- InRow RD direct-expansion cooling unit (Modbus register map 990-3576B)
Air handler (in-row data-centre DX cooling unit) · Modbus register map
APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B) Modbus register map
Updated 19 November 2026
The InRow RD is an in-row direct-expansion cooling unit for data-centre rows and contained aisles. Its controller serves Modbus RTU and Modbus TCP with everything in holding registers. This page covers the single-register points: group configuration and fan-speed settings, unit operating mode and type, compressor and I/O states, and about 50 alarm flags.
This page lists 72 Modbus registers for the APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B) — 16 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from APC (Schneider Electric)’s own free documentation (linked below) and checked against it.
- Manufacturer
- APC (Schneider Electric)
- Model
- InRow RD direct-expansion cooling unit (Modbus register map 990-3576B)
- Equipment type
- Air handler (in-row data-centre DX cooling unit)
- Registers
- 72 (16 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- InRow RD, 990-3576B, Schneider Electric InRow RD
- Source document
- Modbus Register Map: InRow RD · 990-3576B · rev. 2015-08
Integration notes: APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B)
Read OPERATE_MODE (141), UNIT_TYPE (142) and OVERALL_STATUS (64) for the unit state, then the individual alarm flags from 256 up. Group settings such as fan speed preference (7) can be written with function code 6.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 141 | OPERATE_MODE | UINT16 | Operating mode | Read |
| HR 64 | OVERALL_STATUS | UINT16 | Overall alarm status | Read |
| HR 142 | UNIT_TYPE | UINT16 | Unit type | Read |
| HR 211 | COMPRESSOR_STATE | UINT16 | Compressor on/off | Read |
| HR 259 | COOL_FAIL | UINT16 | Cooling failure alarm | Read |
| HR 278 | WATER_DETECTED | UINT16 | Water detected alarm | Read |
| HR 7 | FAN_SPEED_PREFERENCE | UINT16 | Group fan speed preference | Read/write |
| HR 6 | CONFIGURATION_TYPE | UINT16 | Group configuration type | Read/write |
Enable Modbus control & writes
Not described in the register map.
Byte order & addressing
- The decimal absolute register number is the wire address; Modicon numbering adds 40001.
- Points shown on unsupported units read as 0 rather than returning an error.
Network setup
- Modbus RTU (serial) and Modbus TCP are both supported per the map; serial settings and unit ID are not given in this document.
Watch out for
- A large block read can take 2 s or more; read fewer registers or raise the timeout if requests time out.
- Reading before the controller has data returns an invalid-address error.
APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 6doc 6 (0x0006) | CONFIGURATION_TYPE | UINT16 | Read/write | 0 = RACS; 1 = Spot; 2 = In-Row; 3 = HACS; 4 = CACS | ||||
| HR | 7doc 7 (0x0007) | FAN_SPEED_PREFERENCE | UINT16 | Read/write | 0 = Low; 1 = Med-Low; 2 = Med; 3 = Med-High; 4 = High | ||||
| HR | 8doc 8 (0x0008) | CAPACITY_CTRL | UINT16 | Read/write | 0 = Discrete (Disc); 1 = Proportional (Prop) | ||||
| HR | 9doc 9 (0x0009) | FAN_SPEED_CTRL | UINT16 | Read/write | 0 = Automatic; 1 = Manual | ||||
| HR | 34doc 34 (0x0022) | RUNTIME_BALANCING_ENABLE | UINT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 35doc 35 (0x0023) | LOAD_ASSIST_ENABLE | UINT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 40doc 40 (0x0028) | ACTIVE_FLOW_CONTROL_BIAS | UINT16 | Read/write | 0 = Positive; 1 = Slightly Positive; 2 = Zero; 3 = Slightly Neg; 4 = Negative | ||||
| HR | 41doc 41 (0x0029) | ACTIVE_FLOW_CONTROL_STATUS | UINT16 | Read | 0 = Under; 1 = Okay; 2 = Over; 3 = N/A | ||||
| HR | 42doc 42 (0x002A) | ACTIVE_FLOW_CONTROL_LAMP_TEST | UINT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 64doc 64 (0x0040) | OVERALL_STATUS | UINT16 | Read | 0 = No Alarm; 2 = Informational; 4 = Warning; 8 = Critical | ||||
| HR | 141doc 141 (0x008D) | OPERATE_MODE | UINT16 | Read | 0 = Standby; 1 = On; 2 = Idle; 4 = Service; 5 = Backup; 6 = Assist | ||||
| HR | 142doc 142 (0x008E) | UNIT_TYPE | UINT16 | Read | 0 = Not Configured; 1 = Fluid Cooled; 2 = Air Cooled | ||||
