Air handler (computer room air conditioner) · Modbus register map

Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC) Modbus register map

Updated 17 November 2026

Short answer

The s-MEXT-G00 is a Mitsubishi Electric direct-expansion close-control unit for computer rooms (6-44 kW). With the Modbus serial board fitted, its controller exposes Boolean variables as coils and analogue/integer variables as holding registers over RS-485 Modbus RTU. This map covers unit status and on/off, setpoints, room/delivery/outside temperatures, humidity, pressures, fan and damper positions, operating mode, run hours and the electrical readings.

This page lists 68 Modbus registers for the Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC) — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Mitsubishi Electric’s own free documentation (linked below) and checked against it.

Manufacturer
Mitsubishi Electric
Model
s-MEXT-G00 computer room air conditioner (ME28 relC)
Equipment type
Air handler (computer room air conditioner)
Registers
68 (10 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
8N2
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Firmware
ME28-relC
Also known as
s-MEXT, s-MEXT-G00 006-044, s-MEXT G00, ME28 relC
Source document
Computer room air conditioner model s-MEXT-G00 006-044 Interface Manual · SM_s-MEXT_ME28relC_00_12_19_EN · rev. 2019-12
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC)

Integration in brief

Read unit status and alarm coils, room/delivery temperature, humidity and operating mode; write the on/off coil and the cold/hot setpoints (x10).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
CO 1Unit statusBITUnit statusRead
CO 2Presence of alarmBITAlarm presentRead
CO 8On/Off command by supervisorBITOn/off commandRead/write
HR 1Cold temperature setpointINT16Cold temperature setpointRead/write
HR 6Room temperatureINT16Room temperatureRead
HR 21Ambient humidityINT16Ambient humidityRead
HR 142Unit operating modeUINT16Unit operating modeRead
HR 160Active alarm code (with greater priority)UINT16Active alarm codeRead

Enable Modbus control & writes

Fit the Modbus serial board, then in the User menu (User password) set P30.01 Enable supervision = Y, P30.02 BMS address, P30.03 protocol = Modbus and P30.04 baud rate. Set P30.05 On/Off by BMS = Y so the on/off coil works.

