- NetMan 204 network card (UPS Modbus TCP map)
UPS network card · Modbus register map
Riello UPS NetMan 204 network card (UPS Modbus TCP map) Modbus register map
Updated 17 November 2026
NetMan 204 is Riello UPS's Ethernet card. Besides SNMP and BACnet it serves a fixed Modbus TCP table on port 502 with UPS state bits, input/bypass/output measurements, battery data, nominal ratings and a small command block. This map covers that whole published UPS table.
This page lists 61 Modbus registers for the Riello UPS NetMan 204 network card (UPS Modbus TCP map) — 3 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Riello UPS’s own free documentation (linked below) and checked against it.
- Manufacturer
- Riello UPS
- Model
- NetMan 204 network card (UPS Modbus TCP map)
- Equipment type
- UPS network card
- Registers
- 61 (3 writable)
- Transport
- Modbus TCP
- Default unit ID
- Not stated
- TCP port
- 502
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- NetMan 204, Riello UPS Modbus TCP
- Source document
- NetMan 204 user manual · 0MNACCSA4ENUL
Integration notes: Riello UPS NetMan 204 network card (UPS Modbus TCP map)
Enable Modbus on the card's MODBus/BACNET page, then poll holding registers 11-63 (addresses) over TCP port 502 for measurements and read discrete inputs 0-63 for the state flags. Treat 0xFFFF as 'not available'.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| DI 13 | Battery working | BIT | Running on battery | Read |
| DI 12 | Battery low | BIT | Battery low | Read |
| DI 31 | UPS failure | BIT | UPS failure | Read |
| DI 63 | Communication lost with UPS | BIT | Card lost the UPS | Read |
| HR 51 | Remaining battery capacity | UINT16 | Remaining battery capacity | Read |
| HR 53 | Remaining back-up time | UINT16 | Remaining back-up time | Read |
| HR 37 | Load phase L1 | UINT16 | Load phase L1 | Read |
| HR 11 | Input mains star voltage V1 | UINT16 | Input voltage V1 | Read |
Enable Modbus control & writes
Log in to the card's web page as admin, open the MODBus/BACNET configuration and tick Enable MODBUS. Modbus is not one of the services active from the factory.
Byte order & addressing
- Register numbers are 1-based; subtract 1 for the wire address.
- Total output energy is 32-bit with the low word first (registers 59 then 60).
- Unavailable measurements return 0xFFFF rather than an exception.
- Commands: write the code to address 112, then read address 116 for the result (code, code+100 if refused, 0 if invalid).
Network setup
- Factory default is DHCP. Holding the reset button about 10 s until the LED is solid red reboots the card on static 192.168.0.204 / 255.255.0.0 temporarily.
- Allow about 2 minutes after power-up or reboot before the card answers.
- Modbus TCP listens on port 502.
Watch out for
- The same table is used for every Riello UPS family, so many registers stay 0xFFFF on single-phase units.
- No Modbus unit ID is documented.
Riello UPS NetMan 204 network card (UPS Modbus TCP map) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| DI | 1doc bit 2 | Test in progress | BIT | Read | 0 = No; 1 = Yes | ||||
| DI | 3doc bit 4 | Shutdown active | BIT | Read | 0 = No; 1 = Yes | ||||
| DI | 5doc bit 6 | Battery charged | BIT | Read | 0 = No; 1 = Yes | ||||
| DI | 6doc bit 7 | Battery charging | BIT | Read | 0 = No; 1 = Yes | ||||
| DI | 7doc bit 8 | Bypass bad | Bypass supply is out of tolerance. | BIT | Read | 0 = No; 1 = Yes | |||
| DI | 9doc bit 10 | Normal operation | BIT | Read | 0 = No; 1 = Yes | ||||
| DI | 11doc bit 12 | On bypass | Load is fed from the bypass line. | BIT | Read | 0 = No; 1 = Yes | |||
| DI | 12doc bit 13 | Battery low | BIT | Read | 0 = No; 1 = Yes | ||||
| DI | 13doc bit 14 | Battery working | UPS is running on battery. | BIT | Read | 0 = No; 1 = Yes | |||
| DI | 14doc bit 15 | UPS locked | BIT | Read | 0 = No; 1 = Yes | ||||
| DI | 15doc bit 16 | Output powered | BIT | Read | 0 = No; 1 = Yes | ||||
| DI | 28doc bit 29 | Input mains present | BIT | Read | 0 = No; 1 = Yes | ||||
| DI | 29doc bit 30 | Alarm temperature | BIT | Read | 0 = No; 1 = Yes | ||||
| DI | 30doc bit 31 | Alarm overload | BIT | Read | 0 = No; 1 = Yes | ||||
| DI | 31doc bit 32 | UPS failure | BIT | Read | 0 = No; 1 = Yes | ||||
