Air handler (computer room air conditioner) · Modbus register map
Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC) Modbus register map
Updated 17 November 2026
The s-MEXT-G00 is a Mitsubishi Electric direct-expansion close-control unit for computer rooms (6-44 kW). With the Modbus serial board fitted, its controller exposes Boolean variables as coils and analogue/integer variables as holding registers over RS-485 Modbus RTU. This map covers unit status and on/off, setpoints, room/delivery/outside temperatures, humidity, pressures, fan and damper positions, operating mode, run hours and the electrical readings.
This page lists 68 Modbus registers for the Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC) — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Mitsubishi Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- Mitsubishi Electric
- Model
- s-MEXT-G00 computer room air conditioner (ME28 relC)
- Equipment type
- Air handler (computer room air conditioner)
- Registers
- 68 (10 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 8N2
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Firmware
- ME28-relC
- Also known as
- s-MEXT, s-MEXT-G00 006-044, s-MEXT G00, ME28 relC
Integration notes: Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC)
Read unit status and alarm coils, room/delivery temperature, humidity and operating mode; write the on/off coil and the cold/hot setpoints (x10).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| CO 1 | Unit status | BIT | Unit status | Read |
| CO 2 | Presence of alarm | BIT | Alarm present | Read |
| CO 8 | On/Off command by supervisor | BIT | On/off command | Read/write |
| HR 1 | Cold temperature setpoint | INT16 | Cold temperature setpoint | Read/write |
| HR 6 | Room temperature | INT16 | Room temperature | Read |
| HR 21 | Ambient humidity | INT16 | Ambient humidity | Read |
| HR 142 | Unit operating mode | UINT16 | Unit operating mode | Read |
| HR 160 | Active alarm code (with greater priority) | UINT16 | Active alarm code | Read |
Enable Modbus control & writes
Fit the Modbus serial board, then in the User menu (User password) set P30.01 Enable supervision = Y, P30.02 BMS address, P30.03 protocol = Modbus and P30.04 baud rate. Set P30.05 On/Off by BMS = Y so the on/off coil works.
Byte order & addressing
- Numbering starts at 1: coil 002 is wire address 1 and register 40002 is wire address 1 (subtract 40001).
- Integer variables sit 128 registers above their software address.
Network setup
- Up to 200 units on one network; polling time grows with the number of units.
- Line settings are fixed at 8 data bits, no parity, 2 stop bits.
Watch out for
- A probe in alarm reads -999 (-99.9 after scaling); a probe or parameter that is not configured reads -888.
Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 1doc 002 | Unit status | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 2doc 003 | Presence of alarm | BIT | Read | 0 = Unit OK; 1 = Alarm | ||||
| CO | 8doc 009 | On/Off command by supervisor | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 15doc 016 | Status step 1 heating elements | BIT | Read | |||||
| CO | 16doc 017 | Status step 2 heating elements | BIT | Read | |||||
| CO | 37doc 038 | Free cooling stopped by BMS | BIT | Write | 0 = Normal free-cooling operation; 1 = Free cooling disabled | ||||
| HR | 1doc 40002 | Cold temperature setpoint | Write value x10 (21.3 °C = 213). | INT16 | × 0.1 | °C | Read/write | ||
