Easy Modbus
  1. Home
  2. Modbus register maps
  3. APC
  4. Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702)

UPS · Modbus register map

APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702) Modbus register map

Updated 17 November 2026

Short answer

APC's older Smart-UPS family, plus the three-phase Smart-UPS VT and MGE Galaxy 3500, publish a compact Modbus map through the Network Management Card. Everything is a single 16-bit holding register: status words with per-bit flags, battery charge and runtime, input/output voltages and frequency, per-phase currents and load, transfer settings and an 8-character UPS ID. Modbus TCP is on AP9630/AP9631/AP9635 cards; RTU only on AP9635.

This page lists 73 Modbus registers for the APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from APC’s own free documentation (linked below) and checked against it.

Manufacturer
APC
Model
Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702)
Equipment type
UPS
Registers
73 (0 writable)
Transport
Modbus TCP, Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
990-5702, AP9630, AP9631, AP9635, Smart-UPS VT, MGE Galaxy 3500, Schneider Electric APC Smart-UPS
Source document
Modbus Register Map - MGE Galaxy 3500, Smart-UPS VT, and Smart-UPS · 990-5702 · rev. 2018-08 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702)

Integration in brief

Read holding registers 0-77 with function 03; a block read that starts on a valid register returns zeros for reserved ones. Status Word 3 (0x0003) gives on-line/on-battery/overload/low-battery/replace-battery at a glance.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 3Status Word 3BITMAP16Status word 3: on line / on battery / low batteryRead
HR 5% Battery State of Charge (0-100)UINT16Battery state of chargeRead
HR 6Runtime RemainingUINT16Runtime remaining (minutes)Read
HR 12% Power drawn by loadUINT16Load percentRead
HR 17Input VoltageUINT16Input voltageRead
HR 14Actual Output VoltageUINT16Output voltageRead
HR 8UPS Internal TemperatureUINT16Internal temperatureRead

Enable Modbus control & writes

Enable Modbus on the Network Management Card (TCP on AP9630/AP9631/AP9635, serial RTU on AP9635).