| DI | 63doc bit 64 | Communication lost with UPS | NetMan card has lost contact with the UPS. | BIT | Read | 0 = No; 1 = Yes | |||
| HR | 11doc 12 | Input mains star voltage V1 | UINT16 | V | Read | ||||
| HR | 12doc 13 | Input mains star voltage V2 | UINT16 | V | Read | ||||
| HR | 13doc 14 | Input mains star voltage V3 | UINT16 | V | Read | ||||
| HR | 14doc 15 | Input current phase L1 | UINT16 | × 0.1 | A | Read | |||
| HR | 15doc 16 | Input current phase L2 | UINT16 | × 0.1 | A | Read | |||
| HR | 16doc 17 | Input current phase L3 | UINT16 | × 0.1 | A | Read | |||
| HR | 17doc 18 | Input frequency | UINT16 | × 0.1 | Hz | Read | |||
| HR | 21doc 22 | Bypass mains star voltage V1 | UINT16 | V | Read | ||||
| HR | 22doc 23 | Bypass mains star voltage V2 | UINT16 | V | Read | ||||
| HR | 23doc 24 | Bypass mains star voltage V3 | UINT16 | V | Read | ||||
| HR | 24doc 25 | Bypass frequency | UINT16 | × 0.1 | Hz | Read | |||
| HR | 25doc 26 | Output star voltage V1 | UINT16 | V | Read | ||||
| HR | 26doc 27 | Output star voltage V2 | UINT16 | V | Read | ||||
| HR | 27doc 28 | Output star voltage V3 | UINT16 | V | Read | ||||
| HR | 31doc 32 | Output current phase L1 | UINT16 | × 0.1 | A | Read | |||
| HR | 32doc 33 | Output current phase L2 | UINT16 | × 0.1 | A | Read | |||
| HR | 33doc 34 | Output current phase L3 | UINT16 | × 0.1 | A | Read | |||
| HR | 34doc 35 | Output peak current phase L1 | UINT16 | × 0.1 | A | Read | |||
| HR | 35doc 36 | Output peak current phase L2 | UINT16 | × 0.1 | A | Read | |||
| HR | 36doc 37 | Output peak current phase L3 | UINT16 | × 0.1 | A | Read | |||
| HR | 37doc 38 | Load phase L1 | UINT16 | % | Read | ||||
| HR | 38doc 39 | Load phase L2 | UINT16 | % | Read | ||||
| HR | 39doc 40 | Load phase L3 | UINT16 | % | Read | ||||
| HR | 40doc 41 | Output active power phase L1 | UINT16 | × 0.1 | kW | Read | |||
| HR | 41doc 42 | Output active power phase L2 | UINT16 | × 0.1 | kW | Read | |||
| HR | 42doc 43 | Output active power phase L3 | UINT16 | × 0.1 | kW | Read | |||
| HR | 43doc 44 | Output frequency | UINT16 | × 0.1 | Hz | Read | |||
| HR | 47doc 48 | Battery voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 48doc 49 | Positive battery voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 51doc 52 | Remaining battery capacity | UINT16 | % | Read | ||||
| HR | 53doc 54 | Remaining back-up time | UINT16 | min | Read | ||||
| HR | 58doc 59-60 | Total output energy | 32-bit; register 59 is the low word, 60 the high word. | UINT32 | CDAB | × 0.1 | kWh | Read | |
| HR | 77doc 78 | Output nominal voltage (star) | UINT16 | V | Read | ||||
| HR | 78doc 79 | Output nominal frequency | UINT16 | × 0.1 | Hz | Read | |||
| HR | 79doc 80 | Output nominal power | Rated output apparent power in steps of 100 VA. | UINT16 | × 100 | VA | Read | ||
| HR | 83doc 84 | Battery nominal capacity | Includes any battery expansion. | UINT16 | Ah | Read | |||
| HR | 84doc 85 | Battery benches | 1 or 2. | UINT16 | Read | ||||
| HR | 85doc 86 | Battery type | Integer code; meaning not listed in this manual. | UINT16 | Read | ||||
| HR | 112doc 113 | Command code | Write a code to start a UPS command. | UINT16 | Read/write | 1 = Shutdown; 2 = Shutdown and restore; 3 = Cancel command 1, 2 or 12; 12 = UPS on bypass; 20 = Battery test; 22 = Panel test | |||
| HR | 113doc 114 | Shutdown delay time | Delay used by the shutdown commands. | UINT16 | s | Read/write | |||
| HR | 114doc 115 | Restore delay time | Delay before the UPS restarts after shutdown and restore. | UINT16 | min | Read/write | |||
| HR | 116doc 117 | Command result | Equals the code if handled, code+100 if not handled, 0 if the code was invalid. | UINT16 | Read | ||||
| HR | 118doc 119 | Good message counter | Count of correctly processed Modbus messages. | UINT16 | Read | ||||
| HR | 119doc 120 | Bad message counter | Count of rejected Modbus messages. | UINT16 | Read | ||||
| HR | 128doc 129 | NetMan firmware version | Integer. | UINT16 | Read |
Notes on this map
- Function codes 1/2 read the state bits, 3/4 read all registers (the same table either way, listed here as holding registers), and 6/16 write only the command registers.