| HR | 2doc 40003 | Hot temperature setpoint | Write value x10 (21.3 °C = 213). | INT16 | × 0.1 | °C | Read/write | ||
| HR | 4doc 40005 | Cold temperature setpoint active | Tenths. | INT16 | × 0.1 | °C | Read | ||
| HR | 5doc 40006 | Hot temperature active set point | Tenths. | INT16 | × 0.1 | °C | Read | ||
| HR | 6doc 40007 | Room temperature | Tenths; -999 = probe alarm, -888 = not configured. | INT16 | × 0.1 | °C | Read | ||
| HR | 7doc 40008 | Delivery temperature | Tenths; -999 = probe alarm, -888 = not configured. | INT16 | × 0.1 | °C | Read | ||
| HR | 8doc 40009 | Temperature used for adjustment | Tenths; -999 = probe alarm, -888 = not configured. | INT16 | × 0.1 | °C | Read | ||
| HR | 16doc 40017 | Low pressure | Tenths; -999 = probe alarm, -888 = not configured. | INT16 | × 0.1 | bar | Read | ||
| HR | 17doc 40018 | Circuit 2 low pressure | Tenths; -999 = probe alarm, -888 = not configured. | INT16 | × 0.1 | bar | Read | ||
| HR | 20doc 40021 | External air temperature | Tenths; -999 = probe alarm, -888 = not configured. | INT16 | × 0.1 | °C | Read | ||
| HR | 21doc 40022 | Ambient humidity | Tenths; -999 = probe alarm, -888 = not configured. | INT16 | × 0.1 | % | Read | ||
| HR | 23doc 40024 | Address 129 auxiliary probe temperature | Tenths; -999 = probe alarm, -888 = not configured. | INT16 | × 0.1 | °C | Read | ||
| HR | 24doc 40025 | Address 129 auxiliary probe humidity | Tenths; -999 = probe alarm, -888 = not configured. | INT16 | × 0.1 | % | Read | ||
| HR | 40doc 40041 | Fan speed | Tenths. | INT16 | × 0.1 | % | Read | ||
| HR | 53doc 40054 | Position of Freecooling damper | Tenths. | INT16 | × 0.1 | % | Read | ||
| HR | 54doc 40055 | Humidifier request | Tenths. | INT16 | × 0.1 | % | Read | ||
| HR | 131doc 40132 | Software version | UINT16 | Read | |||||
| HR | 132doc 40133 | Software version (revision) | UINT16 | Read | |||||
| HR | 138doc 40139 | Flow control type | UINT16 | Read | 0 = Adjustable head; 1 = Constant flow; 2 = Constant head | ||||
| HR | 139doc 40140 | Probe used for adjustment | UINT16 | Read | 0 = Ambient air probe; 1 = Delivery air probe | ||||
| HR | 140doc 40141 | Unit status | UINT16 | Read | 0 = ON from keyboard; 1 = ON from digital input; 2 = ON from pLAN; 3 = ON from time bands; 4 = ON from supervision; 5 = OFF from alarm; 6 = OFF from supervision; 7 = OFF from time bands; 8 = OFF from pLAN; 9 = OFF from digital input; 10 = OFF from keyboard; 11 = OFF from deselected ventilation; 12 = Switching off | ||||
| HR | 142doc 40143 | Unit operating mode | UINT16 | Read | 0 = Unit OFF; 1 = Ventilation only; 2 = Cooling; 3 = Free cooling; 4 = Cooling + free cooling; 5 = Dehumidification; 6 = Dehumidification + post heating; 7 = Humidification; 8 = Cooling + humidification; 9 = Heating; 10 = Heating + humidification | ||||
| HR | 153doc 40154 | Year | UINT16 | Read | |||||
| HR | 154doc 40155 | Month | UINT16 | Read | |||||
| HR | 155doc 40156 | Day | UINT16 | Read | |||||
| HR | 156doc 40157 | Time | UINT16 | h | Read | ||||
| HR | 157doc 40158 | Minutes | UINT16 | min | Read | ||||
| HR | 160doc 40161 | Active alarm code (with greater priority) | UINT16 | Read | |||||
| HR | 162doc 40163 | Cold thermoregulator request (%) | UINT16 | × 0.1 | % | Read | |||
| HR | 165doc 40166 | Heat request (%) | UINT16 | × 0.1 | % | Read | |||
| HR | 168doc 40169 | Post-heating request (%) | UINT16 | × 0.1 | % | Read | |||
| HR | 174doc 40175 | Dehumidification setpoint (%) | UINT16 | % | Read/write | ||||
