UPS · Modbus register map

APC Symmetra PX 250/500 kW Modbus register map

Updated 17 November 2026

Short answer

The Symmetra PX 250/500 kW publishes a large Modbus map through its AP9635 network card, over RTU or TCP. Status and alarm registers at 40001 onward are bit fields; measurements (battery, input, bypass, output per phase, load, energy, temperatures, operating modes and component lifetimes) are 16- or 32-bit holding registers from 44097 onward, with documented multiply/divide scaling.

This page lists 156 Modbus registers for the APC Symmetra PX 250/500 kW — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from APC’s own free documentation (linked below) and checked against it.

Manufacturer
APC
Model
Symmetra PX 250/500 kW
Equipment type
UPS
Registers
156 (0 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Firmware
sypx510-sypx516 per revision table
Also known as
990-3936D, Symmetra PX 250 kW, Symmetra PX 500 kW, SYPX
Source document
Modbus Register Map: Symmetra PX 250/500 kW · 990-3936D · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: APC Symmetra PX 250/500 kW

Integration in brief

Read the status/alarm block from 0 and the measurement blocks from 0x1100 (battery), 0x1200 (input), 0x1300 (bypass), 0x1400 (output) and 0x1500 (system) with function 03 or 04.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0UPS StatusBITMAP16UPS status bits (on battery, bypass, alarms)Read
HR 4354Runtime remainingUINT32 ABCDRuntime remainingRead
HR 4358Estimated charge %UINT16Battery charge %Read
HR 5145Total Percent loadUINT16Total output load %Read
HR 5143Total active power (output)UINT16Total output active powerRead
HR 5378UPS Mode Operation mode of the UPSUINT16UPS operating modeRead

Enable Modbus control & writes

Enable Modbus (serial RTU or TCP) on the AP9635 Network Management Card; see its user's guide.

