- Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702)
UPS · Modbus register map
APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702) Modbus register map
Updated 17 November 2026
APC's older Smart-UPS family, plus the three-phase Smart-UPS VT and MGE Galaxy 3500, publish a compact Modbus map through the Network Management Card. Everything is a single 16-bit holding register: status words with per-bit flags, battery charge and runtime, input/output voltages and frequency, per-phase currents and load, transfer settings and an 8-character UPS ID. Modbus TCP is on AP9630/AP9631/AP9635 cards; RTU only on AP9635.
This page lists 73 Modbus registers for the APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from APC’s own free documentation (linked below) and checked against it.
- Manufacturer
- APC
- Model
- Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702)
- Equipment type
- UPS
- Registers
- 73 (0 writable)
- Transport
- Modbus TCP, Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- 990-5702, AP9630, AP9631, AP9635, Smart-UPS VT, MGE Galaxy 3500, Schneider Electric APC Smart-UPS
Integration notes: APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702)
Read holding registers 0-77 with function 03; a block read that starts on a valid register returns zeros for reserved ones. Status Word 3 (0x0003) gives on-line/on-battery/overload/low-battery/replace-battery at a glance.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 3 | Status Word 3 | BITMAP16 | Status word 3: on line / on battery / low battery | Read |
| HR 5 | % Battery State of Charge (0-100) | UINT16 | Battery state of charge | Read |
| HR 6 | Runtime Remaining | UINT16 | Runtime remaining (minutes) | Read |
| HR 12 | % Power drawn by load | UINT16 | Load percent | Read |
| HR 17 | Input Voltage | UINT16 | Input voltage | Read |
| HR 14 | Actual Output Voltage | UINT16 | Output voltage | Read |
| HR 8 | UPS Internal Temperature | UINT16 | Internal temperature | Read |
Enable Modbus control & writes
Enable Modbus on the Network Management Card (TCP on AP9630/AP9631/AP9635, serial RTU on AP9635).
Byte order & addressing
- Line quality (0x0004) reads 0x00FF when acceptable and 0 when not.
- Sensitivity (0x0021) returns an ASCII letter H, M or L (0 = not supported).
Network setup
- Serial and TCP parameters are set in the Network Management Card configuration; the map itself gives no defaults.
Watch out for
- SMT, SMX, SURTD and SRT Smart-UPS models use a different map and are not covered here.
APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Status Word 0 | BITMAP16 | Read | bit 0 = UPS turning on; bit 1 = UPS in bypass due to an internal fault (indicated through register 0002 or 0003); bit 2 = UPS going to bypass due to command; bit 3 = UPS in bypass due to command; bit 4 = UPS returning from bypass; bit 5 = UPS in bypass mode as a result of manual bypass control; bit 6 = UPS ready to power load upon user command; bit 7 = UPS ready to power load upon return of normal line or upon user command | ||||
| HR | 1doc 40002 | Status Word 1 | BITMAP16 | Read | bit 0 = UPS output not powered due to low battery shutdown; bit 1 = UPS unable to transfer to on-battery operation due to overload; bit 2 = UPS fault - main relay malfunction; bit 3 = UPS in sleep mode; bit 4 = UPS in shutdown mode; bit 5 = UPS fault - battery charger failure; bit 7 = UPS fault - internal temperature has exceeded nominal limits | ||||
| HR | 2doc 40003 | Status Word 2 | BITMAP16 | Read | bit 4 = UPS fault - UPS in bypass; or DC imbalance in inverter; bit 5 = UPS commanded out of bypass with no batteries attached; or No batteries attached; bit 6 = Boost or trim relay fault; bit 7 = Inverter fault; or Output overvoltage | ||||
