Variable frequency drive · Modbus register map
Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU) Modbus register map
Updated 19 November 2026
Mitsubishi Electric's previous-generation high-performance inverter. Its RS-485 terminal block can speak Modbus RTU, exposing system variables (control word, operation mode, frequency command) at 40002-40015, a real-time monitor block from 40201, fault history at 40501 and parameters 0-999 at 41000 + parameter number. This map covers control, status, monitors, fault codes and the communication parameters.
This page lists 46 Modbus registers for the Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU) — 21 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Mitsubishi Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- Mitsubishi Electric
- Model
- FR-A700 inverter (RS-485 terminals, Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 46 (21 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8E1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- FR-A720, FR-A740, FR-A700 series
Integration notes: Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU)
Set Pr.549 = 1 and Pr.331 to 1-247 (initial 0 is broadcast) and reset, then switch to NET mode by writing H0014 to 40010. Write the frequency to 40014 (0.01 Hz) and the run bits to 40009, and poll 40009, 40201, 40224 and 40501.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 8 | Inverter status / control input instruction | BITMAP16 | Run/stop command and inverter status | Read/write |
| HR 9 | Operation mode / inverter setting | UINT16 | Operation mode (write H0014 for NET) | Read/write |
| HR 13 | Running frequency (RAM) | UINT16 | Frequency command (RAM) | Read/write |
| HR 200 | Output frequency / speed | UINT16 | Output frequency | Read |
| HR 223 | Motor load factor | UINT16 | Motor load factor | Read |
| HR 500 | Fault record 1 | UINT16 | Latest fault code | Read/write |
Enable Modbus control & writes
Pr.549 = 1 selects Modbus-RTU (RS-485 terminals only); set Pr.331, Pr.332 and Pr.334 and reset. Run/frequency commands need NET operation mode (write H0014 to 40010; allowed depending on Pr.79/Pr.340). With a communication option fitted and Pr.550 = 9999, RS-485 terminal commands are ignored.
Communication loss & watchdog
Pr.539 Modbus-RTU communication check time interval (0.1-999.8 s, same behaviour as Pr.122); 9999 (initial) = no check; 0 lets Modbus run but the drive trips in NET mode.
Byte order & addressing
- Request address = register - 40001.
- Station 0 is broadcast and never replies.
- 40009 means control input when written and inverter status when read.
Network setup
- Pr.332 initial 96 = 9600 bps; Pr.334 initial 2 = even parity, 1 stop bit; data length fixed at 8 bits.
- Modbus-RTU cannot be used in PU operation mode.
Watch out for
- Current and power monitors change resolution at 75K, so check the drive size before scaling them.
Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 40002 | Inverter reset | Write any value to reset the inverter. | UINT16 | Write | ||||
| HR | 2doc 40003 | Parameter clear | Write H965A. | UINT16 | Write | ||||
| HR | 3doc 40004 | All parameter clear | Write H99AA. | UINT16 | Write | ||||
| HR | 5doc 40006 | Parameter clear (keep comm settings) | Write H5A96; communication parameters are kept. | UINT16 | Write | ||||
| HR | 6doc 40007 | All parameter clear (keep comm settings) | Write HAA99; communication parameters are kept. | UINT16 | Write | ||||
