modbus thermostats listed in the data table: T7600-TF21, T7601-TF20 (ECM fan), T7600-TF20 (relay), T7603-T000 (single-stage heating) and T7600-TB21 (with AI); data table revision 2.4 (2019-12-23).
Also known as: T7600-TF21-9JS0, T7601-TF20-9JS0, T7600-TF20-9JS0, T7603-T000-9JF0, T7600-TF21-1JS0, T7601-TF20-1JS0, T7600-TF20-1JS0, T7603-T000-1JF0, T7600-TB21-9JA0, T7600, T7601, T7603 - Air handler (compact make-up air unit)
Neptronic CMU compact make-up air unit (Modbus communication module)
Neptronic CMU compact make-up air units with the Modbus communication module, guide CMU-Modbus Guide-211125.
Also known as: Compact Make-up Air Unit, Neptronic CMU, CMU Series - Air handler humidifier (steam-to-steam)
Neptronic SKS4 steam-to-steam humidifier (Modbus communication module)
Neptronic SKS4 series steam-to-steam humidifiers with the Modbus communication module, guide SKS4-Modbus Guide-220509 (V2.03).
Also known as: SKS4-E, SKS4-N, SKS4 Steam to Steam Humidifier, Neptronic SKS4 Modbus - Thermostat
Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU)
SMT-770 thermostat (with or without a paired EC-02 module), communications addendum v4.6 for firmware 2.31.
Also known as: SMT-770 Chameleon, EC-02, SMT770
All hvac equipment Modbus register maps →
Source: Modbus Register Map: InRow ACSC 100 Series · 990-3027D. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.