| HR | 3doc 40004 | Status Word 3 | BITMAP16 | Read | bit 0 = Performing battery calibration discharge; bit 1 = Smart trim; bit 2 = Smart boost; bit 3 = On line; bit 4 = On battery; bit 5 = Overload; bit 6 = Low battery (runtime remaining <= low battery duraton); bit 7 = Replace battery | ||||
| HR | 4doc 40005 | Line Quality | UINT16 | Read | 0 = Unacceptable utility line quality; 255 = Acceptable utility line quality (0x00FF) | ||||
| HR | 5doc 40006 | % Battery State of Charge (0-100) | UINT16 | % | Read | ||||
| HR | 6doc 40007 | Runtime Remaining | UINT16 | min | Read | ||||
| HR | 7doc 40008 | Battery Voltage | UINT16 | V | Read | ||||
| HR | 8doc 40009 | UPS Internal Temperature | Internal or battery temperature, depending on the UPS. | UINT16 | °C | Read | |||
| HR | 9doc 40010 | Amps Drawn by Load | UINT16 | A | Read | ||||
| HR | 10doc 40011 | Quantity of battery packs with bad batteries | UINT16 | Read | |||||
| HR | 11doc 40012 | Quantity of battery packs | UINT16 | Read | |||||
| HR | 12doc 40013 | % Power drawn by load | UINT16 | % | Read | ||||
| HR | 13doc 40014 | Nominal Output Voltage | UINT16 | V | Read | ||||
| HR | 14doc 40015 | Actual Output Voltage | UINT16 | V | Read | ||||
| HR | 15doc 40016 | Maximum Input Voltage Since Last Reading | UINT16 | V | Read | ||||
| HR | 16doc 40017 | Minimum Input Voltage Since Last Reading | UINT16 | V | Read | ||||
| HR | 17doc 40018 | Input Voltage | UINT16 | V | Read | ||||
| HR | 18doc 40019 | Input Frequency | UINT16 | Hz | Read | ||||
| HR | 19doc 40020 | Measure-UPS Temperature Reading (Probe 1) | Needs the discontinued AP9612TH environmental monitoring card. | UINT16 | °C | Read | |||
| HR | 20doc 40021 | Measure-UPS Humidity Reading (Probe 1) | Needs the discontinued AP9612TH environmental monitoring card. | UINT16 | % | Read | |||
| HR | 21doc 40022 | Measure-UPS Temperature Reading (Probe 2) | Needs the discontinued AP9612TH environmental monitoring card. | UINT16 | °C | Read | |||
| HR | 22doc 40023 | Measure-UPS Humidity Reading (Probe 2) | Needs the discontinued AP9612TH environmental monitoring card. | UINT16 | % | Read | |||
| HR | 23doc 40024 | Measure-UPS Contact Position | Needs the discontinued AP9612TH environmental monitoring card. | UINT16 | Read | ||||
| HR | 26doc 40027 | Minimum Return Battery Capacity | UINT16 | % | Read | ||||
| HR | 27doc 40028 | Lower Transfer Point | UINT16 | V | Read | ||||
| HR | 28doc 40029 | Upper Transfer Point | UINT16 | V | Read | ||||
| HR | 29doc 40030 | Nominal Output Voltage | UINT16 | V | Read | ||||
| HR | 30doc 40031 | Shutdown Delay | UINT16 | s | Read | ||||
| HR | 31doc 40032 | Low Battery Duration | UINT16 | min | Read | ||||
| HR | 32doc 40033 | Turn On Delay | UINT16 | s | Read | ||||
| HR | 33doc 40034 | Sensitivity | UINT16 | Read | 0 = not supported by this UPS; 72 = highest (normal) sensitivity to utility voltage fluctuations; 76 = lowest sensitivity to utility voltage fluctuations; 77 = medium (reduced) sensitivity to utility voltage fluctuations | ||||
| HR | 34doc 40035 | UPS ID Character #1 | One ASCII character per register. | STRING[2] | Read | ||||
| HR | 35doc 40036 | UPS ID Character #2 | One ASCII character per register. | STRING[2] | Read | ||||
| HR | 36doc 40037 | UPS ID Character #3 | One ASCII character per register. | STRING[2] | Read | ||||
| HR | 37doc 40038 | UPS ID Character #4 | One ASCII character per register. | STRING[2] | Read | ||||
| HR | 38doc 40039 | UPS ID Character #5 | One ASCII character per register. | STRING[2] | Read | ||||
| HR | 39doc 40040 | UPS ID Character #6 | One ASCII character per register. | STRING[2] | Read | ||||
| HR | 40doc 40041 | UPS ID Character #7 | One ASCII character per register. | STRING[2] | Read | ||||
| HR | 41doc 40042 | UPS ID Character #8 | One ASCII character per register. | STRING[2] | Read | ||||
