- G7 drive (CIMR-G7U, legacy) - Modbus RTU
Variable frequency drive · Modbus register map
Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU Modbus register map
Updated 17 November 2026
The G7 is Yaskawa's legacy high-performance vector drive with built-in Modbus RTU. Commands are written to hex registers 0001h-000Fh, detailed fault/alarm words are read from 0010h-001Bh, status from 0020h-002Dh, U1/U2/U3 monitors from 0031h upward, and every parameter has its own hex address. This map covers the command block, all status/fault words, monitors with their published units, decoded fault history, and the b1/H5 parameters.
This page lists 76 Modbus registers for the Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU — 19 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yaskawa’s own free documentation (linked below) and checked against it.
- Manufacturer
- Yaskawa
- Model
- G7 drive (CIMR-G7U, legacy) - Modbus RTU
- Equipment type
- Variable frequency drive
- Registers
- 76 (19 writable)
- Transport
- Modbus RTU
- Default unit ID
- 31
- Default serial
- 9600 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- CIMR-G7U, G7U, G7 Drive
Integration notes: Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU
Set H5-01..H5-03 at the keypad and power-cycle, set b1-01 = 2 and b1-02 = 2, then write 0001h and 0002h with function 10h and poll 0020h-002Dh and 0040h-0046h.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1 | Digital input command | BITMAP16 | Run/stop, direction, reset | Read/write |
| HR 2 | Frequency reference setpoint | UINT16 | Frequency reference | Read/write |
| HR 32 | Inverter status (0020h) | BITMAP16 | Run/fault status | Read |
| HR 33 | Fault contents | BITMAP16 | Fault summary | Read |
| HR 44 | Inverter status (002Ch) | BITMAP16 | Status incl. comm timeout | Read |
| HR 65 | Output frequency (U1-02) | UINT16 | Output frequency | Read |
| HR 66 | Output current (U1-03) | UINT16 | Output current | Read |
| HR 128 | Current fault (U2-01) | UINT16 | Current fault code | Read |
Enable Modbus control & writes
H5-01 node address (default 1Fh, 0h-20h), H5-02 baud (default 3 = 9600), H5-03 parity (default none); cycle power. b1-01 = 2 and b1-02 = 2 select Modbus for reference and run (or set 0001h bits 4/5).
Communication loss & watchdog
H5-05 = 1 (default) enables CE detection; H5-04 selects the response: 0 ramp, 1 coast, 2 fast-stop, 3 alarm only (default). 002Ch bit F shows a comm timeout.
Byte order & addressing
- Registers and the node address are hex.
- Read 1-8 registers per 03h message.
- Command registers (0000h-00FFh) act immediately; parameter writes (0100h-07FFh) wait in an off-line area until 0 is written to 0910h (ACCEPT) or 0900h (ENTER, about 100,000 writes). Unconfirmed writes cause 'Busy Write Protected' on the keypad.
- Network digital inputs are ORed with the physical terminals.
Network setup
- RS-422/485 on control terminals R+, R-, S+, S- (see the G7 user manual for 2-wire wiring).
- Node address 1-20h; 0 is broadcast and is not valid for reads.
- 8 data bits, 1 stop bit; 1200-19200 baud.
Watch out for
- Two output-current registers use different resolutions (0026h 0.01 A, 0042h 0.1 A).
Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 0001h | Digital input command | Run, direction, external fault, reset, network inputs S3-S12. | BITMAP16 | Read/write | bit 0 = Run command (0 stop, 1 run); bit 1 = Direction (0 forward, 1 reverse); bit 2 = External fault; bit 3 = Fault reset; bit 4 = Frequency reference source (1 = Modbus); bit 5 = Run command source (1 = Modbus); bit 6 = Terminal S3 (H1-01); bit 7 = Terminal S4 (H1-02); bit 8 = Terminal S5 (H1-03); bit 9 = Terminal S6 (H1-04); bit 10 = Terminal S7 (H1-05); bit 11 = Terminal S8 (H1-06); bit 12 = Terminal S9 (H1-07); bit 13 = Terminal S10 (H1-08); bit 14 = Terminal S11 (H1-09); bit 15 = Terminal S12 (H1-10) | |||
| HR | 2doc 0002h | Frequency reference setpoint | Scaling depends on o1-03; unscaled here. | UINT16 | Read/write | ||||
| HR | 6doc 0006h | PID setpoint | Used when 000Fh bit 1 is set. | UINT16 | Read/write | ||||
| HR | 7doc 0007h | Analog output FM setpoint | -1540 = -11 V ... 1540 = +11 V. | INT16 | Read/write | ||||
| HR | 8doc 0008h | Analog output AM setpoint | -1540 = -11 V ... 1540 = +11 V. | INT16 | Read/write | ||||
