Air handler (in-row chilled-water cooling unit) · Modbus register map

APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm) Modbus register map

Updated 19 November 2026

Short answer

The InRow ACRC30x is a 300 mm wide chilled-water cooling unit that sits between server racks. Its controller answers Modbus RTU and Modbus TCP, with every value in holding registers that can also be read with function 04. This map covers the group values (cooling output, setpoints, airflow), the unit readings (temperatures, fan speed, chilled water valve, flow, power and energy, run hours), configuration items and the full list of one-register alarm flags.

This page lists 163 Modbus registers for the APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm) — 27 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from APC (Schneider Electric)’s own free documentation (linked below) and checked against it.

Manufacturer
APC (Schneider Electric)
Model
InRow ACRC30x chilled-water cooling unit (300 mm)
Equipment type
Air handler (in-row chilled-water cooling unit)
Registers
163 (27 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
ACRC30x, ACRC300, ACRC301, InRow RC 300 mm
Source document
Modbus Register Map: InRow ACRC30x · 990-4742B
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm)

Integration in brief

Poll holding registers from address 0 with function 03 or 04. Read OVERALL_STATUS and OPERATING_MODE first, then the 32-bit temperatures and cooling output in tenths, and scan the alarm block at 384-456 for active flags.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Overall statusUINT16Overall alarm severityRead
HR 206Operating modeUINT16Unit operating modeRead
HR 207Unit cool outputINT32 ABCDUnit cooling outputRead
HR 211Unit max rack inlet tempINT32 ABCDHighest rack inlet temperatureRead
HR 213Supply air tempINT32 ABCDSupply air temperatureRead
HR 215Return air tempINT32 ABCDReturn air temperatureRead
HR 219Fan speedINT32 ABCDFan speedRead
HR 5Cool setpointINT32 ABCDCooling setpoint (writable)Read/write
HR 386Cool function unavailableUINT16Cooling function unavailable alarmRead
HR 403Water detectedUINT16Water detected alarmRead

Enable Modbus control & writes

The register map does not describe how to enable Modbus or set the network parameters.