Byte order & addressing

Network setup

Watch out for

APC Symmetra PX 250/500 kW Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

156 of 156 shown
APC Symmetra PX 250/500 kW Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001UPS Status1 = condition active.BITMAP16Readbit 0 = Load is being powered from battery; bit 1 = Low Battery; bit 2 = System is in Bypass; bit 3 = Self-test in progress; bit 4 = Load is not powered; bit 7 = Abnormal condition present; bit 8 = Power Module Failure; bit 9 = Battery System Failure; bit 10 = Intelligence Module has detected alarm condition; bit 11 = Static Switch failure; bit 12 = Power Supply Unit failure; bit 14 = Warning alarm present; bit 15 = Critical alarm present
HR2doc 40003Alarm Register 400031 = condition active.BITMAP16Readbit 0 = Lost local network management interface - to - UPS communication; bit 1 = Parallel PBUS cables are swapped; bit 2 = Parallel communication error on PBUS cable 1; bit 3 = Parallel communication error on PBUS cable 2; bit 4 = Overload on parallel installation; bit 5 = Parallel mixed mode error: Units in battery and normal operation; bit 6 = UPS parallel address configuration number error; bit 7 = Parallel master not detected (deprecated); bit 8 = Parallel unit disabled; bit 9 = Parallel unit is incompatible; bit 10 = PBUS cable termination fault; bit 11 = Parallel unit not present (deprecated); bit 12 = Isolated Test mode is active; bit 13 = Parallel unit redundancy lost; bit 15 = Parallel load share error
HR3doc 40004Alarm Register 400041 = condition active.BITMAP16Readbit 0 = On battery in response to an input power failure; bit 1 = In bypass: User-initiated from Front Panel; bit 2 = UPS operation mode - Forced bypass; bit 3 = In Bypass: For maintenance; bit 4 = Started a self-test; bit 5 = Output power turned off; bit 6 = UPS operation mode - Initialize; bit 7 = UPS operation mode - Hot standby; bit 8 = Compensating for a low input voltage; bit 9 = Compensating for a high input voltage; bit 10 = Input voltage waveform error detected; bit 11 = Input phase sequence error; bit 12 = Input frequency fault; bit 13 = Output frequency fault; bit 14 = Mega Tie mode is active; bit 15 = External synchronization source is selected and out of tolerance
HR4doc 40005Alarm Register 400051 = condition active.BITMAP16Readbit 0 = Bypass voltage error: low voltage; bit 1 = Bypass voltage error: high voltage; bit 2 = Bypass voltage waveform error detected; bit 3 = Bypass input frequency fault; bit 4 = Bypass phase sequence error; bit 5 = Output voltage low; bit 6 = Output voltage high; bit 7 = Output voltage waveform error detected; bit 8 = Overload; bit 9 = Overload on bypass static switch; bit 10 = Ambient temperature out of range; bit 11 = EPO activated; bit 12 = Ground fault detected; bit 13 = PSU module failed
HR5doc 40006Alarm Register 400061 = condition active.BITMAP16Readbit 0 = System locked in bypass operation; bit 1 = Batteries are discharging; bit 2 = PSU module not present; bit 3 = System frequency not detected; bit 5 = Charge power is reduced; bit 6 = Display communication to MIM and RIM is lost; bit 7 = CBUS terminator fault; bit 8 = ABUS terminator fault; bit 10 = MIM not present; bit 11 = MIM heartbeat signal error; bit 12 = RIM in control; bit 13 = Battery condition is weak; bit 14 = Battery condition is poor
HR6doc 40007Alarm Register 400071 = condition active.BITMAP16Readbit 0 = Battery voltage error - voltage above warning level; bit 1 = Battery voltage error - voltage above shutdown level; bit 2 = Battery monitor board communication error; bit 4 = Battery is below minimum acceptable runtime; bit 5 = Power module communication to MIM error; bit 6 = Power module locked by IM; bit 7 = Power module operation mode is different from other modules; bit 9 = Switchgear board not present; bit 10 = Switchgear board communication error; bit 11 = ID & Relay board not present; bit 12 = ID & Relay board communication error; bit 13 = Battery voltage collapse detected; bit 14 = Power module redundancy lost
HR7doc 40008Alarm Register 400081 = condition active.BITMAP16Readbit 7 = Load on subfeed is above warning level; bit 8 = Load on subfeed is above critical level; bit 9 = Load on UPS is above warning level; bit 10 = Power module firmware version is incompatible; bit 11 = Static Bypass Switch module not present; bit 12 = Overload on installation; bit 13 = Bypass static switch communication error; bit 14 = RIM not present; bit 15 = RIM heartbeat signal error
HR8doc 40009Alarm Register 400091 = condition active.BITMAP16Readbit 0 = Bonding wire between neutral and ground is missing; bit 1 = Bonding wire between neutral and ground error; bit 2 = Power module communication to RIM error; bit 3 = Battery voltage error - voltage below warning level; bit 4 = Battery voltage error - voltage below shutdown level; bit 5 = ECT board has an error; bit 6 = External connections board not present; bit 7 = EPO circuit test mode is enabled; bit 8 = IM internal memory for storing configuration settings error; bit 10 = Auxiliary monitor board for maintenance bypass panel comm error; bit 11 = Auxiliary monitor board for battery breaker enclosure comm error; bit 13 = Power module removed from the system; bit 14 = INFO Battery module removed from system