| HR | 9doc 0009h | Digital output command | BITMAP16 | Read/write | bit 0 = Output 1 (M1-M2); bit 1 = Output 2 (M3-M4); bit 2 = Output 3 (M5-M6); bit 3 = Output 4 (P3-C3); bit 4 = Output 5 (P4-C4); bit 6 = Fault contact output enable (use bit 7); bit 7 = Fault contact output (MA, MB, MC) | ||||
| HR | 15doc 000Fh | Command selection | BITMAP16 | Read/write | bit 1 = PID setpoint enable (use 0006h); bit 12 = Broadcast terminal S5 enable; bit 13 = Broadcast terminal S6 enable; bit 14 = Broadcast terminal S7 enable; bit 15 = Broadcast terminal S8 enable | ||||
| HR | 16doc 0010h | Inverter status (0010h) | BITMAP16 | Read | bit 0 = Run; bit 3 = Fault reset signal; bit 4 = Speed agree; bit 5 = Inverter ready; bit 6 = Minor fault (alarm); bit 7 = Major fault; bit 14 = Frequency reference source = Modbus; bit 15 = Run command source = Modbus | ||||
| HR | 17doc 0011h | Operator status | BITMAP16 | Read | bit 0 = OPE keypad setting error; bit 1 = ERR EEPROM write failure; bit 2 = PRG keypad programming mode; bit 3 = PC connected (0 = digital operator) | ||||
| HR | 18doc 0012h | OPE keypad setting error | BITMAP16 | Read | bit 1 = OPE01 kVA setting error; bit 2 = OPE02 parameter out of range; bit 3 = OPE03 multi-function input error; bit 5 = OPE05 run command selection error; bit 6 = OPE06 control method error; bit 7 = OPE07 analog input selection error; bit 8 = OPE08 function selection error; bit 9 = OPE09 PID setup error; bit 10 = OPE10 V/f pattern error; bit 11 = OPE11 carrier frequency error | ||||
| HR | 20doc 0014h | Fault contents 1 | BITMAP16 | Read | bit 0 = PUF DC bus fuse; bit 1 = UV1 main circuit undervoltage; bit 2 = UV2 control circuit undervoltage; bit 3 = UV3 pre-charge contactor; bit 5 = GF ground fault; bit 6 = OC overcurrent; bit 7 = OV overvoltage; bit 8 = OH inverter overheat; bit 9 = OH1 inverter overheat warning; bit 10 = OL1 motor overload; bit 11 = OL2 inverter overload; bit 12 = OL3 overtorque 1; bit 13 = OL4 overtorque 2; bit 14 = RR braking resistor failure; bit 15 = RH braking resistor overheat | ||||
| HR | 21doc 0015h | Fault contents 2 | BITMAP16 | Read | bit 0 = EF3; bit 1 = EF4; bit 2 = EF5; bit 3 = EF6; bit 4 = EF7; bit 5 = EF8; bit 7 = OS overspeed; bit 8 = DEV speed deviation; bit 9 = PGO encoder feedback loss; bit 10 = PF input phase loss; bit 11 = LF output phase loss; bit 12 = OH3 overheat; bit 13 = OPR operator disconnected; bit 14 = ERR EEPROM write failure; bit 15 = OH4 motor overheat | ||||
| HR | 22doc 0016h | Fault contents 3 | BITMAP16 | Read | bit 0 = CE communication loss; bit 1 = BUS option card fault; bit 2 = E-15 SI-F/G fault; bit 3 = E-10 SI-F/G fault; bit 4 = CF loss of motor control; bit 5 = SVE zero servo fault; bit 6 = EF0 option external fault; bit 7 = FBL PID feedback loss; bit 8 = UL3 undertorque 1; bit 9 = UL4 undertorque 2; bit 10 = OL7 high slip braking overload; bit 11 = EF9; bit 12 = EF10; bit 13 = EF11; bit 14 = EF12 | ||||
| HR | 23doc 0017h | CPF contents 1 | BITMAP16 | Read | bit 2 = CPF02; bit 3 = CPF03; bit 4 = CPF04; bit 5 = CPF05; bit 6 = CPF06; bit 7 = CPF07; bit 8 = CPF08; bit 9 = CPF09; bit 10 = CPF10 | ||||
| HR | 24doc 0018h | CPF contents 2 | BITMAP16 | Read | bit 0 = CPF20; bit 1 = CPF21; bit 2 = CPF22; bit 3 = CPF23 | ||||
| HR | 25doc 0019h | Minor fault contents 1 | Alarms. | BITMAP16 | Read | bit 0 = UV undervoltage; bit 1 = OV overvoltage; bit 2 = OH inverter overheat; bit 3 = OH2 overheat warning; bit 4 = OL3 overtorque 1; bit 5 = OL4 overtorque 2; bit 6 = EF 2-wire sequence input fault; bit 7 = BB baseblock; bit 8 = EF3; bit 9 = EF4; bit 10 = EF5; bit 11 = EF6; bit 12 = EF7; bit 15 = OS overspeed | |||
| HR | 26doc 001Ah | Minor fault contents 2 | Alarms. | BITMAP16 | Read | bit 0 = DEV speed deviation; bit 1 = PGO encoder loss; bit 2 = OPR operator disconnected; bit 3 = CE communication loss; bit 4 = BUS option card fault; bit 5 = CALL waiting for communications; bit 6 = OL1 motor overload; bit 7 = OL2 inverter overload; bit 8 = E-15 SI-F/G communication fault; bit 9 = E-10 SI-F/G fault; bit 10 = Motor switch during run; bit 11 = FBL PID feedback loss; bit 12 = CALL waiting for first communication; bit 13 = UL3 undertorque 1; bit 14 = UL4 undertorque 2; bit 15 = Communication test fault | |||
| HR | 27doc 001Bh | Minor fault contents 3 | Alarms. | BITMAP16 | Read | bit 0 = OH3 motor overheat alarm; bit 1 = Drive not enabled | |||