| HR | 8doc 40009 | Inverter status / control input instruction | Write = control input, read = inverter status. | BITMAP16 | Read/write | bit 0 = Write: stop command / Read: RUN (inverter running); bit 1 = Write: forward rotation / Read: forward rotation; bit 2 = Write: reverse rotation / Read: reverse rotation; bit 3 = Write: RH (high speed) / Read: SU (up to frequency); bit 4 = Write: RM (middle speed) / Read: OL (overload); bit 5 = Write: RL (low speed) / Read: IPF (instantaneous power failure); bit 6 = Write: JOG / Read: FU (frequency detection); bit 7 = Write: RT (second function) / Read: ABC1 (fault); bit 8 = Write: AU (current input selection) / Read: ABC2; bit 9 = Write: CS (automatic restart selection); bit 10 = Write: MRS (output stop); bit 11 = Write: STOP (start self-holding); bit 12 = Write: RES (reset); bit 15 = Read: fault occurrence | |||
| HR | 9doc 40010 | Operation mode / inverter setting | Read = current mode; write H0010 EXT, H0011 PU, H0014 NET. | UINT16 | Read/write | 0 = Read: EXT; 1 = Read: PU; 2 = Read: EXT JOG; 3 = Read: PU JOG; 4 = Read: NET; 5 = Read: PU + EXT; 16 = Write: EXT (H0010); 17 = Write: PU (H0011); 20 = Write: NET (H0014) | |||
| HR | 13doc 40014 | Running frequency (RAM) | Frequency command, not stored in EEPROM. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 14doc 40015 | Running frequency (EEPROM) | Frequency command, also stored in EEPROM. | UINT16 | × 0.01 | Hz | Write | ||
| HR | 200doc 40201 | Output frequency / speed | 0.01 Hz; 1 unit when Pr.37 = 1-9998 or Pr.144 = 2-10/102-110. | UINT16 | × 0.01 | Hz | Read | ||
| HR | 202doc 40203 | Output voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 204doc 40205 | Frequency setting value / speed setting | 0.01 Hz; 1 unit with Pr.37/Pr.144 speed display. | UINT16 | × 0.01 | Hz | Read | ||
| HR | 205doc 40206 | Running speed | UINT16 | r/min | Read | ||||
| HR | 207doc 40208 | Converter output voltage | DC bus voltage. | UINT16 | × 0.1 | V | Read | ||
| HR | 208doc 40209 | Regenerative brake duty | UINT16 | × 0.1 | % | Read | |||
| HR | 209doc 40210 | Electronic thermal relay function load factor | UINT16 | × 0.1 | % | Read | |||
| HR | 211doc 40212 | Converter output voltage peak value | UINT16 | × 0.1 | V | Read | |||
| HR | 214doc 40215 | Input terminal status | 1 = on. | BITMAP16 | Read | bit 0 = STF; bit 1 = STR; bit 2 = AU; bit 3 = RT; bit 4 = RL; bit 5 = RM; bit 6 = RH; bit 7 = JOG; bit 8 = MRS; bit 9 = STOP; bit 10 = RES; bit 11 = CS | |||
| HR | 215doc 40216 | Output terminal status | 1 = on. | BITMAP16 | Read | bit 0 = RUN; bit 1 = SU; bit 2 = IPF; bit 3 = OL; bit 4 = FU; bit 5 = ABC1; bit 6 = ABC2 | |||
| HR | 216doc 40217 | Load meter | UINT16 | × 0.1 | % | Read | |||
| HR | 219doc 40220 | Cumulative energization time | UINT16 | h | Read | ||||
| HR | 222doc 40223 | Actual operation time | UINT16 | h | Read | ||||
| HR | 223doc 40224 | Motor load factor | UINT16 | × 0.1 | % | Read | |||
| HR | 224doc 40225 | Cumulative power | UINT16 | kWh | Read | ||||
| HR | 251doc 40252 | PID set point | UINT16 | × 0.1 | % | Read | |||
| HR | 252doc 40253 | PID measured value | UINT16 | × 0.1 | % | Read | |||
| HR | 500doc 40501 | Fault record 1 | Low byte = fault code (H00xx). Write any value to clear history. | UINT16 | Read/write | 0 = No alarm; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 80 = E.IPF; 81 = E.UVT; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 160 = E.OPT; 163 = E.OP3; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 193 = E.CTE; 194 = E.P24; 196 = E.CDO; 197 = E.IOH; 198 = E.SER; 199 = E.AIE; 200 = E.USB; 208 = E.OS; 209 = E.OSD; 210 = E.ECT; 211 = E.OD; 213 = E.MB1; 214 = E.MB2; 215 = E.MB3; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 220 = E.EP; 241 = E.1; 242 = E.2; 243 = E.3; 246 = E.6; 247 = E.7; 251 = E.11; 253 = E.13 | |||