Byte order & addressing

Network setup

Watch out for

APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

163 of 163 shown
APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001 (absolute 0)Overall statusWorst active alarm severity for the unit.UINT16Read0 = No Alarm; 1 = Informational; 2 = Warning; 3 = Critical
HR1doc 40002 (absolute 1)Group cool outputCooling delivered by the whole InRow group.INT32ABCD× 0.1kWRead
HR3doc 40004 (absolute 3)Group cool demandCooling requested by the whole group.INT32ABCD× 0.1kWRead
HR5doc 40006 (absolute 5)Cool setpointCooling setpoint the group controls to.INT32ABCD× 0.1°FRead/write
HR7doc 40008 (absolute 7)Supply air setpointSupply air temperature setpoint.INT32ABCD× 0.1°FRead/write
HR9doc 40010 (absolute 9)Group air flowTotal airflow of the group.INT32ABCDCFMRead
HR11doc 40012 (absolute 11)Group max rack tempINT32ABCD× 0.1°FRead
HR13doc 40014 (absolute 13)Group min rack tempINT32ABCD× 0.1°FRead
HR15doc 40016 (absolute 15)Airflow controlFan speed preference: automatic or a fixed percentage.UINT16Read/write0 = Automatic; 1 = 60%; 2 = 70%; 3 = 80%; 4 = 90%; 5 = 100%
HR16doc 40017 (absolute 16)Number of unitsINT32ABCDRead/write
HR18doc 40019 (absolute 18)Configuration typeContainment arrangement the group is set up for.UINT16Read0 = RACS; 1 = HACS; 2 = InRow; 3 = CACS
HR19doc 40020 (absolute 19)Cool pid pINT32ABCD× 0.01Read
HR21doc 40022 (absolute 21)Cool pid iINT32ABCD× 0.01Read
HR23doc 40024 (absolute 23)Cool pid dINT32ABCD× 0.01Read
HR25doc 40026 (absolute 25)Percent glycolINT32ABCD%Read
HR27doc 40028 (absolute 27)Max fan speedUpper limit for fan speed.INT32ABCD%Read/write
HR30doc 40031 (absolute 30)AltitudeINT32ABCDftRead/write
HR32doc 40033 (absolute 32)Number active flow controllersINT32ABCDRead/write
HR34doc 40035 (absolute 34)Active flow control biasUINT16Read0 = Positive; 1 = Slightly Positive; 2 = Zero; 3 = Slightly Negative; 4 = Negative
HR35doc 40036 (absolute 35)Active flow control statusUINT16Read0 = Under; 1 = Okay; 2 = Over; 3 = N/A
HR36doc 40037 (absolute 36)Active flow control lamp testUINT16Read/write0 = Disable; 1 = Enable
HR37doc 40038 (absolute 37)Delta t setpointUINT16Read/write0 = 10 Deg F; 1 = 15 Deg F; 2 = 20 Deg F; 3 = 25 Deg F; 4 = 30 Deg F; 5 = 35 Deg F; 6 = 40 Deg F
HR128doc 40129 (absolute 128)Unit nameSTRING[42]Read/write
HR149doc 40150 (absolute 149)Unit locationSTRING[42]Read/write
HR172doc 40173 (absolute 172)Model numberSTRING[20]Read
HR182doc 40183 (absolute 182)Serial numberSTRING[20]Read
HR192doc 40193 (absolute 192)Firmware revSTRING[8]Read
HR196doc 40197 (absolute 196)Hardware revSTRING[8]Read
HR200doc 40201 (absolute 200)Date of manufactureSTRING[12]Read
HR206doc 40207 (absolute 206)Operating modeCurrent unit state.UINT16Read0 = Standby; 1 = On; 2 = idle; 3 = Maintenance
HR207doc 40208 (absolute 207)Unit cool outputCooling delivered by this unit.INT32ABCD× 0.1kWRead
HR209doc 40210 (absolute 209)Unit cool demandINT32ABCD× 0.1kWRead
HR211doc 40212 (absolute 211)Unit max rack inlet tempHighest rack inlet temperature seen by this unit.INT32ABCD× 0.1°FRead
HR213doc 40214 (absolute 213)Supply air tempAir temperature leaving the unit.INT32ABCD× 0.1°FRead
HR215doc 40216 (absolute 215)Return air tempAir temperature entering the unit.INT32ABCD× 0.1°FRead
HR217doc 40218 (absolute 217)Unit air flowINT32ABCDCFMRead
HR219doc 40220 (absolute 219)Fan speedCurrent fan speed.INT32ABCD× 0.1%Read
HR221doc 40222 (absolute 221)Active power sourceUINT16Read0 = Primary; 1 = Secondary
HR222doc 40223 (absolute 222)Filter differential pressureINT32ABCD× 0.01in W.C.Read
HR226doc 40227 (absolute 226)Chilled water valve positionChilled water valve opening.INT32ABCD%Read
HR228doc 40229 (absolute 228)Chilled water flowINT32ABCD× 0.1GPMRead
HR230doc 40231 (absolute 230)Chilled water temp inEntering chilled water temperature.INT32ABCD× 0.1°FRead