| HR | 32doc 0020h | Inverter status (0020h) | BITMAP16 | Read | bit 0 = Run; bit 1 = Reverse direction; bit 2 = Inverter ready; bit 3 = Fault; bit 4 = Data setting error; bit 5 = Output 1 (M1-M2); bit 6 = Output 2 (M3-M4); bit 7 = Output 3 (M5-M6); bit 8 = Output 4 (P3-C3); bit 9 = Output 5 (P4-C4) | ||||
| HR | 33doc 0021h | Fault contents | Summary bits. | BITMAP16 | Read | bit 0 = OC or GF; bit 1 = OV; bit 2 = OL2; bit 3 = OH1 or OH2; bit 4 = RR or RH; bit 5 = PUF; bit 6 = FBL; bit 7 = EFx or EF0; bit 8 = CPF hardware; bit 9 = OL1, OL3 or OL4; bit 10 = PGO, OS or DEV; bit 11 = UV; bit 12 = UV1, UV2 or UV3; bit 13 = SPI or SPO phase loss; bit 14 = CE communication loss; bit 15 = OPR operator disconnected | |||
| HR | 34doc 0022h | Data link status | BITMAP16 | Read | bit 0 = Writing data; bit 3 = Upper or lower data limit error; bit 4 = Data integrity error | ||||
| HR | 35doc 0023h | Frequency reference monitor (U1-01) | Scaling follows o1-03. | UINT16 | Read | ||||
| HR | 36doc 0024h | Output frequency monitor (U1-02) | Scaling follows o1-03. | UINT16 | Read | ||||
| HR | 38doc 0026h | Output current monitor (U1-03) | UINT16 | × 0.01 | A | Read | |||
| HR | 43doc 002Bh | Digital input status | Terminals S1-S12 closed. | BITMAP16 | Read | bit 0 = S1 closed; bit 1 = S2 closed; bit 2 = S3 closed; bit 3 = S4 closed; bit 4 = S5 closed; bit 5 = S6 closed; bit 6 = S7 closed; bit 7 = S8 closed; bit 8 = S9 closed; bit 9 = S10 closed; bit 10 = S11 closed; bit 11 = S12 closed | |||
| HR | 44doc 002Ch | Inverter status (002Ch) | BITMAP16 | Read | bit 0 = During run 1; bit 1 = Zero speed; bit 2 = Speed agree 1; bit 3 = Fref/set speed agree 1; bit 4 = Frequency detection 1; bit 5 = Frequency detection 2; bit 6 = Inverter ready; bit 7 = Undervoltage; bit 8 = Baseblock; bit 9 = Frequency reference from digital operator; bit 10 = Run command from digital operator; bit 11 = Overtorque detection 1; bit 12 = Loss of frequency reference; bit 13 = During fault retry; bit 14 = Fault; bit 15 = Communication timeout (CE) | ||||
| HR | 45doc 002Dh | Digital output status | BITMAP16 | Read | bit 0 = Output 1 (M1-M2); bit 1 = Output 2 (M3-M4); bit 2 = Output 3 (M5-M6); bit 3 = Output 4 (P3-C3); bit 4 = Output 5 (P4-C4) | ||||
| HR | 49doc 0031h | Main circuit DC bus voltage (U1-07) | UINT16 | V | Read | ||||
| HR | 59doc 003Bh | Drive CPU number (U1-28) | Last 5 digits of CPU software number. | UINT16 | Read | ||||
| HR | 60doc 003Ch | Drive software number (U1-14) | Last 5 digits. | UINT16 | Read | ||||
| HR | 61doc 003Dh | Communication error | BITMAP16 | Read | bit 0 = CRC error; bit 1 = Invalid data length; bit 3 = Parity error; bit 4 = Overrun error; bit 5 = Framing error; bit 6 = Timeout | ||||
| HR | 62doc 003Eh | kVA setting | Same data as o2-04. | UINT16 | Read | ||||
| HR | 63doc 003Fh | Control mode (U1-04) | Range 0-4, see A1-02. | UINT16 | Read | ||||
| HR | 64doc 0040h | Frequency reference (U1-01) | Scaling follows o1-03. | UINT16 | Read | ||||
| HR | 65doc 0041h | Output frequency (U1-02) | Scaling follows o1-03. | UINT16 | Read | ||||
| HR | 66doc 0042h | Output current (U1-03) | UINT16 | × 0.1 | A | Read | |||
| HR | 69doc 0045h | Output voltage reference (U1-06) | UINT16 | × 0.1 | V | Read | |||
| HR | 70doc 0046h | DC bus voltage (U1-07) | UINT16 | V | Read | ||||
| HR | 73doc 0049h | Digital input terminal status (U1-10) | BITMAP16 | Read | bit 0 = S1; bit 1 = S2; bit 2 = S3; bit 3 = S4; bit 4 = S5; bit 5 = S6; bit 6 = S7; bit 7 = S8 | ||||
| HR | 74doc 004Ah | Digital output terminal status (U1-11) | BITMAP16 | Read | bit 0 = M1-M2; bit 1 = M3-M4; bit 2 = M5-M6; bit 3 = P3-C3; bit 4 = P4-C4; bit 7 = Fault output | ||||
| HR | 75doc 004Bh | Drive operation status (U1-12) | BITMAP16 | Read | bit 0 = Run; bit 1 = Zero speed; bit 2 = Reverse direction; bit 3 = Fault reset; bit 4 = Speed agree; bit 5 = Inverter ready; bit 6 = Minor fault (alarm); bit 7 = Major fault | ||||
| HR | 76doc 004Ch | Elapsed time (U1-13) | UINT16 | h | Read | ||||
| HR | 78doc 004Eh | Analog input A1 level (U1-15) | UINT16 | × 0.1 | % | Read | |||
| HR | 79doc 004Fh | Analog input A2 level (U1-16) | UINT16 | × 0.1 | % | Read | |||
| HR | 80doc 0050h | Analog input A3 level (U1-17) | UINT16 | × 0.1 | % | Read | |||
| HR | 83doc 0053h | Frequency reference after soft starter (U1-20) | UINT16 | × 0.01 | Hz | Read | |||
