UPS · Modbus register map
APC Symmetra PX 250/500 kW Modbus register map
Updated 17 November 2026
The Symmetra PX 250/500 kW publishes a large Modbus map through its AP9635 network card, over RTU or TCP. Status and alarm registers at 40001 onward are bit fields; measurements (battery, input, bypass, output per phase, load, energy, temperatures, operating modes and component lifetimes) are 16- or 32-bit holding registers from 44097 onward, with documented multiply/divide scaling.
This page lists 156 Modbus registers for the APC Symmetra PX 250/500 kW — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from APC’s own free documentation (linked below) and checked against it.
- Manufacturer
- APC
- Model
- Symmetra PX 250/500 kW
- Equipment type
- UPS
- Registers
- 156 (0 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- sypx510-sypx516 per revision table
- Also known as
- 990-3936D, Symmetra PX 250 kW, Symmetra PX 500 kW, SYPX
Integration notes: APC Symmetra PX 250/500 kW
Read the status/alarm block from 0 and the measurement blocks from 0x1100 (battery), 0x1200 (input), 0x1300 (bypass), 0x1400 (output) and 0x1500 (system) with function 03 or 04.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | UPS Status | BITMAP16 | UPS status bits (on battery, bypass, alarms) | Read |
| HR 4354 | Runtime remaining | UINT32 ABCD | Runtime remaining | Read |
| HR 4358 | Estimated charge % | UINT16 | Battery charge % | Read |
| HR 5145 | Total Percent load | UINT16 | Total output load % | Read |
| HR 5143 | Total active power (output) | UINT16 | Total output active power | Read |
| HR 5378 | UPS Mode Operation mode of the UPS | UINT16 | UPS operating mode | Read |
Enable Modbus control & writes
Enable Modbus (serial RTU or TCP) on the AP9635 Network Management Card; see its user's guide.
Byte order & addressing
- Status bits are only consistent within one register; do not combine bits across registers.
- Frequencies, PF, crest factor and % load use a 0.1 scale.
Network setup
- Serial/TCP parameters and unit ID are configured on the AP9635 card.
Watch out for
- Some registers were added in later firmware (sypx512, sypx515, sypx516) and may be missing on older firmware.
APC Symmetra PX 250/500 kW Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | UPS Status | 1 = condition active. | BITMAP16 | Read | bit 0 = Load is being powered from battery; bit 1 = Low Battery; bit 2 = System is in Bypass; bit 3 = Self-test in progress; bit 4 = Load is not powered; bit 7 = Abnormal condition present; bit 8 = Power Module Failure; bit 9 = Battery System Failure; bit 10 = Intelligence Module has detected alarm condition; bit 11 = Static Switch failure; bit 12 = Power Supply Unit failure; bit 14 = Warning alarm present; bit 15 = Critical alarm present | |||
| HR | 2doc 40003 | Alarm Register 40003 | 1 = condition active. | BITMAP16 | Read | bit 0 = Lost local network management interface - to - UPS communication; bit 1 = Parallel PBUS cables are swapped; bit 2 = Parallel communication error on PBUS cable 1; bit 3 = Parallel communication error on PBUS cable 2; bit 4 = Overload on parallel installation; bit 5 = Parallel mixed mode error: Units in battery and normal operation; bit 6 = UPS parallel address configuration number error; bit 7 = Parallel master not detected (deprecated); bit 8 = Parallel unit disabled; bit 9 = Parallel unit is incompatible; bit 10 = PBUS cable termination fault; bit 11 = Parallel unit not present (deprecated); bit 12 = Isolated Test mode is active; bit 13 = Parallel unit redundancy lost; bit 15 = Parallel load share error | |||
