UPS · Modbus register map

APC (Schneider Electric) Galaxy VL 200-500 kW three-phase UPS Modbus register map

Updated 19 November 2026

Short answer

The Galaxy VL is a 200-500 kW three-phase UPS. It serves Modbus TCP and Modbus RTU, with all data read from holding registers using function 03 only. This map covers the status and alarm bit words, identification strings, input, bypass and output measurements, battery and charger values, operating modes, parallel-system totals and the configuration settings (as read-only values).

This page lists 161 Modbus registers for the APC (Schneider Electric) Galaxy VL 200-500 kW three-phase UPS — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from APC (Schneider Electric)’s own free documentation (linked below) and checked against it.

Manufacturer
APC (Schneider Electric)
Model
Galaxy VL 200-500 kW three-phase UPS
Equipment type
UPS
Registers
161 (0 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Firmware
7.23 and later
Also known as
Galaxy VL, GVL, Galaxy VL 200 kW, Galaxy VL 500 kW
Source document
Modbus Register Map: Galaxy VL 200-500 kW · 990-6447
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: APC (Schneider Electric) Galaxy VL 200-500 kW three-phase UPS

Integration in brief

Read holding registers with function 03. Poll the UPS status word at 1 and the alarm words 2-23, the UPS operation mode at 5892, and the output, input and battery measurements in the 0x1300, 0x1400 and 0x1600 blocks, applying the 0.1 or 0.01 multipliers.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1UPS status bitsBITMAP16UPS status bits (on battery, bypass, alarms)Read
HR 4608Unit alarm statusUINT16Overall alarm severityRead
HR 5892UPS operation modeUINT16UPS operation modeRead
HR 4889Output current % of capacityUINT16Output load as % of capacityRead
HR 4891Output active power totalUINT16Total output active powerRead
HR 5636Battery runtime remainingUINT32 ABCDBattery runtime remainingRead
HR 5640Battery chargeUINT16Battery charge %Read
HR 5139Input frequencyUINT16Input frequencyRead
HR 4882Output voltage L-N L1UINT16Output voltage L1-NRead

Enable Modbus control & writes

Modbus settings are made on the UPS display; the register map refers to the display for detailed configuration.

Byte order & addressing

Network setup

Watch out for

APC (Schneider Electric) Galaxy VL 200-500 kW three-phase UPS Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