| HR | 92doc 005Ch | Accumulated kWh (U1-29) | UINT16 | kWh | Read | ||||
| HR | 93doc 005Dh | Accumulated MWh (U1-30) | UINT16 | MWh | Read | ||||
| HR | 97doc 0061h | First parameter causing OPE (U1-34) | Modbus address of the offending parameter. | UINT16 | Read | ||||
| HR | 102doc 0066h | Communication error code (U1-39) | BITMAP16 | Read | bit 0 = CRC error; bit 1 = Data length error; bit 3 = Parity error; bit 4 = Over-run error; bit 5 = Framing error; bit 6 = Timeout error | ||||
| HR | 103doc 0067h | Heatsink fan operation time (U1-40) | UINT16 | h | Read | ||||
| HR | 128doc 0080h | Current fault (U2-01) | UINT16 | Read | 1 = PUF DC bus fuse open; 2 = UV1 DC bus undervoltage; 3 = UV2 control PS undervoltage; 4 = UV3 MC answerback; 5 = SC short circuit; 6 = GF ground fault; 7 = OC overcurrent; 8 = OV DC bus overvoltage; 9 = OH heatsink overtemperature; 10 = OH1 heatsink max temperature; 11 = OL1 motor overload; 12 = OL2 inverter overload; 13 = OL3 overtorque detection 1; 14 = OL4 overtorque detection 2; 15 = RR braking transistor failure; 16 = RH braking resistor overheat; 17 = EF3 external fault S3; 18 = EF4 external fault S4; 19 = EF5 external fault S5; 20 = EF6 external fault S6; 21 = EF7 external fault S7; 22 = EF8 external fault S8; 24 = OS overspeed; 25 = DEV speed deviation; 26 = PGO encoder (PG) loss; 27 = PF input phase loss; 28 = LF output phase loss; 29 = OH3 motor overheat 1; 30 = OPR operator disconnected; 31 = ERR EEPROM read/write error; 32 = OH4 motor overheat 2; 33 = CE Modbus communication loss; 34 = BUS option communication error; 35 = E-15 SI-F/G communication error; 36 = E-10 SI-F/G communication loss; 37 = CF loss of motor control; 38 = SVE zero servo fault; 39 = EF0 option external fault; 40 = FBL PID feedback loss; 41 = UL3 undertorque detection 1; 42 = UL4 undertorque detection 2; 43 = OL7 high slip braking overload; 44 = EF9 external fault S9; 45 = EF10 external fault S10; 46 = EF11 external fault S11; 47 = EF12 external fault S12; 49 = VCN neutral point detection; 56 = PGOH encoder (PG) loss; 57 = E-5 SI-T communication loss; 58 = CF2 loss of motor control 2; 59 = SER speed search error; 60 = CFAL1 CASE fault 1; 61 = CFAL2 CASE fault 2; 62 = CFAL3 CASE fault 3; 63 = CFAL4 CASE fault 4; 64 = CFAL5 CASE fault 5 | ||||
| HR | 129doc 0081h | Previous fault (U2-02) | UINT16 | Read | 1 = PUF DC bus fuse open; 2 = UV1 DC bus undervoltage; 3 = UV2 control PS undervoltage; 4 = UV3 MC answerback; 5 = SC short circuit; 6 = GF ground fault; 7 = OC overcurrent; 8 = OV DC bus overvoltage; 9 = OH heatsink overtemperature; 10 = OH1 heatsink max temperature; 11 = OL1 motor overload; 12 = OL2 inverter overload; 13 = OL3 overtorque detection 1; 14 = OL4 overtorque detection 2; 15 = RR braking transistor failure; 16 = RH braking resistor overheat; 17 = EF3 external fault S3; 18 = EF4 external fault S4; 19 = EF5 external fault S5; 20 = EF6 external fault S6; 21 = EF7 external fault S7; 22 = EF8 external fault S8; 24 = OS overspeed; 25 = DEV speed deviation; 26 = PGO encoder (PG) loss; 27 = PF input phase loss; 28 = LF output phase loss; 29 = OH3 motor overheat 1; 30 = OPR operator disconnected; 31 = ERR EEPROM read/write error; 32 = OH4 motor overheat 2; 33 = CE Modbus communication loss; 34 = BUS option communication error; 35 = E-15 SI-F/G communication error; 36 = E-10 SI-F/G communication loss; 37 = CF loss of motor control; 38 = SVE zero servo fault; 39 = EF0 option external fault; 40 = FBL PID feedback loss; 41 = UL3 undertorque detection 1; 42 = UL4 undertorque detection 2; 43 = OL7 high slip braking overload; 44 = EF9 external fault S9; 45 = EF10 external fault S10; 46 = EF11 external fault S11; 47 = EF12 external fault S12; 49 = VCN neutral point detection; 56 = PGOH encoder (PG) loss; 57 = E-5 SI-T communication loss; 58 = CF2 loss of motor control 2; 59 = SER speed search error; 60 = CFAL1 CASE fault 1; 61 = CFAL2 CASE fault 2; 62 = CFAL3 CASE fault 3; 63 = CFAL4 CASE fault 4; 64 = CFAL5 CASE fault 5 | ||||
| HR | 130doc 0082h | Frequency reference at previous fault (U2-03) | UINT16 | × 0.01 | Hz | Read | |||
| HR | 131doc 0083h | Output frequency at previous fault (U2-04) | UINT16 | × 0.01 | Hz | Read | |||
| HR | 132doc 0084h | Output current at previous fault (U2-05) | UINT16 | × 0.1 | A | Read | |||
| HR | 134doc 0086h | Output voltage at previous fault (U2-07) | UINT16 | × 0.1 | V | Read | |||
