Air handler (in-row chilled-water cooling unit) · Modbus register map
APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm) Modbus register map
Updated 19 November 2026
The InRow ACRC30x is a 300 mm wide chilled-water cooling unit that sits between server racks. Its controller answers Modbus RTU and Modbus TCP, with every value in holding registers that can also be read with function 04. This map covers the group values (cooling output, setpoints, airflow), the unit readings (temperatures, fan speed, chilled water valve, flow, power and energy, run hours), configuration items and the full list of one-register alarm flags.
This page lists 163 Modbus registers for the APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm) — 27 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from APC (Schneider Electric)’s own free documentation (linked below) and checked against it.
- Manufacturer
- APC (Schneider Electric)
- Model
- InRow ACRC30x chilled-water cooling unit (300 mm)
- Equipment type
- Air handler (in-row chilled-water cooling unit)
- Registers
- 163 (27 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- ACRC30x, ACRC300, ACRC301, InRow RC 300 mm
- Source document
- Modbus Register Map: InRow ACRC30x · 990-4742B
Integration notes: APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm)
Poll holding registers from address 0 with function 03 or 04. Read OVERALL_STATUS and OPERATING_MODE first, then the 32-bit temperatures and cooling output in tenths, and scan the alarm block at 384-456 for active flags.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Overall status | UINT16 | Overall alarm severity | Read |
| HR 206 | Operating mode | UINT16 | Unit operating mode | Read |
| HR 207 | Unit cool output | INT32 ABCD | Unit cooling output | Read |
| HR 211 | Unit max rack inlet temp | INT32 ABCD | Highest rack inlet temperature | Read |
| HR 213 | Supply air temp | INT32 ABCD | Supply air temperature | Read |
| HR 215 | Return air temp | INT32 ABCD | Return air temperature | Read |
| HR 219 | Fan speed | INT32 ABCD | Fan speed | Read |
| HR 5 | Cool setpoint | INT32 ABCD | Cooling setpoint (writable) | Read/write |
| HR 386 | Cool function unavailable | UINT16 | Cooling function unavailable alarm | Read |
| HR 403 | Water detected | UINT16 | Water detected alarm | Read |
Enable Modbus control & writes
The register map does not describe how to enable Modbus or set the network parameters.
Byte order & addressing
- 32-bit values are high word first (ABCD).
- Temperatures are tenths of a degree Fahrenheit; the map has no Celsius registers.
- A single-register read of a reserved address fails, while block reads across gaps return zeros.
Network setup
- Modbus RTU and Modbus TCP are both supported; serial settings and unit ID are not in this map.
Watch out for
- Large reads can take 2 seconds or more; shorten blocks or raise the response timeout if requests time out.
- Reading an item before the controller has data for it returns an invalid-address error, so retry later.
- Alarm flags are only consistent within one register; do not combine bits across registers.
APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 (absolute 0) | Overall status | Worst active alarm severity for the unit. | UINT16 | Read | 0 = No Alarm; 1 = Informational; 2 = Warning; 3 = Critical | |||
| HR | 1doc 40002 (absolute 1) | Group cool output | Cooling delivered by the whole InRow group. | INT32 | ABCD | × 0.1 | kW | Read | |
| HR | 3doc 40004 (absolute 3) | Group cool demand | Cooling requested by the whole group. | INT32 | ABCD | × 0.1 | kW | Read | |
| HR | 5doc 40006 (absolute 5) | Cool setpoint | Cooling setpoint the group controls to. | INT32 | ABCD | × 0.1 | °F | Read/write | |
| HR | 7doc 40008 (absolute 7) | Supply air setpoint | Supply air temperature setpoint. | INT32 | ABCD | × 0.1 | °F | Read/write | |
| HR | 9doc 40010 (absolute 9) | Group air flow | Total airflow of the group. | INT32 | ABCD | CFM | Read | ||
| HR | 11doc 40012 (absolute 11) | Group max rack temp | INT32 | ABCD | × 0.1 | °F | Read | ||
| HR | 13doc 40014 (absolute 13) | Group min rack temp | INT32 | ABCD | × 0.1 | °F | Read | ||
| HR | 15doc 40016 (absolute 15) | Airflow control | Fan speed preference: automatic or a fixed percentage. | UINT16 | Read/write | 0 = Automatic; 1 = 60%; 2 = 70%; 3 = 80%; 4 = 90%; 5 = 100% | |||
| HR | 16doc 40017 (absolute 16) | Number of units | INT32 | ABCD | Read/write | ||||
| HR | 18doc 40019 (absolute 18) | Configuration type | Containment arrangement the group is set up for. | UINT16 | Read | 0 = RACS; 1 = HACS; 2 = InRow; 3 = CACS | |||
| HR | 19doc 40020 (absolute 19) | Cool pid p | INT32 | ABCD | × 0.01 | Read | |||
| HR | 21doc 40022 (absolute 21) | Cool pid i | INT32 | ABCD | × 0.01 | Read | |||
| HR | 23doc 40024 (absolute 23) | Cool pid d | INT32 | ABCD | × 0.01 | Read | |||
| HR | 25doc 40026 (absolute 25) | Percent glycol | INT32 | ABCD | % | Read | |||
| HR | 27doc 40028 (absolute 27) | Max fan speed | Upper limit for fan speed. | INT32 | ABCD | % | Read/write | ||
| HR | 30doc 40031 (absolute 30) | Altitude | INT32 | ABCD | ft | Read/write | |||
| HR | 32doc 40033 (absolute 32) | Number active flow controllers | INT32 | ABCD | Read/write | ||||
| HR | 34doc 40035 (absolute 34) | Active flow control bias | UINT16 | Read | 0 = Positive; 1 = Slightly Positive; 2 = Zero; 3 = Slightly Negative; 4 = Negative | ||||
| HR | 35doc 40036 (absolute 35) | Active flow control status | UINT16 | Read | 0 = Under; 1 = Okay; 2 = Over; 3 = N/A | ||||
| HR | 36doc 40037 (absolute 36) | Active flow control lamp test | UINT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 37doc 40038 (absolute 37) | Delta t setpoint | UINT16 | Read/write | 0 = 10 Deg F; 1 = 15 Deg F; 2 = 20 Deg F; 3 = 25 Deg F; 4 = 30 Deg F; 5 = 35 Deg F; 6 = 40 Deg F | ||||
| HR | 128doc 40129 (absolute 128) | Unit name | STRING[42] | Read/write | |||||
| HR | 149doc 40150 (absolute 149) | Unit location | STRING[42] | Read/write | |||||
| HR | 172doc 40173 (absolute 172) | Model number | STRING[20] | Read | |||||
| HR | 182doc 40183 (absolute 182) | Serial number | STRING[20] | Read | |||||
| HR | 192doc 40193 (absolute 192) | Firmware rev | STRING[8] | Read | |||||
| HR | 196doc 40197 (absolute 196) | Hardware rev | STRING[8] | Read | |||||
| HR | 200doc 40201 (absolute 200) | Date of manufacture | STRING[12] | Read | |||||
| HR | 206doc 40207 (absolute 206) | Operating mode | Current unit state. | UINT16 | Read | 0 = Standby; 1 = On; 2 = idle; 3 = Maintenance | |||
| HR | 207doc 40208 (absolute 207) | Unit cool output | Cooling delivered by this unit. | INT32 | ABCD | × 0.1 | kW | Read | |
| HR | 209doc 40210 (absolute 209) | Unit cool demand | INT32 | ABCD | × 0.1 | kW | Read | ||
| HR | 211doc 40212 (absolute 211) | Unit max rack inlet temp | Highest rack inlet temperature seen by this unit. | INT32 | ABCD | × 0.1 | °F | Read | |
| HR | 213doc 40214 (absolute 213) | Supply air temp | Air temperature leaving the unit. | INT32 | ABCD | × 0.1 | °F | Read | |
| HR | 215doc 40216 (absolute 215) | Return air temp | Air temperature entering the unit. | INT32 | ABCD | × 0.1 | °F | Read | |
| HR | 217doc 40218 (absolute 217) | Unit air flow | INT32 | ABCD | CFM | Read | |||