HR232doc 40233 (absolute 232)Chilled water temp outLeaving chilled water temperature.INT32ABCD× 0.1°FRead
HR234doc 40235 (absolute 234)Air filter runhourINT32ABCDhRead
HR236doc 40237 (absolute 236)Fan 1 runhourINT32ABCDhRead
HR238doc 40239 (absolute 238)Fan 2 runhourINT32ABCDhRead
HR240doc 40241 (absolute 240)Fan 3 runhourINT32ABCDhRead
HR242doc 40243 (absolute 242)Fan 4 runhourINT32ABCDhRead
HR244doc 40245 (absolute 244)Fan 5 runhourINT32ABCDhRead
HR246doc 40247 (absolute 246)Fan 6 runhourINT32ABCDhRead
HR248doc 40249 (absolute 248)Fan 7 runhourINT32ABCDhRead
HR250doc 40251 (absolute 250)Fan 8 runhourINT32ABCDhRead
HR252doc 40253 (absolute 252)Fan psu 1 runhourINT32ABCDhRead
HR254doc 40255 (absolute 254)Fan psu 2 runhourINT32ABCDhRead
HR256doc 40257 (absolute 256)Condensate pump runhourINT32ABCDhRead
HR258doc 40259 (absolute 258)Air filter service intervalINT32ABCDweeksRead/write
HR260doc 40261 (absolute 260)Air filter service interval alarmUINT16Read/write0 = Enable; 1 = Disable
HR261doc 40262 (absolute 261)Rack temp high threshINT32ABCD× 0.1°FRead/write
HR263doc 40264 (absolute 263)Supply air temp high threshINT32ABCD× 0.1°FRead/write
HR265doc 40266 (absolute 265)Return air temp high threshINT32ABCD× 0.1°FRead/write
HR267doc 40268 (absolute 267)Entering chilled water temp high threshINT32ABCD× 0.1°FRead/write
HR269doc 40270 (absolute 269)Startup delayDelay before the unit starts after power-up.INT32ABCDsRead/write
HR271doc 40272 (absolute 271)Chilled water valve controlUINT16Read0 = Automatic; 1 = Open
HR272doc 40273 (absolute 272)Idle on leak0 means the unit idles when a leak is detected.UINT16Read/write0 = Yes; 1 = No
HR273doc 40274 (absolute 273)Standby input normal stateUINT16Read/write0 = Open; 1 = Closed
HR274doc 40275 (absolute 274)Standby input stateUINT16Read0 = Open; 1 = Closed
HR276doc 40277 (absolute 276)Output state 1Same as decimal address 280. For legacy systems.UINT16Read0 = Abnormal; 1 = Normal
HR278doc 40279 (absolute 278)Power sourceUINT16Read/write0 = Single; 1 = Dual
HR279doc 40280 (absolute 279)Idle on cool fail0 means the unit idles when cooling fails.UINT16Read/write0 = Yes; 1 = No
HR280doc 40281 (absolute 280)Output state 1Same as decimal address 276.UINT16Read0 = Abnormal; 1 = Normal
HR281doc 40282 (absolute 281)Output state 2UINT16Read0 = Abnormal; 1 = Normal
HR282doc 40283 (absolute 282)Output state 3UINT16Read0 = Abnormal; 1 = Normal
HR283doc 40284 (absolute 283)Output state 4UINT16Read0 = Abnormal; 1 = Normal
HR289doc 40290 (absolute 289)Maximum chilled water flowINT32ABCD× 0.1GPMRead
HR291doc 40292 (absolute 291)Bypass value positionUINT16Read/write0 = Open; 1 = Closed
HR292doc 40293 (absolute 292)Unit service intervalINT32ABCDweeksRead
HR294doc 40295 (absolute 294)Unit service interval alarmUINT16Read0 = Enable; 1 = Disable
HR295doc 40296 (absolute 295)Dew point tempDew point measured at the unit.INT32ABCD× 0.1°FRead
HR297doc 40298 (absolute 297)Coil chilled water tempINT32ABCD× 0.1°FRead
HR299doc 40300 (absolute 299)Unit powerElectrical power drawn by the unit.INT32ABCD× 0.1kWRead
HR301doc 40302 (absolute 301)Unit energyEnergy used by the unit.INT32ABCD× 0.1kWhRead
HR303doc 40304 (absolute 303)Unit runhourINT32ABCDhRead
HR305doc 40306 (absolute 305)Circulation pump runhourINT32ABCDhRead
HR307doc 40308 (absolute 307)Number of rack inlet temperature sensorsINT32ABCDRead/write
HR309doc 40310 (absolute 309)Number of leak detectorsINT32ABCDRead/write
HR311doc 40312 (absolute 311)Air filter typeUINT16Read/write0 = Standard; 1 = Pleated
HR312doc 40313 (absolute 312)Leak detector state 1UINT16Read0 = No Leak; 1 = Leak Detected
HR313doc 40314 (absolute 313)Leak detector state 2UINT16Read0 = No Leak; 1 = Leak Detected
HR314doc 40315 (absolute 314)Leak detector state 3UINT16Read0 = No Leak; 1 = Leak Detected