| HR | 3doc 40004 | Alarm Register 40004 | 1 = condition active. | BITMAP16 | Read | bit 0 = On battery in response to an input power failure; bit 1 = In bypass: User-initiated from Front Panel; bit 2 = UPS operation mode - Forced bypass; bit 3 = In Bypass: For maintenance; bit 4 = Started a self-test; bit 5 = Output power turned off; bit 6 = UPS operation mode - Initialize; bit 7 = UPS operation mode - Hot standby; bit 8 = Compensating for a low input voltage; bit 9 = Compensating for a high input voltage; bit 10 = Input voltage waveform error detected; bit 11 = Input phase sequence error; bit 12 = Input frequency fault; bit 13 = Output frequency fault; bit 14 = Mega Tie mode is active; bit 15 = External synchronization source is selected and out of tolerance | |||
| HR | 4doc 40005 | Alarm Register 40005 | 1 = condition active. | BITMAP16 | Read | bit 0 = Bypass voltage error: low voltage; bit 1 = Bypass voltage error: high voltage; bit 2 = Bypass voltage waveform error detected; bit 3 = Bypass input frequency fault; bit 4 = Bypass phase sequence error; bit 5 = Output voltage low; bit 6 = Output voltage high; bit 7 = Output voltage waveform error detected; bit 8 = Overload; bit 9 = Overload on bypass static switch; bit 10 = Ambient temperature out of range; bit 11 = EPO activated; bit 12 = Ground fault detected; bit 13 = PSU module failed | |||
| HR | 5doc 40006 | Alarm Register 40006 | 1 = condition active. | BITMAP16 | Read | bit 0 = System locked in bypass operation; bit 1 = Batteries are discharging; bit 2 = PSU module not present; bit 3 = System frequency not detected; bit 5 = Charge power is reduced; bit 6 = Display communication to MIM and RIM is lost; bit 7 = CBUS terminator fault; bit 8 = ABUS terminator fault; bit 10 = MIM not present; bit 11 = MIM heartbeat signal error; bit 12 = RIM in control; bit 13 = Battery condition is weak; bit 14 = Battery condition is poor | |||
| HR | 6doc 40007 | Alarm Register 40007 | 1 = condition active. | BITMAP16 | Read | bit 0 = Battery voltage error - voltage above warning level; bit 1 = Battery voltage error - voltage above shutdown level; bit 2 = Battery monitor board communication error; bit 4 = Battery is below minimum acceptable runtime; bit 5 = Power module communication to MIM error; bit 6 = Power module locked by IM; bit 7 = Power module operation mode is different from other modules; bit 9 = Switchgear board not present; bit 10 = Switchgear board communication error; bit 11 = ID & Relay board not present; bit 12 = ID & Relay board communication error; bit 13 = Battery voltage collapse detected; bit 14 = Power module redundancy lost | |||
| HR | 7doc 40008 | Alarm Register 40008 | 1 = condition active. | BITMAP16 | Read | bit 7 = Load on subfeed is above warning level; bit 8 = Load on subfeed is above critical level; bit 9 = Load on UPS is above warning level; bit 10 = Power module firmware version is incompatible; bit 11 = Static Bypass Switch module not present; bit 12 = Overload on installation; bit 13 = Bypass static switch communication error; bit 14 = RIM not present; bit 15 = RIM heartbeat signal error | |||
| HR | 8doc 40009 | Alarm Register 40009 | 1 = condition active. | BITMAP16 | Read | bit 0 = Bonding wire between neutral and ground is missing; bit 1 = Bonding wire between neutral and ground error; bit 2 = Power module communication to RIM error; bit 3 = Battery voltage error - voltage below warning level; bit 4 = Battery voltage error - voltage below shutdown level; bit 5 = ECT board has an error; bit 6 = External connections board not present; bit 7 = EPO circuit test mode is enabled; bit 8 = IM internal memory for storing configuration settings error; bit 10 = Auxiliary monitor board for maintenance bypass panel comm error; bit 11 = Auxiliary monitor board for battery breaker enclosure comm error; bit 13 = Power module removed from the system; bit 14 = INFO Battery module removed from system | |||