| HR | 193doc 193 (0x00C1) | AIR_FILTER_SERV_INT_ALARM | UINT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 202doc 202 (0x00CA) | IDLE_ON_LEAK | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 203doc 203 (0x00CB) | INPUT_NORMAL | UINT16 | Read/write | 0 = Open; 1 = Closed | ||||
| HR | 204doc 204 (0x00CC) | INPUT_STATE | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| HR | 205doc 205 (0x00CD) | OUTPUT_NORMAL | UINT16 | Read/write | 0 = Open; 1 = Closed | ||||
| HR | 206doc 206 (0x00CE) | OUTPUT_STATE | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| HR | 207doc 207 (0x00CF) | OUTPUT_SOURCE | UINT16 | Read/write | 0 = Any Alarm; 1 = Only Critical Alarms | ||||
| HR | 208doc 208 (0x00D0) | OHE_INPUT_NORMAL | UINT16 | Read/write | 0 = Open; 1 = Closed | ||||
| HR | 209doc 209 (0x00D1) | OHE_INPUT_STATE | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| HR | 210doc 210 (0x00D2) | OHE_OUTPUT_STATE | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| HR | 211doc 211 (0x00D3) | COMPRESSOR_STATE | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 216doc 216 (0x00D8) | UNIT_ROLE_OVERRIDE | UINT16 | Read/write | 0 = Automatic; 1 = Forced On | ||||
| HR | 217doc 217 (0x00D9) | IDLE_ON_COOL_FAIL | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 256doc 256 (0x0100) | INTERNAL_COMM_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 257doc 257 (0x0101) | ALINK_ISOLATION_RELAY_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 258doc 258 (0x0102) | EXTERNAL_COMMUNICATION_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 259doc 259 (0x0103) | COOL_FAIL | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 260doc 260 (0x0104) | RACK_TEMP_HIGH_VIOLATION | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 261doc 261 (0x0105) | AIR_FILTER_CLOGGED | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 262doc 262 (0x0106) | UPPER_RTN_AIR_SENSOR_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 264doc 264 (0x0108) | LOWER_RTN_AIR_SENSOR_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 265doc 265 (0x0109) | UPPER_SPLY_AIR_SENSOR_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 266doc 266 (0x010A) | MIDDLE_SPLY_AIR_SENSOR_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 267doc 267 (0x010B) | LOWER_SPLY_AIR_SENSOR_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 268doc 268 (0x010C) | RACK_TEMP_SENSOR_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 269doc 269 (0x010D) | CONDENSOR_FLUID_ACUATOR_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 270doc 270 (0x010E) | HIGH_DISCHARGE_PRESSURE_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 271doc 271 (0x010F) | LOW_SUCTION_PRESSURE_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 272doc 272 (0x0110) | EVAPORATOR_FAN_1_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 273doc 273 (0x0111) | EVAPORATOR_FAN_2_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 274doc 274 (0x0112) | EVAPORATOR_FAN_3_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 275doc 275 (0x0113) | EVAPORATOR_FAN_4_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 276doc 276 (0x0114) | EVAPORATOR_FAN_5_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 277doc 277 (0x0115) | EVAPORATOR_FAN_6_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 278doc 278 (0x0116) | WATER_DETECTED | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 279doc 279 (0x0117) | CHECK_CONDENSATE_SYSTEM | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 280doc 280 (0x0118) | CONDENSATE_PAN_FULL | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 281doc 281 (0x0119) | TOP_FAN_PWRSP_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 282doc 282 (0x011A) | BOTTOM_FAN_PWRSP_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 283doc 283 (0x011B) | AIR_FILTER_RUNHOUR_VIOLATION | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 284doc 284 (0x011C) | GROUP_COMM_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 285doc 285 (0x011D) | SUPPLY_HIGH_TEMP_VIOLATION | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 286doc 286 (0x011E) | RETURN_HIGH_TEMP_VIOLATION | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 287doc 287 (0x011F) | FILTER_DP_SENSOR_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 288doc 288 (0x0120) | SUCTION_TEMP_SENSOR_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 