Byte order & addressing

Network setup

Watch out for

APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

73 of 73 shown
APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001Status Word 0BITMAP16Readbit 0 = UPS turning on; bit 1 = UPS in bypass due to an internal fault (indicated through register 0002 or 0003); bit 2 = UPS going to bypass due to command; bit 3 = UPS in bypass due to command; bit 4 = UPS returning from bypass; bit 5 = UPS in bypass mode as a result of manual bypass control; bit 6 = UPS ready to power load upon user command; bit 7 = UPS ready to power load upon return of normal line or upon user command
HR1doc 40002Status Word 1BITMAP16Readbit 0 = UPS output not powered due to low battery shutdown; bit 1 = UPS unable to transfer to on-battery operation due to overload; bit 2 = UPS fault - main relay malfunction; bit 3 = UPS in sleep mode; bit 4 = UPS in shutdown mode; bit 5 = UPS fault - battery charger failure; bit 7 = UPS fault - internal temperature has exceeded nominal limits
HR2doc 40003Status Word 2BITMAP16Readbit 4 = UPS fault - UPS in bypass; or DC imbalance in inverter; bit 5 = UPS commanded out of bypass with no batteries attached; or No batteries attached; bit 6 = Boost or trim relay fault; bit 7 = Inverter fault; or Output overvoltage
HR3doc 40004Status Word 3BITMAP16Readbit 0 = Performing battery calibration discharge; bit 1 = Smart trim; bit 2 = Smart boost; bit 3 = On line; bit 4 = On battery; bit 5 = Overload; bit 6 = Low battery (runtime remaining <= low battery duraton); bit 7 = Replace battery
HR4doc 40005Line QualityUINT16Read0 = Unacceptable utility line quality; 255 = Acceptable utility line quality (0x00FF)
HR5doc 40006% Battery State of Charge (0-100)UINT16%Read
HR6doc 40007Runtime RemainingUINT16minRead
HR7doc 40008Battery VoltageUINT16VRead
HR8doc 40009UPS Internal TemperatureInternal or battery temperature, depending on the UPS.UINT16°CRead
HR9doc 40010Amps Drawn by LoadUINT16ARead
HR10doc 40011Quantity of battery packs with bad batteriesUINT16Read
HR11doc 40012Quantity of battery packsUINT16Read
HR12doc 40013% Power drawn by loadUINT16%Read
HR13doc 40014Nominal Output VoltageUINT16VRead
HR14doc 40015Actual Output VoltageUINT16VRead
HR15doc 40016Maximum Input Voltage Since Last ReadingUINT16VRead
HR16doc 40017Minimum Input Voltage Since Last ReadingUINT16VRead
HR17doc 40018Input VoltageUINT16VRead
HR18doc 40019Input FrequencyUINT16HzRead
HR19doc 40020Measure-UPS Temperature Reading (Probe 1)Needs the discontinued AP9612TH environmental monitoring card.UINT16°CRead
HR20doc 40021Measure-UPS Humidity Reading (Probe 1)Needs the discontinued AP9612TH environmental monitoring card.UINT16%Read
HR21doc 40022Measure-UPS Temperature Reading (Probe 2)Needs the discontinued AP9612TH environmental monitoring card.UINT16°CRead
HR22doc 40023Measure-UPS Humidity Reading (Probe 2)Needs the discontinued AP9612TH environmental monitoring card.UINT16%Read
HR23doc 40024Measure-UPS Contact PositionNeeds the discontinued AP9612TH environmental monitoring card.UINT16Read
HR26doc 40027Minimum Return Battery CapacityUINT16%Read
HR27doc 40028Lower Transfer PointUINT16VRead
HR28doc 40029Upper Transfer PointUINT16VRead
HR29doc 40030Nominal Output VoltageUINT16VRead
HR30doc 40031Shutdown DelayUINT16sRead
HR31doc 40032Low Battery DurationUINT16minRead
HR32doc 40033Turn On DelayUINT16sRead
HR33doc 40034SensitivityUINT16Read0 = not supported by this UPS; 72 = highest (normal) sensitivity to utility voltage fluctuations; 76 = lowest sensitivity to utility voltage fluctuations; 77 = medium (reduced) sensitivity to utility voltage fluctuations
HR34doc 40035UPS ID Character #1One ASCII character per register.STRING[2]Read
HR35doc 40036UPS ID Character #2One ASCII character per register.STRING[2]Read
HR36doc 40037UPS ID Character #3One ASCII character per register.STRING[2]Read
HR37doc 40038UPS ID Character #4One ASCII character per register.STRING[2]Read
HR38doc 40039UPS ID Character #5One ASCII character per register.STRING[2]Read
HR39doc 40040UPS ID Character #6One ASCII character per register.STRING[2]Read
HR40doc 40041UPS ID Character #7One ASCII character per register.STRING[2]Read
HR41doc 40042UPS ID Character #8One ASCII character per register.STRING[2]Read
HR42doc 40043Status Word 4BITMAP16Readbit 3 = Run time below alarm threshold; bit 4 = XR frame fault; bit 5 = Output voltage out of range; bit 6 = System not synchronized; bit 7 = No batteries; bit 8 = Battery voltage high; bit 9 = Fault found in register 0049, 004A, 004B or 004C; bit 10 = Site wiring fault
HR43doc 40044Status Word 5BITMAP16Readbit 0 = An installed Power Module has failed; bit 3 = An installed Battery has failed; bit 4 = Load is above alarm threshold; bit 7 = Bypass not in range (either freq or voltage unacceptable); bit 10 = UPS in bypass due to internal fault; bit 11 = UPS in bypass due to overload; bit 12 = System is in maintenance bypass; bit 14 = System level fan failed
HR44doc 40045Nominal Battery VoltageUINT16VRead
HR45doc 40046Actual Battery VoltageUINT16VRead
HR46doc 40047Utility Input Voltage Phase AUINT16VRead
HR47doc 40048Utility Input Current Phase AUINT16ARead
HR48doc 40049Bypass Input Voltage Phase AUINT16VRead
HR49doc 40050Percent of Maximum Output VA’s Phase A @ n+0UINT16%Read
HR50doc 40051Percent of Maximum Output VA’s Phase A @ n+xUINT16%Read
HR51doc 40052Phase A Output kVAUINT16kVARead
HR52doc 40053Output Voltage Phase AUINT16VRead
HR54doc 40055Peak Output Current Phase AUINT16ARead
HR55doc 40056Utility Input Voltage Phase BUINT16VRead
HR56doc 40057Utility Input Current Phase BUINT16ARead
HR57doc 40058Bypass Input Voltage Phase BUINT16VRead
HR58doc 40059Percent of Maximum Output VA’s Phase B @ n+0UINT16%Read
HR59doc 40060Percent of Maximum Output VA’s Phase B @ n+xUINT16%Read
HR60doc 40061Phase B Output kVAUINT16kVARead
HR61doc 40062Output Voltage Phase BUINT16VRead
HR62doc 40063Output Current Phase BUINT16ARead
HR63doc 40064Peak Output Current Phase BUINT16ARead
HR64doc 40065Utility Input Voltage Phase CUINT16VRead
HR65doc 40066Utility Input Current Phase CUINT16ARead
HR66doc 40067Bypass Input Voltage Phase CUINT16VRead
HR67doc 40068Percent of Maximum Output VA’s Phase C @ n+0UINT16%Read
HR68doc 40069Percent of Maximum Output VA’s Phase C @ n+xUINT16%Read
HR69doc 40070Phase C Output kVAUINT16kVARead
HR70doc 40071Output Voltage Phase CUINT16VRead
HR71doc 40072Output Current Phase CUINT16ARead
HR72doc 40073Peak Output Current Phase CUINT16ARead
HR75doc 40076Status Word 8BITMAP16Readbit 0 = Parallel config fault; bit 1 = Dust filter must be changed soon; bit 2 = Dust filter must be changed immediately
HR76doc 40077Status Word 9BITMAP16Readbit 0 = EPO active; bit 1 = SBS fault; bit 2 = System config fault; bit 3 = Emergency PSU fault; bit 4 = Weak battery; bit 5 = Battery over temp; bit 6 = Mechanical bypass active (not a fault; bit 7 = Parallel redundancy lost; bit 8 = Parallel bus comm lost cable 1; bit 9 = Parallel bus comm lost cable 2; bit 10 = Auxiliary bus comm lost; bit 11 = Parallel bus termination fault cable 1; bit 12 = Parallel bus termination fault cable 2; bit 13 = Auxiliary bus termination fault; bit 14 = No master in parallel system; bit 15 = Overload on parallel unit
HR77doc 40078Battery CurrentPositive = current into the battery, negative = current out.INT16ARead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702)