| HR | 501doc 40502 | Fault record 2 | Low byte = fault code (H00xx). | UINT16 | Read | 0 = No alarm; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 80 = E.IPF; 81 = E.UVT; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 160 = E.OPT; 163 = E.OP3; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 193 = E.CTE; 194 = E.P24; 196 = E.CDO; 197 = E.IOH; 198 = E.SER; 199 = E.AIE; 200 = E.USB; 208 = E.OS; 209 = E.OSD; 210 = E.ECT; 211 = E.OD; 213 = E.MB1; 214 = E.MB2; 215 = E.MB3; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 220 = E.EP; 241 = E.1; 242 = E.2; 243 = E.3; 246 = E.6; 247 = E.7; 251 = E.11; 253 = E.13 | |||
| HR | 502doc 40503 | Fault record 3 | Low byte = fault code (H00xx). | UINT16 | Read | 0 = No alarm; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 80 = E.IPF; 81 = E.UVT; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 160 = E.OPT; 163 = E.OP3; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 193 = E.CTE; 194 = E.P24; 196 = E.CDO; 197 = E.IOH; 198 = E.SER; 199 = E.AIE; 200 = E.USB; 208 = E.OS; 209 = E.OSD; 210 = E.ECT; 211 = E.OD; 213 = E.MB1; 214 = E.MB2; 215 = E.MB3; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 220 = E.EP; 241 = E.1; 242 = E.2; 243 = E.3; 246 = E.6; 247 = E.7; 251 = E.11; 253 = E.13 | |||
| HR | 503doc 40504 | Fault record 4 | Low byte = fault code (H00xx). | UINT16 | Read | 0 = No alarm; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 80 = E.IPF; 81 = E.UVT; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 160 = E.OPT; 163 = E.OP3; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 193 = E.CTE; 194 = E.P24; 196 = E.CDO; 197 = E.IOH; 198 = E.SER; 199 = E.AIE; 200 = E.USB; 208 = E.OS; 209 = E.OSD; 210 = E.ECT; 211 = E.OD; 213 = E.MB1; 214 = E.MB2; 215 = E.MB3; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 220 = E.EP; 241 = E.1; 242 = E.2; 243 = E.3; 246 = E.6; 247 = E.7; 251 = E.11; 253 = E.13 | |||
| HR | 504doc 40505 | Fault record 5 | Low byte = fault code (H00xx). | UINT16 | Read | 0 = No alarm; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 80 = E.IPF; 81 = E.UVT; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 160 = E.OPT; 163 = E.OP3; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 193 = E.CTE; 194 = E.P24; 196 = E.CDO; 197 = E.IOH; 198 = E.SER; 199 = E.AIE; 200 = E.USB; 208 = E.OS; 209 = E.OSD; 210 = E.ECT; 211 = E.OD; 213 = E.MB1; 214 = E.MB2; 215 = E.MB3; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 220 = E.EP; 241 = E.1; 242 = E.2; 243 = E.3; 246 = E.6; 247 = E.7; 251 = E.11; 253 = E.13 | |||
| HR | 505doc 40506 | Fault record 6 | Low byte = fault code (H00xx). | UINT16 | Read | 0 = No alarm; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 80 = E.IPF; 81 = E.UVT; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 160 = E.OPT; 163 = E.OP3; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 193 = E.CTE; 194 = E.P24; 196 = E.CDO; 197 = E.IOH; 198 = E.SER; 199 = E.AIE; 200 = E.USB; 208 = E.OS; 209 = E.OSD; 210 = E.ECT; 211 = E.OD; 213 = E.MB1; 214 = E.MB2; 215 = E.MB3; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 220 = E.EP; 241 = E.1; 242 = E.2; 243 = E.3; 246 = E.6; 247 = E.7; 251 = E.11; 253 = E.13 | |||