| HR | 175doc 40176 | Humidification setpoint (%) | UINT16 | % | Read/write | ||||
| HR | 176doc 40177 | Unit operating hours (Thousands) | Thousands part; total = this x 1000 + units register. | UINT16 | h | Read | |||
| HR | 177doc 40178 | Unit operating hours (Units) | UINT16 | h | Read | ||||
| HR | 190doc 40191 | Heating element 1 operating hours (Thousands) | Thousands part; total = this x 1000 + units register. | UINT16 | h | Read | |||
| HR | 191doc 40192 | Heating element 1 operating hours (Units) | UINT16 | h | Read | ||||
| HR | 192doc 40193 | Heating element 2 operating hours (Thousands) | Thousands part; total = this x 1000 + units register. | UINT16 | h | Read | |||
| HR | 193doc 40194 | Heating element 2 operating hours (Units) | UINT16 | h | Read | ||||
| HR | 194doc 40195 | Humidifier operating hours (Thousands) | Thousands part; total = this x 1000 + units register. | UINT16 | h | Read | |||
| HR | 195doc 40196 | Humidifier operating hours (Units) | UINT16 | h | Read | ||||
| HR | 196doc 40197 | High ambient temperature set point | UINT16 | °C | Read/write | ||||
| HR | 197doc 40198 | Low ambient temperature set point | UINT16 | °C | Read/write | ||||
| HR | 198doc 40199 | Ambient humidity high set point | UINT16 | % | Read/write | ||||
| HR | 199doc 40200 | Low ambient humidity set point | UINT16 | % | Read/write | ||||
| HR | 208doc 40209 | Voltage measured between L1 and N | UINT16 | V | Read | ||||
| HR | 209doc 40210 | Voltage measured between L2 and N | UINT16 | V | Read | ||||
| HR | 210doc 40211 | Voltage measured between L3 and N | UINT16 | V | Read | ||||
| HR | 211doc 40212 | Voltage measured between L1 and L2 | UINT16 | V | Read | ||||
| HR | 212doc 40213 | Voltage measured between L2 and L3 | UINT16 | V | Read | ||||
| HR | 213doc 40214 | Voltage measured between L3 and L1 | UINT16 | V | Read | ||||
| HR | 214doc 40215 | Maximum current at L1 | UINT16 | × 0.1 | A | Read | |||
| HR | 215doc 40216 | Maximum current at L2 | UINT16 | × 0.1 | A | Read | |||
| HR | 216doc 40217 | Maximum current at L3 | UINT16 | × 0.1 | A | Read | |||
| HR | 217doc 40218 | Maximum current at N | UINT16 | × 0.1 | A | Read | |||
| HR | 218doc 40219 | L1 power | UINT16 | × 0.1 | kW | Read | |||
| HR | 219doc 40220 | L2 power | UINT16 | × 0.1 | kW | Read | |||
| HR | 220doc 40221 | L3 power | UINT16 | × 0.1 | kW | Read | |||
| HR | 221doc 40222 | Total Power | UINT16 | × 0.1 | kW | Read | |||
| HR | 222doc 40223 | Energy | UINT16 | kWh | Read | ||||
| HR | 231doc 40232 | Average differential pressure for DeltaP control with APL | UINT16 | Pa | Read | ||||
| HR | 232doc 40233 | Differential pressure for DeltaP control | UINT16 | Pa | Read |
Notes on this map
- Scale: the manual's conversion factors are 'Value x10' for writes and 'Value/10' for reads, so those registers hold tenths (scale 0.1); 'Value x1' registers are unscaled.
- Analogue (type A) variables are listed as INT16 because the manual documents negative sentinel values (-999 probe alarm, -888 not configured); integer (type I) variables are listed as UINT16 since none carry negative ranges. The manual does not state signedness explicitly.
- Flow OUT = read only, IN = written by the BMS; rows listing both are read-write. Coil 038 is IN only (write).
- Run hours are split into a 'thousands' and a 'units' register.
- Serial settings per the manual: 8 data bits, 2 stop bits, no parity (fixed); baud selectable 1200-19200 in the user menu (P30.04); unit ID 001-200.