| HR | 219doc 40220 (absolute 219) | Fan speed | Current fan speed. | INT32 | ABCD | × 0.1 | % | Read | |
| HR | 221doc 40222 (absolute 221) | Active power source | UINT16 | Read | 0 = Primary; 1 = Secondary | ||||
| HR | 222doc 40223 (absolute 222) | Filter differential pressure | INT32 | ABCD | × 0.01 | in W.C. | Read | ||
| HR | 226doc 40227 (absolute 226) | Chilled water valve position | Chilled water valve opening. | INT32 | ABCD | % | Read | ||
| HR | 228doc 40229 (absolute 228) | Chilled water flow | INT32 | ABCD | × 0.1 | GPM | Read | ||
| HR | 230doc 40231 (absolute 230) | Chilled water temp in | Entering chilled water temperature. | INT32 | ABCD | × 0.1 | °F | Read | |
| HR | 232doc 40233 (absolute 232) | Chilled water temp out | Leaving chilled water temperature. | INT32 | ABCD | × 0.1 | °F | Read | |
| HR | 234doc 40235 (absolute 234) | Air filter runhour | INT32 | ABCD | h | Read | |||
| HR | 236doc 40237 (absolute 236) | Fan 1 runhour | INT32 | ABCD | h | Read | |||
| HR | 238doc 40239 (absolute 238) | Fan 2 runhour | INT32 | ABCD | h | Read | |||
| HR | 240doc 40241 (absolute 240) | Fan 3 runhour | INT32 | ABCD | h | Read | |||
| HR | 242doc 40243 (absolute 242) | Fan 4 runhour | INT32 | ABCD | h | Read | |||
| HR | 244doc 40245 (absolute 244) | Fan 5 runhour | INT32 | ABCD | h | Read | |||
| HR | 246doc 40247 (absolute 246) | Fan 6 runhour | INT32 | ABCD | h | Read | |||
| HR | 248doc 40249 (absolute 248) | Fan 7 runhour | INT32 | ABCD | h | Read | |||
| HR | 250doc 40251 (absolute 250) | Fan 8 runhour | INT32 | ABCD | h | Read | |||
| HR | 252doc 40253 (absolute 252) | Fan psu 1 runhour | INT32 | ABCD | h | Read | |||
| HR | 254doc 40255 (absolute 254) | Fan psu 2 runhour | INT32 | ABCD | h | Read | |||
| HR | 256doc 40257 (absolute 256) | Condensate pump runhour | INT32 | ABCD | h | Read | |||
| HR | 258doc 40259 (absolute 258) | Air filter service interval | INT32 | ABCD | weeks | Read/write | |||
| HR | 260doc 40261 (absolute 260) | Air filter service interval alarm | UINT16 | Read/write | 0 = Enable; 1 = Disable | ||||
| HR | 261doc 40262 (absolute 261) | Rack temp high thresh | INT32 | ABCD | × 0.1 | °F | Read/write | ||
| HR | 263doc 40264 (absolute 263) | Supply air temp high thresh | INT32 | ABCD | × 0.1 | °F | Read/write | ||
| HR | 265doc 40266 (absolute 265) | Return air temp high thresh | INT32 | ABCD | × 0.1 | °F | Read/write | ||
| HR | 267doc 40268 (absolute 267) | Entering chilled water temp high thresh | INT32 | ABCD | × 0.1 | °F | Read/write | ||
| HR | 269doc 40270 (absolute 269) | Startup delay | Delay before the unit starts after power-up. | INT32 | ABCD | s | Read/write | ||
| HR | 271doc 40272 (absolute 271) | Chilled water valve control | UINT16 | Read | 0 = Automatic; 1 = Open | ||||
| HR | 272doc 40273 (absolute 272) | Idle on leak | 0 means the unit idles when a leak is detected. | UINT16 | Read/write | 0 = Yes; 1 = No | |||
| HR | 273doc 40274 (absolute 273) | Standby input normal state | UINT16 | Read/write | 0 = Open; 1 = Closed | ||||
| HR | 274doc 40275 (absolute 274) | Standby input state | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| HR | 276doc 40277 (absolute 276) | Output state 1 | Same as decimal address 280. For legacy systems. | UINT16 | Read | 0 = Abnormal; 1 = Normal | |||
| HR | 278doc 40279 (absolute 278) | Power source | UINT16 | Read/write | 0 = Single; 1 = Dual | ||||
| HR | 279doc 40280 (absolute 279) | Idle on cool fail | 0 means the unit idles when cooling fails. | UINT16 | Read/write | 0 = Yes; 1 = No | |||
| HR | 280doc 40281 (absolute 280) | Output state 1 | Same as decimal address 276. | UINT16 | Read | 0 = Abnormal; 1 = Normal | |||
| HR | 281doc 40282 (absolute 281) | Output state 2 | UINT16 | Read | 0 = Abnormal; 1 = Normal | ||||
| HR | 282doc 40283 (absolute 282) | Output state 3 | UINT16 | Read | 0 = Abnormal; 1 = Normal | ||||
| HR | 283doc 40284 (absolute 283) | Output state 4 | UINT16 | Read | 0 = Abnormal; 1 = Normal | ||||
| HR | 289doc 40290 (absolute 289) | Maximum chilled water flow | INT32 | ABCD | × 0.1 | GPM | Read | ||
| HR | 291doc 40292 (absolute 291) | Bypass value position | UINT16 | Read/write | 0 = Open; 1 = Closed | ||||