| HR | 135doc 0087h | DC bus voltage at previous fault (U2-08) | UINT16 | V | Read | ||||
| HR | 141doc 008Dh | Elapsed time at previous fault (U2-14) | UINT16 | h | Read | ||||
| HR | 384doc 0180h | b1-01 Reference source | UINT16 | Read/write | 0 = Operator; 1 = Terminals; 2 = Modbus communication; 3 = Option card; 4 = Pulse input | ||||
| HR | 385doc 0181h | b1-02 Run source | UINT16 | Read/write | 0 = Operator; 1 = Terminals; 2 = Modbus communication; 3 = Option card | ||||
| HR | 1061doc 0425h | H5-01 Modbus node address | 0h-20h; default 1Fh. | UINT16 | Read/write | ||||
| HR | 1062doc 0426h | H5-02 Baud rate | UINT16 | Read/write | 0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200 | ||||
| HR | 1063doc 0427h | H5-03 Parity | UINT16 | Read/write | 0 = None; 1 = Even; 2 = Odd | ||||
| HR | 1064doc 0428h | H5-04 CE fault response | UINT16 | Read/write | 0 = Ramp to stop; 1 = Coast to stop; 2 = Fast-stop (C1-09); 3 = Alarm only | ||||
| HR | 1065doc 0429h | H5-05 CE fault detection | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 1066doc 042Ah | H5-06 Transmit wait time | 5-65 ms. | UINT16 | ms | Read/write | |||
| HR | 1067doc 042Bh | H5-07 RTS control | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 1078doc 0436h | H5-10 Unit for register 0025h | UINT16 | Read/write | 0 = 0.1 V; 1 = 1 V | ||||
| HR | 2048doc 0800h | Most recent fault (U3-01) | UINT16 | Read | 1 = PUF DC bus fuse open; 2 = UV1 DC bus undervoltage; 3 = UV2 control PS undervoltage; 4 = UV3 MC answerback; 5 = SC short circuit; 6 = GF ground fault; 7 = OC overcurrent; 8 = OV DC bus overvoltage; 9 = OH heatsink overtemperature; 10 = OH1 heatsink max temperature; 11 = OL1 motor overload; 12 = OL2 inverter overload; 13 = OL3 overtorque detection 1; 14 = OL4 overtorque detection 2; 15 = RR braking transistor failure; 16 = RH braking resistor overheat; 17 = EF3 external fault S3; 18 = EF4 external fault S4; 19 = EF5 external fault S5; 20 = EF6 external fault S6; 21 = EF7 external fault S7; 22 = EF8 external fault S8; 24 = OS overspeed; 25 = DEV speed deviation; 26 = PGO encoder (PG) loss; 27 = PF input phase loss; 28 = LF output phase loss; 29 = OH3 motor overheat 1; 30 = OPR operator disconnected; 31 = ERR EEPROM read/write error; 32 = OH4 motor overheat 2; 33 = CE Modbus communication loss; 34 = BUS option communication error; 35 = E-15 SI-F/G communication error; 36 = E-10 SI-F/G communication loss; 37 = CF loss of motor control; 38 = SVE zero servo fault; 39 = EF0 option external fault; 40 = FBL PID feedback loss; 41 = UL3 undertorque detection 1; 42 = UL4 undertorque detection 2; 43 = OL7 high slip braking overload; 44 = EF9 external fault S9; 45 = EF10 external fault S10; 46 = EF11 external fault S11; 47 = EF12 external fault S12; 49 = VCN neutral point detection; 56 = PGOH encoder (PG) loss; 57 = E-5 SI-T communication loss; 58 = CF2 loss of motor control 2; 59 = SER speed search error; 60 = CFAL1 CASE fault 1; 61 = CFAL2 CASE fault 2; 62 = CFAL3 CASE fault 3; 63 = CFAL4 CASE fault 4; 64 = CFAL5 CASE fault 5 | ||||
| HR | 2049doc 0801h | 2nd most recent fault (U3-02) | UINT16 | Read | 1 = PUF DC bus fuse open; 2 = UV1 DC bus undervoltage; 3 = UV2 control PS undervoltage; 4 = UV3 MC answerback; 5 = SC short circuit; 6 = GF ground fault; 7 = OC overcurrent; 8 = OV DC bus overvoltage; 9 = OH heatsink overtemperature; 10 = OH1 heatsink max temperature; 11 = OL1 motor overload; 12 = OL2 inverter overload; 13 = OL3 overtorque detection 1; 14 = OL4 overtorque detection 2; 15 = RR braking transistor failure; 16 = RH braking resistor overheat; 17 = EF3 external fault S3; 18 = EF4 external fault S4; 19 = EF5 external fault S5; 20 = EF6 external fault S6; 21 = EF7 external fault S7; 22 = EF8 external fault S8; 24 = OS overspeed; 25 = DEV speed deviation; 26 = PGO encoder (PG) loss; 27 = PF input phase loss; 28 = LF output phase loss; 29 = OH3 motor overheat 1; 30 = OPR operator disconnected; 31 = ERR EEPROM read/write error; 32 = OH4 motor overheat 2; 33 = CE Modbus communication loss; 34 = BUS option communication error; 35 = E-15 SI-F/G communication error; 36 = E-10 SI-F/G communication loss; 37 = CF loss of motor control; 38 = SVE zero servo fault; 39 = EF0 option external fault; 40 = FBL PID feedback loss; 41 = UL3 undertorque detection 1; 42 = UL4 undertorque detection 2; 43 = OL7 high slip braking overload; 44 = EF9 external fault S9; 45 = EF10 external fault S10; 46 = EF11 external fault S11; 47 = EF12 external fault S12; 49 = VCN neutral point detection; 56 = PGOH encoder (PG) loss; 57 = E-5 SI-T communication loss; 58 = CF2 loss of motor control 2; 59 = SER speed search error; 60 = CFAL1 CASE fault 1; 61 = CFAL2 CASE fault 2; 62 = CFAL3 CASE fault 3; 63 = CFAL4 CASE fault 4; 64 = CFAL5 CASE fault 5 | ||||