| HR | 506doc 40507 | Fault record 7 | Low byte = fault code (H00xx). | UINT16 | Read | 0 = No alarm; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 80 = E.IPF; 81 = E.UVT; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 160 = E.OPT; 163 = E.OP3; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 193 = E.CTE; 194 = E.P24; 196 = E.CDO; 197 = E.IOH; 198 = E.SER; 199 = E.AIE; 200 = E.USB; 208 = E.OS; 209 = E.OSD; 210 = E.ECT; 211 = E.OD; 213 = E.MB1; 214 = E.MB2; 215 = E.MB3; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 220 = E.EP; 241 = E.1; 242 = E.2; 243 = E.3; 246 = E.6; 247 = E.7; 251 = E.11; 253 = E.13 | |||
| HR | 507doc 40508 | Fault record 8 | Low byte = fault code (H00xx). | UINT16 | Read | 0 = No alarm; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 80 = E.IPF; 81 = E.UVT; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 160 = E.OPT; 163 = E.OP3; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 193 = E.CTE; 194 = E.P24; 196 = E.CDO; 197 = E.IOH; 198 = E.SER; 199 = E.AIE; 200 = E.USB; 208 = E.OS; 209 = E.OSD; 210 = E.ECT; 211 = E.OD; 213 = E.MB1; 214 = E.MB2; 215 = E.MB3; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 220 = E.EP; 241 = E.1; 242 = E.2; 243 = E.3; 246 = E.6; 247 = E.7; 251 = E.11; 253 = E.13 | |||
| HR | 1000doc 41001 | Pr.1 Maximum frequency | UINT16 | × 0.01 | Hz | Read/write | |||
| HR | 1001doc 41002 | Pr.2 Minimum frequency | UINT16 | × 0.01 | Hz | Read/write | |||
| HR | 1003doc 41004 | Pr.4 Multi-speed setting (high speed) | UINT16 | × 0.01 | Hz | Read/write | |||
| HR | 1004doc 41005 | Pr.5 Multi-speed setting (middle speed) | UINT16 | × 0.01 | Hz | Read/write | |||
| HR | 1005doc 41006 | Pr.6 Multi-speed setting (low speed) | UINT16 | × 0.01 | Hz | Read/write | |||
| HR | 1078doc 41079 | Pr.79 Operation mode selection | UINT16 | Read/write | 0 = External/PU switchover (External at power-on); 1 = Fixed PU operation; 2 = Fixed External operation (NET switchable); 3 = External/PU combined mode 1; 4 = External/PU combined mode 2; 6 = Switchover mode; 7 = External operation (PU interlock) | ||||
| HR | 1330doc 41331 | Pr.331 RS-485 communication station number | 0 = broadcast; set 1-247. | UINT16 | Read/write | ||||
| HR | 1331doc 41332 | Pr.332 RS-485 communication speed | Setting x 100 = bps (initial 96 = 9600). | UINT16 | Read/write | ||||
| HR | 1333doc 41334 | Pr.334 RS-485 communication parity check selection | UINT16 | Read/write | 0 = No parity, 2 stop bits; 1 = Odd parity, 1 stop bit; 2 = Even parity, 1 stop bit | ||||
| HR | 1342doc 41343 | Pr.343 Communication error count | Modbus RTU error count (RAM). | UINT16 | Read | ||||
| HR | 1538doc 41539 | Pr.539 Modbus-RTU communication check time interval | 0 = Modbus works but the drive trips in NET mode; 9999 = no check. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 1548doc 41549 | Pr.549 Protocol selection | UINT16 | Read/write | 0 = Mitsubishi inverter protocol (computer link); 1 = Modbus-RTU |
Notes on this map
- All registers are single 16-bit words.
- Left out because the increment depends on capacity (55K or lower / 75K or higher): output current 40202, current peak 40211, input power 40213, output power 40214, excitation current 40218 and motor output 40234. Motor load factor 40224 gives a size-independent current reading.
- Left out because the sign is not stated: motor torque 40207, torque command 40232, torque current command 40233 and PID deviation 40254. Vector-control position/orientation monitors (40219, 40222, 40235), option terminal monitors (40258-40260) and the version-dependent motor temperature 40246 are not listed.
- Frequency registers use 0.01 Hz; with Pr.37/Pr.144 speed display they switch to 1 unit. The 0.01 Hz unit for 40014/40015 comes from the same manual's computer-link set-frequency description.
