Variable frequency drive · Modbus register map

Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

Mitsubishi Electric's previous-generation high-performance inverter. Its RS-485 terminal block can speak Modbus RTU, exposing system variables (control word, operation mode, frequency command) at 40002-40015, a real-time monitor block from 40201, fault history at 40501 and parameters 0-999 at 41000 + parameter number. This map covers control, status, monitors, fault codes and the communication parameters.

This page lists 46 Modbus registers for the Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU) — 21 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Mitsubishi Electric’s own free documentation (linked below) and checked against it.

Manufacturer
Mitsubishi Electric
Model
FR-A700 inverter (RS-485 terminals, Modbus RTU)
Equipment type
Variable frequency drive
Registers
46 (21 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8E1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
FR-A720, FR-A740, FR-A700 series
Source document
FR-A700 Instruction Manual (Applied) · IB(NA)-0600226ENG-E · rev. 2012-02
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU)

Integration in brief

Set Pr.549 = 1 and Pr.331 to 1-247 (initial 0 is broadcast) and reset, then switch to NET mode by writing H0014 to 40010. Write the frequency to 40014 (0.01 Hz) and the run bits to 40009, and poll 40009, 40201, 40224 and 40501.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 8Inverter status / control input instructionBITMAP16Run/stop command and inverter statusRead/write
HR 9Operation mode / inverter settingUINT16Operation mode (write H0014 for NET)Read/write
HR 13Running frequency (RAM)UINT16Frequency command (RAM)Read/write
HR 200Output frequency / speedUINT16Output frequencyRead
HR 223Motor load factorUINT16Motor load factorRead
HR 500Fault record 1UINT16Latest fault codeRead/write

Enable Modbus control & writes

Pr.549 = 1 selects Modbus-RTU (RS-485 terminals only); set Pr.331, Pr.332 and Pr.334 and reset. Run/frequency commands need NET operation mode (write H0014 to 40010; allowed depending on Pr.79/Pr.340). With a communication option fitted and Pr.550 = 9999, RS-485 terminal commands are ignored.

Communication loss & watchdog

Pr.539 Modbus-RTU communication check time interval (0.1-999.8 s, same behaviour as Pr.122); 9999 (initial) = no check; 0 lets Modbus run but the drive trips in NET mode.