| HR | 9doc 40010 | Alarm Register 40010 | 1 = condition active. | BITMAP16 | Read | bit 0 = Power module fault exists; bit 1 = Power module warning; bit 3 = Power module fan fault; bit 4 = Power module is disabled; bit 5 = Power module lifetime error: close to end; bit 6 = Power module lifetime error: lifetime exceeded; bit 7 = Power module fan lifetime error: close to end; bit 8 = Power module fan lifetimerror: lifetime exceeded; bit 9 = Breaker Q1 open; bit 10 = Breaker Q2 open; bit 11 = Breaker Q3 closed; bit 12 = Breaker Q4 open; bit 13 = Breaker Q5 open; bit 14 = Power module phase-neutral displacement fault | |||
| HR | 10doc 40011 | Alarm Register 40011 | 1 = condition active. | BITMAP16 | Read | bit 0 = Forced bypass switch activated; bit 1 = Bypass static switch disabled; bit 2 = Bypass static switch self test failed; bit 4 = Bypass static switch 1 fan fault; bit 5 = Bypass static switch 1 fan weak; bit 8 = Bypass static switch error; module has a critical error; bit 9 = Bypass static switch warning; module is not working properly; bit 10 = Power enclosure air filter lifetime exceeded (informational); bit 11 = Power enclosure air filter lifetime exceeded (warning); bit 14 = Door in MBwD enclosure open; bit 15 = Q2 shunt open error | |||
| HR | 11doc 40012 | Alarm Register 40012 | 1 = condition active. | BITMAP16 | Read | bit 0 = Subfeed breaker SB1 open; bit 1 = Subfeed breaker SB2 open; bit 2 = Subfeed breaker SB3 open; bit 3 = Subfeed breaker SB4 open; bit 4 = Subfeed breaker SB5 open; bit 5 = Subfeed breaker SB6 open; bit 6 = Subfeed breaker SB7 open; bit 7 = Subfeed breaker SB8 open; bit 8 = Subfeed breaker SB9 open; bit 9 = Subfeed breaker SB10 open; bit 10 = Subfeed breaker SB11 open; bit 11 = Subfeed breaker SB12 open; bit 12 = Subfeed breaker SB13 open; bit 13 = Subfeed breaker SB14 open; bit 14 = Subfeed breaker SB15 open; bit 15 = Subfeed breaker SB16 open | |||
| HR | 12doc 40013 | Alarm Register 40013 | 1 = condition active. | BITMAP16 | Read | bit 0 = Breaker Q1 open; bit 1 = Breaker Q2 open; bit 2 = Breaker Q3 closed; bit 3 = Breaker Q4 open; bit 4 = Breaker Q5 open; bit 5 = Door in maintenance bypass panel enclosure open; bit 6 = Q2 shunt open error; bit 7 = MBP enclosure ECT board has an error; bit 8 = ID & Relay board memory card full; bit 9 = Input 3 activated: Battery ground fault detected; bit 10 = ID & Relay board: System firmware not stored at memory card; bit 11 = Input 6 activated: Emergency module off; bit 12 = Input 7 activated: Door in UPS I/O enclosure opened; bit 13 = Input 1 activated: Reduce charging power; bit 14 = IDRC memory card not present; bit 15 = ID & Relay board memory card error | |||
| HR | 13doc 40014 | Alarm Register 40014 | 1 = condition active. | BITMAP16 | Read | bit 0 = Battery breaker open; bit 1 = Battery module fuse cleared or condition of battery is weak; bit 2 = Battery voltage symmetry error; bit 3 = Internal battery temperature exceeds threshold; bit 5 = Battery temperature sensor fault; bit 6 = Mixed battery configuration; bit 7 = Battery module type support error; bit 8 = Battery string disconnected; bit 9 = Battery side car 1 fuse error; bit 11 = Battery enclosure PSU error; bit 12 = Battery breaker motor PSU error; bit 13 = Battery enclosure door open; bit 14 = ECT board has an error; bit 15 = Battery breaker shunt open error | |||