- Fault history registers hold the fault code in the low byte; the values listed are the manual's fault code list.
- Parameters with a 9999 (function off) setting are listed with their normal increment; the manual does not say how the 9999 setting itself is encoded on the wire.
- Parameters 0-999 sit at 41000 + Pr. number; calibration parameters C2-C41 have their own registers and are not listed. Pr.7/Pr.8 are left out (increment depends on Pr.21).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU)
What Modbus registers does the Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU) have?
This map lists 46 registers: 46 holding registers. 21 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints Modicon-style register numbers (40002, 41004) and states: starting address = register number - 40001. Its example reads 41004 (Pr.4) with start address H03EB (1003).
What are the minimum Modbus registers to integrate the Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU)?
Start with HR 8 Inverter status / control input instruction (Run/stop command and inverter status); HR 9 Operation mode / inverter setting (Operation mode (write H0014 for NET)); HR 13 Running frequency (RAM) (Frequency command (RAM)); HR 200 Output frequency / speed (Output frequency); HR 223 Motor load factor (Motor load factor); HR 500 Fault record 1 (Latest fault code).
How do I enable Modbus control of the Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU)?
Pr.549 = 1 selects Modbus-RTU (RS-485 terminals only); set Pr.331, Pr.332 and Pr.334 and reset. Run/frequency commands need NET operation mode (write H0014 to 40010; allowed depending on Pr.79/Pr.340). With a communication option fitted and Pr.550 = 9999, RS-485 terminal commands are ignored.
What happens when the Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU) loses Modbus communication?
Pr.539 Modbus-RTU communication check time interval (0.1-999.8 s, same behaviour as Pr.122); 9999 (initial) = no check; 0 lets Modbus run but the drive trips in NET mode.
Where is the official Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU) Modbus documentation?
The source is FR-A700 Instruction Manual (Applied) (IB(NA)-0600226ENG-E), revision 2012-02, published free by Mitsubishi Electric at https://dl.mitsubishielectric.com/dl/fa/document/manual/inv/ib0600226eng/ib0600226enge.pdf.
More Mitsubishi Electric Modbus register maps
- Variable frequency drive
Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU)
FR-A800 series inverters (FR-A820/A840/A842/A846, incl. -GF) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision P.
Also known as: FR-A820, FR-A840, FR-A842, FR-A846, FR-A800-GF, FR-A800 series - Variable frequency drive
Mitsubishi Electric FR-D700 compact inverter (PU connector, Modbus RTU)
FR-D700 series (FR-D720/D740/D720S/D710W) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision H.
Also known as: FR-D720, FR-D740, FR-D720S, FR-D710W - Variable frequency drive
Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU)
FR-E700 series (FR-E720/E740/E720S/E710W, incl. SC safety-stop models) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision G.
Also known as: FR-E720, FR-E740, FR-E720S, FR-E710W, FR-E700-SC - Variable frequency drive
Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU)
FR-F800 series inverters (FR-F820/F840/F842/F846) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision G.
Also known as: FR-F820, FR-F840, FR-F842, FR-F846, FR-F800 series - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units
Procon MelcoBEMS MINI (A1M) on the CN105/CN92 connector of a Mitsubishi Electric Air-To-Air indoor unit, installation manual v1.1.11 (firmware 3.0.28 for revision 2-4 hardware, 3.1.1 for revision 5).
Also known as: MelcoBEMS MINI (A1M), A1M, Procon A1M, MelcoBEMS MINI - Air handler (heat recovery ventilation unit)
Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)
Procon MelcoBEMS MINI A1M+ (manual v1.0.3, firmware 4.1.1) on Lossnay LGH-15..200RVX-E1, LGH-150..250RVXT-E1 and VL-250..500CZPVU-R/L-E; the older A1M (manual v1.1.11) prints the identical Lossnay table.