Byte order & addressing

Network setup

Watch out for

Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

46 of 46 shown
Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 40002Inverter resetWrite any value to reset the inverter.UINT16Write
HR2doc 40003Parameter clearWrite H965A.UINT16Write
HR3doc 40004All parameter clearWrite H99AA.UINT16Write
HR5doc 40006Parameter clear (keep comm settings)Write H5A96; communication parameters are kept.UINT16Write
HR6doc 40007All parameter clear (keep comm settings)Write HAA99; communication parameters are kept.UINT16Write
HR8doc 40009Inverter status / control input instructionWrite = control input, read = inverter status.BITMAP16Read/writebit 0 = Write: stop command / Read: RUN (inverter running); bit 1 = Write: forward rotation / Read: forward rotation; bit 2 = Write: reverse rotation / Read: reverse rotation; bit 3 = Write: RH (high speed) / Read: SU (up to frequency); bit 4 = Write: RM (middle speed) / Read: OL (overload); bit 5 = Write: RL (low speed) / Read: IPF (instantaneous power failure); bit 6 = Write: JOG / Read: FU (frequency detection); bit 7 = Write: RT (second function) / Read: ABC1 (fault); bit 8 = Write: AU (current input selection) / Read: ABC2; bit 9 = Write: CS (automatic restart selection); bit 10 = Write: MRS (output stop); bit 11 = Write: STOP (start self-holding); bit 12 = Write: RES (reset); bit 15 = Read: fault occurrence
HR9doc 40010Operation mode / inverter settingRead = current mode; write H0010 EXT, H0011 PU, H0014 NET.UINT16Read/write0 = Read: EXT; 1 = Read: PU; 2 = Read: EXT JOG; 3 = Read: PU JOG; 4 = Read: NET; 5 = Read: PU + EXT; 16 = Write: EXT (H0010); 17 = Write: PU (H0011); 20 = Write: NET (H0014)
HR13doc 40014Running frequency (RAM)Frequency command, not stored in EEPROM.UINT16× 0.01HzRead/write
HR14doc 40015Running frequency (EEPROM)Frequency command, also stored in EEPROM.UINT16× 0.01HzWrite
HR200doc 40201Output frequency / speed0.01 Hz; 1 unit when Pr.37 = 1-9998 or Pr.144 = 2-10/102-110.UINT16× 0.01HzRead
HR202doc 40203Output voltageUINT16× 0.1VRead
HR204doc 40205Frequency setting value / speed setting0.01 Hz; 1 unit with Pr.37/Pr.144 speed display.UINT16× 0.01HzRead
HR205doc 40206Running speedUINT16r/minRead
HR207doc 40208Converter output voltageDC bus voltage.UINT16× 0.1VRead
HR208doc 40209Regenerative brake dutyUINT16× 0.1%Read
HR209doc 40210Electronic thermal relay function load factorUINT16× 0.1%Read
HR211doc 40212Converter output voltage peak valueUINT16× 0.1VRead
HR214doc 40215Input terminal status1 = on.BITMAP16Readbit 0 = STF; bit 1 = STR; bit 2 = AU; bit 3 = RT; bit 4 = RL; bit 5 = RM; bit 6 = RH; bit 7 = JOG; bit 8 = MRS; bit 9 = STOP; bit 10 = RES; bit 11 = CS
HR215doc 40216Output terminal status1 = on.BITMAP16Readbit 0 = RUN; bit 1 = SU; bit 2 = IPF; bit 3 = OL; bit 4 = FU; bit 5 = ABC1; bit 6 = ABC2
HR216doc 40217Load meterUINT16× 0.1%Read
HR219doc 40220Cumulative energization timeUINT16hRead
HR222doc 40223Actual operation timeUINT16hRead
HR223doc 40224Motor load factorUINT16× 0.1%Read
HR224doc 40225Cumulative powerUINT16kWhRead
HR251doc 40252PID set pointUINT16× 0.1%Read
HR252doc 40253PID measured valueUINT16× 0.1%Read
HR500doc 40501Fault record 1Low byte = fault code (H00xx). Write any value to clear history.UINT16Read/write0 = No alarm; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 80 = E.IPF; 81 = E.UVT; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 160 = E.OPT; 163 = E.OP3; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 193 = E.CTE; 194 = E.P24; 196 = E.CDO; 197 = E.IOH; 198 = E.SER; 199 = E.AIE; 200 = E.USB; 208 = E.OS; 209 = E.OSD; 210 = E.ECT; 211 = E.OD; 213 = E.MB1; 214 = E.MB2; 215 = E.MB3; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 220 = E.EP; 241 = E.1; 242 = E.2; 243 = E.3; 246 = E.6; 247 = E.7; 251 = E.11; 253 = E.13
HR501doc 40502Fault record 2Low byte = fault code (H00xx).UINT16Read0 = No alarm; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 80 = E.IPF; 81 = E.UVT; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 160 = E.OPT; 163 = E.OP3; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 193 = E.CTE; 194 = E.P24; 196 = E.CDO; 197 = E.IOH; 198 = E.SER; 199 = E.AIE; 200 = E.USB; 208 = E.OS; 209 = E.OSD; 210 = E.ECT; 211 = E.OD; 213 = E.MB1; 214 = E.MB2; 215 = E.MB3; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 220 = E.EP; 241 = E.1; 242 = E.2; 243 = E.3; 246 = E.6; 247 = E.7; 251 = E.11; 253 = E.13
HR502doc 40503Fault record 3Low byte = fault code (H00xx).UINT16Read0 = No alarm; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 80 = E.IPF; 81 = E.UVT; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 160 = E.OPT; 163 = E.OP3; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 193 = E.CTE; 194 = E.P24; 196 = E.CDO; 197 = E.IOH; 198 = E.SER; 199 = E.AIE; 200 = E.USB; 208 = E.OS; 209 = E.OSD; 210 = E.ECT; 211 = E.OD; 213 = E.MB1; 214 = E.MB2; 215 = E.MB3; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 220 = E.EP; 241 = E.1; 242 = E.2; 243 = E.3; 246 = E.6; 247 = E.7; 251 = E.11; 253 = E.13
