TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII) Modbus register map

Updated 17 November 2026

Short answer

The EV is a legacy TECO-Westinghouse micro inverter that speaks Modbus RTU or ASCII through an RS-485 option card. The run command and frequency go to 00E6H/00E7H, status, fault code and monitors are read from 00EFH-00F8H, and each F/C parameter has its own register listed in section 6. This map covers the command and monitor data.

This page lists 12 Modbus registers for the TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII) — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from TECO-Westinghouse’s own free documentation (linked below) and checked against it.

Manufacturer
TECO-Westinghouse
Model
EV micro inverter (Modbus RTU/ASCII)
Equipment type
Variable frequency drive
Registers
12 (2 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
Not stated
Documented addressing
hexadecimal, 0-based
Also known as
TECO EV, EV Inverter Series
Source document
EV Inverter Series: Modbus Communication Manual
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII)

Integration in brief

Fit the RS-485 option card, set the follower address and serial settings on the drive, then write 00E6H (run bits) and 00E7H (frequency) and poll 00EFH-00F6H.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 230Operation commandBITMAP16Run/stop, direction, resetRead/write
HR 231Frequency commandUINT16Frequency commandRead/write
HR 239Operation stateBITMAP16Operation stateRead
HR 240Fault descriptionUINT16Fault codeRead
HR 243Output frequencyUINT16Output frequencyRead
HR 246Output currentUINT16Output currentRead

Enable Modbus control & writes

Install the RS-485 option card and set address and communication parameters per the EV drive manual.

Byte order & addressing

Network setup

Watch out for

TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

12 of 12 shown
TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR230doc 00E6HOperation commandRun, direction, EFO, reset, jog, comm inputs S1-S3.BITMAP16Read/writebit 0 = Run (0 stop); bit 1 = Reverse (0 forward); bit 2 = External fault (EFO); bit 3 = Fault reset; bit 4 = Jog; bit 5 = Comm input S1; bit 6 = Comm input S2; bit 7 = Comm input S3
HR231doc 00E7HFrequency commandScale not printed; see notes.UINT16Read/write
HR239doc 00EFHOperation stateBITMAP16Readbit 0 = Running; bit 1 = Reverse; bit 2 = Ready; bit 3 = Abnormal; bit 4 = Data setting error
HR240doc 00F0HFault descriptionActive fault code.UINT16Read0 = Normal; 1 = Inverter over heat (OH); 2 = Over current at stop (OC); 3 = Under voltage (LV); 4 = Over voltage (OV); 5 = External BB (b.b.); 6 = CPU interrupted (CT); 7 = PID feedback signal loss (PID); 8 = EEPROM abnormal (EPR); 9 = Inverter overload (OL2); 10 = Motor overload (OL1); 11 = Emergency stop (E.S.); 13 = Over current at constant speed (OCC); 14 = Over current during accelerating (OCA); 15 = Over current during decelerating (OCD); 16 = Over current at startup (OCS); 17 = Under voltage during running (LVC); 18 = Over voltage at constant speed / decelerating (OVC); 19 = Inverter over heat at constant speed (OHC); 20 = Stop at 0 Hz (SP0); 21 = Direct start disable (SP1); 22 = Control panel emergency stop (SP2); 23 = Keypad operation error (ER1); 24 = Parameter setting error (ER2); 25 = Analog converting error (ER4); 26 = Modifying parameter in communication (ER5); 27 = Communication failure (ER6); 28 = Incorrect parameter setting (ER7); 29 = Factory setting error (ER8); 30 = Copy (CPY); 31 = Compare (CPR); 32 = Copy error (EP1); 33 = Compare error (EP2); 34 = Inverter over speed (OVS); 35 = Over current limit (OCL)
HR241doc 00F1HTerminal statusBITMAP16Readbit 0 = S1 closed; bit 1 = S2 closed; bit 2 = S3 closed; bit 3 = S4 closed; bit 6 = AIN closed; bit 7 = Relay 1 on
HR242doc 00F2HFrequency command100 = 1 Hz.UINT16× 0.01HzRead
HR243doc 00F3HOutput frequency100 = 1 Hz.UINT16× 0.01HzRead
HR244doc 00F4HOutput voltage command10 = 1 V.UINT16× 0.1VRead
HR245doc 00F5HDC voltage1 = 1 V.UINT16VRead
HR246doc 00F6HOutput current10 = 1 A.UINT16× 0.1ARead
HR247doc 00F7HPID feedback10 = 1 % of max output frequency.UINT16× 0.1%Read
HR248doc 00F8HPID inputSigned; 10 = 1 % of max output frequency.INT16× 0.1%Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII)

What Modbus registers does the TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII) have?

This map lists 12 registers: 12 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and sent unchanged: the 03H example reads start address 00 F2 (frequency command monitor) and gets 1770H. Parameters use the register table in section 6 (e.g. F01 = 0001H, C00 = 0064H), which is not sequential.

What are the minimum Modbus registers to integrate the TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII)?

Start with HR 230 Operation command (Run/stop, direction, reset); HR 231 Frequency command (Frequency command); HR 239 Operation state (Operation state); HR 240 Fault description (Fault code); HR 243 Output frequency (Output frequency); HR 246 Output current (Output current).

How do I enable Modbus control of the TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII)?

Install the RS-485 option card and set address and communication parameters per the EV drive manual.

Where is the official TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII) Modbus documentation?

The source is EV Inverter Series: Modbus Communication Manual, published free by TECO-Westinghouse at https://tecowestinghouse.com/PDF/ev_modbus_manual.pdf.

More TECO-Westinghouse Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: EV Inverter Series: Modbus Communication Manual. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.