| HR | 42doc 40043 | Status Word 4 | BITMAP16 | Read | bit 3 = Run time below alarm threshold; bit 4 = XR frame fault; bit 5 = Output voltage out of range; bit 6 = System not synchronized; bit 7 = No batteries; bit 8 = Battery voltage high; bit 9 = Fault found in register 0049, 004A, 004B or 004C; bit 10 = Site wiring fault | ||||
| HR | 43doc 40044 | Status Word 5 | BITMAP16 | Read | bit 0 = An installed Power Module has failed; bit 3 = An installed Battery has failed; bit 4 = Load is above alarm threshold; bit 7 = Bypass not in range (either freq or voltage unacceptable); bit 10 = UPS in bypass due to internal fault; bit 11 = UPS in bypass due to overload; bit 12 = System is in maintenance bypass; bit 14 = System level fan failed | ||||
| HR | 44doc 40045 | Nominal Battery Voltage | UINT16 | V | Read | ||||
| HR | 45doc 40046 | Actual Battery Voltage | UINT16 | V | Read | ||||
| HR | 46doc 40047 | Utility Input Voltage Phase A | UINT16 | V | Read | ||||
| HR | 47doc 40048 | Utility Input Current Phase A | UINT16 | A | Read | ||||
| HR | 48doc 40049 | Bypass Input Voltage Phase A | UINT16 | V | Read | ||||
| HR | 49doc 40050 | Percent of Maximum Output VA’s Phase A @ n+0 | UINT16 | % | Read | ||||
| HR | 50doc 40051 | Percent of Maximum Output VA’s Phase A @ n+x | UINT16 | % | Read | ||||
| HR | 51doc 40052 | Phase A Output kVA | UINT16 | kVA | Read | ||||
| HR | 52doc 40053 | Output Voltage Phase A | UINT16 | V | Read | ||||
| HR | 54doc 40055 | Peak Output Current Phase A | UINT16 | A | Read | ||||
| HR | 55doc 40056 | Utility Input Voltage Phase B | UINT16 | V | Read | ||||
| HR | 56doc 40057 | Utility Input Current Phase B | UINT16 | A | Read | ||||
| HR | 57doc 40058 | Bypass Input Voltage Phase B | UINT16 | V | Read | ||||
| HR | 58doc 40059 | Percent of Maximum Output VA’s Phase B @ n+0 | UINT16 | % | Read | ||||
| HR | 59doc 40060 | Percent of Maximum Output VA’s Phase B @ n+x | UINT16 | % | Read | ||||
| HR | 60doc 40061 | Phase B Output kVA | UINT16 | kVA | Read | ||||
| HR | 61doc 40062 | Output Voltage Phase B | UINT16 | V | Read | ||||
| HR | 62doc 40063 | Output Current Phase B | UINT16 | A | Read | ||||
| HR | 63doc 40064 | Peak Output Current Phase B | UINT16 | A | Read | ||||
| HR | 64doc 40065 | Utility Input Voltage Phase C | UINT16 | V | Read | ||||
| HR | 65doc 40066 | Utility Input Current Phase C | UINT16 | A | Read | ||||
| HR | 66doc 40067 | Bypass Input Voltage Phase C | UINT16 | V | Read | ||||
| HR | 67doc 40068 | Percent of Maximum Output VA’s Phase C @ n+0 | UINT16 | % | Read | ||||
| HR | 68doc 40069 | Percent of Maximum Output VA’s Phase C @ n+x | UINT16 | % | Read | ||||
| HR | 69doc 40070 | Phase C Output kVA | UINT16 | kVA | Read | ||||
| HR | 70doc 40071 | Output Voltage Phase C | UINT16 | V | Read | ||||
| HR | 71doc 40072 | Output Current Phase C | UINT16 | A | Read | ||||
| HR | 72doc 40073 | Peak Output Current Phase C | UINT16 | A | Read | ||||
| HR | 75doc 40076 | Status Word 8 | BITMAP16 | Read | bit 0 = Parallel config fault; bit 1 = Dust filter must be changed soon; bit 2 = Dust filter must be changed immediately | ||||
| HR | 76doc 40077 | Status Word 9 | BITMAP16 | Read | bit 0 = EPO active; bit 1 = SBS fault; bit 2 = System config fault; bit 3 = Emergency PSU fault; bit 4 = Weak battery; bit 5 = Battery over temp; bit 6 = Mechanical bypass active (not a fault; bit 7 = Parallel redundancy lost; bit 8 = Parallel bus comm lost cable 1; bit 9 = Parallel bus comm lost cable 2; bit 10 = Auxiliary bus comm lost; bit 11 = Parallel bus termination fault cable 1; bit 12 = Parallel bus termination fault cable 2; bit 13 = Auxiliary bus termination fault; bit 14 = No master in parallel system; bit 15 = Overload on parallel unit | ||||
| HR | 77doc 40078 | Battery Current | Positive = current into the battery, negative = current out. | INT16 | A | Read |
Notes on this map
- Source host: the PDF is the APC/Schneider document served from Schneider Electric's product-data CDN for distributors; the apc.com download link refuses automated requests.