- Addresses not listed in the database must not be used, per the manual.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC)
What Modbus registers does the Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC) have?
This map lists 68 registers: 6 coils, 62 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The interface database prints coils as 001-184 and registers as 40001-40257 and states the start address is 1, not 0. So coil 002 is wire address 1 and register 40002 is wire address 1. Integer ('whole') variables start at 40129 (software address + 128).
What are the minimum Modbus registers to integrate the Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC)?
Start with CO 1 Unit status (Unit status); CO 2 Presence of alarm (Alarm present); CO 8 On/Off command by supervisor (On/off command); HR 1 Cold temperature setpoint (Cold temperature setpoint); HR 6 Room temperature (Room temperature); HR 21 Ambient humidity (Ambient humidity); HR 142 Unit operating mode (Unit operating mode); HR 160 Active alarm code (with greater priority) (Active alarm code).
How do I enable Modbus control of the Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC)?
Fit the Modbus serial board, then in the User menu (User password) set P30.01 Enable supervision = Y, P30.02 BMS address, P30.03 protocol = Modbus and P30.04 baud rate. Set P30.05 On/Off by BMS = Y so the on/off coil works.
Where is the official Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC) Modbus documentation?
The source is Computer room air conditioner model s-MEXT-G00 006-044 Interface Manual (SM_s-MEXT_ME28relC_00_12_19_EN), revision 2019-12, published free by Mitsubishi Electric at https://library.mitsubishielectric.co.uk/pdf/download_full/3957.
More Mitsubishi Electric Modbus register maps
- Variable frequency drive
Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU)
FR-A700 series inverters (FR-A720-0.4K to 90K, FR-A740-0.4K to 500K) using the RS-485 terminals with Pr.549 = 1 (Modbus-RTU); Instruction Manual (Applied) revision E.
Also known as: FR-A720, FR-A740, FR-A700 series - Variable frequency drive
Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU)
FR-A800 series inverters (FR-A820/A840/A842/A846, incl. -GF) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision P.
Also known as: FR-A820, FR-A840, FR-A842, FR-A846, FR-A800-GF, FR-A800 series - Variable frequency drive
Mitsubishi Electric FR-D700 compact inverter (PU connector, Modbus RTU)
FR-D700 series (FR-D720/D740/D720S/D710W) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision H.
Also known as: FR-D720, FR-D740, FR-D720S, FR-D710W - Variable frequency drive
Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU)
FR-E700 series (FR-E720/E740/E720S/E710W, incl. SC safety-stop models) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision G.
Also known as: FR-E720, FR-E740, FR-E720S, FR-E710W, FR-E700-SC - Variable frequency drive
Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU)
FR-F800 series inverters (FR-F820/F840/F842/F846) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision G.
Also known as: FR-F820, FR-F840, FR-F842, FR-F846, FR-F800 series - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units
Procon MelcoBEMS MINI (A1M) on the CN105/CN92 connector of a Mitsubishi Electric Air-To-Air indoor unit, installation manual v1.1.11 (firmware 3.0.28 for revision 2-4 hardware, 3.1.1 for revision 5).
Also known as: MelcoBEMS MINI (A1M), A1M, Procon A1M, MelcoBEMS MINI - Air handler (heat recovery ventilation unit)
Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)
Procon MelcoBEMS MINI A1M+ (manual v1.0.3, firmware 4.1.1) on Lossnay LGH-15..200RVX-E1, LGH-150..250RVXT-E1 and VL-250..500CZPVU-R/L-E; the older A1M (manual v1.1.11) prints the identical Lossnay table.