161 of 161 shown
APC (Schneider Electric) Galaxy VL 200-500 kW three-phase UPS Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 40002 (0x0001)UPS status bits1 = condition active.BITMAP16Readbit 0 = UPS operation mode - Battery; bit 1 = Battery is below minimum acceptable runtime; bit 2 = Bypass; bit 3 = UPS operation mode - Battery test; bit 9 = Battery inoperable; bit 13 = Informational alarm present; bit 14 = Warning alarm present; bit 15 = Critical alarm present
HR2doc 40003 (0x0002)Alarms: bypass1 = condition active.BITMAP16Readbit 0 = Bypass voltage out of tolerance; bit 1 = Bypass phase sequence incorrect; bit 2 = Bypass frequency out of tolerance; bit 3 = Bypass phase missing; bit 4 = Bypass backfeed breaker open
HR3doc 40004 (0x0003)Alarms: energy storage (1)1 = condition active.BITMAP16Readbit 0 = Battery breaker BB1 open; bit 1 = Battery breaker BB2 open; bit 2 = Battery breaker BB3 open; bit 3 = Battery breaker BB4 open; bit 4 = Batteries are discharging; bit 5 = Charger shutdown due to high battery temperature; bit 6 = Battery is below minimum acceptable runtime; bit 7 = Battery voltage does not match battery configuration; bit 8 = Battery condition is weak; bit 9 = Battery condition is poor; bit 10 = High battery temperature level; bit 11 = Low battery temperature level; bit 12 = Battery capacity is below minimum acceptable level; bit 13 = Battery charge power is reduced; bit 14 = Battery is not working correctly; bit 15 = Battery float charge current exceeds expected value
HR4doc 40005 (0x0004)Alarms: energy storage (2)1 = condition active.BITMAP16Readbit 0 = High battery temperature shutdown; bit 1 = Battery configuration is incorrect
HR5doc 40006 (0x0005)Alarms: general (1)1 = condition active.BITMAP16Readbit 0 = EPO switch activated; bit 1 = Synchronization unavailable - system is free running; bit 2 = Inverter output is not in phase with bypass input; bit 3 = UPS operation mode - Battery; bit 4 = UPS operation mode - Requested static bypass; bit 5 = UPS operation mode - Forced static bypass; bit 6 = UPS operation mode - Maintenance bypass; bit 7 = UPS operation mode - Battery test; bit 8 = UPS operation mode - Off; bit 9 = UPS operation mode - Initialization; bit 10 = UPS operation mode - Static bypass standby; bit 11 = UPS operation mode - Inverter standby; bit 12 = System operation mode - Off; bit 13 = System operation mode - Forced static bypass; bit 14 = System operation mode - Requested static bypass; bit 15 = System operation mode - Maintenance bypass
HR6doc 40007 (0x0006)Alarms: general (2)1 = condition active.BITMAP16Readbit 0 = System operation mode - Static bypass standby; bit 9 = System locked in bypass operation; bit 10 = Unsupported power frame type detected; bit 11 = Unsupported power module type detected; bit 12 = Unsupported static bypass switch module type detected; bit 13 = Incorrect system voltage configuration detected
HR7doc 40008 (0x0007)Alarms: general (3)1 = condition active.BITMAP16Readbit 0 = Incorrect 3-wire configuration detected; bit 1 = No static bypass switch present; bit 2 = No power module(s) present; bit 4 = Static bypass switch power rating lower than configured UPS power rating; bit 5 = Ambient temperature out of tolerance; bit 6 = Ambient temperature high; bit 7 = Inverter is off due to a request by the user; bit 8 = Settings file not accepted; bit 9 = Warranty expiring soon; bit 10 = Technical check recommended; bit 11 = Air filter technical check recommended; bit 12 = Controller box disabled; bit 13 = UPS surveillance detected fault; bit 14 = Display communication lost - display is disconnected from the system; bit 15 = Display communication lost but the display is connected to the system