HR503doc 40504Fault record 4Low byte = fault code (H00xx).UINT16Read0 = No alarm; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 80 = E.IPF; 81 = E.UVT; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 160 = E.OPT; 163 = E.OP3; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 193 = E.CTE; 194 = E.P24; 196 = E.CDO; 197 = E.IOH; 198 = E.SER; 199 = E.AIE; 200 = E.USB; 208 = E.OS; 209 = E.OSD; 210 = E.ECT; 211 = E.OD; 213 = E.MB1; 214 = E.MB2; 215 = E.MB3; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 220 = E.EP; 241 = E.1; 242 = E.2; 243 = E.3; 246 = E.6; 247 = E.7; 251 = E.11; 253 = E.13
HR504doc 40505Fault record 5Low byte = fault code (H00xx).UINT16Read0 = No alarm; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 80 = E.IPF; 81 = E.UVT; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 160 = E.OPT; 163 = E.OP3; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 193 = E.CTE; 194 = E.P24; 196 = E.CDO; 197 = E.IOH; 198 = E.SER; 199 = E.AIE; 200 = E.USB; 208 = E.OS; 209 = E.OSD; 210 = E.ECT; 211 = E.OD; 213 = E.MB1; 214 = E.MB2; 215 = E.MB3; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 220 = E.EP; 241 = E.1; 242 = E.2; 243 = E.3; 246 = E.6; 247 = E.7; 251 = E.11; 253 = E.13
HR505doc 40506Fault record 6Low byte = fault code (H00xx).UINT16Read0 = No alarm; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 80 = E.IPF; 81 = E.UVT; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 160 = E.OPT; 163 = E.OP3; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 193 = E.CTE; 194 = E.P24; 196 = E.CDO; 197 = E.IOH; 198 = E.SER; 199 = E.AIE; 200 = E.USB; 208 = E.OS; 209 = E.OSD; 210 = E.ECT; 211 = E.OD; 213 = E.MB1; 214 = E.MB2; 215 = E.MB3; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 220 = E.EP; 241 = E.1; 242 = E.2; 243 = E.3; 246 = E.6; 247 = E.7; 251 = E.11; 253 = E.13
HR506doc 40507Fault record 7Low byte = fault code (H00xx).UINT16Read0 = No alarm; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 80 = E.IPF; 81 = E.UVT; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 160 = E.OPT; 163 = E.OP3; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 193 = E.CTE; 194 = E.P24; 196 = E.CDO; 197 = E.IOH; 198 = E.SER; 199 = E.AIE; 200 = E.USB; 208 = E.OS; 209 = E.OSD; 210 = E.ECT; 211 = E.OD; 213 = E.MB1; 214 = E.MB2; 215 = E.MB3; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 220 = E.EP; 241 = E.1; 242 = E.2; 243 = E.3; 246 = E.6; 247 = E.7; 251 = E.11; 253 = E.13
HR507doc 40508Fault record 8Low byte = fault code (H00xx).UINT16Read0 = No alarm; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 80 = E.IPF; 81 = E.UVT; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 160 = E.OPT; 163 = E.OP3; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 193 = E.CTE; 194 = E.P24; 196 = E.CDO; 197 = E.IOH; 198 = E.SER; 199 = E.AIE; 200 = E.USB; 208 = E.OS; 209 = E.OSD; 210 = E.ECT; 211 = E.OD; 213 = E.MB1; 214 = E.MB2; 215 = E.MB3; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 220 = E.EP; 241 = E.1; 242 = E.2; 243 = E.3; 246 = E.6; 247 = E.7; 251 = E.11; 253 = E.13
HR1000doc 41001Pr.1 Maximum frequencyUINT16× 0.01HzRead/write
HR1001doc 41002Pr.2 Minimum frequencyUINT16× 0.01HzRead/write
HR1003doc 41004Pr.4 Multi-speed setting (high speed)UINT16× 0.01HzRead/write
HR1004doc 41005Pr.5 Multi-speed setting (middle speed)UINT16× 0.01HzRead/write
HR1005doc 41006Pr.6 Multi-speed setting (low speed)UINT16× 0.01HzRead/write
HR1078doc 41079Pr.79 Operation mode selectionUINT16Read/write0 = External/PU switchover (External at power-on); 1 = Fixed PU operation; 2 = Fixed External operation (NET switchable); 3 = External/PU combined mode 1; 4 = External/PU combined mode 2; 6 = Switchover mode; 7 = External operation (PU interlock)
HR1330doc 41331Pr.331 RS-485 communication station number0 = broadcast; set 1-247.UINT16Read/write
HR1331doc 41332Pr.332 RS-485 communication speedSetting x 100 = bps (initial 96 = 9600).UINT16Read/write
HR1333doc 41334Pr.334 RS-485 communication parity check selectionUINT16Read/write0 = No parity, 2 stop bits; 1 = Odd parity, 1 stop bit; 2 = Even parity, 1 stop bit
HR1342doc 41343Pr.343 Communication error countModbus RTU error count (RAM).UINT16Read
HR1538doc 41539Pr.539 Modbus-RTU communication check time interval0 = Modbus works but the drive trips in NET mode; 9999 = no check.UINT16× 0.1sRead/write
HR1548doc 41549Pr.549 Protocol selectionUINT16Read/write0 = Mitsubishi inverter protocol (computer link); 1 = Modbus-RTU

