Air handler (in-row data-centre DX cooling unit) · Modbus register map

APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B) Modbus register map

Updated 19 November 2026

Short answer

The InRow RD is an in-row direct-expansion cooling unit for data-centre rows and contained aisles. Its controller serves Modbus RTU and Modbus TCP with everything in holding registers. This page covers the single-register points: group configuration and fan-speed settings, unit operating mode and type, compressor and I/O states, and about 50 alarm flags.

This page lists 72 Modbus registers for the APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B) — 16 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from APC (Schneider Electric)’s own free documentation (linked below) and checked against it.

Manufacturer
APC (Schneider Electric)
Model
InRow RD direct-expansion cooling unit (Modbus register map 990-3576B)
Equipment type
Air handler (in-row data-centre DX cooling unit)
Registers
72 (16 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
InRow RD, 990-3576B, Schneider Electric InRow RD
Source document
Modbus Register Map: InRow RD · 990-3576B · rev. 2015-08
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B)

Integration in brief

Read OPERATE_MODE (141), UNIT_TYPE (142) and OVERALL_STATUS (64) for the unit state, then the individual alarm flags from 256 up. Group settings such as fan speed preference (7) can be written with function code 6.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 141OPERATE_MODEUINT16Operating modeRead
HR 64OVERALL_STATUSUINT16Overall alarm statusRead
HR 142UNIT_TYPEUINT16Unit typeRead
HR 211COMPRESSOR_STATEUINT16Compressor on/offRead
HR 259COOL_FAILUINT16Cooling failure alarmRead
HR 278WATER_DETECTEDUINT16Water detected alarmRead
HR 7FAN_SPEED_PREFERENCEUINT16Group fan speed preferenceRead/write
HR 6CONFIGURATION_TYPEUINT16Group configuration typeRead/write

Enable Modbus control & writes

Not described in the register map.