HR8doc 40009 (0x0008)Alarms: general (4)1 = condition active.BITMAP16Readbit 0 = Display communication not authenticated; bit 1 = Multiple NTP server connections enabled; bit 7 = Internal power module redundancy lost; bit 8 = UPS output load is too low to allow ECOnversion; bit 10 = Incompatible power module type detected; bit 11 = Start-up recommended; bit 12 = UPS output load power factor is too low to allow ECOnversion
HR11doc 40012 (0x000B)Alarms: input1 = condition active.BITMAP16Readbit 0 = Input voltage out of tolerance; bit 1 = Input phase sequence incorrect; bit 2 = Input frequency out of tolerance; bit 3 = Input phase missing; bit 4 = External sync voltage out of tolerance; bit 5 = External sync phase sequence incorrect; bit 6 = External sync frequency out of tolerance; bit 7 = External sync phase missing; bit 8 = External sync temporarily disabled; bit 9 = Neutral displacement detected; bit 10 = Bonding between neutral and ground missing
HR12doc 40013 (0x000C)Alarms: output1 = condition active.BITMAP16Readbit 0 = Output voltage out of tolerance; bit 1 = Output frequency out of tolerance; bit 2 = Overload or short-circuit on UPS; bit 3 = Overload on UPS due to high ambient temperature; bit 4 = Overload on installation; bit 5 = Load on UPS is above warning level
HR13doc 40014 (0x000D)Alarms: parallel system1 = condition active.BITMAP16Readbit 0 = Parallel communication lost on PBUS cable 1; bit 1 = Parallel communication lost on PBUS cable 2; bit 2 = General parallel system event; bit 3 = Parallel mixed operation mode; bit 4 = Parallel unit not present; bit 5 = Parallel redundancy lost; bit 6 = Not enough UPSs ready to turn on inverter; bit 7 = Firmware versions in parallel UPSs are not identical; bit 8 = Confirm redundancy lost and/or transfer to forced static bypass; bit 10 = Parallel breaker status inconsistency detected
HR14doc 40015 (0x000E)Alarms: power module1 = condition active.BITMAP16Readbit 0 = Power module inoperable; bit 1 = Power module temperature warning; bit 2 = Power module overheated; bit 3 = Power module inlet temperature high; bit 4 = Power module inlet temperature out of tolerance; bit 7 = Power module fan inoperable; bit 8 = Power module disabled; bit 9 = Power module surveillance detected fault; bit 10 = PMC communication lost - disconnected; bit 11 = PMC communication lost - connected; bit 12 = PMC communication not authenticated
HR16doc 40017 (0x0010)Alarms: static bypass switch1 = condition active.BITMAP16Readbit 0 = Static bypass switch fan inoperable; bit 2 = Static bypass switch warning; bit 3 = Static bypass switch inoperable; bit 4 = Static bypass switch controller communication lost disconnected; bit 5 = Static bypass switch controller communication lost connected; bit 6 = Static bypass switch controller communication not authenticated
HR17doc 40018 (0x0011)Alarms: switchgear (1)1 = condition active.BITMAP16Readbit 0 = Breaker UIB open; bit 1 = Breaker UOB open; bit 2 = Breaker MBB closed; bit 3 = Breaker SIB open; bit 4 = Breaker SSIB open; bit 9 = Ground fault detected; bit 10 = Genset is supplying the UPS; bit 11 = Battery room ventilation inoperable; bit 12 = External battery monitoring detected fault; bit 13 = UOB redundant monitoring not working correctly; bit 14 = MBB redundant monitoring not working correctly
HR18doc 40019 (0x0012)Alarms: switchgear (2)1 = condition active.BITMAP16Readbit 1 = UPS locked in static bypass mode: activated; bit 2 = High efficiency mode disabled; bit 3 = External energy storage monitoring: minor alarm; bit 4 = External energy storage monitoring: major alarm; bit 5 = External charger off command: activated; bit 6 = Temperature of input and/or output transformer is too high
HR19doc 40020 (0x0013)Alarms: system level controller1 = condition active.BITMAP16Readbit 0 = SLC in controller box is not working correctly