| HR | 2050doc 0802h | 3rd most recent fault (U3-03) | UINT16 | Read | 1 = PUF DC bus fuse open; 2 = UV1 DC bus undervoltage; 3 = UV2 control PS undervoltage; 4 = UV3 MC answerback; 5 = SC short circuit; 6 = GF ground fault; 7 = OC overcurrent; 8 = OV DC bus overvoltage; 9 = OH heatsink overtemperature; 10 = OH1 heatsink max temperature; 11 = OL1 motor overload; 12 = OL2 inverter overload; 13 = OL3 overtorque detection 1; 14 = OL4 overtorque detection 2; 15 = RR braking transistor failure; 16 = RH braking resistor overheat; 17 = EF3 external fault S3; 18 = EF4 external fault S4; 19 = EF5 external fault S5; 20 = EF6 external fault S6; 21 = EF7 external fault S7; 22 = EF8 external fault S8; 24 = OS overspeed; 25 = DEV speed deviation; 26 = PGO encoder (PG) loss; 27 = PF input phase loss; 28 = LF output phase loss; 29 = OH3 motor overheat 1; 30 = OPR operator disconnected; 31 = ERR EEPROM read/write error; 32 = OH4 motor overheat 2; 33 = CE Modbus communication loss; 34 = BUS option communication error; 35 = E-15 SI-F/G communication error; 36 = E-10 SI-F/G communication loss; 37 = CF loss of motor control; 38 = SVE zero servo fault; 39 = EF0 option external fault; 40 = FBL PID feedback loss; 41 = UL3 undertorque detection 1; 42 = UL4 undertorque detection 2; 43 = OL7 high slip braking overload; 44 = EF9 external fault S9; 45 = EF10 external fault S10; 46 = EF11 external fault S11; 47 = EF12 external fault S12; 49 = VCN neutral point detection; 56 = PGOH encoder (PG) loss; 57 = E-5 SI-T communication loss; 58 = CF2 loss of motor control 2; 59 = SER speed search error; 60 = CFAL1 CASE fault 1; 61 = CFAL2 CASE fault 2; 62 = CFAL3 CASE fault 3; 63 = CFAL4 CASE fault 4; 64 = CFAL5 CASE fault 5 | ||||
| HR | 2051doc 0803h | 4th most recent fault (U3-04) | UINT16 | Read | 1 = PUF DC bus fuse open; 2 = UV1 DC bus undervoltage; 3 = UV2 control PS undervoltage; 4 = UV3 MC answerback; 5 = SC short circuit; 6 = GF ground fault; 7 = OC overcurrent; 8 = OV DC bus overvoltage; 9 = OH heatsink overtemperature; 10 = OH1 heatsink max temperature; 11 = OL1 motor overload; 12 = OL2 inverter overload; 13 = OL3 overtorque detection 1; 14 = OL4 overtorque detection 2; 15 = RR braking transistor failure; 16 = RH braking resistor overheat; 17 = EF3 external fault S3; 18 = EF4 external fault S4; 19 = EF5 external fault S5; 20 = EF6 external fault S6; 21 = EF7 external fault S7; 22 = EF8 external fault S8; 24 = OS overspeed; 25 = DEV speed deviation; 26 = PGO encoder (PG) loss; 27 = PF input phase loss; 28 = LF output phase loss; 29 = OH3 motor overheat 1; 30 = OPR operator disconnected; 31 = ERR EEPROM read/write error; 32 = OH4 motor overheat 2; 33 = CE Modbus communication loss; 34 = BUS option communication error; 35 = E-15 SI-F/G communication error; 36 = E-10 SI-F/G communication loss; 37 = CF loss of motor control; 38 = SVE zero servo fault; 39 = EF0 option external fault; 40 = FBL PID feedback loss; 41 = UL3 undertorque detection 1; 42 = UL4 undertorque detection 2; 43 = OL7 high slip braking overload; 44 = EF9 external fault S9; 45 = EF10 external fault S10; 46 = EF11 external fault S11; 47 = EF12 external fault S12; 49 = VCN neutral point detection; 56 = PGOH encoder (PG) loss; 57 = E-5 SI-T communication loss; 58 = CF2 loss of motor control 2; 59 = SER speed search error; 60 = CFAL1 CASE fault 1; 61 = CFAL2 CASE fault 2; 62 = CFAL3 CASE fault 3; 63 = CFAL4 CASE fault 4; 64 = CFAL5 CASE fault 5 | ||||
| HR | 2058doc 080Ah | Elapsed time at most recent fault (U3-05) | UINT16 | h | Read | ||||
| HR | 2304doc 900 | ENTER | Write 0 to store off-line parameter data in EEPROM (about 100,000 writes). | UINT16 | Write | ||||
| HR | 2320doc 910 | ACCEPT | Write 0 to activate off-line parameter data in RAM. | UINT16 | Write |
Notes on this map
- Frequency and speed monitors (0023h, 0024h, 0040h, 0041h, 0044h) scale with o1-03 and are left raw.