Byte order & addressing

Network setup

Watch out for

APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

72 of 72 shown
APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR6doc 6 (0x0006)CONFIGURATION_TYPEUINT16Read/write0 = RACS; 1 = Spot; 2 = In-Row; 3 = HACS; 4 = CACS
HR7doc 7 (0x0007)FAN_SPEED_PREFERENCEUINT16Read/write0 = Low; 1 = Med-Low; 2 = Med; 3 = Med-High; 4 = High
HR8doc 8 (0x0008)CAPACITY_CTRLUINT16Read/write0 = Discrete (Disc); 1 = Proportional (Prop)
HR9doc 9 (0x0009)FAN_SPEED_CTRLUINT16Read/write0 = Automatic; 1 = Manual
HR34doc 34 (0x0022)RUNTIME_BALANCING_ENABLEUINT16Read/write0 = Disable; 1 = Enable
HR35doc 35 (0x0023)LOAD_ASSIST_ENABLEUINT16Read/write0 = Disable; 1 = Enable
HR40doc 40 (0x0028)ACTIVE_FLOW_CONTROL_BIASUINT16Read/write0 = Positive; 1 = Slightly Positive; 2 = Zero; 3 = Slightly Neg; 4 = Negative
HR41doc 41 (0x0029)ACTIVE_FLOW_CONTROL_STATUSUINT16Read0 = Under; 1 = Okay; 2 = Over; 3 = N/A
HR42doc 42 (0x002A)ACTIVE_FLOW_CONTROL_LAMP_TESTUINT16Read/write0 = Disable; 1 = Enable
HR64doc 64 (0x0040)OVERALL_STATUSUINT16Read0 = No Alarm; 2 = Informational; 4 = Warning; 8 = Critical
HR141doc 141 (0x008D)OPERATE_MODEUINT16Read0 = Standby; 1 = On; 2 = Idle; 4 = Service; 5 = Backup; 6 = Assist
HR142doc 142 (0x008E)UNIT_TYPEUINT16Read0 = Not Configured; 1 = Fluid Cooled; 2 = Air Cooled
HR193doc 193 (0x00C1)AIR_FILTER_SERV_INT_ALARMUINT16Read/write0 = Disable; 1 = Enable
HR202doc 202 (0x00CA)IDLE_ON_LEAKUINT16Read/write0 = No; 1 = Yes
HR203doc 203 (0x00CB)INPUT_NORMALUINT16Read/write0 = Open; 1 = Closed
HR204doc 204 (0x00CC)INPUT_STATEUINT16Read0 = Open; 1 = Closed
HR205doc 205 (0x00CD)OUTPUT_NORMALUINT16Read/write0 = Open; 1 = Closed
HR206doc 206 (0x00CE)OUTPUT_STATEUINT16Read0 = Open; 1 = Closed
HR207doc 207 (0x00CF)OUTPUT_SOURCEUINT16Read/write0 = Any Alarm; 1 = Only Critical Alarms
HR208doc 208 (0x00D0)OHE_INPUT_NORMALUINT16Read/write0 = Open; 1 = Closed
HR209doc 209 (0x00D1)OHE_INPUT_STATEUINT16Read0 = Open; 1 = Closed
HR210doc 210 (0x00D2)OHE_OUTPUT_STATEUINT16Read0 = Open; 1 = Closed
HR211doc 211 (0x00D3)COMPRESSOR_STATEUINT16Read0 = Off; 1 = On
HR216doc 216 (0x00D8)UNIT_ROLE_OVERRIDEUINT16Read/write0 = Automatic; 1 = Forced On
HR217doc 217 (0x00D9)IDLE_ON_COOL_FAILUINT16Read/write0 = No; 1 = Yes
HR256doc 256 (0x0100)INTERNAL_COMM_FAULTUINT16Read0 = Clear; 1 = Alarm
HR257doc 257 (0x0101)ALINK_ISOLATION_RELAY_FAULTUINT16Read0 = Clear; 1 = Alarm
HR258doc 258 (0x0102)EXTERNAL_COMMUNICATION_FAULTUINT16Read0 = Clear; 1 = Alarm
HR259doc 259 (0x0103)COOL_FAILUINT16Read0 = Clear; 1 = Alarm
HR260doc 260 (0x0104)RACK_TEMP_HIGH_VIOLATIONUINT16Read0 = Clear; 1 = Alarm
HR261doc 261 (0x0105)AIR_FILTER_CLOGGEDUINT16Read0 = Clear; 1 = Alarm
HR262doc 262 (0x0106)UPPER_RTN_AIR_SENSOR_FAULTUINT16Read0 = Clear; 1 = Alarm
HR264doc 264 (0x0108)LOWER_RTN_AIR_SENSOR_FAULTUINT16Read0 = Clear; 1 = Alarm
HR265doc 265 (0x0109)UPPER_SPLY_AIR_SENSOR_FAULTUINT16Read0 = Clear; 1 = Alarm
HR266doc 266 (0x010A)MIDDLE_SPLY_AIR_SENSOR_FAULTUINT16Read0 = Clear; 1 = Alarm
HR267doc 267 (0x010B)LOWER_SPLY_AIR_SENSOR_FAULTUINT16Read0 = Clear; 1 = Alarm
HR268doc 268 (0x010C)RACK_TEMP_SENSOR_FAULTUINT16Read0 = Clear; 1 = Alarm
HR269doc 269 (0x010D)CONDENSOR_FLUID_ACUATOR_FAULTUINT16Read0 = Clear; 1 = Alarm
HR270doc 270 (0x010E)HIGH_DISCHARGE_PRESSURE_FAULTUINT16Read0 = Clear; 1 = Alarm
HR271doc 271 (0x010F)LOW_SUCTION_PRESSURE_FAULTUINT16Read0 = Clear; 1 = Alarm
HR272doc 272 (0x0110)EVAPORATOR_FAN_1_FAULTUINT16Read0 = Clear; 1 = Alarm
HR273doc 273 (0x0111)EVAPORATOR_FAN_2_FAULTUINT16Read0 = Clear; 1 = Alarm
HR274doc 274 (0x0112)EVAPORATOR_FAN_3_FAULTUINT16Read0 = Clear; 1 = Alarm
HR275doc 275 (0x0113)EVAPORATOR_FAN_4_FAULTUINT16Read0 = Clear; 1 = Alarm
HR276doc 276 (0x0114)EVAPORATOR_FAN_5_FAULTUINT16Read0 = Clear; 1 = Alarm
HR277doc 277 (0x0115)EVAPORATOR_FAN_6_FAULTUINT16Read0 = Clear; 1 = Alarm
HR278doc 278 (0x0116)WATER_DETECTEDUINT16Read0 = Clear; 1 = Alarm
HR279doc 279 (0x0117)CHECK_CONDENSATE_SYSTEMUINT16Read0 = Clear; 1 = Alarm
HR280doc 280 (0x0118)CONDENSATE_PAN_FULLUINT16Read0 = Clear; 1 = Alarm
HR281doc 281 (0x0119)TOP_FAN_PWRSP_FAULTUINT16Read0 = Clear; 1 = Alarm
HR282doc 282 (0x011A)BOTTOM_FAN_PWRSP_FAULTUINT16Read0 = Clear; 1 = Alarm
HR283doc 283 (0x011B)AIR_FILTER_RUNHOUR_VIOLATIONUINT16Read0 = Clear; 1 = Alarm
HR284doc 284 (0x011C)GROUP_COMM_FAULTUINT16Read0 = Clear; 1 = Alarm
HR285doc 285 (0x011D)SUPPLY_HIGH_TEMP_VIOLATIONUINT16Read0 = Clear; 1 = Alarm
HR286doc 286 (0x011E)RETURN_HIGH_TEMP_VIOLATIONUINT16Read0 = Clear; 1 = Alarm
HR287doc 287 (0x011F)FILTER_DP_SENSOR_FAULTUINT16Read0 = Clear; 1 = Alarm
HR288doc 288 (0x0120)SUCTION_TEMP_SENSOR_FAULTUINT16Read0 = Clear; 1 = Alarm
HR289doc 289 (0x0121)SUCTION_PRESSURE_SENSOR_FAULTUINT16Read0 = Clear; 1 = Alarm
HR290doc 290 (0x0122)DISCHARGE_PRESS_SENSOR_FAULTUINT16Read0 = Clear; 1 = Alarm
HR291doc 291 (0x0123)DISCRETE_INPUT_ABNORMALUINT16Read0 = Clear; 1 = Alarm
HR292doc 292 (0x0124)PERSISTENT_HIGH_DISCHARGE_PRESSUREUINT16Read0 = Clear; 1 = Alarm
HR293doc 293 (0x0125)PERSISTENT_LOW_SUCTION_PRESSUREUINT16Read0 = Clear; 1 = Alarm
HR297doc 297 (0x0129)OUTSIDE_HEAT_EXCHANGE_FAULTUINT16Read0 = Clear; 1 = Alarm
HR299doc 299 (0x012B)UNIT_TYPE_CONFLICTUINT16Read0 = Clear; 1 = Alarm
HR300doc 300 (0x012C)LIQUID_REFRIGERANT_SENSOR_FAULTUINT16Read0 = Clear; 1 = Alarm
HR301doc 301 (0x012D)EXCESSIVE_COMP_CYCLING_ALARMUINT16Read0 = Clear; 1 = Alarm
HR302doc 302 (0x012E)NO_BACKUP_UNITS_AVAILABLEUINT16Read0 = Clear; 1 = Alarm
HR303doc 303 (0x012F)COMPRESSOR_DID_NOT_START_ALARMUINT16Read0 = Clear; 1 = Alarm
HR304doc 304 (0x0130)ECOAISLE_DOOR_OPEN_FAULTUINT16Read0 = Clear; 1 = Alarm
HR305doc 305 (0x0131)NUM_OF_ACTIVE_FLOW_CONTROLLERSUINT16Read0 = Clear; 1 = Alarm
HR306doc 306 (0x0132)INSUFFICIENT_AIRFLOW_FAULTUINT16Read0 = Clear; 1 = Alarm
HR307doc 307 (0x0133)ACTIVE_FLOW_CONTROLLER_SENSOR_FAULTUINT16Read0 = Clear; 1 = Alarm