HR20doc 40021 (0x0014)Alarms: unit controller1 = condition active.BITMAP16Readbit 8 = UC in controller box is not working correctly; bit 9 = UC communication lost - disconnected; bit 10 = UC communication lost - connected; bit 11 = UC communication not authenticated
HR22doc 40023 (0x0016)Alarms: energy storage (3)1 = condition active.BITMAP16Readbit 2 = High battery discharge current shutdown
HR23doc 40024 (0x0017)Alarms: network and remote sensor1 = condition active.BITMAP16Readbit 0 = Low temperature threshold violation at remote sensor; bit 1 = Minimum temperature threshols violation at remote sensor; bit 2 = High temperature threshold violation at remote sensor; bit 3 = Maximum temperature threshold violation at remote sensor; bit 4 = Low humidity threshold violation at remote sensor; bit 5 = Minimum humidity threshold violation at remote sensor; bit 6 = High humidity threshold violation at remote sensor; bit 7 = Maximum humidity threshold violation at remote sensor; bit 8 = Lost communication to remote sensor; bit 9 = Communication link between NMC and SLC is lost. NMC is disconnected from the system; bit 10 = Communication link between NMC and SLC is lost but the NMC is connected to the system; bit 11 = Communication link between NMC and SLC is not authenticated; bit 12 = NMC firmware incompatible
HR4096doc 44097 (0x1000)UPS firmware package versionSTRING[16]Read
HR4104doc 44105 (0x1008)UPS hardware versionSTRING[32]Read
HR4120doc 44121 (0x1018)UPS model numberSTRING[32]Read
HR4136doc 44137 (0x1028)UPS serial numberSTRING[32]Read
HR4152doc 44153 (0x1038)NMC firmware versionSTRING[16]Read
HR4160doc 44161 (0x1040)NMC hardware versionSTRING[32]Read
HR4176doc 44177 (0x1050)NMC model numberSTRING[32]Read
HR4192doc 44193 (0x1060)NMC serial numberSTRING[32]Read
HR4608doc 44609 (0x1200)Unit alarm statusUINT16Read0 = No alarms present; 1 = Informational alarm present; 2 = Warning alarm present; 3 = Critical alarm present
HR4864doc 44865 (0x1300)Output apparent power L1UINT16× 0.1kVARead
HR4865doc 44866 (0x1301)Output apparent power L2UINT16× 0.1kVARead
HR4866doc 44867 (0x1302)Output apparent power L3UINT16× 0.1kVARead
HR4867doc 44868 (0x1303)Output current L1UINT16× 0.1ARead
HR4868doc 44869 (0x1304)Output current L2UINT16× 0.1ARead
HR4869doc 44870 (0x1305)Output current L3UINT16× 0.1ARead
HR4870doc 44871 (0x1306)Output crest factor L1UINT16× 0.1Read
HR4871doc 44872 (0x1307)Output crest factor L2UINT16× 0.1Read
HR4872doc 44873 (0x1308)Output crest factor L3UINT16× 0.1Read
HR4873doc 44874 (0x1309)Output current THD L1UINT16× 0.1%Read
HR4874doc 44875 (0x130A)Output current THD L2UINT16× 0.1%Read
HR4875doc 44876 (0x130B)Output current THD L3UINT16× 0.1%Read
HR4876doc 44877 (0x130C)Output power factor L1UINT16× 0.01Read
HR4877doc 44878 (0x130D)Output power factor L2UINT16× 0.01Read
HR4878doc 44879 (0x130E)Output power factor L3UINT16× 0.01Read
HR4879doc 44880 (0x130F)Output active power L1UINT16× 0.1kWRead
HR4880doc 44881 (0x1310)Output active power L2UINT16× 0.1kWRead
HR4881doc 44882 (0x1311)Output active power L3UINT16× 0.1kWRead
HR4882doc 44883 (0x1312)Output voltage L-N L1UINT16× 0.1VRead
HR4883doc 44884 (0x1313)Output voltage L-N L2UINT16× 0.1VRead
HR4884doc 44885 (0x1314)Output voltage L-N L3UINT16× 0.1VRead
HR4885doc 44886 (0x1315)Output voltage L-L L1UINT16× 0.01VRead
HR4886doc 44887 (0x1316)Output voltage L-L L2UINT16× 0.01VRead
HR4887doc 44888 (0x1317)Output voltage L-L L3UINT16× 0.01VRead
HR4888doc 44889 (0x1318)Output apparent power totalUINT16× 0.1kVARead
HR4889doc 44890 (0x1319)Output current % of capacityHighest phase current as a percentage of available current.UINT16× 0.1%Read
HR4890doc 44891 (0x131A)Output frequencyUINT16× 0.1HzRead
HR4891doc 44892 (0x131B)Output active power totalUINT16× 0.01kWRead
HR4892doc 44893 (0x131C)Output energyUINT32ABCD× 0.1kWhRead
HR4894doc 44895 (0x131E)Output neutral currentUINT16× 0.1ARead
HR5120doc 45121 (0x1400)Input apparent power L1UINT16× 0.1kVARead
