Variable frequency drive · Modbus register map
TECO-Westinghouse E510 inverter (Modbus RTU/ASCII) Modbus register map
Updated 17 November 2026
The E510 is TECO-Westinghouse's compact general-purpose inverter with a built-in RS-485 port speaking Modbus RTU or ASCII. Run/stop and frequency are written to hex registers 2501H/2502H, status and monitors are read from 2520H-252DH, and each parameter nn-mm has its own register (group in the high byte, number in the low byte). This map covers the command and monitor tables.
This page lists 11 Modbus registers for the TECO-Westinghouse E510 inverter (Modbus RTU/ASCII) — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from TECO-Westinghouse’s own free documentation (linked below) and checked against it.
- Manufacturer
- TECO-Westinghouse
- Model
- E510 inverter (Modbus RTU/ASCII)
- Equipment type
- Variable frequency drive
- Registers
- 11 (2 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- Not stated
- Documented addressing
- hexadecimal, 0-based
- Also known as
- TECO E510, E510 Communication Addendum
Integration notes: TECO-Westinghouse E510 inverter (Modbus RTU/ASCII)
Configure the drive's RS-485 node address and serial settings, select communication as the run and frequency source in the E510 parameters, then write 2501H (run bits) and 2502H (frequency) and poll 2520H-2527H.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 9473 | Operation signal | BITMAP16 | Run/stop, direction, reset | Read/write |
| HR 9474 | Frequency command | UINT16 | Frequency command | Read/write |
| HR 9504 | State signal | BITMAP16 | Run/ready/fault status | Read |
| HR 9505 | Error description | UINT16 | Error code | Read |
| HR 9508 | Output frequency | UINT16 | Output frequency | Read |
| HR 9511 | Output current | UINT16 | Output current | Read |
Enable Modbus control & writes
Set the node address and communication parameters at the keypad (parameter numbers are in the E510 manual, not this addendum) and select RS-485 communication as the run and frequency command source.
Byte order & addressing
- Registers are hex: 2520H is sent as 25 20.
- Functions 03H, 06H, 08H and 10H; maximum frame 80 bytes.
- Node addresses 01H-FEH; 00H is broadcast.
- Write 0 to unused bits and never write reserved registers.
Network setup
- RS-485 on CON2 (RJ45): pin 1 or 3 = S+, pin 2 or 6 = S-.
- Up to 31 inverters per network (Appendix A).
- The addendum asks for 120 ohm terminators on p. 1-1 but 220 ohm in Appendix A; check the drive manual.
Watch out for
- Exception codes: 01 function, 02 register number, 03 number, 04 data setting, 05 write mode error.
- Inverter response time is about 10 ms.
TECO-Westinghouse E510 inverter (Modbus RTU/ASCII) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 9473doc 2501H | Operation signal | Run/stop, direction, external fault, reset, comm inputs S1-S6, relays. | BITMAP16 | Read/write | bit 0 = Run (0 stop); bit 1 = Reverse (0 forward); bit 2 = External fault; bit 3 = Fault reset; bit 6 = Comm input S1; bit 7 = Comm input S2; bit 8 = Comm input S3; bit 9 = Comm input S4; bit 10 = Comm input S5; bit 11 = Comm input S6; bit 12 = Relay R1 on; bit 13 = Relay R2 on | |||
| HR | 9474doc 2502H | Frequency command | Scale not printed in the command table. | UINT16 | Read/write | ||||
| HR | 9504doc 2520H | State signal | BITMAP16 | Read | bit 0 = Running (0 stopped); bit 1 = Reverse (0 forward); bit 2 = Inverter ready; bit 3 = Fault; bit 4 = Data setting error | ||||