- State bits are listed as discrete inputs at their bit addresses (bit number minus 1). The manual gives bit numbers, not the bit position inside registers 1-4, so the register words themselves are not decoded here.
- Left out because the manual does not say whether they are signed: battery current (51), negative battery voltage (50), internal UPS temperature (62) and sensor temperatures (63, 64).
- Special flag registers 121-128 (Sentry 'SENTR' status codes) are not decoded; the manual points to each UPS manual for them.
- Gaps in the table (e.g. 9-11, 19-21, 45-47) are reserved. Any measurement the connected UPS does not provide reads 0xFFFF.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Riello UPS NetMan 204 network card (UPS Modbus TCP map)
What Modbus registers does the Riello UPS NetMan 204 network card (UPS Modbus TCP map) have?
This map lists 61 registers: 16 discrete inputs, 45 holding registers. 3 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Riello UPS NetMan 204 network card (UPS Modbus TCP map) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The tables print both a register NUMBER and an ADDRESS column, and a footnote says register n is sent as n-1 (e.g. register 12, input voltage V1, is address 11). State bits likewise: bit number n is bit address n-1. This map uses the ADDRESS column.
What byte order does the Riello UPS NetMan 204 network card (UPS Modbus TCP map) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Riello UPS NetMan 204 network card (UPS Modbus TCP map)?
Start with DI 13 Battery working (Running on battery); DI 12 Battery low (Battery low); DI 31 UPS failure (UPS failure); DI 63 Communication lost with UPS (Card lost the UPS); HR 51 Remaining battery capacity (Remaining battery capacity); HR 53 Remaining back-up time (Remaining back-up time); HR 37 Load phase L1 (Load phase L1); HR 11 Input mains star voltage V1 (Input voltage V1).
How do I enable Modbus control of the Riello UPS NetMan 204 network card (UPS Modbus TCP map)?
Log in to the card's web page as admin, open the MODBus/BACNET configuration and tick Enable MODBUS. Modbus is not one of the services active from the factory.
Where is the official Riello UPS NetMan 204 network card (UPS Modbus TCP map) Modbus documentation?
The source is NetMan 204 user manual (0MNACCSA4ENUL), published free by Riello UPS at https://www.riello-ups.com/uploads/file/768/2768/0MNACCSA4ENUL__MAN_ACC_NETMAN_204_EN_.pdf.
Other ups register maps
- UPS
APC (Schneider Electric) Galaxy VL 200-500 kW three-phase UPS
Schneider Electric Galaxy VL 200-500 kW UPS with firmware 7.23 or later, per register map 990-6447.
Also known as: Galaxy VL, GVL, Galaxy VL 200 kW, Galaxy VL 500 kW - UPS
APC Symmetra PX 250/500 kW
APC Symmetra PX 250/500 kW three-phase UPS via Network Management Card AP9635, register map 990-3936D (firmware sypx510 to sypx516 changes listed in the source).
Also known as: 990-3936D, Symmetra PX 250 kW, Symmetra PX 500 kW, SYPX - UPS
APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702)
APC Smart-UPS (excluding SMT, SMX, SURTD and SRT prefixes), Smart-UPS VT and MGE Galaxy 3500 through Network Management Card AP9630/AP9631/AP9635 (TCP) or AP9635 (RTU), part number 990-5702.
Also known as: 990-5702, AP9630, AP9631, AP9635, Smart-UPS VT, MGE Galaxy 3500, Schneider Electric APC Smart-UPS
All ups Modbus register maps →
Source: NetMan 204 user manual · 0MNACCSA4ENUL. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.