HR5121doc 45122 (0x1401)Input apparent power L2UINT16× 0.1kVARead
HR5122doc 45123 (0x1402)Input apparent power L3UINT16× 0.1kVARead
HR5123doc 45124 (0x1403)Input current L1UINT16× 0.1ARead
HR5124doc 45125 (0x1404)Input current L2UINT16× 0.1ARead
HR5125doc 45126 (0x1405)Input current L3UINT16× 0.1ARead
HR5126doc 45127 (0x1406)Input power factor L1UINT16× 0.01Read
HR5127doc 45128 (0x1407)Input power factor L2UINT16× 0.01Read
HR5128doc 45129 (0x1408)Input power factor L3UINT16× 0.01Read
HR5129doc 45130 (0x1409)Input active power L1UINT16× 0.1kWRead
HR5130doc 45131 (0x140A)Input active power L2UINT16× 0.1kWRead
HR5131doc 45132 (0x140B)Input active power L3UINT16× 0.1kWRead
HR5132doc 45133 (0x140C)Input voltage L-N L1UINT16× 0.1VRead
HR5133doc 45134 (0x140D)Input voltage L-N L2UINT16× 0.1VRead
HR5134doc 45135 (0x140E)Input voltage L-N L3UINT16× 0.1VRead
HR5135doc 45136 (0x140F)Input voltage L-L L1UINT16× 0.01VRead
HR5136doc 45137 (0x1410)Input voltage L-L L2UINT16× 0.01VRead
HR5137doc 45138 (0x1411)Input voltage L-L L3UINT16× 0.01VRead
HR5138doc 45139 (0x1412)Input apparent power totalUINT16× 0.1kVARead
HR5139doc 45140 (0x1413)Input frequencyUINT16× 0.1HzRead
HR5140doc 45141 (0x1414)Input active power totalUINT16× 0.01kWRead
HR5141doc 45142 (0x1415)Input energyUINT32ABCD× 0.1kWhRead
HR5376doc 45377 (0x1500)Bypass apparent power L1UINT16× 0.1kVARead
HR5377doc 45378 (0x1501)Bypass apparent power L2UINT16× 0.1kVARead
HR5378doc 45379 (0x1502)Bypass apparent power L3UINT16× 0.1kVARead
HR5379doc 45380 (0x1503)Bypass current L1UINT16× 0.1ARead
HR5380doc 45381 (0x1504)Bypass current L2UINT16× 0.1ARead
HR5381doc 45382 (0x1505)Bypass current L3UINT16× 0.1ARead
HR5382doc 45383 (0x1506)Bypass power factor L1UINT16× 0.01Read
HR5383doc 45384 (0x1507)Bypass power factor L2UINT16× 0.01Read
HR5384doc 45385 (0x1508)Bypass power factor L3UINT16× 0.01Read
HR5385doc 45386 (0x1509)Bypass active power L1UINT16× 0.1kWRead
HR5386doc 45387 (0x150A)Bypass active power L2UINT16× 0.1kWRead
HR5387doc 45388 (0x150B)Bypass active power L3UINT16× 0.1kWRead
HR5388doc 45389 (0x150C)Bypass voltage L-N L1UINT16× 0.1VRead
HR5389doc 45390 (0x150D)Bypass voltage L-N L2UINT16× 0.1VRead
HR5390doc 45391 (0x150E)Bypass voltage L-N L3UINT16× 0.1VRead
HR5391doc 45392 (0x150F)Bypass voltage L-L L1UINT16× 0.01VRead
HR5392doc 45393 (0x1510)Bypass voltage L-L L2UINT16× 0.01VRead
HR5393doc 45394 (0x1511)Bypass voltage L-L L3UINT16× 0.01VRead
HR5394doc 45395 (0x1512)Bypass apparent power totalUINT16× 0.1kVARead
HR5395doc 45396 (0x1513)Bypass frequencyUINT16× 0.1HzRead
HR5396doc 45397 (0x1514)Bypass active power totalUINT16× 0.01kWRead
HR5632doc 45633 (0x1600)Charger conditionUINT16Read0 = Float charging; 1 = Boost charging; 2 = Cyclic resting; 3 = Not charging; 4 = Equalization charging; 5 = Test in progress; 6 = Cyclic float charging
HR5633doc 45634 (0x1601)Highest battery temperatureHighest reading of the connected battery temperature sensors.UINT16× 0.1°CRead
HR5634doc 45635 (0x1602)Battery DC powerUINT16× 0.1kWRead
HR5635doc 45636 (0x1603)Battery breakers statusUINT16Read0 = Open; 1 = Closed
HR5636doc 45637 (0x1604)Battery runtime remainingTime until batteries reach the low-voltage shutdown level.UINT32ABCDsRead
HR5638doc 45639 (0x1606)Battery recharge timeUINT32ABCDsRead
HR5640doc 45641 (0x1608)Battery chargeUINT16%Read
HR5641doc 45642 (0x1609)Battery voltageUINT16× 0.1VRead
HR5643doc 45644 (0x160B)Battery self-test statusUINT16Read0 = Battery self-test is inactive; 1 = Battery self-test is running; 2 = Battery self-test is aborted because the system detects a critical alarm; 3 = Battery self-test is aborted due to user command; 4 = Battery self-test is completed
HR5644doc 45645 (0x160C)Battery healthUINT16Read0 = Battery condition is OK; 1 = Battery condition is unknown; 2 = Battery condition is weak; 3 = Battery condition is poor