Also known as: A1M+ Lossnay, MelcoBEMS MINI Lossnay, Procon A1M+, Procon A1M, A1M, Lossnay LGH-RVX Modbus, LGH-15RVX-E1, LGH-200RVX-E1, LGH-150RVXT-E1, LGH-250RVXT-E1, VL-250CZPVU-R-E, VL-500CZPVU-L-E, Lossnay VL Vertical - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series)
MelcoBEMS MINI (A1M+) on the CN105 connector of a Mitsubishi Electric Air-To-Air indoor unit (M series MSZ/MFZ/MLZ, S series SEZ/SLZ, P series per Appendix A), installation manual v1.0.3, firmware 4.1.1.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, MelcoBEMS MINI A1M PLUS, A1M+ ATA - Chiller / heat pump gateway (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 on Mitsubishi Electric CAHV and CRHV heat pumps, QAHV CO2 heat pumps and EAHV / EACV e-series chillers (master and slave units); holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, CAHV, CRHV, QAHV, EAHV, EACV, e-series chiller - Heat pump (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 connected to an Ecodan FTC4, FTC5 or FTC6 air-to-water controller; holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, Ecodan FTC4, Ecodan FTC5, Ecodan FTC6 - Air handler DX interface (VRF / split AC gateway)
Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU)
PAC-IF013B-E and PAC-SIF013B-E interface controllers linking a Mitsubishi Electric outdoor unit to an AHU coil, Modbus manual dated September 2015 (RG79F084H01).
Also known as: PAC-IF013B-E, PAC-SIF013B-E, PAC-(S)IF013B-E - VRF / split AC gateway (retail controller)
Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units
Procon MelcoRETAIL MINI on the CN105/CN92 connector of Mitsubishi Electric M, S and P series Air-To-Air indoor units, installation manual v1.0.6, firmware 1.0.3.
Also known as: MelcoRETAIL MINI, Procon MelcoRETAIL MINI
Other hvac equipment register maps
- Air handler humidifier (gas-fired steam)
Neptronic SKG4 gas-fired steam humidifier (Modbus communication module)
Neptronic SKG4 series gas-fired steam humidifiers (one to four burner modules) with the Modbus communication module, guide SKG4-Modbus Guide-221114 (V2.04).
Also known as: SKG4-E, SKG4-N, SKG4 Gas Fired Humidifier, Neptronic SKG4 Modbus - Air handler controller
Regin Corrigo ventilation controller (ventilation application 3.6)
Regin Corrigo controllers running the pre-programmed ventilation (air handling unit) application, version 3.6 or later; not the heating or Exigo applications.
Also known as: Corrigo E, Corrigo ventilation, Corrigo E ventilation, Corrigo AHU controller - Air handler (heat recovery unit controller)
Swegon TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural)
Swegon (Global) TAC5 DG, DM and DT regulation boards with the SAT MODBUS (RTU) or SAT WIFI/ETHERNET (TCP) satellite; TAC5 + MODBUS TABLE Cid 050338 (2021-09-20). The TAC5 SC/F single-flow boards use other registers and are not covered.
Also known as: TAC5 DG, TAC5 DM, TAC5 DT, Global HRglobal, Global HRup, Global HRflat, Global HRtotal, Global HRmural, SAT MODBUS - Thermostat / temperature controller
Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU)
Watlow EZ-ZONE PM panel-mount controllers (PID, limit and integrated models) with Modbus RTU, per communications manual 0600-0056-0000 Rev. B (Nov 2007).
Also known as: EZ-ZONE PM, EZ-ZONE PM Limit, EZ-ZONE PM Integrated - Air handler humidifier (hybrid / spray)
Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP)
Condair DL with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair DL, Condair DL II, DL - Air handler humidifier (steam humidifier controller)
DriSteem Vapor-logic 6 humidifier controller (Modbus RTU)
DriSteem humidifiers and humidification systems controlled by Vapor-logic firmware 6.X.X, per IOM form VL6-IOM-EN-REVH-0225.
Also known as: Vapor-logic, Vapor-logic version 6, VL6, DriSteem GTS, DriSteem XT, DriSteem STS, DriSteem LTS, Vaporstream
All hvac equipment Modbus register maps →
Source: Computer room air conditioner model s-MEXT-G00 006-044 Interface Manual · SM_s-MEXT_ME28relC_00_12_19_EN · rev. 2019-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.