Byte order & addressing

Network setup

Watch out for

Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

68 of 68 shown
Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO1doc 002Unit statusBITRead0 = Off; 1 = On
CO2doc 003Presence of alarmBITRead0 = Unit OK; 1 = Alarm
CO8doc 009On/Off command by supervisorBITRead/write0 = Off; 1 = On
CO15doc 016Status step 1 heating elementsBITRead
CO16doc 017Status step 2 heating elementsBITRead
CO37doc 038Free cooling stopped by BMSBITWrite0 = Normal free-cooling operation; 1 = Free cooling disabled
HR1doc 40002Cold temperature setpointWrite value x10 (21.3 °C = 213).INT16× 0.1°CRead/write
HR2doc 40003Hot temperature setpointWrite value x10 (21.3 °C = 213).INT16× 0.1°CRead/write
HR4doc 40005Cold temperature setpoint activeTenths.INT16× 0.1°CRead
HR5doc 40006Hot temperature active set pointTenths.INT16× 0.1°CRead
HR6doc 40007Room temperatureTenths; -999 = probe alarm, -888 = not configured.INT16× 0.1°CRead
HR7doc 40008Delivery temperatureTenths; -999 = probe alarm, -888 = not configured.INT16× 0.1°CRead
HR8doc 40009Temperature used for adjustmentTenths; -999 = probe alarm, -888 = not configured.INT16× 0.1°CRead
HR16doc 40017Low pressureTenths; -999 = probe alarm, -888 = not configured.INT16× 0.1barRead
HR17doc 40018Circuit 2 low pressureTenths; -999 = probe alarm, -888 = not configured.INT16× 0.1barRead
HR20doc 40021External air temperatureTenths; -999 = probe alarm, -888 = not configured.INT16× 0.1°CRead
HR21doc 40022Ambient humidityTenths; -999 = probe alarm, -888 = not configured.INT16× 0.1%Read
HR23doc 40024Address 129 auxiliary probe temperatureTenths; -999 = probe alarm, -888 = not configured.INT16× 0.1°CRead
HR24doc 40025Address 129 auxiliary probe humidityTenths; -999 = probe alarm, -888 = not configured.INT16× 0.1%Read
HR40doc 40041Fan speedTenths.INT16× 0.1%Read
HR53doc 40054Position of Freecooling damperTenths.INT16× 0.1%Read
HR54doc 40055Humidifier requestTenths.INT16× 0.1%Read
HR131doc 40132Software versionUINT16Read
HR132doc 40133Software version (revision)UINT16Read
HR138doc 40139Flow control typeUINT16Read0 = Adjustable head; 1 = Constant flow; 2 = Constant head
HR139doc 40140Probe used for adjustmentUINT16Read0 = Ambient air probe; 1 = Delivery air probe
HR140doc 40141Unit statusUINT16Read0 = ON from keyboard; 1 = ON from digital input; 2 = ON from pLAN; 3 = ON from time bands; 4 = ON from supervision; 5 = OFF from alarm; 6 = OFF from supervision; 7 = OFF from time bands; 8 = OFF from pLAN; 9 = OFF from digital input; 10 = OFF from keyboard; 11 = OFF from deselected ventilation; 12 = Switching off
HR142doc 40143Unit operating modeUINT16Read0 = Unit OFF; 1 = Ventilation only; 2 = Cooling; 3 = Free cooling; 4 = Cooling + free cooling; 5 = Dehumidification; 6 = Dehumidification + post heating; 7 = Humidification; 8 = Cooling + humidification; 9 = Heating; 10 = Heating + humidification
HR153doc 40154YearUINT16Read
HR154doc 40155MonthUINT16Read
HR155doc 40156DayUINT16Read
HR156doc 40157TimeUINT16hRead
HR157doc 40158MinutesUINT16minRead
HR160doc 40161Active alarm code (with greater priority)UINT16Read
HR162doc 40163Cold thermoregulator request (%)UINT16× 0.1%Read
HR165doc 40166Heat request (%)UINT16× 0.1%Read
HR168doc 40169Post-heating request (%)UINT16× 0.1%Read
HR174doc 40175Dehumidification setpoint (%)UINT16%Read/write
HR175doc 40176Humidification setpoint (%)UINT16%Read/write
HR176doc 40177Unit operating hours (Thousands)Thousands part; total = this x 1000 + units register.UINT16hRead
HR177doc 40178Unit operating hours (Units)UINT16hRead
HR190doc 40191Heating element 1 operating hours (Thousands)Thousands part; total = this x 1000 + units register.UINT16hRead
HR191doc 40192Heating element 1 operating hours (Units)UINT16hRead
HR192doc 40193Heating element 2 operating hours (Thousands)Thousands part; total = this x 1000 + units register.UINT16hRead
HR193doc 40194Heating element 2 operating hours (Units)UINT16hRead
HR194doc 40195Humidifier operating hours (Thousands)Thousands part; total = this x 1000 + units register.UINT16hRead
HR195doc 40196Humidifier operating hours (Units)UINT16hRead
HR196doc 40197High ambient temperature set pointUINT16°CRead/write
HR197doc 40198Low ambient temperature set pointUINT16°CRead/write
HR198doc 40199Ambient humidity high set pointUINT16%Read/write
HR199doc 40200Low ambient humidity set pointUINT16%Read/write
HR208doc 40209Voltage measured between L1 and NUINT16VRead
HR209doc 40210Voltage measured between L2 and NUINT16VRead
HR210doc 40211Voltage measured between L3 and NUINT16VRead
HR211doc 40212Voltage measured between L1 and L2UINT16VRead
HR212doc 40213Voltage measured between L2 and L3UINT16VRead
HR213doc 40214Voltage measured between L3 and L1UINT16VRead
HR214doc 40215Maximum current at L1UINT16× 0.1ARead
HR215doc 40216Maximum current at L2UINT16× 0.1ARead
HR216doc 40217Maximum current at L3UINT16× 0.1ARead
HR217doc 40218Maximum current at NUINT16× 0.1ARead
HR218doc 40219L1 powerUINT16× 0.1kWRead
HR219doc 40220L2 powerUINT16× 0.1kWRead
HR220doc 40221L3 powerUINT16× 0.1kWRead
HR221doc 40222Total PowerUINT16× 0.1kWRead
HR222doc 40223EnergyUINT16kWhRead
HR231doc 40232Average differential pressure for DeltaP control with APLUINT16PaRead
HR232doc 40233Differential pressure for DeltaP controlUINT16PaRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC)

What Modbus registers does the Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC) have?

This map lists 68 registers: 6 coils, 62 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The interface database prints coils as 001-184 and registers as 40001-40257 and states the start address is 1, not 0. So coil 002 is wire address 1 and register 40002 is wire address 1. Integer ('whole') variables start at 40129 (software address + 128).

What are the minimum Modbus registers to integrate the Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC)?

Start with CO 1 Unit status (Unit status); CO 2 Presence of alarm (Alarm present); CO 8 On/Off command by supervisor (On/off command); HR 1 Cold temperature setpoint (Cold temperature setpoint); HR 6 Room temperature (Room temperature); HR 21 Ambient humidity (Ambient humidity); HR 142 Unit operating mode (Unit operating mode); HR 160 Active alarm code (with greater priority) (Active alarm code).

How do I enable Modbus control of the Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC)?

Fit the Modbus serial board, then in the User menu (User password) set P30.01 Enable supervision = Y, P30.02 BMS address, P30.03 protocol = Modbus and P30.04 baud rate. Set P30.05 On/Off by BMS = Y so the on/off coil works.

Where is the official Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC) Modbus documentation?

The source is Computer room air conditioner model s-MEXT-G00 006-044 Interface Manual (SM_s-MEXT_ME28relC_00_12_19_EN), revision 2019-12, published free by Mitsubishi Electric at https://library.mitsubishielectric.co.uk/pdf/download_full/3957.

More Mitsubishi Electric Modbus register maps

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: Computer room air conditioner model s-MEXT-G00 006-044 Interface Manual · SM_s-MEXT_ME28relC_00_12_19_EN · rev. 2019-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.