HR315doc 40316 (absolute 315)Leak detector state 4UINT16Read0 = No Leak; 1 = Leak Detected
HR316doc 40317 (absolute 316)Unit rack inlet temp 1INT32ABCD× 0.1°FRead
HR318doc 40319 (absolute 318)Unit rack inlet temp 2INT32ABCD× 0.1°FRead
HR320doc 40321 (absolute 320)Unit rack inlet temp 3INT32ABCD× 0.1°FRead
HR322doc 40323 (absolute 322)Unit rack inlet temp 4INT32ABCD× 0.1°FRead
HR324doc 40325 (absolute 324)Alarm on standbyUINT16Read/write0 = No; 1 = Yes
HR325doc 40326 (absolute 325)Circulation pump flowINT32ABCD× 0.1GPMRead
HR327doc 40328 (absolute 327)Circulation pump speedINT32ABCD%Read
HR329doc 40330 (absolute 329)Circulation pump powerINT32ABCDWRead
HR384doc 40385 (absolute 384)Internal comm errorUINT16Read0 = Clear; 1 = Alarm
HR386doc 40387 (absolute 386)Cool function unavailableUINT16Read0 = Clear; 1 = Alarm
HR387doc 40388 (absolute 387)High rack tempUINT16Read0 = Clear; 1 = Alarm
HR388doc 40389 (absolute 388)Air filter cloggedUINT16Read0 = Clear; 1 = Alarm
HR389doc 40390 (absolute 389)Lower return air sensor errorUINT16Read0 = Clear; 1 = Alarm
HR390doc 40391 (absolute 390)Upper return air sensor errorUINT16Read0 = Clear; 1 = Alarm
HR391doc 40392 (absolute 391)Lower supply air sensor errorUINT16Read0 = Clear; 1 = Alarm
HR392doc 40393 (absolute 392)Upper supply air sensor errorUINT16Read0 = Clear; 1 = Alarm
HR393doc 40394 (absolute 393)Rack temp sensor 1 errorUINT16Read0 = Clear; 1 = Alarm
HR394doc 40395 (absolute 394)Chilled water valve actuator errorUINT16Read0 = Clear; 1 = Alarm
HR395doc 40396 (absolute 395)Fan 1 errorUINT16Read0 = Clear; 1 = Alarm
HR396doc 40397 (absolute 396)Fan 2 errorUINT16Read0 = Clear; 1 = Alarm
HR397doc 40398 (absolute 397)Fan 3 errorUINT16Read0 = Clear; 1 = Alarm
HR398doc 40399 (absolute 398)Fan 4 errorUINT16Read0 = Clear; 1 = Alarm
HR399doc 40400 (absolute 399)Fan 5 errorUINT16Read0 = Clear; 1 = Alarm
HR400doc 40401 (absolute 400)Fan 6 errorUINT16Read0 = Clear; 1 = Alarm
HR401doc 40402 (absolute 401)Fan 7 errorUINT16Read0 = Clear; 1 = Alarm
HR402doc 40403 (absolute 402)Fan 8 errorUINT16Read0 = Clear; 1 = Alarm
HR403doc 40404 (absolute 403)Water detectedUINT16Read0 = Clear; 1 = Alarm
HR404doc 40405 (absolute 404)Check conds mgmt systemUINT16Read0 = Clear; 1 = Alarm
HR405doc 40406 (absolute 405)Chilled water flowmeter errorUINT16Read0 = Clear; 1 = Alarm
HR406doc 40407 (absolute 406)Entering chilled water high tempUINT16Read0 = Clear; 1 = Alarm
HR407doc 40408 (absolute 407)Entering chilled water temp sensor errorUINT16Read0 = Clear; 1 = Alarm
HR408doc 40409 (absolute 408)Leaving chilled water temp sensor errorUINT16Read0 = Clear; 1 = Alarm
HR409doc 40410 (absolute 409)Condensate pan fullUINT16Read0 = Clear; 1 = Alarm
HR410doc 40411 (absolute 410)Primary power source unavailableUINT16Read0 = Clear; 1 = Alarm
HR411doc 40412 (absolute 411)Secondary power source unavailableUINT16Read0 = Clear; 1 = Alarm
HR412doc 40413 (absolute 412)Fan power supply 1 errorUINT16Read0 = Clear; 1 = Alarm
HR413doc 40414 (absolute 413)Fan power supply 2 errorUINT16Read0 = Clear; 1 = Alarm
HR414doc 40415 (absolute 414)Air filter runhour violationUINT16Read0 = Clear; 1 = Alarm
HR416doc 40417 (absolute 416)Standby due to input contactUINT16Read0 = Clear; 1 = Alarm
HR417doc 40418 (absolute 417)Unexpected number of units in groupUINT16Read0 = Clear; 1 = Alarm
HR418doc 40419 (absolute 418)Supply high temperatureUINT16Read0 = Clear; 1 = Alarm
HR419doc 40420 (absolute 419)Return high temperatureUINT16Read0 = Clear; 1 = Alarm
HR420doc 40421 (absolute 420)Dp filter sensor errorUINT16Read0 = Clear; 1 = Alarm
HR422doc 40423 (absolute 422)Chilled water valve not set to autoUINT16Read0 = Clear; 1 = Alarm
HR423doc 40424 (absolute 423)Idle due to leak detectedUINT16Read0 = Clear; 1 = Alarm
HR429doc 40430 (absolute 429)Ecoaisle door openUINT16Read0 = Clear; 1 = Alarm
HR430doc 40431 (absolute 430)Unexpected number of active flow controllersUINT16Read0 = Clear; 1 = Alarm