HR5645doc 45646 (0x160D)Charger operation modeUINT16Read0 = Battery is resting; 1 = Battery is charging; 2 = Battery is discharging
HR5646doc 45647 (0x160E)Battery capacityUINT16AhRead
HR5888doc 45889 (0x1700)Switchgear status bitsBit = 1 means the breaker is closed.BITMAP16Readbit 0 = Unit input breaker (UIB) status; bit 1 = Unit output breaker (UOB) status; bit 2 = Static switch input breaker (SSIB) status; bit 4 = Maintenance bypass breaker (MBB) status; bit 6 = System isolation breaker (SIB) status
HR5889doc 45890 (0x1701)Firmware upgrade statusUINT16Read0 = Firmware update in INIT state; 1 = Firmware update in IDLE State; 2 = Firmware package is DOWNLOADING; 3 = Firmware package is INSTALLING; 4 = Firmware package is in REBOOTING state; 5 = Firmware update in FULL_SYS_UPDATE_FAIL state; 6 = Firmware update in FULL_SYS_UPDATE_DONE state; 7 = Firmware update in FULL_SYS_UPDATE_ABORTED state; 8 = Firmware update in SPARE_PART_UPDATE state; 9 = Firmware update did not succeed
HR5891doc 45892 (0x1703)System operation modeUINT16Read0 = System: off operation; 1 = System: inverter operation; 2 = System: forced static bypass operation; 3 = System: requested static bypass operation; 4 = System: maintenance bypass operation; 5 = System: static bypass standby operation; 6 = System: ECOnversion mode; 7 = System: ECO mode
HR5892doc 45893 (0x1704)UPS operation modeUINT16Read0 = UPS: initialize operation; 1 = UPS: off operation; 2 = UPS: battery operation; 3 = UPS: normal operation; 4 = UPS: forced static bypass operation; 5 = UPS: requested static bypass operation; 6 = UPS: maintenance bypass operation; 7 = UPS: emergency static bypass operation; 8 = UPS: inverter standby operation; 9 = UPS: static bypass standby operation; 10 = UPS: battery test; 11 = UPS: inverter SPoT mode; 12 = UPS: charger SPoT mode; 13 = UPS: battery SPoT mode; 14 = UPS: ECOnversion mode; 15 = UPS: ECO mode
HR5893doc 45894 (0x1705)Base model number checkUINT16Read0 = State is OK; 1 = State is not OK
HR6144doc 46145 (0x1800)Parallel system input current L1UINT16ARead
HR6145doc 46146 (0x1801)Parallel system input current L2UINT16ARead
HR6146doc 46147 (0x1802)Parallel system input current L3UINT16ARead
HR6147doc 46148 (0x1803)Parallel system bypass current L1UINT16ARead
HR6148doc 46149 (0x1804)Parallel system bypass current L2UINT16ARead
HR6149doc 46150 (0x1805)Parallel system bypass current L3UINT16ARead
HR6150doc 46151 (0x1806)Parallel system output current L1UINT16ARead
HR6151doc 46152 (0x1807)Parallel system output current L2UINT16ARead
HR6152doc 46153 (0x1808)Parallel system output current L3UINT16ARead
HR6153doc 46154 (0x1809)Parallel system output apparent powerTotal for the parallel system.UINT16× 0.1kVARead
HR6154doc 46155 (0x180A)Parallel system loadShare of system capacity in use, based on the most loaded phase.UINT16× 0.1%Read
HR6155doc 46156 (0x180B)Parallel system output active powerTotal for the parallel system.UINT16× 0.1kWRead
HR6400doc 46401 (0x1900)Remote sensor temperatureUINT16× 0.1°CRead
HR6401doc 46402 (0x1901)Remote sensor humidityUINT16× 0.1%RHRead
HR8192doc 48193 (0x2000)AC voltage system settingUINT16Read0 = Output voltage 380VAC PhPh; 1 = Output voltage 400VAC PhPh; 2 = Output voltage 415VAC PhPh; 3 = Output voltage 480VAC PhPh; 4 = Output voltage 208VAC PhPh; 5 = Output voltage 200VAC PhPh; 6 = Output voltage 220VAC PhPh; 7 = Output voltage 440VAC PhPh
HR8193doc 48194 (0x2001)Single or dual mainsUINT16Read0 = Single mains system; 1 = Dual mains system
HR8195doc 48196 (0x2003)AC wiring configurationUINT16Read0 = 3-wire system configuration; 1 = 4-wire system configuration; 2 = 4-wire system configuration HRG
HR8196doc 48197 (0x2004)Energy storage typeUINT16Read0 = No energy storage; 1 = Battery/batteries; 2 = Flywheel; 3 = Ultra capacitors
HR8197doc 48198 (0x2005)Cable voltage compensationRaises output voltage to make up for cable length.UINT16× 0.1%Read