HR9doc 40010Alarm Register 400101 = condition active.BITMAP16Readbit 0 = Power module fault exists; bit 1 = Power module warning; bit 3 = Power module fan fault; bit 4 = Power module is disabled; bit 5 = Power module lifetime error: close to end; bit 6 = Power module lifetime error: lifetime exceeded; bit 7 = Power module fan lifetime error: close to end; bit 8 = Power module fan lifetimerror: lifetime exceeded; bit 9 = Breaker Q1 open; bit 10 = Breaker Q2 open; bit 11 = Breaker Q3 closed; bit 12 = Breaker Q4 open; bit 13 = Breaker Q5 open; bit 14 = Power module phase-neutral displacement fault
HR10doc 40011Alarm Register 400111 = condition active.BITMAP16Readbit 0 = Forced bypass switch activated; bit 1 = Bypass static switch disabled; bit 2 = Bypass static switch self test failed; bit 4 = Bypass static switch 1 fan fault; bit 5 = Bypass static switch 1 fan weak; bit 8 = Bypass static switch error; module has a critical error; bit 9 = Bypass static switch warning; module is not working properly; bit 10 = Power enclosure air filter lifetime exceeded (informational); bit 11 = Power enclosure air filter lifetime exceeded (warning); bit 14 = Door in MBwD enclosure open; bit 15 = Q2 shunt open error
HR11doc 40012Alarm Register 400121 = condition active.BITMAP16Readbit 0 = Subfeed breaker SB1 open; bit 1 = Subfeed breaker SB2 open; bit 2 = Subfeed breaker SB3 open; bit 3 = Subfeed breaker SB4 open; bit 4 = Subfeed breaker SB5 open; bit 5 = Subfeed breaker SB6 open; bit 6 = Subfeed breaker SB7 open; bit 7 = Subfeed breaker SB8 open; bit 8 = Subfeed breaker SB9 open; bit 9 = Subfeed breaker SB10 open; bit 10 = Subfeed breaker SB11 open; bit 11 = Subfeed breaker SB12 open; bit 12 = Subfeed breaker SB13 open; bit 13 = Subfeed breaker SB14 open; bit 14 = Subfeed breaker SB15 open; bit 15 = Subfeed breaker SB16 open
HR12doc 40013Alarm Register 400131 = condition active.BITMAP16Readbit 0 = Breaker Q1 open; bit 1 = Breaker Q2 open; bit 2 = Breaker Q3 closed; bit 3 = Breaker Q4 open; bit 4 = Breaker Q5 open; bit 5 = Door in maintenance bypass panel enclosure open; bit 6 = Q2 shunt open error; bit 7 = MBP enclosure ECT board has an error; bit 8 = ID & Relay board memory card full; bit 9 = Input 3 activated: Battery ground fault detected; bit 10 = ID & Relay board: System firmware not stored at memory card; bit 11 = Input 6 activated: Emergency module off; bit 12 = Input 7 activated: Door in UPS I/O enclosure opened; bit 13 = Input 1 activated: Reduce charging power; bit 14 = IDRC memory card not present; bit 15 = ID & Relay board memory card error
HR13doc 40014Alarm Register 400141 = condition active.BITMAP16Readbit 0 = Battery breaker open; bit 1 = Battery module fuse cleared or condition of battery is weak; bit 2 = Battery voltage symmetry error; bit 3 = Internal battery temperature exceeds threshold; bit 5 = Battery temperature sensor fault; bit 6 = Mixed battery configuration; bit 7 = Battery module type support error; bit 8 = Battery string disconnected; bit 9 = Battery side car 1 fuse error; bit 11 = Battery enclosure PSU error; bit 12 = Battery breaker motor PSU error; bit 13 = Battery enclosure door open; bit 14 = ECT board has an error; bit 15 = Battery breaker shunt open error
HR14doc 40015Alarm Register 400151 = condition active.BITMAP16Readbit 0 = Battery breaker open error; bit 1 = Battery breaker enclosure fuse 1 error; bit 2 = Battery breaker enclosure fuse 2 error; bit 3 = Battery temperature 1 high; bit 4 = Battery temperature 2 high; bit 5 = Battery temperature sensor 1 fault; bit 6 = Battery temperature sensor 2 fault; bit 7 = Battery breaker enclosure door open error; bit 8 = Battery breaker enclosure ECT board has an error; bit 9 = Battery breaker shunt open error; bit 10 = Battery ground fault detected error
HR15doc 40016Alarm Register 400161 = condition active.BITMAP16Readbit 0 = Battery fuse bank 1 cleared; bit 1 = Battery fuse bank 2 cleared; bit 2 = Battery fuse bank 3 cleared; bit 3 = Battery fuse bank 4 cleared; bit 4 = Battery fuse bank 5 cleared; bit 5 = Battery fuse bank 6 cleared; bit 6 = Battery fuse bank 7 cleared; bit 7 = Battery fuse bank 8 cleared; bit 8 = Input for gas alarm has been activated