| HR | 292doc 40293 (absolute 292) | Unit service interval | INT32 | ABCD | weeks | Read | |||
| HR | 294doc 40295 (absolute 294) | Unit service interval alarm | UINT16 | Read | 0 = Enable; 1 = Disable | ||||
| HR | 295doc 40296 (absolute 295) | Dew point temp | Dew point measured at the unit. | INT32 | ABCD | × 0.1 | °F | Read | |
| HR | 297doc 40298 (absolute 297) | Coil chilled water temp | INT32 | ABCD | × 0.1 | °F | Read | ||
| HR | 299doc 40300 (absolute 299) | Unit power | Electrical power drawn by the unit. | INT32 | ABCD | × 0.1 | kW | Read | |
| HR | 301doc 40302 (absolute 301) | Unit energy | Energy used by the unit. | INT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 303doc 40304 (absolute 303) | Unit runhour | INT32 | ABCD | h | Read | |||
| HR | 305doc 40306 (absolute 305) | Circulation pump runhour | INT32 | ABCD | h | Read | |||
| HR | 307doc 40308 (absolute 307) | Number of rack inlet temperature sensors | INT32 | ABCD | Read/write | ||||
| HR | 309doc 40310 (absolute 309) | Number of leak detectors | INT32 | ABCD | Read/write | ||||
| HR | 311doc 40312 (absolute 311) | Air filter type | UINT16 | Read/write | 0 = Standard; 1 = Pleated | ||||
| HR | 312doc 40313 (absolute 312) | Leak detector state 1 | UINT16 | Read | 0 = No Leak; 1 = Leak Detected | ||||
| HR | 313doc 40314 (absolute 313) | Leak detector state 2 | UINT16 | Read | 0 = No Leak; 1 = Leak Detected | ||||
| HR | 314doc 40315 (absolute 314) | Leak detector state 3 | UINT16 | Read | 0 = No Leak; 1 = Leak Detected | ||||
| HR | 315doc 40316 (absolute 315) | Leak detector state 4 | UINT16 | Read | 0 = No Leak; 1 = Leak Detected | ||||
| HR | 316doc 40317 (absolute 316) | Unit rack inlet temp 1 | INT32 | ABCD | × 0.1 | °F | Read | ||
| HR | 318doc 40319 (absolute 318) | Unit rack inlet temp 2 | INT32 | ABCD | × 0.1 | °F | Read | ||
| HR | 320doc 40321 (absolute 320) | Unit rack inlet temp 3 | INT32 | ABCD | × 0.1 | °F | Read | ||
| HR | 322doc 40323 (absolute 322) | Unit rack inlet temp 4 | INT32 | ABCD | × 0.1 | °F | Read | ||
| HR | 324doc 40325 (absolute 324) | Alarm on standby | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 325doc 40326 (absolute 325) | Circulation pump flow | INT32 | ABCD | × 0.1 | GPM | Read | ||
| HR | 327doc 40328 (absolute 327) | Circulation pump speed | INT32 | ABCD | % | Read | |||
| HR | 329doc 40330 (absolute 329) | Circulation pump power | INT32 | ABCD | W | Read | |||
| HR | 384doc 40385 (absolute 384) | Internal comm error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 386doc 40387 (absolute 386) | Cool function unavailable | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 387doc 40388 (absolute 387) | High rack temp | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 388doc 40389 (absolute 388) | Air filter clogged | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 389doc 40390 (absolute 389) | Lower return air sensor error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 390doc 40391 (absolute 390) | Upper return air sensor error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 391doc 40392 (absolute 391) | Lower supply air sensor error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 392doc 40393 (absolute 392) | Upper supply air sensor error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 393doc 40394 (absolute 393) | Rack temp sensor 1 error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 394doc 40395 (absolute 394) | Chilled water valve actuator error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 395doc 40396 (absolute 395) | Fan 1 error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 396doc 40397 (absolute 396) | Fan 2 error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 397doc 40398 (absolute 397) | Fan 3 error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 398doc 40399 (absolute 398) | Fan 4 error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 399doc 40400 (absolute 399) | Fan 5 error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 400doc 40401 (absolute 400) | Fan 6 error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 401doc 40402 (absolute 