| HR | 14doc 40015 | Alarm Register 40015 | 1 = condition active. | BITMAP16 | Read | bit 0 = Battery breaker open error; bit 1 = Battery breaker enclosure fuse 1 error; bit 2 = Battery breaker enclosure fuse 2 error; bit 3 = Battery temperature 1 high; bit 4 = Battery temperature 2 high; bit 5 = Battery temperature sensor 1 fault; bit 6 = Battery temperature sensor 2 fault; bit 7 = Battery breaker enclosure door open error; bit 8 = Battery breaker enclosure ECT board has an error; bit 9 = Battery breaker shunt open error; bit 10 = Battery ground fault detected error | |||
| HR | 15doc 40016 | Alarm Register 40016 | 1 = condition active. | BITMAP16 | Read | bit 0 = Battery fuse bank 1 cleared; bit 1 = Battery fuse bank 2 cleared; bit 2 = Battery fuse bank 3 cleared; bit 3 = Battery fuse bank 4 cleared; bit 4 = Battery fuse bank 5 cleared; bit 5 = Battery fuse bank 6 cleared; bit 6 = Battery fuse bank 7 cleared; bit 7 = Battery fuse bank 8 cleared; bit 8 = Input for gas alarm has been activated | |||
| HR | 16doc 40017 | Alarm Register 40017 | 1 = condition active. | BITMAP16 | Read | bit 0 = Test firmware installed at power module; bit 1 = Not expected firmware installed at power module; bit 2 = Not expected firmware installed at battery monitor board; bit 3 = Not expected firmware installed at SBS module; bit 4 = Not expected firmware installed at ID & Relay board; bit 5 = Not expected firmware installed at switchgear board; bit 6 = Not expected firmware installed at auxiliary monitor board for maintenance; bit 7 = Not expected firmware installed at auxiliary monitor board for battery breaker; bit 8 = Not expected firmware installed at redundant IM; bit 9 = Test firmware installed at battery monitor board; bit 10 = Test firmware installed at SBS module; bit 11 = Test firmware installed at ID & Relay board; bit 12 = Test firmware installed at switchgear board; bit 13 = Test firmware installed at auxiliary monitor board for maintenance bypass panel; bit 14 = Test firmware installed at auxiliary monitor board for battery breaker enclosure; bit 15 = Test firmware installed at IM | |||
| HR | 4096doc 44097 | NMC Model Number | Two characters per register, high byte first. | STRING[18] | Read | ||||
| HR | 4105doc 44106 | NMC Serial Number | Two characters per register, high byte first. | STRING[16] | Read | ||||
| HR | 4113doc 44114 | NMC Firmware Revision APP | Two characters per register, high byte first. | STRING[18] | Read | ||||
| HR | 4122doc 44123 | NMC Hardware Revision | Two characters per register, high byte first. | STRING[18] | Read | ||||
| HR | 4131doc 44132 | NMC Date of Manufacture | Two characters per register, high byte first. | STRING[12] | Read | ||||
| HR | 4137doc 44138 | UPS Model Name | Two characters per register, high byte first. | STRING[16] | Read | ||||
| HR | 4145doc 44146 | UPS Serial Number | Two characters per register, high byte first. | STRING[12] | Read | ||||
| HR | 4151doc 44152 | UPS Firmware Version | Two characters per register, high byte first. | STRING[24] | Read | ||||
| HR | 4163doc 44164 | UPS Name | Two characters per register, high byte first. | STRING[8] | Read | ||||
| HR | 4167doc 44168 | Parallel System Name | Two characters per register, high byte first. | STRING[8] | Read | ||||
| HR | 4352doc 44353 | Time on battery | UINT32 | ABCD | s | Read | |||
| HR | 4354doc 44355 | Runtime remaining | UINT32 | ABCD | s | Read | |||
| HR | 4356doc 44357 | Estimated charge time | UINT32 | ABCD | s | Read | |||
| HR | 4358doc 44359 | Estimated charge % | UINT16 | % | Read | ||||
| HR | 4359doc 44360 | Battery (+) Voltage | UINT16 | V | Read | ||||
| HR | 4360doc 44361 | Battery (-) Voltage | UINT16 | V | Read | ||||
| HR | 4361doc 44362 | Battery (+) Current | INT16 | A | Read | ||||
| HR | 4362doc 44363 | Battery (-) Current | INT16 | A | Read | ||||
| HR | 4363doc 44364 | Total time on battery | UINT32 | ABCD | s | Read | |||
