TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII) Modbus register map
Updated 17 November 2026
The EV is a legacy TECO-Westinghouse micro inverter that speaks Modbus RTU or ASCII through an RS-485 option card. The run command and frequency go to 00E6H/00E7H, status, fault code and monitors are read from 00EFH-00F8H, and each F/C parameter has its own register listed in section 6. This map covers the command and monitor data.
This page lists 12 Modbus registers for the TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII) — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from TECO-Westinghouse’s own free documentation (linked below) and checked against it.
- Manufacturer
- TECO-Westinghouse
- Model
- EV micro inverter (Modbus RTU/ASCII)
- Equipment type
- Variable frequency drive
- Registers
- 12 (2 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- Not stated
- Documented addressing
- hexadecimal, 0-based
- Also known as
- TECO EV, EV Inverter Series
- Source document
- EV Inverter Series: Modbus Communication Manual
Integration notes: TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII)
Fit the RS-485 option card, set the follower address and serial settings on the drive, then write 00E6H (run bits) and 00E7H (frequency) and poll 00EFH-00F6H.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 230 | Operation command | BITMAP16 | Run/stop, direction, reset | Read/write |
| HR 231 | Frequency command | UINT16 | Frequency command | Read/write |
| HR 239 | Operation state | BITMAP16 | Operation state | Read |
| HR 240 | Fault description | UINT16 | Fault code | Read |
| HR 243 | Output frequency | UINT16 | Output frequency | Read |
| HR 246 | Output current | UINT16 | Output current | Read |
Enable Modbus control & writes
Install the RS-485 option card and set address and communication parameters per the EV drive manual.
Byte order & addressing
- Registers are hex.
- Functions 03H, 06H, 08H and 10H; maximum frame 80 bytes.
- Follower addresses 01H-FEH.
- Parameter registers in section 6 are not in parameter order (e.g. F07 = 0008H, F08 = 0007H).
Network setup
- RS-485 via the option card terminals RSA/RSB; 120 ohm, 1/4 W terminators at both ends.
Watch out for
- Unused bits read as 0; registers marked not used are read-only.
TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 230doc 00E6H | Operation command | Run, direction, EFO, reset, jog, comm inputs S1-S3. | BITMAP16 | Read/write | bit 0 = Run (0 stop); bit 1 = Reverse (0 forward); bit 2 = External fault (EFO); bit 3 = Fault reset; bit 4 = Jog; bit 5 = Comm input S1; bit 6 = Comm input S2; bit 7 = Comm input S3 | |||
| HR | 231doc 00E7H | Frequency command | Scale not printed; see notes. | UINT16 | Read/write | ||||
| HR | 239doc 00EFH | Operation state | BITMAP16 | Read | bit 0 = Running; bit 1 = Reverse; bit 2 = Ready; bit 3 = Abnormal; bit 4 = Data setting error | ||||
| HR | 240doc 00F0H | Fault description | Active fault code. | UINT16 | Read | 0 = Normal; 1 = Inverter over heat (OH); 2 = Over current at stop (OC); 3 = Under voltage (LV); 4 = Over voltage (OV); 5 = External BB (b.b.); 6 = CPU interrupted (CT); 7 = PID feedback signal loss (PID); 8 = EEPROM abnormal (EPR); 9 = Inverter overload (OL2); 10 = Motor overload (OL1); 11 = Emergency stop (E.S.); 13 = Over current at constant speed (OCC); 14 = Over current during accelerating (OCA); 15 = Over current during decelerating (OCD); 16 = Over current at startup (OCS); 17 = Under voltage during running (LVC); 18 = Over voltage at constant speed / decelerating (OVC); 19 = Inverter over heat at constant speed (OHC); 20 = Stop at 0 Hz (SP0); 21 = Direct start disable (SP1); 22 = Control panel emergency stop (SP2); 23 = Keypad operation error (ER1); 24 = Parameter setting error (ER2); 25 = Analog converting error (ER4); 26 = Modifying parameter in communication (ER5); 27 = Communication failure (ER6); 28 = Incorrect parameter setting (ER7); 29 = Factory setting error (ER8); 30 = Copy (CPY); 31 = Compare (CPR); 32 = Copy error (EP1); 33 = Compare error (EP2); 34 = Inverter over speed (OVS); 35 = Over current limit (OCL) | |||
| HR | 241doc 00F1H | Terminal status | BITMAP16 | Read | bit 0 = S1 closed; bit 1 = S2 closed; bit 2 = S3 closed; bit 3 = S4 closed; bit 6 = AIN closed; bit 7 = Relay 1 on | ||||
| HR | 242doc 00F2H | Frequency command | 100 = 1 Hz. | UINT16 | × 0.01 | Hz | Read | ||
| HR | 243doc 00F3H | Output frequency | 100 = 1 Hz. | UINT16 | × 0.01 | Hz | Read | ||
| HR | 244doc 00F4H | Output voltage command | 10 = 1 V. | UINT16 | × 0.1 | V | Read | ||
| HR | 245doc 00F5H | DC voltage | 1 = 1 V. | UINT16 | V | Read | |||
| HR | 246doc 00F6H | Output current | 10 = 1 A. | UINT16 | × 0.1 | A | Read | ||
| HR | 247doc 00F7H | PID feedback | 10 = 1 % of max output frequency. | UINT16 | × 0.1 | % | Read | ||
| HR | 248doc 00F8H | PID input | Signed; 10 = 1 % of max output frequency. | INT16 | × 0.1 | % | Read |
Notes on this map
- 00E7H frequency command has no printed scale; the 06H example labels the write '60.0 Hz' but sends 1770H (6000), so it is left unscaled. The 00F2H/00F3H monitors are 100 = 1 Hz.