Also known as: A1M+ Lossnay, MelcoBEMS MINI Lossnay, Procon A1M+, Procon A1M, A1M, Lossnay LGH-RVX Modbus, LGH-15RVX-E1, LGH-200RVX-E1, LGH-150RVXT-E1, LGH-250RVXT-E1, VL-250CZPVU-R-E, VL-500CZPVU-L-E, Lossnay VL Vertical - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series)
MelcoBEMS MINI (A1M+) on the CN105 connector of a Mitsubishi Electric Air-To-Air indoor unit (M series MSZ/MFZ/MLZ, S series SEZ/SLZ, P series per Appendix A), installation manual v1.0.3, firmware 4.1.1.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, MelcoBEMS MINI A1M PLUS, A1M+ ATA - Chiller / heat pump gateway (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 on Mitsubishi Electric CAHV and CRHV heat pumps, QAHV CO2 heat pumps and EAHV / EACV e-series chillers (master and slave units); holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, CAHV, CRHV, QAHV, EAHV, EACV, e-series chiller - Heat pump (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 connected to an Ecodan FTC4, FTC5 or FTC6 air-to-water controller; holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, Ecodan FTC4, Ecodan FTC5, Ecodan FTC6 - Air handler DX interface (VRF / split AC gateway)
Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU)
PAC-IF013B-E and PAC-SIF013B-E interface controllers linking a Mitsubishi Electric outdoor unit to an AHU coil, Modbus manual dated September 2015 (RG79F084H01).
Also known as: PAC-IF013B-E, PAC-SIF013B-E, PAC-(S)IF013B-E - VRF / split AC gateway (retail controller)
Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units
Procon MelcoRETAIL MINI on the CN105/CN92 connector of Mitsubishi Electric M, S and P series Air-To-Air indoor units, installation manual v1.0.6, firmware 1.0.3.
Also known as: MelcoRETAIL MINI, Procon MelcoRETAIL MINI - Air handler (computer room air conditioner)
Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC)
Mitsubishi Electric (Hydronics & IT Cooling) s-MEXT-G00 006-044 close-control units with ME28-relC software and the Modbus serial board.
Also known as: s-MEXT, s-MEXT-G00 006-044, s-MEXT G00, ME28 relC
Other variable frequency drives register maps
- Variable frequency drive
Schneider Electric Altivar Machine ATV320 (embedded Modbus RTU)
ATV320 Book (ATV320...B) and Compact (ATV320...C) drives on the built-in RJ45 Modbus serial port; register map per Communication Parameters file NVE41316 V3.5.
Also known as: ATV320, Altivar 320, ATV320U, ATV320D, ATV320 Book, ATV320 Compact - Variable frequency drive
SEW-EURODRIVE MOVITRAC LTP-B standard inverter (built-in Modbus RTU)
SEW-EURODRIVE MOVITRAC LTP-B inverters on the RJ45 Modbus RTU port (no communication or encoder option card fitted), per product manual 31554814/EN edition 10/2023.
Also known as: MOVITRAC LTP-B, LTP-B, MC LTP B - Variable frequency drive
TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII)
TECO-Westinghouse EV series micro inverters with the RS-485 option card, per the EV Inverter Series Modbus Communication Manual.
Also known as: TECO EV, EV Inverter Series - Variable frequency drive
WEG CFW500 frequency inverter (Modbus RTU)
WEG CFW500 drives as a Modbus RTU slave on the RS-485 port of the plug-in module (Modbus RTU User's Guide 10002253377 rev 04); parameter scaling from the V2.2X programming manual.
Also known as: CFW500 VFD, CFW500-IOS, CFW500-CRS485, CFW500-CUSB, CFW500-CRS232 - Variable frequency drive
Yaskawa GA500 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA500 drives using the built-in RS-485 MEMOBUS/Modbus port (terminal TB4), per technical reference SIEPC71061752 revision C.
Also known as: CIPR-GA50U, GA500 Versatile Compact - Variable frequency drive
Yaskawa iQpump1000 intelligent pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump1000 drives (CIMR-PW) using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEPYAIP1W01G.
Also known as: CIMR-PW, CIMR-PWA, iQpump1000 AC Drive
All variable frequency drives Modbus register maps →
Source: FR-A700 Instruction Manual (Applied) · IB(NA)-0600226ENG-E · rev. 2012-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.