| HR | 4365doc 44366 | Total number of times on battery | UINT16 | Read | |||||
| HR | 4367doc 44368 | BatterySystem/Temperature | UINT16 | °C | Read | ||||
| HR | 4368doc 44369 | User Supplied Battery System Charger Status | 1 = condition active. | BITMAP16 | Read | bit 0 = Float Charging | |||
| HR | 4369doc 44370 | Battery Power | INT16 | × 0.1 | kW | Read | |||
| HR | 4370doc 44371 | Available Amp Hours | UINT16 | Ah | Read | ||||
| HR | 4371doc 44372 | Last Battery Replacement | Two characters per register, high byte first. | STRING[8] | Read | ||||
| HR | 4608doc 44609 | Frequency (input) | UINT16 | × 0.1 | Hz | Read | |||
| HR | 4609doc 44610 | Voltage L1-2 (input) | UINT16 | V | Read | ||||
| HR | 4610doc 44611 | Voltage L2-3 (input) | UINT16 | V | Read | ||||
| HR | 4611doc 44612 | Voltage L3-1 (input) | UINT16 | V | Read | ||||
| HR | 4612doc 44613 | Current L1 (input) | UINT16 | A | Read | ||||
| HR | 4613doc 44614 | Current L2 (input) | UINT16 | A | Read | ||||
| HR | 4614doc 44615 | Current L3 (input) | UINT16 | A | Read | ||||
| HR | 4615doc 44616 | Active power L1 (input) | UINT16 | kW | Read | ||||
| HR | 4616doc 44617 | Active power L2 (input) | UINT16 | kW | Read | ||||
| HR | 4617doc 44618 | Active power L3 (input) | UINT16 | kW | Read | ||||
| HR | 4618doc 44619 | Apparent power L1 (input) | UINT16 | kVA | Read | ||||
| HR | 4619doc 44620 | Apparent power L2 (input) | UINT16 | kVA | Read | ||||
| HR | 4620doc 44621 | Apparent power L3 (input) | UINT16 | kVA | Read | ||||
| HR | 4621doc 44622 | Total active power (input) | UINT16 | kW | Read | ||||
| HR | 4622doc 44623 | Total apparent power (input) | UINT16 | kVA | Read | ||||
| HR | 4623doc 44624 | Current L1 (parallel input) | UINT16 | A | Read | ||||
| HR | 4624doc 44625 | Current L2 (parallel input) | UINT16 | A | Read | ||||
| HR | 4625doc 44626 | Current L3 (parallel input) | UINT16 | A | Read | ||||
| HR | 4864doc 44865 | Frequency (bypass) | UINT16 | × 0.1 | Hz | Read | |||
| HR | 4865doc 44866 | Voltage L1-2 (bypass) | UINT16 | V | Read | ||||
| HR | 4866doc 44867 | Voltage L2-3 (bypass) | UINT16 | V | Read | ||||
| HR | 4867doc 44868 | Voltage L3-1 (bypass) | UINT16 | V | Read | ||||
| HR | 4868doc 44869 | Current L1 (bypass) | UINT16 | A | Read | ||||
| HR | 4869doc 44870 | Current L2 (bypass) | UINT16 | A | Read | ||||
| HR | 4870doc 44871 | Current L3 (bypass) | UINT16 | A | Read | ||||
| HR | 4871doc 44872 | Active power L1 (bypass) | UINT16 | kW | Read | ||||
| HR | 4872doc 44873 | Active power L2 (bypass) | UINT16 | kW | Read | ||||
| HR | 4873doc 44874 | Active power L3 (bypass) | UINT16 | kW | Read | ||||
| HR | 4874doc 44875 | Apparent power L1 (bypass) | UINT16 | kVA | Read | ||||
| HR | 4875doc 44876 | Apparent power L2 (bypass) | UINT16 | kVA | Read | ||||
| HR | 4876doc 44877 | Apparent power L3 (bypass) | UINT16 | kVA | Read | ||||
| HR | 4877doc 44878 | Total active power (bypass) | UINT16 | kW | Read | ||||
| HR | 4878doc 44879 | Total apparent power (bypass) | UINT16 | kVA | Read | ||||
| HR | 4879doc 44880 | Current L1 (parallel bypass) | UINT16 | A | Read | ||||
| HR | 4880doc 44881 | Current L2 (parallel bypass) | UINT16 | A | Read | ||||
| HR | 4881doc 44882 | Current L3 (parallel bypass) | UINT16 | A | Read | ||||
| HR | 5120doc 45121 | Nominal (Apparent) output rating | UINT16 | kVA | Read | ||||
| HR | 5121doc 45122 | Frequency (output) | UINT16 | × 0.1 | Hz | Read | |||
| HR | 5122doc 45123 | Voltage L1-2 (output) | UINT16 | V | Read | ||||
| HR | 5123doc 45124 | Voltage L2-3 (output) | UINT16 | V | Read | ||||
| HR | 5124doc 45125 | Voltage L3-1 (output) | UINT16 | V | Read | ||||
| HR | 5125doc 45126 | Current L1 (output) | UINT16 | A | Read | ||||