HR431doc 40432 (absolute 431)Insufficient airflowUINT16Read0 = Clear; 1 = Alarm
HR432doc 40433 (absolute 432)Active flow controller sensor errorUINT16Read0 = Clear; 1 = Alarm
HR433doc 40434 (absolute 433)Rack temp sensor 2 errorUINT16Read0 = Clear; 1 = Alarm
HR434doc 40435 (absolute 434)Rack temp sensor 3 errorUINT16Read0 = Clear; 1 = Alarm
HR435doc 40436 (absolute 435)Rack temp sensor 4 errorUINT16Read0 = Clear; 1 = Alarm
HR436doc 40437 (absolute 436)Unit service requiredUINT16Read0 = Clear; 1 = Alarm
HR437doc 40438 (absolute 437)Humidity sensor errorUINT16Read0 = Clear; 1 = Alarm
HR438doc 40439 (absolute 438)Coil condensation possibleUINT16Read0 = Clear; 1 = Alarm
HR439doc 40440 (absolute 439)Controller power supply 1 errorUINT16Read0 = Clear; 1 = Alarm
HR440doc 40441 (absolute 440)Controller power supply 2 errorUINT16Read0 = Clear; 1 = Alarm
HR441doc 40442 (absolute 441)Coil chilled water temp sensor errorUINT16Read0 = Clear; 1 = Alarm
HR442doc 40443 (absolute 442)Fan power supply 1 current sensor errorUINT16Read0 = Clear; 1 = Alarm
HR443doc 40444 (absolute 443)Fan power supply 2 current sensor errorUINT16Read0 = Clear; 1 = Alarm
HR444doc 40445 (absolute 444)Factory configuration not completeUINT16Read0 = Clear; 1 = Alarm
HR445doc 40446 (absolute 445)Unit in maintenance modeUINT16Read0 = Clear; 1 = Alarm
HR446doc 40447 (absolute 446)Unexpected number of rack inlet sensorsUINT16Read0 = Clear; 1 = Alarm
HR447doc 40448 (absolute 447)Unexpected number of leak sensorsUINT16Read0 = Clear; 1 = Alarm
HR448doc 40449 (absolute 448)Output relay 1 abnormalUINT16Read0 = Clear; 1 = Alarm
HR449doc 40450 (absolute 449)Output relay 2 abnormalUINT16Read0 = Clear; 1 = Alarm
HR450doc 40451 (absolute 450)Output relay 3 abnormalUINT16Read0 = Clear; 1 = Alarm
HR451doc 40452 (absolute 451)Output relay 4 abnormalUINT16Read0 = Clear; 1 = Alarm
HR452doc 40453 (absolute 452)Circulation pump errorUINT16Read0 = Clear; 1 = Alarm
HR453doc 40454 (absolute 453)Standby due to user actionUINT16Read0 = Clear; 1 = Alarm
HR454doc 40454 (absolute 454)Circulation pump comm lossUINT16Read0 = Clear; 1 = Alarm
HR455doc 40454 (absolute 455)Circulation pump warningUINT16Read0 = Clear; 1 = Alarm
HR456doc 40454 (absolute 456)Circulation pump needs serviceUINT16Read0 = Clear; 1 = Alarm

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm)

What Modbus registers does the APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm) have?

This map lists 163 registers: 163 holding registers. 27 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row gives a Modicon number (40001 style) plus the absolute address in hex and decimal. Note 11 says absolute address 0 equals register 40001 and is address zero on the wire, so the decimal column is the wire address.

What byte order does the APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm)?

Start with HR 0 Overall status (Overall alarm severity); HR 206 Operating mode (Unit operating mode); HR 207 Unit cool output (Unit cooling output); HR 211 Unit max rack inlet temp (Highest rack inlet temperature); HR 213 Supply air temp (Supply air temperature); HR 215 Return air temp (Return air temperature); HR 219 Fan speed (Fan speed); HR 5 Cool setpoint (Cooling setpoint (writable)); HR 386 Cool function unavailable (Cooling function unavailable alarm); HR 403 Water detected (Water detected alarm).

How do I enable Modbus control of the APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm)?

The register map does not describe how to enable Modbus or set the network parameters.

Where is the official APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm) Modbus documentation?

The source is Modbus Register Map: InRow ACRC30x (990-4742B), published free by APC (Schneider Electric) at https://download.se.com/files?p_Doc_Ref=SPD_KKRZ-99YNMA_EN.