What Modbus registers does the APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702) have?

This map lists 73 registers: 73 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map prints the Modicon number (40001...) next to the absolute address in hex and decimal; note 10 states that absolute address 0 equals register 40001 and is address zero on the wire.

What are the minimum Modbus registers to integrate the APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702)?

Start with HR 3 Status Word 3 (Status word 3: on line / on battery / low battery); HR 5 % Battery State of Charge (0-100) (Battery state of charge); HR 6 Runtime Remaining (Runtime remaining (minutes)); HR 12 % Power drawn by load (Load percent); HR 17 Input Voltage (Input voltage); HR 14 Actual Output Voltage (Output voltage); HR 8 UPS Internal Temperature (Internal temperature).

How do I enable Modbus control of the APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702)?

Enable Modbus on the Network Management Card (TCP on AP9630/AP9631/AP9635, serial RTU on AP9635).

Where is the official APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702) Modbus documentation?

The source is Modbus Register Map - MGE Galaxy 3500, Smart-UPS VT, and Smart-UPS (990-5702), revision 2018-08. APC doesn't publish it on its own website, so this map was re-typed from a free copy at https://media.distributordatasolutions.com/schneider2/2020q3/documents/8a7edbbda9bc66f4fc6a910f8bcea3af8cb87a47.pdf. It may be an older revision, so check it against the live unit.

More APC Modbus register maps

Other ups register maps

All ups Modbus register maps →

Source: Modbus Register Map - MGE Galaxy 3500, Smart-UPS VT, and Smart-UPS · 990-5702 · rev. 2018-08 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.