HR8198doc 48199 (0x2006)Output frequency settingUINT16Read0 = Frequency of 50 Hz +/- 1.0 Hz.; 1 = Frequency of 50 Hz +/- 3.0 Hz.; 2 = Frequency of 60 Hz +/- 1.0 Hz.; 3 = Frequency of 60 Hz +/- 3.0 Hz.; 4 = Frequency of 50 Hz +/- 10.0 Hz.; 5 = Frequency of 60 Hz +/- 10.0 Hz.
HR8201doc 48202 (0x2009)Inverter autostart after outageUINT16Read0 = Function disabled; 1 = Function enabled
HR8202doc 48203 (0x200A)Output overload thresholdUINT16× 0.1%Read
HR8203doc 48204 (0x200B)Charger autoboostUINT16Read0 = Disable autoboost charger; 1 = Enable autoboost charger
HR8204doc 48205 (0x200C)Charge current rateUINT16× 0.01Read
HR8205doc 48206 (0x200D)Auto cyclic charge modeUINT16Read0 = Function disabled; 1 = Function enabled
HR8206doc 48207 (0x200E)Breaker configuration (8206)Two consecutive rows are both named 'Configuration of breakers'; the breaker is not identified.UINT16Read0 = Not present; 1 = Present
HR8207doc 48208 (0x200F)Breaker configuration (8207)See 8206; the breaker is not identified in the source.UINT16Read0 = Not present; 1 = Present
HR8208doc 48209 (0x2010)Battery deep dischargeUINT16Read0 = Deep discharge is not allowed.; 1 = Deep discharge is allowed.
HR8209doc 48210 (0x2011)Battery minimum temperatureUINT16× 0.1°CRead
HR8210doc 48211 (0x2012)Battery maximum temperatureUINT16× 0.1°CRead
HR8211doc 48212 (0x2013)Battery solutionUINT16Read0 = Custom battery solution; 1 = Battery solution type GVSCBC7A; 2 = Battery solution type GVSCBC7B; 3 = Battery solution type GVSCBC7C; 4 = Battery solution type GVSCBC10A/GVSCBC10A2; 5 = Battery solution type GVSCBC10B/GVSCBC10B2; 6 = Battery solution type GVSCBT1/GVSCBT1ST; 7 = Battery solution type GVSCBT2/GVSCBT2ST; 8 = Battery solution type GVSCBT3/GVSCBT3ST; 9 = Battery solution type GVSCBT4/GVSCBT4ST; 10 = Battery solution type GVSCBT5/GVSCBT5ST; 11 = Battery solution type LIBATTSMGEIEC; 12 = Battery solution type LIBATTSMGEUL; 13 = Modular battery solution; 14 = Battery solution type GVSCBT6ST; 15 = Battery solution type GVSCBT7ST
HR8212doc 48213 (0x2014)Automatic battery test intervalUINT16Read0 = Never autotest; 1 = Autotest every week; 2 = Autotest every 2 week; 3 = Autotest every 4 week; 4 = Autotest every 8 week; 5 = Autotest every 12 week; 6 = Autotest every 26 week; 7 = Autotest every 52 week
HR8213doc 48214 (0x2015)Battery test time of daySeconds after midnight, 0-86399.UINT32ABCDsRead
HR8215doc 48216 (0x2017)Battery test day of weekUINT16Read0 = Test on Monday; 1 = Test on Tuesday; 2 = Test on Wednesday; 3 = Test on Thursday; 4 = Test on Friday; 5 = Test on Saturday; 6 = Test on Sunday
HR8216doc 48217 (0x2018)Switchgear configuration bitsOne bit per breaker in the switchgear configuration.BITMAP16Readbit 0 = Unit input breaker (UIB) setting; bit 1 = Unit output breaker (UOB) setting; bit 2 = Static switch input breaker (SSIB) setting; bit 3 = Maintenance bypass breaker (MBB) setting; bit 5 = System isolation breaker (SIB) setting
HR8217doc 48218 (0x2019)Inverter slew rateUINT16Read0 = Slew rate is 0.25 Hz/s; 1 = Slew rate is 0.50 Hz/s; 2 = Slew rate is 1 Hz/s; 3 = Slew rate is 2 Hz/s; 4 = Slew rate is 4 Hz/s; 5 = Slew rate is 6 Hz/s
HR8219doc 48220 (0x201B)Asynchronous bypass break durationInterruption time on transfer to an asynchronous bypass.UINT16msRead
HR8220doc 48221 (0x201C)Charging capacityUINT16%Read
HR8222doc 48223 (0x201E)Parallel UPS numberUINT16Read
HR8223doc 48224 (0x201F)Parallel UPSs presentOne bit per parallel unit; 1 = present.BITMAP16Readbit 0 = unit_1; bit 1 = unit_2; bit 2 = unit_3; bit 3 = unit_4
HR8224doc 48225 (0x2020)Redundancy settingUINT16Read0 = N+0; 1 = N+1; 2 = N+2; 3 = N+3
HR8225doc 48226 (0x2021)Minimum units for auto start-upUINT16Read
HR8226doc 48227 (0x2022)Enough UPSs for inverter operationUINT16Read0 = State is OK; 1 = State is not OK