401) | Fan 7 error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 402doc 40403 (absolute 402) | Fan 8 error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 403doc 40404 (absolute 403) | Water detected | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 404doc 40405 (absolute 404) | Check conds mgmt system | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 405doc 40406 (absolute 405) | Chilled water flowmeter error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 406doc 40407 (absolute 406) | Entering chilled water high temp | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 407doc 40408 (absolute 407) | Entering chilled water temp sensor error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 408doc 40409 (absolute 408) | Leaving chilled water temp sensor error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 409doc 40410 (absolute 409) | Condensate pan full | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 410doc 40411 (absolute 410) | Primary power source unavailable | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 411doc 40412 (absolute 411) | Secondary power source unavailable | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 412doc 40413 (absolute 412) | Fan power supply 1 error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 413doc 40414 (absolute 413) | Fan power supply 2 error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 414doc 40415 (absolute 414) | Air filter runhour violation | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 416doc 40417 (absolute 416) | Standby due to input contact | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 417doc 40418 (absolute 417) | Unexpected number of units in group | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 418doc 40419 (absolute 418) | Supply high temperature | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 419doc 40420 (absolute 419) | Return high temperature | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 420doc 40421 (absolute 420) | Dp filter sensor error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 422doc 40423 (absolute 422) | Chilled water valve not set to auto | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 423doc 40424 (absolute 423) | Idle due to leak detected | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 429doc 40430 (absolute 429) | Ecoaisle door open | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 430doc 40431 (absolute 430) | Unexpected number of active flow controllers | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 431doc 40432 (absolute 431) | Insufficient airflow | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 432doc 40433 (absolute 432) | Active flow controller sensor error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 433doc 40434 (absolute 433) | Rack temp sensor 2 error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 434doc 40435 (absolute 434) | Rack temp sensor 3 error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 435doc 40436 (absolute 435) | Rack temp sensor 4 error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 436doc 40437 (absolute 436) | Unit service required | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 437doc 40438 (absolute 437) | Humidity sensor error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 438doc 40439 (absolute 438) | Coil condensation possible | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 439doc 40440 (absolute 439) | Controller power supply 1 error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 440doc 40441 (absolute 440) | Controller power supply 2 error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 441doc 40442 (absolute 441) | Coil chilled water temp sensor error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 442doc 40443 (absolute 442) | Fan power supply 1 current sensor error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 443doc 40444 (absolute 443) | Fan power supply 2 current sensor error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 444doc 40445 (absolute 444) | Factory configuration not complete | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 445doc 40446 (absolute 445) | Unit in maintenance mode | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 446doc 40447 (absolute 446) | Unexpected number of rack inlet sensors | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 447doc 40448 (absolute 447) | Unexpected number of leak sensors | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 448doc 40449 (absolute 448) | Output relay 1 abnormal | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 449doc 40450 (absolute 449) | Output relay 2 abnormal | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 450doc 40451 (absolute 450) | Output relay 3 abnormal | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 451doc 40452 (absolute 451) | Output relay 4 abnormal | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 452doc 40453 (absolute 452) | Circulation pump error | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 453doc 40454 (absolute 453) | Standby due to user action | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 454doc 40454 (absolute 454) | Circulation pump comm loss | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 455doc 40454 (absolute 455) | Circulation pump warning | UINT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 456doc 40454 (absolute 456) | Circulation pump needs service | UINT16 | Read | 0 = Clear; 1 = Alarm |
Notes on this map
- Word order: note 2 says INT32 and UINT32 keep the most significant word at n+0, so 32-bit values are ABCD (big-endian). Note 5: signed values are two's complement.
- Scale comes from the units column: '(Tenths)' is 0.1 and '(Hundredths)' is 0.01. Temperatures are in tenths of a degree Fahrenheit only; the map has no Celsius registers.
- Function codes 3 and 4 both read the same registers. Writes use function 16, or function 6 for one-register items.
- Strings hold two characters per register, high byte first; a null terminator must be included when writing.
- The last four alarm rows (decimal 453-456) all print Modicon 40454 in the source. Their hex and decimal columns run 453, 454, 455, 456, and those are used here.
- In revision B the column headed hexadecimal actually prints the decimal value (for example 40017 shows 16, not 0010); the decimal column is used for the wire address.
- Reserved rows are left out. Reading an undefined register on its own returns an error; a block read that starts on a valid register returns zeros for gaps.
- The register map does not give serial settings, a unit ID or a TCP port.
- An older edition, 990-4742A, is also published by Schneider; it lacks the rows added in revision B (for example OPERATE_MODE is named OPERATING_MODE in B).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm)
What Modbus registers does the APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm) have?
This map lists 163 registers: 163 holding registers. 27 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row gives a Modicon number (40001 style) plus the absolute address in hex and decimal. Note 11 says absolute address 0 equals register 40001 and is address zero on the wire, so the decimal column is the wire address.
What byte order does the APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm)?
Start with HR 0 Overall status (Overall alarm severity); HR 206 Operating mode (Unit operating mode); HR 207 Unit cool output (Unit cooling output); HR 211 Unit max rack inlet temp (Highest rack inlet temperature); HR 213 Supply air temp (Supply air temperature); HR 215 Return air temp (Return air temperature); HR 219 Fan speed (Fan speed); HR 5 Cool setpoint (Cooling setpoint (writable)); HR 386 Cool function unavailable (Cooling function unavailable alarm); HR 403 Water detected (Water detected alarm).
How do I enable Modbus control of the APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm)?
The register map does not describe how to enable Modbus or set the network parameters.
Where is the official APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm) Modbus documentation?
The source is Modbus Register Map: InRow ACRC30x (990-4742B), published free by APC (Schneider Electric) at https://download.se.com/files?p_Doc_Ref=SPD_KKRZ-99YNMA_EN.
