UPS network card · Modbus register map

Riello UPS NetMan 204 network card (UPS Modbus TCP map) Modbus register map

Updated 17 November 2026

Short answer

NetMan 204 is Riello UPS's Ethernet card. Besides SNMP and BACnet it serves a fixed Modbus TCP table on port 502 with UPS state bits, input/bypass/output measurements, battery data, nominal ratings and a small command block. This map covers that whole published UPS table.

This page lists 61 Modbus registers for the Riello UPS NetMan 204 network card (UPS Modbus TCP map) — 3 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Riello UPS’s own free documentation (linked below) and checked against it.

Manufacturer
Riello UPS
Model
NetMan 204 network card (UPS Modbus TCP map)
Equipment type
UPS network card
Registers
61 (3 writable)
Transport
Modbus TCP
Default unit ID
Not stated
TCP port
502
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
CDAB low word first (word-swapped)
Also known as
NetMan 204, Riello UPS Modbus TCP
Source document
NetMan 204 user manual · 0MNACCSA4ENUL
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Riello UPS NetMan 204 network card (UPS Modbus TCP map)

Integration in brief

Enable Modbus on the card's MODBus/BACNET page, then poll holding registers 11-63 (addresses) over TCP port 502 for measurements and read discrete inputs 0-63 for the state flags. Treat 0xFFFF as 'not available'.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
DI 13Battery workingBITRunning on batteryRead
DI 12Battery lowBITBattery lowRead
DI 31UPS failureBITUPS failureRead
DI 63Communication lost with UPSBITCard lost the UPSRead
HR 51Remaining battery capacityUINT16Remaining battery capacityRead
HR 53Remaining back-up timeUINT16Remaining back-up timeRead
HR 37Load phase L1UINT16Load phase L1Read
HR 11Input mains star voltage V1UINT16Input voltage V1Read

Enable Modbus control & writes

Log in to the card's web page as admin, open the MODBus/BACNET configuration and tick Enable MODBUS. Modbus is not one of the services active from the factory.

Byte order & addressing

Network setup

Watch out for

Riello UPS NetMan 204 network card (UPS Modbus TCP map) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