| HR | 9505doc 2521H | Error description | Active error code. | UINT16 | Read | 1 = OH; 2 = OC; 3 = LV; 4 = OV; 6 = External BB (bb); 7 = CTER; 8 = PDER; 9 = EPR; 10 = ATER; 11 = OL3; 12 = OL2; 13 = OL1; 14 = EFO; 15 = External bb (E.S.); 16 = LOC; 18 = OC-C; 19 = OC-A; 20 = OC-D; 21 = OC-S; 23 = LV-C; 24 = OV-C; 25 = OH-C; 26 = STP0; 27 = STP1; 28 = STP2; 29 = Err1; 30 = Err2; 31 = Err4; 32 = Err5; 33 = Err6; 34 = Err7; 35 = Err8; 38 = EPR1; 39 = EPR2; 40 = OVSP | |||
| HR | 9506doc 2522H | DI state | BITMAP16 | Read | bit 0 = Comm S1 on; bit 1 = Comm S2 on; bit 2 = Comm S3 on; bit 3 = Comm S4 on; bit 4 = Comm S5 on; bit 5 = Comm S6 on; bit 6 = Relay R1 on; bit 7 = Relay R2 on | ||||
| HR | 9507doc 2523H | Frequency command | 100 = 1 Hz. | UINT16 | × 0.01 | Hz | Read | ||
| HR | 9508doc 2524H | Output frequency | 100 = 1 Hz. | UINT16 | × 0.01 | Hz | Read | ||
| HR | 9509doc 2525H | Output voltage | 10 = 1 V. | UINT16 | × 0.1 | V | Read | ||
| HR | 9510doc 2526H | DC voltage | 1 = 1 V. | UINT16 | V | Read | |||
| HR | 9511doc 2527H | Output current | 10 = 1 A. | UINT16 | × 0.1 | A | Read | ||
| HR | 9514doc 252AH | PID feedback | 10 = 1 %, 100 % = fmax. | UINT16 | × 0.1 | % | Read |
Notes on this map
- The addendum does not name the drive parameters for node address, baud rate, parity or remote run/frequency source; set those per the E510 instruction manual.
- 2502H frequency command has no scale in the command table; the 06H example writes 1770H (6000) for 60.00 Hz but to register 0102H, not 2502H, so 2502H is left unscaled (read-back 2523H uses 100 = 1 Hz).
- 2521H is listed as a code table (0-40), not bit flags, so it is mapped as an enum.
- Left out: 2529H output torque (no unit), 252BH PID input (sign not stated), 252CH/252DH AVI/ACI inputs (footnote *1 not explained).
- The parameter register rule (group high byte, number low byte in hex) is described in the notes and not expanded into individual registers; Group 14-15 PLC registers are in a separate E510 PLC section.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the TECO-Westinghouse E510 inverter (Modbus RTU/ASCII)
What Modbus registers does the TECO-Westinghouse E510 inverter (Modbus RTU/ASCII) have?
This map lists 11 registers: 11 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the TECO-Westinghouse E510 inverter (Modbus RTU/ASCII) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and are sent unchanged: the 06H example writes start register 01 02 (0102H) and the 03H example reads 01 23 (0123H). Parameters map as group in the high byte and number in the low byte, e.g. 00-10 = 000AH, 01-12 = 010CH, 11-17 = 0B11H.
What are the minimum Modbus registers to integrate the TECO-Westinghouse E510 inverter (Modbus RTU/ASCII)?
Start with HR 9473 Operation signal (Run/stop, direction, reset); HR 9474 Frequency command (Frequency command); HR 9504 State signal (Run/ready/fault status); HR 9505 Error description (Error code); HR 9508 Output frequency (Output frequency); HR 9511 Output current (Output current).
How do I enable Modbus control of the TECO-Westinghouse E510 inverter (Modbus RTU/ASCII)?
Set the node address and communication parameters at the keypad (parameter numbers are in the E510 manual, not this addendum) and select RS-485 communication as the run and frequency command source.
Where is the official TECO-Westinghouse E510 inverter (Modbus RTU/ASCII) Modbus documentation?