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B)

What Modbus registers does the APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B) have?

This map lists 72 registers: 72 holding registers. 16 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map prints the 'Absolute Starting Register Number' in hex and in decimal. Note 11 says absolute register 0 equals Modicon 40001 and is address zero on the wire, so the decimal number is the wire address (e.g. SUPPLY_TEMP 149 = 0x0095 = Modicon 40150).

What are the minimum Modbus registers to integrate the APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B)?

Start with HR 141 OPERATE_MODE (Operating mode); HR 64 OVERALL_STATUS (Overall alarm status); HR 142 UNIT_TYPE (Unit type); HR 211 COMPRESSOR_STATE (Compressor on/off); HR 259 COOL_FAIL (Cooling failure alarm); HR 278 WATER_DETECTED (Water detected alarm); HR 7 FAN_SPEED_PREFERENCE (Group fan speed preference); HR 6 CONFIGURATION_TYPE (Group configuration type).

How do I enable Modbus control of the APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B)?

Not described in the register map.

Where is the official APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B) Modbus documentation?

The source is Modbus Register Map: InRow RD (990-3576B), revision 2015-08, published free by APC (Schneider Electric) at https://download.se.com/files?p_Doc_Ref=SPD_JBOR-7NZSGZ_EN.

More APC (Schneider Electric) Modbus register maps

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: Modbus Register Map: InRow RD · 990-3576B · rev. 2015-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.