More APC (Schneider Electric) Modbus register maps
- UPS
APC (Schneider Electric) Galaxy VL 200-500 kW three-phase UPS
Schneider Electric Galaxy VL 200-500 kW UPS with firmware 7.23 or later, per register map 990-6447.
Also known as: Galaxy VL, GVL, Galaxy VL 200 kW, Galaxy VL 500 kW - Air handler (in-row data-centre cooling unit)
APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786)
APC / Schneider Electric InRow ACRD60x and ACRC60x in-row cooling units, register map part number 990-5786A.
Also known as: ACRD60x, ACRC60x, InRow ACRD60x, InRow ACRC60x, 990-5786 - Air handler (in-row self-contained DX cooling unit)
APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit
APC by Schneider Electric InRow SC (ACSC 100 series) self-contained cooling units, per register map part number 990-3027D.
Also known as: ACSC100, InRow SC, InRow ACSC - Air handler (in-row data-centre DX cooling unit)
APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B)
APC / Schneider Electric InRow RD cooling units, register map part number 990-3576B (08/2015).
Also known as: InRow RD, 990-3576B, Schneider Electric InRow RD - UPS
APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702)
APC Smart-UPS (excluding SMT, SMX, SURTD and SRT prefixes), Smart-UPS VT and MGE Galaxy 3500 through Network Management Card AP9630/AP9631/AP9635 (TCP) or AP9635 (RTU), part number 990-5702.
Also known as: 990-5702, AP9630, AP9631, AP9635, Smart-UPS VT, MGE Galaxy 3500, Schneider Electric APC Smart-UPS - UPS
APC Symmetra PX 250/500 kW
APC Symmetra PX 250/500 kW three-phase UPS via Network Management Card AP9635, register map 990-3936D (firmware sypx510 to sypx516 changes listed in the source).
Also known as: 990-3936D, Symmetra PX 250 kW, Symmetra PX 500 kW, SYPX
Other hvac equipment register maps
- Air handler humidifier (resistive steam)
Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP)
Condair RS with the Integrated Controller (cylinders A and B), per addendum 2603326-G.
Also known as: Condair RS, Condair RS II, RS - Air handler (EC fan)
ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite)
ebm-papst EC fans and motors whose electronics report the MODBUS Lite parameter set (series 84 / 112 / 150 / 200 Lite), specification V5.01.
Also known as: MODBUS Lite V5.01, ebm-papst RadiCal Modbus, ebm-papst RadiPac Modbus, ebm-papst series 84 Lite, ebm-papst series 112 Lite, ebm-papst series 150 Lite, ebm-papst series 200 Lite - Thermostat
Johnson Controls PENN TC3223 refrigeration temperature controller (Modbus RTU)
PENN TC3223 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3223, TC3, PENN TC3, LIT-12013523 - Air handler (computer room air conditioner)
Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC)
Mitsubishi Electric (Hydronics & IT Cooling) s-MEXT-G00 006-044 close-control units with ME28-relC software and the Modbus serial board.
Also known as: s-MEXT, s-MEXT-G00 006-044, s-MEXT G00, ME28 relC - Air handler humidifier (gas-fired steam)
Neptronic SKG4 gas-fired steam humidifier (Modbus communication module)
Neptronic SKG4 series gas-fired steam humidifiers (one to four burner modules) with the Modbus communication module, guide SKG4-Modbus Guide-221114 (V2.04).
Also known as: SKG4-E, SKG4-N, SKG4 Gas Fired Humidifier, Neptronic SKG4 Modbus - Air handler controller
Regin Corrigo ventilation controller (ventilation application 3.6)
Regin Corrigo controllers running the pre-programmed ventilation (air handling unit) application, version 3.6 or later; not the heating or Exigo applications.
Also known as: Corrigo E, Corrigo ventilation, Corrigo E ventilation, Corrigo AHU controller
All hvac equipment Modbus register maps →
Source: Modbus Register Map: InRow ACRC30x · 990-4742B. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.