- Output current is 0.01 A at 0026h but 0.1 A at 0042h, exactly as printed in Table 4.3.
- Left out because the sign is not stated: output power (0027h, 0033h, 0047h), torque reference (0028h, 0048h), Iq/Id (0032h, 0051h, 0052h), PID levels and PID input/output (0038h-003Ah, 0063h-0065h), ASR and ACR monitors. 0025h output voltage reference is omitted because its unit switches with H5-10.
- Fault values for U2-01/U2-02/U3-xx are the decimal codes of Table 4.17 (e.g. 33 = CE).
- The command registers here differ from those of the CM090 Modbus TCP/IP option card, which is not covered.
- Broadcast (slave 0) uses 0001h and 0002h only; see the manual's Table 4.2.
- 8 data bits and 1 stop bit for RS-422/485 come from the free G7 user manual TM.G7.01 (https://www.yaskawa.com/delegate/getAttachment?documentId=TM.G7.01&cmd=documents&documentName=TM.G7.01.pdf); TM.G7.11 states them only for the RS-232 port.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU
What Modbus registers does the Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU have?
This map lists 76 registers: 76 holding registers. 19 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. All addresses are hex and sent unchanged: the manual's read example uses starting register 00h 20h to read 0020h-0023h. Parameter addresses are the hex values in the parameter tables (b1-01 = 0180h, H5-01 = 0425h); ENTER/ACCEPT are printed as 900/910 (0900h/0910h).
What are the minimum Modbus registers to integrate the Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU?
Start with HR 1 Digital input command (Run/stop, direction, reset); HR 2 Frequency reference setpoint (Frequency reference); HR 32 Inverter status (0020h) (Run/fault status); HR 33 Fault contents (Fault summary); HR 44 Inverter status (002Ch) (Status incl. comm timeout); HR 65 Output frequency (U1-02) (Output frequency); HR 66 Output current (U1-03) (Output current); HR 128 Current fault (U2-01) (Current fault code).
How do I enable Modbus control of the Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU?
H5-01 node address (default 1Fh, 0h-20h), H5-02 baud (default 3 = 9600), H5-03 parity (default none); cycle power. b1-01 = 2 and b1-02 = 2 select Modbus for reference and run (or set 0001h bits 4/5).
What happens when the Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU loses Modbus communication?
H5-05 = 1 (default) enables CE detection; H5-04 selects the response: 0 ramp, 1 coast, 2 fast-stop, 3 alarm only (default). 002Ch bit F shows a comm timeout.
Where is the official Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU Modbus documentation?
The source is Modbus Communication Manual G7 (TM.G7.11 Rev 07-01), revision 2007-01-05, published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=TM.G7.11&cmd=documents&documentName=TM.G7.11.pdf.
More Yaskawa Modbus register maps
- Variable frequency drive
Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa A1000 drives (CIMR-AU; 200 V, 400 V and 600 V classes) using the built-in RS-422/485 MEMOBUS/Modbus terminals (TB5), per Technical Manual SIEP C710616 41H.
Also known as: CIMR-AU, CIMR-AUA, A1000 High Performance Vector Control Drive - Variable frequency drive (HVAC)
Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU
Yaskawa E7 (CIMR-E7U) HVAC fan and pump drives using the built-in RS-422/485 terminals with H5-08 = 0 (Memobus/Modbus), per Parameter Access Technical Manual TM.E7.11 (rev 3016).
Also known as: CIMR-E7U, E7U, E7 Drive - Variable frequency drive
Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU
Yaskawa F7 (CIMR-F7U) general-purpose drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.F7.01 Appendix D, with parameter and monitor addresses from TM.F7.11.
Also known as: CIMR-F7U, F7U, F7 Drive - Variable frequency drive
Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU)
Yaskawa FP605 enclosed bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (MEMOBUS/Modbus); Technical Reference SIEPYAIF6B01C, section 10.6.