289doc 289 (0x0121) | SUCTION_PRESSURE_SENSOR_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 290doc 290 (0x0122) | DISCHARGE_PRESS_SENSOR_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 291doc 291 (0x0123) | DISCRETE_INPUT_ABNORMAL | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 292doc 292 (0x0124) | PERSISTENT_HIGH_DISCHARGE_PRESSURE | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 293doc 293 (0x0125) | PERSISTENT_LOW_SUCTION_PRESSURE | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 297doc 297 (0x0129) | OUTSIDE_HEAT_EXCHANGE_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 299doc 299 (0x012B) | UNIT_TYPE_CONFLICT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 300doc 300 (0x012C) | LIQUID_REFRIGERANT_SENSOR_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 301doc 301 (0x012D) | EXCESSIVE_COMP_CYCLING_ALARM | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 302doc 302 (0x012E) | NO_BACKUP_UNITS_AVAILABLE | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 303doc 303 (0x012F) | COMPRESSOR_DID_NOT_START_ALARM | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 304doc 304 (0x0130) | ECOAISLE_DOOR_OPEN_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 305doc 305 (0x0131) | NUM_OF_ACTIVE_FLOW_CONTROLLERS | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 306doc 306 (0x0132) | INSUFFICIENT_AIRFLOW_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 307doc 307 (0x0133) | ACTIVE_FLOW_CONTROLLER_SENSOR_FAULT | UINT16 | Read | 0 = Clear; 1 = Alarm |
Notes on this map
- The download is a ZIP holding JBOR-7NZSGZ_R2_EN.pdf (and an identical _SRC copy).
- All two-register points (setpoints, deadband, temperatures, cooling output and demand, airflow, fan speed, pressures, PID terms, run hours, thresholds and the Modbus diagnostic counters) are typed "LONG" in the map, a type its own data-type list does not define, so they are left out here: signedness for LONG is not stated. The baud-rate register at 65534 is typed "INTEGER", also undefined, and is left out too.
- Every point kept here is ENUM, which the map defines as an unsigned 16-bit value with a list of states.
- Reads use function code 3 or 4; writes use function code 16, or 6 for single-register points.
- Text registers (unit name, location, model, serial number, firmware and hardware revision, date of manufacture at 65-140) are left out; reserved rows are left out.
- Some alarm names are cut off in the printed cells (0x0124, 0x0133 and 0x0131); 0x0124 and 0x0133 are completed here as PERSISTENT_HIGH_DISCHARGE_PRESSURE and ACTIVE_FLOW_CONTROLLER_SENSOR_FAULT. 0x0131 shows NUM_OF_ACTIVE_FLOW_CONTROLLERS (the end of the name is hidden) with Clear/Alarm values, kept as printed.
- Single-register reads of reserved or undefined registers return an exception; a block read starting on a valid register returns zeros for undefined ones.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B)
What Modbus registers does the APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B) have?
This map lists 72 registers: 72 holding registers. 16 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map prints the 'Absolute Starting Register Number' in hex and in decimal. Note 11 says absolute register 0 equals Modicon 40001 and is address zero on the wire, so the decimal number is the wire address (e.g. SUPPLY_TEMP 149 = 0x0095 = Modicon 40150).
What are the minimum Modbus registers to integrate the APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B)?
Start with HR 141 OPERATE_MODE (Operating mode); HR 64 OVERALL_STATUS (Overall alarm status); HR 142 UNIT_TYPE (Unit type); HR 211 COMPRESSOR_STATE (Compressor on/off); HR 259 COOL_FAIL (Cooling failure alarm); HR 278 WATER_DETECTED (Water detected alarm); HR 7 FAN_SPEED_PREFERENCE (Group fan speed preference); HR 6 CONFIGURATION_TYPE (Group configuration type).
How do I enable Modbus control of the APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B)?
Not described in the register map.
Where is the official APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B) Modbus documentation?
The source is Modbus Register Map: InRow RD (990-3576B), revision 2015-08, published free by APC (Schneider Electric) at https://download.se.com/files?p_Doc_Ref=SPD_JBOR-7NZSGZ_EN.