61 of 61 shown
Riello UPS NetMan 204 network card (UPS Modbus TCP map) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
DI1doc bit 2Test in progressBITRead0 = No; 1 = Yes
DI3doc bit 4Shutdown activeBITRead0 = No; 1 = Yes
DI5doc bit 6Battery chargedBITRead0 = No; 1 = Yes
DI6doc bit 7Battery chargingBITRead0 = No; 1 = Yes
DI7doc bit 8Bypass badBypass supply is out of tolerance.BITRead0 = No; 1 = Yes
DI9doc bit 10Normal operationBITRead0 = No; 1 = Yes
DI11doc bit 12On bypassLoad is fed from the bypass line.BITRead0 = No; 1 = Yes
DI12doc bit 13Battery lowBITRead0 = No; 1 = Yes
DI13doc bit 14Battery workingUPS is running on battery.BITRead0 = No; 1 = Yes
DI14doc bit 15UPS lockedBITRead0 = No; 1 = Yes
DI15doc bit 16Output poweredBITRead0 = No; 1 = Yes
DI28doc bit 29Input mains presentBITRead0 = No; 1 = Yes
DI29doc bit 30Alarm temperatureBITRead0 = No; 1 = Yes
DI30doc bit 31Alarm overloadBITRead0 = No; 1 = Yes
DI31doc bit 32UPS failureBITRead0 = No; 1 = Yes
DI63doc bit 64Communication lost with UPSNetMan card has lost contact with the UPS.BITRead0 = No; 1 = Yes
HR11doc 12Input mains star voltage V1UINT16VRead
HR12doc 13Input mains star voltage V2UINT16VRead
HR13doc 14Input mains star voltage V3UINT16VRead
HR14doc 15Input current phase L1UINT16× 0.1ARead
HR15doc 16Input current phase L2UINT16× 0.1ARead
HR16doc 17Input current phase L3UINT16× 0.1ARead
HR17doc 18Input frequencyUINT16× 0.1HzRead
HR21doc 22Bypass mains star voltage V1UINT16VRead
HR22doc 23Bypass mains star voltage V2UINT16VRead
HR23doc 24Bypass mains star voltage V3UINT16VRead
HR24doc 25Bypass frequencyUINT16× 0.1HzRead
HR25doc 26Output star voltage V1UINT16VRead
HR26doc 27Output star voltage V2UINT16VRead
HR27doc 28Output star voltage V3UINT16VRead
HR31doc 32Output current phase L1UINT16× 0.1ARead
HR32doc 33Output current phase L2UINT16× 0.1ARead
HR33doc 34Output current phase L3UINT16× 0.1ARead
HR34doc 35Output peak current phase L1UINT16× 0.1ARead
HR35doc 36Output peak current phase L2UINT16× 0.1ARead
HR36doc 37Output peak current phase L3UINT16× 0.1ARead
HR37doc 38Load phase L1UINT16%Read
HR38doc 39Load phase L2UINT16%Read
HR39doc 40Load phase L3UINT16%Read
HR40doc 41Output active power phase L1UINT16× 0.1kWRead
HR41doc 42Output active power phase L2UINT16× 0.1kWRead
HR42doc 43Output active power phase L3UINT16× 0.1kWRead
HR43doc 44Output frequencyUINT16× 0.1HzRead
HR47doc 48Battery voltageUINT16× 0.1VRead
HR48doc 49Positive battery voltageUINT16× 0.1VRead
HR51doc 52Remaining battery capacityUINT16%Read
HR53doc 54Remaining back-up timeUINT16minRead
HR58doc 59-60Total output energy32-bit; register 59 is the low word, 60 the high word.UINT32CDAB× 0.1kWhRead
HR77doc 78Output nominal voltage (star)UINT16VRead
HR78doc 79Output nominal frequencyUINT16× 0.1HzRead
HR79doc 80Output nominal powerRated output apparent power in steps of 100 VA.UINT16× 100VARead
HR83doc 84Battery nominal capacityIncludes any battery expansion.UINT16AhRead
HR84doc 85Battery benches1 or 2.UINT16Read
HR85doc 86Battery typeInteger code; meaning not listed in this manual.UINT16Read
HR112doc 113Command codeWrite a code to start a UPS command.UINT16Read/write1 = Shutdown; 2 = Shutdown and restore; 3 = Cancel command 1, 2 or 12; 12 = UPS on bypass; 20 = Battery test; 22 = Panel test
HR113doc 114Shutdown delay timeDelay used by the shutdown commands.UINT16sRead/write
HR114doc 115Restore delay timeDelay before the UPS restarts after shutdown and restore.UINT16minRead/write
HR116doc 117Command resultEquals the code if handled, code+100 if not handled, 0 if the code was invalid.UINT16Read
HR118doc 119Good message counterCount of correctly processed Modbus messages.UINT16Read
HR119doc 120Bad message counterCount of rejected Modbus messages.UINT16Read
HR128doc 129NetMan firmware versionInteger.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Riello UPS NetMan 204 network card (UPS Modbus TCP map)

What Modbus registers does the Riello UPS NetMan 204 network card (UPS Modbus TCP map) have?

This map lists 61 registers: 16 discrete inputs, 45 holding registers. 3 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Riello UPS NetMan 204 network card (UPS Modbus TCP map) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The tables print both a register NUMBER and an ADDRESS column, and a footnote says register n is sent as n-1 (e.g. register 12, input voltage V1, is address 11). State bits likewise: bit number n is bit address n-1. This map uses the ADDRESS column.

What byte order does the Riello UPS NetMan 204 network card (UPS Modbus TCP map) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Riello UPS NetMan 204 network card (UPS Modbus TCP map)?

Start with DI 13 Battery working (Running on battery); DI 12 Battery low (Battery low); DI 31 UPS failure (UPS failure); DI 63 Communication lost with UPS (Card lost the UPS); HR 51 Remaining battery capacity (Remaining battery capacity); HR 53 Remaining back-up time (Remaining back-up time); HR 37 Load phase L1 (Load phase L1); HR 11 Input mains star voltage V1 (Input voltage V1).

How do I enable Modbus control of the Riello UPS NetMan 204 network card (UPS Modbus TCP map)?

Log in to the card's web page as admin, open the MODBus/BACNET configuration and tick Enable MODBUS. Modbus is not one of the services active from the factory.

Where is the official Riello UPS NetMan 204 network card (UPS Modbus TCP map) Modbus documentation?

The source is NetMan 204 user manual (0MNACCSA4ENUL), published free by Riello UPS at https://www.riello-ups.com/uploads/file/768/2768/0MNACCSA4ENUL__MAN_ACC_NETMAN_204_EN_.pdf.

Other ups register maps

All ups Modbus register maps →

Source: NetMan 204 user manual · 0MNACCSA4ENUL. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.