| HR | 5126doc 45127 | Current L2 (output) | UINT16 | A | Read | ||||
| HR | 5127doc 45128 | Current L3 (output) | UINT16 | A | Read | ||||
| HR | 5128doc 45129 | Peak current L1 (output) | UINT32 | ABCD | A | Read | |||
| HR | 5130doc 45131 | Peak current L2 (output) | UINT32 | ABCD | A | Read | |||
| HR | 5132doc 45133 | Peak current L3 (output) | UINT32 | ABCD | A | Read | |||
| HR | 5134doc 45135 | Active power L1 (output) | UINT16 | kW | Read | ||||
| HR | 5135doc 45136 | Active power L2 (output) | UINT16 | kW | Read | ||||
| HR | 5136doc 45137 | Active power L3 (output) | UINT16 | kW | Read | ||||
| HR | 5137doc 45138 | Apparent power L1 (output) | UINT16 | kVA | Read | ||||
| HR | 5138doc 45139 | Apparent power L2 (output) | UINT16 | kVA | Read | ||||
| HR | 5139doc 45140 | Apparent power L3 (output) | UINT16 | kVA | Read | ||||
| HR | 5140doc 45141 | % Load L1 | UINT16 | × 0.1 | % | Read | |||
| HR | 5141doc 45142 | % Load L2 | UINT16 | × 0.1 | % | Read | |||
| HR | 5142doc 45143 | % Load L3 | UINT16 | × 0.1 | % | Read | |||
| HR | 5143doc 45144 | Total active power (output) | UINT16 | kW | Read | ||||
| HR | 5144doc 45145 | Total apparent power (output) | UINT16 | kVA | Read | ||||
| HR | 5145doc 45146 | Total Percent load | UINT16 | × 0.1 | % | Read | |||
| HR | 5146doc 45147 | Power factor L1 (output) | UINT16 | × 0.1 | Read | ||||
| HR | 5147doc 45148 | Power factor L2 (output) | UINT16 | × 0.1 | Read | ||||
| HR | 5148doc 45149 | Power factor L3 (output) | UINT16 | × 0.1 | Read | ||||
| HR | 5149doc 45150 | Current crest factor L1 (output) | UINT16 | × 0.1 | Read | ||||
| HR | 5150doc 45151 | Current crest factor L2 (output) | UINT16 | × 0.1 | Read | ||||
| HR | 5151doc 45152 | Current crest factor L3 (output) | UINT16 | × 0.1 | Read | ||||
| HR | 5152doc 45153 | Parallel System Output CurrentAC L1 | UINT16 | A | Read | ||||
| HR | 5153doc 45154 | Parallel System Output CurrentAC L2 | UINT16 | A | Read | ||||
| HR | 5154doc 45155 | Parallel System Output CurrentAC L3 | UINT16 | A | Read | ||||
| HR | 5155doc 45156 | Parallel System Output Active Power L1 | UINT16 | kW | Read | ||||
| HR | 5156doc 45157 | Parallel System Output Active Power L2 | UINT16 | kW | Read | ||||
| HR | 5157doc 45158 | Parallel System Output Active Power L3 | UINT16 | kW | Read | ||||
| HR | 5158doc 45159 | Parallel System Output Apparent Power L1 | UINT16 | kVA | Read | ||||
| HR | 5159doc 45160 | Parallel System Output Apparent Power L2 | UINT16 | kVA | Read | ||||
| HR | 5160doc 45161 | Parallel System Output Apparent Power L3 | UINT16 | kVA | Read | ||||
| HR | 5164doc 45165 | ParallelSystem Output Total Active Power | UINT16 | kW | Read | ||||
| HR | 5165doc 45166 | ParallelSystem Output Total Apparent Power | UINT16 | kVA | Read | ||||
| HR | 5167doc 45168 | Energy Meter kwH | UINT32 | ABCD | kWh | Read | |||
| HR | 5169doc 45170 | UPS Installation Load % (Standalone ) | UINT16 | × 0.1 | % | Read | |||
| HR | 5170doc 45171 | UPS Installation Load % (Parallel ) | UINT16 | × 0.1 | % | Read | |||
| HR | 5376doc 45377 | Ambient temperature | UINT16 | °C | Read | ||||
| HR | 5377doc 45378 | Switch gear status | Per bit: 0 = open, 1 = closed. | BITMAP16 | Read | bit 0 = Q1; bit 1 = Q2; bit 2 = Q3; bit 4 = Q5 | |||
| HR | 5378doc 45379 | UPS Mode Operation mode of the UPS | UINT16 | Read | 0 = Indicates that the NMC can not communicate with the IM in the UPS; 1 = Normal operation; 2 = Battery Operation; 3 = UPS is performing a Battery test; 4 = Bypass operation due to a user request.; 5 = Equals the internal “Temporary bypass”. Bypass operation due to fault on system; 6 = Q3 is activated and UPS is in bypass; 7 = The UPS is Off and unavailable; 8 = Reserved; 9 = UPS is in Hotstanby Mode | ||||
