TECO-Westinghouse E510 inverter (Modbus RTU/ASCII) Modbus register map

Updated 17 November 2026

Short answer

The E510 is TECO-Westinghouse's compact general-purpose inverter with a built-in RS-485 port speaking Modbus RTU or ASCII. Run/stop and frequency are written to hex registers 2501H/2502H, status and monitors are read from 2520H-252DH, and each parameter nn-mm has its own register (group in the high byte, number in the low byte). This map covers the command and monitor tables.

This page lists 11 Modbus registers for the TECO-Westinghouse E510 inverter (Modbus RTU/ASCII) — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from TECO-Westinghouse’s own free documentation (linked below) and checked against it.

Manufacturer
TECO-Westinghouse
Model
E510 inverter (Modbus RTU/ASCII)
Equipment type
Variable frequency drive
Registers
11 (2 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
Not stated
Documented addressing
hexadecimal, 0-based
Also known as
TECO E510, E510 Communication Addendum
Source document
E510 Communication Addendum Modbus RTU/ASCII · DOCUMENT-TECO-E510-AC001 Ver01 · rev. 2015-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: TECO-Westinghouse E510 inverter (Modbus RTU/ASCII)

Integration in brief

Configure the drive's RS-485 node address and serial settings, select communication as the run and frequency source in the E510 parameters, then write 2501H (run bits) and 2502H (frequency) and poll 2520H-2527H.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 9473Operation signalBITMAP16Run/stop, direction, resetRead/write
HR 9474Frequency commandUINT16Frequency commandRead/write
HR 9504State signalBITMAP16Run/ready/fault statusRead
HR 9505Error descriptionUINT16Error codeRead
HR 9508Output frequencyUINT16Output frequencyRead
HR 9511Output currentUINT16Output currentRead

Enable Modbus control & writes

Set the node address and communication parameters at the keypad (parameter numbers are in the E510 manual, not this addendum) and select RS-485 communication as the run and frequency command source.

Byte order & addressing

Network setup

Watch out for

TECO-Westinghouse E510 inverter (Modbus RTU/ASCII) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

11 of 11 shown
TECO-Westinghouse E510 inverter (Modbus RTU/ASCII) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR9473doc 2501HOperation signalRun/stop, direction, external fault, reset, comm inputs S1-S6, relays.BITMAP16Read/writebit 0 = Run (0 stop); bit 1 = Reverse (0 forward); bit 2 = External fault; bit 3 = Fault reset; bit 6 = Comm input S1; bit 7 = Comm input S2; bit 8 = Comm input S3; bit 9 = Comm input S4; bit 10 = Comm input S5; bit 11 = Comm input S6; bit 12 = Relay R1 on; bit 13 = Relay R2 on
HR9474doc 2502HFrequency commandScale not printed in the command table.UINT16Read/write
HR9504doc 2520HState signalBITMAP16Readbit 0 = Running (0 stopped); bit 1 = Reverse (0 forward); bit 2 = Inverter ready; bit 3 = Fault; bit 4 = Data setting error
HR9505doc 2521HError descriptionActive error code.UINT16Read1 = OH; 2 = OC; 3 = LV; 4 = OV; 6 = External BB (bb); 7 = CTER; 8 = PDER; 9 = EPR; 10 = ATER; 11 = OL3; 12 = OL2; 13 = OL1; 14 = EFO; 15 = External bb (E.S.); 16 = LOC; 18 = OC-C; 19 = OC-A; 20 = OC-D; 21 = OC-S; 23 = LV-C; 24 = OV-C; 25 = OH-C; 26 = STP0; 27 = STP1; 28 = STP2; 29 = Err1; 30 = Err2; 31 = Err4; 32 = Err5; 33 = Err6; 34 = Err7; 35 = Err8; 38 = EPR1; 39 = EPR2; 40 = OVSP
HR9506doc 2522HDI stateBITMAP16Readbit 0 = Comm S1 on; bit 1 = Comm S2 on; bit 2 = Comm S3 on; bit 3 = Comm S4 on; bit 4 = Comm S5 on; bit 5 = Comm S6 on; bit 6 = Relay R1 on; bit 7 = Relay R2 on
HR9507doc 2523HFrequency command100 = 1 Hz.UINT16× 0.01HzRead
HR9508doc 2524HOutput frequency100 = 1 Hz.UINT16× 0.01HzRead
HR9509doc 2525HOutput voltage10 = 1 V.UINT16× 0.1VRead
HR9510doc 2526HDC voltage1 = 1 V.UINT16VRead
HR9511doc 2527HOutput current10 = 1 A.UINT16× 0.1ARead
HR9514doc 252AHPID feedback10 = 1 %, 100 % = fmax.UINT16× 0.1%Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the TECO-Westinghouse E510 inverter (Modbus RTU/ASCII)

What Modbus registers does the TECO-Westinghouse E510 inverter (Modbus RTU/ASCII) have?

This map lists 11 registers: 11 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the TECO-Westinghouse E510 inverter (Modbus RTU/ASCII) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and are sent unchanged: the 06H example writes start register 01 02 (0102H) and the 03H example reads 01 23 (0123H). Parameters map as group in the high byte and number in the low byte, e.g. 00-10 = 000AH, 01-12 = 010CH, 11-17 = 0B11H.

What are the minimum Modbus registers to integrate the TECO-Westinghouse E510 inverter (Modbus RTU/ASCII)?

Start with HR 9473 Operation signal (Run/stop, direction, reset); HR 9474 Frequency command (Frequency command); HR 9504 State signal (Run/ready/fault status); HR 9505 Error description (Error code); HR 9508 Output frequency (Output frequency); HR 9511 Output current (Output current).

How do I enable Modbus control of the TECO-Westinghouse E510 inverter (Modbus RTU/ASCII)?

Set the node address and communication parameters at the keypad (parameter numbers are in the E510 manual, not this addendum) and select RS-485 communication as the run and frequency command source.

Where is the official TECO-Westinghouse E510 inverter (Modbus RTU/ASCII) Modbus documentation?

The source is E510 Communication Addendum Modbus RTU/ASCII (DOCUMENT-TECO-E510-AC001 Ver01), revision 2015-03, published free by TECO-Westinghouse at https://tecowestinghouse.com/PDF/E510_comm_addendum.pdf.