HR16doc 40017Alarm Register 400171 = condition active.BITMAP16Readbit 0 = Test firmware installed at power module; bit 1 = Not expected firmware installed at power module; bit 2 = Not expected firmware installed at battery monitor board; bit 3 = Not expected firmware installed at SBS module; bit 4 = Not expected firmware installed at ID & Relay board; bit 5 = Not expected firmware installed at switchgear board; bit 6 = Not expected firmware installed at auxiliary monitor board for maintenance; bit 7 = Not expected firmware installed at auxiliary monitor board for battery breaker; bit 8 = Not expected firmware installed at redundant IM; bit 9 = Test firmware installed at battery monitor board; bit 10 = Test firmware installed at SBS module; bit 11 = Test firmware installed at ID & Relay board; bit 12 = Test firmware installed at switchgear board; bit 13 = Test firmware installed at auxiliary monitor board for maintenance bypass panel; bit 14 = Test firmware installed at auxiliary monitor board for battery breaker enclosure; bit 15 = Test firmware installed at IM
HR4096doc 44097NMC Model NumberTwo characters per register, high byte first.STRING[18]Read
HR4105doc 44106NMC Serial NumberTwo characters per register, high byte first.STRING[16]Read
HR4113doc 44114NMC Firmware Revision APPTwo characters per register, high byte first.STRING[18]Read
HR4122doc 44123NMC Hardware RevisionTwo characters per register, high byte first.STRING[18]Read
HR4131doc 44132NMC Date of ManufactureTwo characters per register, high byte first.STRING[12]Read
HR4137doc 44138UPS Model NameTwo characters per register, high byte first.STRING[16]Read
HR4145doc 44146UPS Serial NumberTwo characters per register, high byte first.STRING[12]Read
HR4151doc 44152UPS Firmware VersionTwo characters per register, high byte first.STRING[24]Read
HR4163doc 44164UPS NameTwo characters per register, high byte first.STRING[8]Read
HR4167doc 44168Parallel System NameTwo characters per register, high byte first.STRING[8]Read
HR4352doc 44353Time on batteryUINT32ABCDsRead
HR4354doc 44355Runtime remainingUINT32ABCDsRead
HR4356doc 44357Estimated charge timeUINT32ABCDsRead
HR4358doc 44359Estimated charge %UINT16%Read
HR4359doc 44360Battery (+) VoltageUINT16VRead
HR4360doc 44361Battery (-) VoltageUINT16VRead
HR4361doc 44362Battery (+) CurrentINT16ARead
HR4362doc 44363Battery (-) CurrentINT16ARead
HR4363doc 44364Total time on batteryUINT32ABCDsRead
HR4365doc 44366Total number of times on batteryUINT16Read
HR4367doc 44368BatterySystem/TemperatureUINT16°CRead
HR4368doc 44369User Supplied Battery System Charger Status1 = condition active.BITMAP16Readbit 0 = Float Charging
HR4369doc 44370Battery PowerINT16× 0.1kWRead
HR4370doc 44371Available Amp HoursUINT16AhRead
HR4371doc 44372Last Battery ReplacementTwo characters per register, high byte first.STRING[8]Read
HR4608doc 44609Frequency (input)UINT16× 0.1HzRead
HR4609doc 44610Voltage L1-2 (input)UINT16VRead
HR4610doc 44611Voltage L2-3 (input)UINT16VRead
HR4611doc 44612Voltage L3-1 (input)UINT16VRead
HR4612doc 44613Current L1 (input)UINT16ARead
HR4613doc 44614Current L2 (input)UINT16ARead
HR4614doc 44615Current L3 (input)UINT16ARead
HR4615doc 44616Active power L1 (input)UINT16kWRead
HR4616doc 44617Active power L2 (input)UINT16kWRead
HR4617doc 44618Active power L3 (input)UINT16kWRead
HR4618doc 44619Apparent power L1 (input)UINT16kVARead
HR4619doc 44620Apparent power L2 (input)UINT16kVARead
HR4620doc 44621Apparent power L3 (input)UINT16kVARead
HR4621doc 44622Total active power (input)UINT16kWRead
HR4622doc 44623Total apparent power (input)UINT16kVARead
HR4623doc 44624Current L1 (parallel input)UINT16ARead
HR4624doc 44625Current L2 (parallel input)UINT16ARead
HR4625doc 44626Current L3 (parallel input)UINT16ARead
HR4864doc 44865Frequency (bypass)UINT16× 0.1HzRead
HR4865doc 44866Voltage L1-2 (bypass)UINT16VRead
HR4866doc 44867Voltage L2-3 (bypass)UINT16VRead
HR4867doc 44868Voltage L3-1 (bypass)UINT16VRead
HR4868doc 44869Current L1 (bypass)UINT16ARead
HR4869doc 44870Current L2 (bypass)UINT16ARead
HR4870doc 44871Current L3 (bypass)UINT16ARead
HR4871doc 44872Active power L1 (bypass)UINT16kWRead
HR4872doc 44873Active power L2 (bypass)UINT16kWRead
HR4873doc 44874Active power L3 (bypass)UINT16kWRead
HR4874doc 44875Apparent power L1 (bypass)UINT16kVARead
HR4875doc 44876Apparent power L2 (bypass)UINT16kVARead
HR4876doc 44877Apparent power L3 (bypass)UINT16kVARead
HR4877doc 44878Total active power (bypass)UINT16kWRead
HR4878doc 44879Total apparent power (bypass)UINT16kVARead
HR4879doc 44880Current L1 (parallel bypass)UINT16ARead
HR4880doc 44881Current L2 (parallel bypass)UINT16ARead
HR4881doc 44882Current L3 (parallel bypass)UINT16ARead
HR5120doc 45121Nominal (Apparent) output ratingUINT16kVARead
HR5121doc 45122Frequency (output)UINT16× 0.1HzRead
HR5122doc 45123Voltage L1-2 (output)UINT16VRead
HR5123doc 45124Voltage L2-3 (output)UINT16VRead
HR5124doc 45125Voltage L3-1 (output)UINT16VRead
HR5125doc 45126Current L1 (output)UINT16ARead
HR5126doc 45127Current L2 (output)UINT16ARead
HR5127doc 45128Current L3 (output)UINT16ARead
HR5128doc 45129Peak current L1 (output)UINT32ABCDARead
HR5130doc 45131Peak current L2 (output)UINT32ABCDARead
HR5132doc 45133Peak current L3 (output)UINT32ABCDARead
HR5134doc 45135Active power L1 (output)UINT16kWRead
HR5135doc 45136Active power L2 (output)UINT16kWRead
HR5136doc 45137Active power L3 (output)UINT16kWRead
HR5137doc 45138Apparent power L1 (output)UINT16kVARead
HR5138doc 45139Apparent power L2 (output)UINT16kVARead