| HR | 5379doc 45380 | Number of Active Alarms | UINT16 | Read | |||||
| HR | 5380doc 45381 | Highest alarm severity | UINT16 | Read | 0 = none; 1 = informational; 2 = warning; 3 = critical | ||||
| HR | 5381doc 45382 | System Mode | UINT16 | Read | 1 = UPS(s) in normal or battery operation; 2 = UPS(s) in requested bypass operation, due to a user request; 3 = UPS(s) in “forced bypass” operation, due to fault on system; 4 = All UPS(s) are Off; 5 = Indicates that the NMC is trying to establish communication to the display; 6 = Q3 is closed | ||||
| HR | 5385doc 45386 | NMC/UPS Time | Two characters per register, high byte first. | STRING[8] | Read | ||||
| HR | 5389doc 45390 | NMC/UPS Date | Two characters per register, high byte first. | STRING[10] | Read | ||||
| HR | 5633doc 45634 | Bypass Estimated Lifetime Remaining | INT16 | d | Read | ||||
| HR | 5635doc 45636 | Bypass fan Estimated Lifetime Remaining | INT16 | d | Read | ||||
| HR | 5889doc 45890 | Frame[0] Power Module[0] Estimated Lifetime Remaining | INT16 | d | Read | ||||
| HR | 5891doc 45892 | Frame[0] Power Module[0] Fan Estimated Lifetime Remaining | INT16 | d | Read | ||||
| HR | 5893doc 45894 | Frame[0] Power Module[1] Estimated Lifetime Remaining | INT16 | d | Read | ||||
| HR | 5895doc 45896 | Frame[0] Power Module[1] Fan Estimated Lifetime Remaining | INT16 | d | Read | ||||
| HR | 5897doc 45898 | Frame[0] Power Module[2] Estimated Lifetime Remaining | INT16 | d | Read | ||||
| HR | 5899doc 45900 | Frame[0] Power Module[2] Fan Estimated Lifetime Remaining | INT16 | d | Read | ||||
| HR | 5901doc 45902 | Frame[0] Power Module[3] Estimated Lifetime Remaining | INT16 | d | Read | ||||
| HR | 5903doc 45904 | Frame[0] Power Module[3] Fan Estimated Lifetime Remaining | INT16 | d | Read | ||||
| HR | 5905doc 45906 | Frame[0] Power Module[4] Estimated Lifetime Remaining | INT16 | d | Read | ||||
| HR | 5907doc 45908 | Frame[0] Power Module[4] Fan Estimated Lifetime Remaining | INT16 | d | Read | ||||
| HR | 5909doc 45910 | Frame[0] Power Module[5] Estimated Lifetime Remaining | INT16 | d | Read | ||||
| HR | 5911doc 45912 | Frame[0] Power Module[5] Fan Estimated Lifetime Remaining | INT16 | d | Read | ||||
| HR | 5913doc 45914 | Frame[0] Power Module[6] Estimated Lifetime Remaining | INT16 | d | Read | ||||
| HR | 5915doc 45916 | Frame[0] Power Module[6] Fan Estimated Lifetime Remaining | INT16 | d | Read | ||||
| HR | 5917doc 45918 | Frame[0] Power Module[7] Estimated Lifetime Remaining | INT16 | d | Read | ||||
| HR | 5919doc 45920 | Frame[0] Power Module[7] Fan Estimated Lifetime Remaining | INT16 | d | Read | ||||
| HR | 5921doc 45922 | Frame[0] Power Module[8] Estimated Lifetime Remaining | INT16 | d | Read | ||||
| HR | 5923doc 45924 | Frame[0] Power Module[8] Fan Estimated Lifetime Remaining | INT16 | d | Read | ||||
| HR | 5925doc 45926 | Frame[0] Power Module[9] Estimated Lifetime Remaining | INT16 | d | Read | ||||
| HR | 5927doc 45928 | Frame[0] Power Module[9] Fan Estimated Lifetime Remaining | INT16 | d | Read | ||||
| HR | 8192doc 48193 | Number of Power Modules | UINT16 | Read | |||||
| HR | 8193doc 48194 | Number of Battery Monitor Boards | UINT16 | Read | |||||
| HR | 8194doc 48195 | Number of Battery Breaker Motors | UINT16 | Read | |||||
| HR | 8195doc 48196 | Number of Battery Modules | UINT16 | Read | |||||
| HR | 8197doc 48198 | Number of Battery Enclosures | UINT16 | Read | |||||
| HR | 8198doc 48199 | Number of PSUs | UINT16 | Read |
Notes on this map
- Source host: this is the APC document as republished by integrator Control Concepts (ccontrols.com); APC's own download links refuse automated requests.