- Left out: 00F9H/00FAH AIN values (footnote *1 not explained) and the remote-keypad registers.
- The section 6 table maps every F and C parameter to an individual hex register; those are not expanded here.
- Communication setup parameters (address, baud, protocol) are not named in this manual; see the EV drive manual.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII)
What Modbus registers does the TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII) have?
This map lists 12 registers: 12 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and sent unchanged: the 03H example reads start address 00 F2 (frequency command monitor) and gets 1770H. Parameters use the register table in section 6 (e.g. F01 = 0001H, C00 = 0064H), which is not sequential.
What are the minimum Modbus registers to integrate the TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII)?
Start with HR 230 Operation command (Run/stop, direction, reset); HR 231 Frequency command (Frequency command); HR 239 Operation state (Operation state); HR 240 Fault description (Fault code); HR 243 Output frequency (Output frequency); HR 246 Output current (Output current).
How do I enable Modbus control of the TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII)?
Install the RS-485 option card and set address and communication parameters per the EV drive manual.
Where is the official TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII) Modbus documentation?
The source is EV Inverter Series: Modbus Communication Manual, published free by TECO-Westinghouse at https://tecowestinghouse.com/PDF/ev_modbus_manual.pdf.
More TECO-Westinghouse Modbus register maps
- Variable frequency drive
TECO-Westinghouse A510 inverter (Modbus RTU/ASCII)
TECO-Westinghouse A510 inverters using the built-in RS-485 port (CN6), per communication addendum DOCUMENT-TECO-A510-AC001 Ver01 (2015-04).
Also known as: TECO A510, A510s - Variable frequency drive
TECO-Westinghouse E510 Compact (E510N1) inverter (Modbus RTU/ASCII)
TECO-Westinghouse E510 Compact (E510N1) inverters with the built-in RS-485 port (CON2), per communication addendum DOCUMENT-TECO-E510N1-AC002 Ver01 (2017-08).
Also known as: E510N1, E510s, TECO E510 Compact - Variable frequency drive
TECO-Westinghouse E510 inverter (Modbus RTU/ASCII)
TECO-Westinghouse E510 inverters using the built-in RS-485 port (CON2), per communication addendum DOCUMENT-TECO-E510-AC001 Ver01 (2015-03).
Also known as: TECO E510, E510 Communication Addendum - Variable frequency drive (HVAC fan / pump)
TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII)
TECO-Westinghouse F510 HVAC inverters using the built-in RS-485 port (CN6) in Modbus mode, per communication addendum DOCUMENT-TECO-F510-AC001 Ver01 (2015-03).
Also known as: TECO F510, F510 HVAC drive - Variable frequency drive
TECO-Westinghouse L510 inverter (Modbus RTU/ASCII)
TECO-Westinghouse L510 micro inverters with the RS-485 option card, per communication addendum DOCUMENT-TECO-L510-AC001 Ver01 (2015-06).
Also known as: TECO L510, L510 Communication Addendum
Other variable frequency drives register maps
- Variable frequency drive
WEG CFW500 frequency inverter (Modbus RTU)
WEG CFW500 drives as a Modbus RTU slave on the RS-485 port of the plug-in module (Modbus RTU User's Guide 10002253377 rev 04); parameter scaling from the V2.2X programming manual.
Also known as: CFW500 VFD, CFW500-IOS, CFW500-CRS485, CFW500-CUSB, CFW500-CRS232 - Variable frequency drive
Yaskawa GA500 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA500 drives using the built-in RS-485 MEMOBUS/Modbus port (terminal TB4), per technical reference SIEPC71061752 revision C.
Also known as: CIPR-GA50U, GA500 Versatile Compact - Variable frequency drive
Yaskawa iQpump1000 intelligent pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump1000 drives (CIMR-PW) using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEPYAIP1W01G.
Also known as: CIMR-PW, CIMR-PWA, iQpump1000 AC Drive - Variable frequency drive
Yaskawa U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU)
Yaskawa U1000 matrix drives using the built-in RS-422/485 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP C710636 04E.
Also known as: CIMR-UU, U1000 Industrial MATRIX Drive - Variable frequency drive
ABB ACH550-UH HVAC drive (embedded Modbus RTU)
ACH550-UH HVAC drives using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AUA0000081823 Rev F.
Also known as: ACH550-UH, ACH550 - Variable frequency drive
ABB ACS480 general purpose drive (embedded Modbus RTU)
ACS480 drives running the ACS480 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000047399 Rev G.
Also known as: ACS480-04, ACS480 standard control program
All variable frequency drives Modbus register maps →
Source: EV Inverter Series: Modbus Communication Manual. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.