HR5139doc 45140Apparent power L3 (output)UINT16kVARead
HR5140doc 45141% Load L1UINT16× 0.1%Read
HR5141doc 45142% Load L2UINT16× 0.1%Read
HR5142doc 45143% Load L3UINT16× 0.1%Read
HR5143doc 45144Total active power (output)UINT16kWRead
HR5144doc 45145Total apparent power (output)UINT16kVARead
HR5145doc 45146Total Percent loadUINT16× 0.1%Read
HR5146doc 45147Power factor L1 (output)UINT16× 0.1Read
HR5147doc 45148Power factor L2 (output)UINT16× 0.1Read
HR5148doc 45149Power factor L3 (output)UINT16× 0.1Read
HR5149doc 45150Current crest factor L1 (output)UINT16× 0.1Read
HR5150doc 45151Current crest factor L2 (output)UINT16× 0.1Read
HR5151doc 45152Current crest factor L3 (output)UINT16× 0.1Read
HR5152doc 45153Parallel System Output CurrentAC L1UINT16ARead
HR5153doc 45154Parallel System Output CurrentAC L2UINT16ARead
HR5154doc 45155Parallel System Output CurrentAC L3UINT16ARead
HR5155doc 45156Parallel System Output Active Power L1UINT16kWRead
HR5156doc 45157Parallel System Output Active Power L2UINT16kWRead
HR5157doc 45158Parallel System Output Active Power L3UINT16kWRead
HR5158doc 45159Parallel System Output Apparent Power L1UINT16kVARead
HR5159doc 45160Parallel System Output Apparent Power L2UINT16kVARead
HR5160doc 45161Parallel System Output Apparent Power L3UINT16kVARead
HR5164doc 45165ParallelSystem Output Total Active PowerUINT16kWRead
HR5165doc 45166ParallelSystem Output Total Apparent PowerUINT16kVARead
HR5167doc 45168Energy Meter kwHUINT32ABCDkWhRead
HR5169doc 45170UPS Installation Load % (Standalone )UINT16× 0.1%Read
HR5170doc 45171UPS Installation Load % (Parallel )UINT16× 0.1%Read
HR5376doc 45377Ambient temperatureUINT16°CRead
HR5377doc 45378Switch gear statusPer bit: 0 = open, 1 = closed.BITMAP16Readbit 0 = Q1; bit 1 = Q2; bit 2 = Q3; bit 4 = Q5
HR5378doc 45379UPS Mode Operation mode of the UPSUINT16Read0 = Indicates that the NMC can not communicate with the IM in the UPS; 1 = Normal operation; 2 = Battery Operation; 3 = UPS is performing a Battery test; 4 = Bypass operation due to a user request.; 5 = Equals the internal “Temporary bypass”. Bypass operation due to fault on system; 6 = Q3 is activated and UPS is in bypass; 7 = The UPS is Off and unavailable; 8 = Reserved; 9 = UPS is in Hotstanby Mode
HR5379doc 45380Number of Active AlarmsUINT16Read
HR5380doc 45381Highest alarm severityUINT16Read0 = none; 1 = informational; 2 = warning; 3 = critical
HR5381doc 45382System ModeUINT16Read1 = UPS(s) in normal or battery operation; 2 = UPS(s) in requested bypass operation, due to a user request; 3 = UPS(s) in “forced bypass” operation, due to fault on system; 4 = All UPS(s) are Off; 5 = Indicates that the NMC is trying to establish communication to the display; 6 = Q3 is closed
HR5385doc 45386NMC/UPS TimeTwo characters per register, high byte first.STRING[8]Read
HR5389doc 45390NMC/UPS DateTwo characters per register, high byte first.STRING[10]Read
HR5633doc 45634Bypass Estimated Lifetime RemainingINT16dRead
HR5635doc 45636Bypass fan Estimated Lifetime RemainingINT16dRead
HR5889doc 45890Frame[0] Power Module[0] Estimated Lifetime RemainingINT16dRead
HR5891doc 45892Frame[0] Power Module[0] Fan Estimated Lifetime RemainingINT16dRead
HR5893doc 45894Frame[0] Power Module[1] Estimated Lifetime RemainingINT16dRead
HR5895doc 45896Frame[0] Power Module[1] Fan Estimated Lifetime RemainingINT16dRead
HR5897doc 45898Frame[0] Power Module[2] Estimated Lifetime RemainingINT16dRead
HR5899doc 45900Frame[0] Power Module[2] Fan Estimated Lifetime RemainingINT16dRead
HR5901doc 45902Frame[0] Power Module[3] Estimated Lifetime RemainingINT16dRead
HR5903doc 45904Frame[0] Power Module[3] Fan Estimated Lifetime RemainingINT16dRead
HR5905doc 45906Frame[0] Power Module[4] Estimated Lifetime RemainingINT16dRead
HR5907doc 45908Frame[0] Power Module[4] Fan Estimated Lifetime RemainingINT16dRead
HR5909doc 45910Frame[0] Power Module[5] Estimated Lifetime RemainingINT16dRead
HR5911doc 45912Frame[0] Power Module[5] Fan Estimated Lifetime RemainingINT16dRead
HR5913doc 45914Frame[0] Power Module[6] Estimated Lifetime RemainingINT16dRead
HR5915doc 45916Frame[0] Power Module[6] Fan Estimated Lifetime RemainingINT16dRead
HR5917doc 45918Frame[0] Power Module[7] Estimated Lifetime RemainingINT16dRead
HR5919doc 45920Frame[0] Power Module[7] Fan Estimated Lifetime RemainingINT16dRead
HR5921doc 45922Frame[0] Power Module[8] Estimated Lifetime RemainingINT16dRead
HR5923doc 45924Frame[0] Power Module[8] Fan Estimated Lifetime RemainingINT16dRead
HR5925doc 45926Frame[0] Power Module[9] Estimated Lifetime RemainingINT16dRead
HR5927doc 45928Frame[0] Power Module[9] Fan Estimated Lifetime RemainingINT16dRead
HR8192doc 48193Number of Power ModulesUINT16Read
HR8193doc 48194Number of Battery Monitor BoardsUINT16Read
HR8194doc 48195Number of Battery Breaker MotorsUINT16Read
HR8195doc 48196Number of Battery ModulesUINT16Read
HR8197doc 48198Number of Battery EnclosuresUINT16Read
HR8198doc 48199Number of PSUsUINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the APC Symmetra PX 250/500 kW