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU)

What Modbus registers does the Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU) have?

This map lists 46 registers: 46 holding registers. 21 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints Modicon-style register numbers (40002, 41004) and states: starting address = register number - 40001. Its example reads 41004 (Pr.4) with start address H03EB (1003).

What are the minimum Modbus registers to integrate the Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU)?

Start with HR 8 Inverter status / control input instruction (Run/stop command and inverter status); HR 9 Operation mode / inverter setting (Operation mode (write H0014 for NET)); HR 13 Running frequency (RAM) (Frequency command (RAM)); HR 200 Output frequency / speed (Output frequency); HR 223 Motor load factor (Motor load factor); HR 500 Fault record 1 (Latest fault code).

How do I enable Modbus control of the Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU)?

Pr.549 = 1 selects Modbus-RTU (RS-485 terminals only); set Pr.331, Pr.332 and Pr.334 and reset. Run/frequency commands need NET operation mode (write H0014 to 40010; allowed depending on Pr.79/Pr.340). With a communication option fitted and Pr.550 = 9999, RS-485 terminal commands are ignored.

What happens when the Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU) loses Modbus communication?

Pr.539 Modbus-RTU communication check time interval (0.1-999.8 s, same behaviour as Pr.122); 9999 (initial) = no check; 0 lets Modbus run but the drive trips in NET mode.

Where is the official Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU) Modbus documentation?

The source is FR-A700 Instruction Manual (Applied) (IB(NA)-0600226ENG-E), revision 2012-02, published free by Mitsubishi Electric at https://dl.mitsubishielectric.com/dl/fa/document/manual/inv/ib0600226eng/ib0600226enge.pdf.

More Mitsubishi Electric Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: FR-A700 Instruction Manual (Applied) · IB(NA)-0600226ENG-E · rev. 2012-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.