More APC (Schneider Electric) Modbus register maps
- UPS
APC (Schneider Electric) Galaxy VL 200-500 kW three-phase UPS
Schneider Electric Galaxy VL 200-500 kW UPS with firmware 7.23 or later, per register map 990-6447.
Also known as: Galaxy VL, GVL, Galaxy VL 200 kW, Galaxy VL 500 kW - Air handler (in-row chilled-water cooling unit)
APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm)
APC by Schneider Electric InRow ACRC30x (300 mm chilled water) units, per register map part number 990-4742B.
Also known as: ACRC30x, ACRC300, ACRC301, InRow RC 300 mm - Air handler (in-row data-centre cooling unit)
APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786)
APC / Schneider Electric InRow ACRD60x and ACRC60x in-row cooling units, register map part number 990-5786A.
Also known as: ACRD60x, ACRC60x, InRow ACRD60x, InRow ACRC60x, 990-5786 - Air handler (in-row self-contained DX cooling unit)
APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit
APC by Schneider Electric InRow SC (ACSC 100 series) self-contained cooling units, per register map part number 990-3027D.
Also known as: ACSC100, InRow SC, InRow ACSC - UPS
APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702)
APC Smart-UPS (excluding SMT, SMX, SURTD and SRT prefixes), Smart-UPS VT and MGE Galaxy 3500 through Network Management Card AP9630/AP9631/AP9635 (TCP) or AP9635 (RTU), part number 990-5702.
Also known as: 990-5702, AP9630, AP9631, AP9635, Smart-UPS VT, MGE Galaxy 3500, Schneider Electric APC Smart-UPS - UPS
APC Symmetra PX 250/500 kW
APC Symmetra PX 250/500 kW three-phase UPS via Network Management Card AP9635, register map 990-3936D (firmware sypx510 to sypx516 changes listed in the source).
Also known as: 990-3936D, Symmetra PX 250 kW, Symmetra PX 500 kW, SYPX
Other hvac equipment register maps
- Thermostat / heating controller (district heating and HVAC)
Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP)
ECL Comfort 210, 296 and 310 controllers (and B versions) with any application key; many parameters depend on the loaded application.
Also known as: ECL Comfort 210, ECL Comfort 296, ECL Comfort 310, ECL Comfort 210B, ECL Comfort 310B, 087H3020, 087H3024, 087H3030, 087H3034, 087H3040, 087H3044, 087H3050, 087H3054 - Air handler (heat recovery ventilation unit)
Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP)
Futura L/M/S from firmware FUA.P.06.71, register list v5.0 (13.10.2025). Futura L+ uses different addresses and is not covered.
Also known as: Futura L, Futura M, Futura S, JABLOTRON FUTURA - Thermostat (room operating unit with sensors)
LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU)
LSTAT-800/801/802 room operating units (all button layouts), user manual version 3.2.8 (document 88085811).
Also known as: L-STAT, LSTAT-800, LSTAT-801, LSTAT-802, LSTAT-800-Gx-Lx, LSTAT-801-Gx-Lx, LSTAT-802-Gx-Lx - Thermostat / fan coil controller
Neptronic EFCB Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB Series fan coil controllers (24, 120 and 240 Vac; 2 or 4 relays) with the Modbus communication module, guide EFCB-Modbus Guide-260626.
Also known as: EFCB10TU2, EFCB10TU4, EFCB11TU2, EFCB11TU4, EFCB12TU2, EFCB12TU4, EFCB fan coil controller - Air handler evaporative cooler (adiabatic cooling / humidification)
Neptronic SKVF evaporative cooler / humidifier (Modbus communication module)
Neptronic SKVF series evaporative coolers with the Modbus communication module, guide SKVF-Modbus Guide-211025.
Also known as: SKVF Evaporative Cooler, SKVF Series, Neptronic SKVF Modbus - Thermostat / room controller (chilled beam, fan coil water circuits)
Swegon CONDUCTOR W1 room controller (waterborne cooling/heating, Modbus RTU)
Swegon CONDUCTOR W1 room controller, software 1.38 and later (technical manual updated 2015-06-15).
Also known as: CONDUCTOR RE W1, Conductor W1, 942334001
All hvac equipment Modbus register maps →
Source: Modbus Register Map: InRow RD · 990-3576B · rev. 2015-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.