- Word order: note 2 says INT32/UINT32 have the most significant word in n+0, so 32-bit values are ABCD. Note 3: function codes 3 and 4 are both supported.
- Strings are two characters per register, high byte first, without a null terminator.
- Left out: rows whose multiply and divide columns disagree (the parallel-system %-load registers show multiply 1 but divide 10), rows with no data type, and per-module lifetime registers for frames 1-3 (frame 0 kept as the pattern).
- Accessing an undefined range returns an illegal-data-address error. Detailed comms settings are in the AP9635 user's guide.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the APC Symmetra PX 250/500 kW
What Modbus registers does the APC Symmetra PX 250/500 kW have?
This map lists 156 registers: 156 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the APC Symmetra PX 250/500 kW Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row shows the Modicon number, the absolute address in hex and decimal; note 12 says absolute address 0 is register 40001 and address zero on the wire.
What byte order does the APC Symmetra PX 250/500 kW use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the APC Symmetra PX 250/500 kW?
Start with HR 0 UPS Status (UPS status bits (on battery, bypass, alarms)); HR 4354 Runtime remaining (Runtime remaining); HR 4358 Estimated charge % (Battery charge %); HR 5145 Total Percent load (Total output load %); HR 5143 Total active power (output) (Total output active power); HR 5378 UPS Mode Operation mode of the UPS (UPS operating mode).
How do I enable Modbus control of the APC Symmetra PX 250/500 kW?
Enable Modbus (serial RTU or TCP) on the AP9635 Network Management Card; see its user's guide.
Where is the official APC Symmetra PX 250/500 kW Modbus documentation?
The source is Modbus Register Map: Symmetra PX 250/500 kW (990-3936D). APC doesn't publish it on its own website, so this map was re-typed from a free copy at https://ccontrols.com/support/dp/APC_RegMap.pdf. It may be an older revision, so check it against the live unit.
More APC Modbus register maps
- UPS
APC (Schneider Electric) Galaxy VL 200-500 kW three-phase UPS
Schneider Electric Galaxy VL 200-500 kW UPS with firmware 7.23 or later, per register map 990-6447.
Also known as: Galaxy VL, GVL, Galaxy VL 200 kW, Galaxy VL 500 kW - Air handler (in-row chilled-water cooling unit)
APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm)
APC by Schneider Electric InRow ACRC30x (300 mm chilled water) units, per register map part number 990-4742B.
Also known as: ACRC30x, ACRC300, ACRC301, InRow RC 300 mm - Air handler (in-row data-centre cooling unit)
APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786)
APC / Schneider Electric InRow ACRD60x and ACRC60x in-row cooling units, register map part number 990-5786A.
Also known as: ACRD60x, ACRC60x, InRow ACRD60x, InRow ACRC60x, 990-5786 - Air handler (in-row self-contained DX cooling unit)
APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit
APC by Schneider Electric InRow SC (ACSC 100 series) self-contained cooling units, per register map part number 990-3027D.
Also known as: ACSC100, InRow SC, InRow ACSC - Air handler (in-row data-centre DX cooling unit)
APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B)
APC / Schneider Electric InRow RD cooling units, register map part number 990-3576B (08/2015).
Also known as: InRow RD, 990-3576B, Schneider Electric InRow RD - UPS
APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702)
APC Smart-UPS (excluding SMT, SMX, SURTD and SRT prefixes), Smart-UPS VT and MGE Galaxy 3500 through Network Management Card AP9630/AP9631/AP9635 (TCP) or AP9635 (RTU), part number 990-5702.
Also known as: 990-5702, AP9630, AP9631, AP9635, Smart-UPS VT, MGE Galaxy 3500, Schneider Electric APC Smart-UPS
Other ups register maps
All ups Modbus register maps →
Source: Modbus Register Map: Symmetra PX 250/500 kW · 990-3936D · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.