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the APC (Schneider Electric) Galaxy VL 200-500 kW three-phase UPS

What Modbus registers does the APC (Schneider Electric) Galaxy VL 200-500 kW three-phase UPS have?

This map lists 161 registers: 161 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the APC (Schneider Electric) Galaxy VL 200-500 kW three-phase UPS Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row lists a Modicon number plus the absolute address in hex and decimal. Note 12 says absolute address 0 is register 40001 and address zero on the wire, so 44865 (0x1300) is wire address 4864.

What byte order does the APC (Schneider Electric) Galaxy VL 200-500 kW three-phase UPS use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the APC (Schneider Electric) Galaxy VL 200-500 kW three-phase UPS?

Start with HR 1 UPS status bits (UPS status bits (on battery, bypass, alarms)); HR 4608 Unit alarm status (Overall alarm severity); HR 5892 UPS operation mode (UPS operation mode); HR 4889 Output current % of capacity (Output load as % of capacity); HR 4891 Output active power total (Total output active power); HR 5636 Battery runtime remaining (Battery runtime remaining); HR 5640 Battery charge (Battery charge %); HR 5139 Input frequency (Input frequency); HR 4882 Output voltage L-N L1 (Output voltage L1-N).

How do I enable Modbus control of the APC (Schneider Electric) Galaxy VL 200-500 kW three-phase UPS?

Modbus settings are made on the UPS display; the register map refers to the display for detailed configuration.

Where is the official APC (Schneider Electric) Galaxy VL 200-500 kW three-phase UPS Modbus documentation?

The source is Modbus Register Map: Galaxy VL 200-500 kW (990-6447), published free by APC (Schneider Electric) at https://download.se.com/files?p_Doc_Ref=Modbus_Register_Map_Galaxy_VL.