- All registers are one word, transmitted MSB first; signed values are two's complement. Strings are one character per register.
- Single-register reads of reserved/undefined addresses return an error; block reads starting on a valid register return zeros for undefined ones. Addresses 0x0050 and above are invalid.
- Left out: 40054 'Output Current Phase A' because the table prints its unit as V while the matching phase B/C registers are in A; and Status Words 6-7, which are reserved for future use.
- Many registers are marked as not supported on all UPS models.
- Status bits are only consistent within one register, not across registers.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702)
What Modbus registers does the APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702) have?
This map lists 73 registers: 73 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map prints the Modicon number (40001...) next to the absolute address in hex and decimal; note 10 states that absolute address 0 equals register 40001 and is address zero on the wire.
What are the minimum Modbus registers to integrate the APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702)?
Start with HR 3 Status Word 3 (Status word 3: on line / on battery / low battery); HR 5 % Battery State of Charge (0-100) (Battery state of charge); HR 6 Runtime Remaining (Runtime remaining (minutes)); HR 12 % Power drawn by load (Load percent); HR 17 Input Voltage (Input voltage); HR 14 Actual Output Voltage (Output voltage); HR 8 UPS Internal Temperature (Internal temperature).
How do I enable Modbus control of the APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702)?
Enable Modbus on the Network Management Card (TCP on AP9630/AP9631/AP9635, serial RTU on AP9635).
Where is the official APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702) Modbus documentation?
The source is Modbus Register Map - MGE Galaxy 3500, Smart-UPS VT, and Smart-UPS (990-5702), revision 2018-08. APC doesn't publish it on its own website, so this map was re-typed from a free copy at https://media.distributordatasolutions.com/schneider2/2020q3/documents/8a7edbbda9bc66f4fc6a910f8bcea3af8cb87a47.pdf. It may be an older revision, so check it against the live unit.
More APC Modbus register maps
- UPS
APC (Schneider Electric) Galaxy VL 200-500 kW three-phase UPS
Schneider Electric Galaxy VL 200-500 kW UPS with firmware 7.23 or later, per register map 990-6447.
Also known as: Galaxy VL, GVL, Galaxy VL 200 kW, Galaxy VL 500 kW - Air handler (in-row chilled-water cooling unit)
APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm)
APC by Schneider Electric InRow ACRC30x (300 mm chilled water) units, per register map part number 990-4742B.
Also known as: ACRC30x, ACRC300, ACRC301, InRow RC 300 mm - Air handler (in-row data-centre cooling unit)
APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786)
APC / Schneider Electric InRow ACRD60x and ACRC60x in-row cooling units, register map part number 990-5786A.
Also known as: ACRD60x, ACRC60x, InRow ACRD60x, InRow ACRC60x, 990-5786 - Air handler (in-row self-contained DX cooling unit)
APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit
APC by Schneider Electric InRow SC (ACSC 100 series) self-contained cooling units, per register map part number 990-3027D.
Also known as: ACSC100, InRow SC, InRow ACSC - Air handler (in-row data-centre DX cooling unit)
APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B)
APC / Schneider Electric InRow RD cooling units, register map part number 990-3576B (08/2015).
Also known as: InRow RD, 990-3576B, Schneider Electric InRow RD - UPS