The source is E510 Communication Addendum Modbus RTU/ASCII (DOCUMENT-TECO-E510-AC001 Ver01), revision 2015-03, published free by TECO-Westinghouse at https://tecowestinghouse.com/PDF/E510_comm_addendum.pdf.
More TECO-Westinghouse Modbus register maps
- Variable frequency drive
TECO-Westinghouse A510 inverter (Modbus RTU/ASCII)
TECO-Westinghouse A510 inverters using the built-in RS-485 port (CN6), per communication addendum DOCUMENT-TECO-A510-AC001 Ver01 (2015-04).
Also known as: TECO A510, A510s - Variable frequency drive
TECO-Westinghouse E510 Compact (E510N1) inverter (Modbus RTU/ASCII)
TECO-Westinghouse E510 Compact (E510N1) inverters with the built-in RS-485 port (CON2), per communication addendum DOCUMENT-TECO-E510N1-AC002 Ver01 (2017-08).
Also known as: E510N1, E510s, TECO E510 Compact - Variable frequency drive
TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII)
TECO-Westinghouse EV series micro inverters with the RS-485 option card, per the EV Inverter Series Modbus Communication Manual.
Also known as: TECO EV, EV Inverter Series - Variable frequency drive (HVAC fan / pump)
TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII)
TECO-Westinghouse F510 HVAC inverters using the built-in RS-485 port (CN6) in Modbus mode, per communication addendum DOCUMENT-TECO-F510-AC001 Ver01 (2015-03).
Also known as: TECO F510, F510 HVAC drive - Variable frequency drive
TECO-Westinghouse L510 inverter (Modbus RTU/ASCII)
TECO-Westinghouse L510 micro inverters with the RS-485 option card, per communication addendum DOCUMENT-TECO-L510-AC001 Ver01 (2015-06).
Also known as: TECO L510, L510 Communication Addendum
Other variable frequency drives register maps
- Variable frequency drive
Vacon VACON 20 AC drive (built-in Modbus RTU)
VACON 20 compact drives with the standard Vacon 20 application on the built-in RS-485 Modbus RTU port, per complete user manual DPD00716H1 (software FW0107V012).
Also known as: VACON 20, Vacon 20, VACON0020 - Variable frequency drive
Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU
Yaskawa G7 (CIMR-G7U) drives using built-in Modbus RTU on terminals R+/R-/S+/S-, per the Modbus Communication Manual G7 TM.G7.11 (rev 07-01).
Also known as: CIMR-G7U, G7U, G7 Drive - Variable frequency drive
Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump Micro drives using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEP YAIQPM 03B.
Also known as: CIMR-PW (iQpump Micro), iQpump Micro AC Drive, iQpump Micro Compact Intelligent Pump Controller - Variable frequency drive (fan / pump bypass package)
Yaskawa P7B drive/bypass (legacy) - Modbus RTU
Yaskawa P7B drive/bypass packages (P7 drive CIMR-P7U inside a bypass enclosure, option V native Modbus) using the drive's RS-422/485 terminals, per technical manual TM.P7B.01 Appendix D.
Also known as: P7B, P7 Bypass - Variable frequency drive
ABB ACH480 HVAC drive (embedded Modbus RTU)
ACH480 drives running the ACH480 HVAC control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000247134 Rev E.
Also known as: ACH480-04, ACH480 HVAC control program - Variable frequency drive
ABB ACS380 machinery drive (embedded Modbus RTU)
ACS380 drives running the machinery control program with the BMIO-01 I/O and Modbus RTU module, embedded fieldbus (EFB), addressing mode 0 (default); firmware manual 3AXD50000029275 Rev J.
Also known as: ACS380-04, ACS380 machinery control program, BMIO-01
All variable frequency drives Modbus register maps →
Source: E510 Communication Addendum Modbus RTU/ASCII · DOCUMENT-TECO-E510-AC001 Ver01 · rev. 2015-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.