What Modbus registers does the APC Symmetra PX 250/500 kW have?

This map lists 156 registers: 156 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the APC Symmetra PX 250/500 kW Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row shows the Modicon number, the absolute address in hex and decimal; note 12 says absolute address 0 is register 40001 and address zero on the wire.

What byte order does the APC Symmetra PX 250/500 kW use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the APC Symmetra PX 250/500 kW?

Start with HR 0 UPS Status (UPS status bits (on battery, bypass, alarms)); HR 4354 Runtime remaining (Runtime remaining); HR 4358 Estimated charge % (Battery charge %); HR 5145 Total Percent load (Total output load %); HR 5143 Total active power (output) (Total output active power); HR 5378 UPS Mode Operation mode of the UPS (UPS operating mode).

How do I enable Modbus control of the APC Symmetra PX 250/500 kW?

Enable Modbus (serial RTU or TCP) on the AP9635 Network Management Card; see its user's guide.

Where is the official APC Symmetra PX 250/500 kW Modbus documentation?

The source is Modbus Register Map: Symmetra PX 250/500 kW (990-3936D). APC doesn't publish it on its own website, so this map was re-typed from a free copy at https://ccontrols.com/support/dp/APC_RegMap.pdf. It may be an older revision, so check it against the live unit.

More APC Modbus register maps

Other ups register maps

All ups Modbus register maps →

Source: Modbus Register Map: Symmetra PX 250/500 kW · 990-3936D · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.