Also known as: FP605 Enclosed Bypass, FP605 bypass package - Variable frequency drive
Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa FP605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per technical reference SIEPC7106171F.
Also known as: CIPR-FP6, FP605 drive, FP605 AC Drive for Industrial Fan and Pump Applications - Variable frequency drive
Yaskawa GA500 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA500 drives using the built-in RS-485 MEMOBUS/Modbus port (terminal TB4), per technical reference SIEPC71061752 revision C.
Also known as: CIPR-GA50U, GA500 Versatile Compact - Variable frequency drive
Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA800 drives using the built-in RS-485 MEMOBUS/Modbus port, per technical reference SIEPC71061737 revision G.
Also known as: CIPR-GA80, GA800 Industrial AC Microdrive - Variable frequency drive
Yaskawa HV305 HVAC micro drive (MEMOBUS/Modbus RTU)
Yaskawa HV305 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPYAIHV3001B.
Also known as: HV35U, HV305 drive, HV305 Versatile Compact Drive - Variable frequency drive
Yaskawa HV600 HVAC fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa HV600 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPC71061732 revision F.
Also known as: CIPR-HV60, HV600 HVAC drive - Variable frequency drive (HVAC bypass package)
Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)
Yaskawa HV600 Narrow and Enclosed Bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (Modbus); Technical Reference SIEPYAIH6B01F, section 10.6.
Also known as: HV600 Bypass, HV600 Enclosed Bypass, HV600 Narrow Bypass - Variable frequency drive (pump)
Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU
Legacy Yaskawa iQpump drives built on the P7U platform (CIMR-P7U...), per user manual TM.iQp.01, using the built-in RS-422/485 terminals R+/R-/S+/S-.
Also known as: iQpump, CIMR-P7U iQpump, iQpump Drive - Variable frequency drive
Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump Micro drives using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEP YAIQPM 03B.
Also known as: CIMR-PW (iQpump Micro), iQpump Micro AC Drive, iQpump Micro Compact Intelligent Pump Controller - Variable frequency drive
Yaskawa iQpump1000 intelligent pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump1000 drives (CIMR-PW) using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEPYAIP1W01G.
Also known as: CIMR-PW, CIMR-PWA, iQpump1000 AC Drive - Variable frequency drive
Yaskawa iQpump605 intelligent pump controller (MEMOBUS/Modbus RTU)
Yaskawa iQpump605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per user manual SIEPYAIWM6502D.
Also known as: WM65W, iQpump605 drive, iQpump605 Intelligent Pump Controller - Variable frequency drive
Yaskawa J1000 compact V/f drive (MEMOBUS/Modbus RTU)
Yaskawa J1000 drives (CIMR-JU/JC) with the optional RS-422/485 MEMOBUS/Modbus interface, per Technical Manual SIEP C710606 31D.
Also known as: CIMR-JU, CIMR-JC, J1000 Compact V/f Control Drive - Variable frequency drive (HVAC bypass package)
Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU)
P1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIP1B 01D, appendix D.
Also known as: P1000 Bypass, P1B - Variable frequency drive
Yaskawa P1000 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa P1000 drives using the built-in RS-485/422 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP YAIP1U 01C.
Also known as: CIMR-PU, P1000 Industrial Fan and Pump Drive - Variable frequency drive (fan / pump)
Yaskawa P7 fan/pump drive (CIMR-P7U, legacy) - Modbus RTU
Yaskawa P7 (CIMR-P7U) fan and pump drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.P7.01 Appendix D.
Also known as: CIMR-P7U, P7U, P7 Drive - Variable frequency drive (fan / pump bypass package)
Yaskawa P7B drive/bypass (legacy) - Modbus RTU
Yaskawa P7B drive/bypass packages (P7 drive CIMR-P7U inside a bypass enclosure, option V native Modbus) using the drive's RS-422/485 terminals, per technical manual TM.P7B.01 Appendix D.
Also known as: P7B, P7 Bypass - Variable frequency drive
Yaskawa U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU)
Yaskawa U1000 matrix drives using the built-in RS-422/485 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP C710636 04E.
Also known as: CIMR-UU, U1000 Industrial MATRIX Drive - Variable frequency drive
Yaskawa V1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa V1000 drives (CIMR-VU; 200 V single/three-phase and 400 V three-phase, 0.1-18.5 kW) using the built-in RS-422/485 MEMOBUS/Modbus terminals, per Technical Manual SIEP C710606 18F.
Also known as: CIMR-VU, V1000 Compact Vector Control Drive - Variable frequency drive
Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU
Yaskawa V7 (CIMR-V7AM) and V74X (CIMR-V7CU) compact drives with built-in Modbus RTU (keypad RJ-45 or R+/R-/S+/S- terminals), per TM.V7.11 Rev 07-01.
Also known as: CIMR-V7AM, CIMR-V7CU, V74X - Variable frequency drive (HVAC bypass package)
Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU)
Z1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIZ1B 01F, appendix D.
Also known as: Z1000 Bypass, Z1B1 - Variable frequency drive (HVAC fan / pump)
Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000 HVAC drives (CIMR-ZU) using the built-in RS-485 terminals with H5-08 = 0, per Programming Manual SIEP YAIZ1U 03C (the copy covers the 600 V class models 5A0007-5A0242).
Also known as: CIMR-ZU, Z1000 AC Drive for HVAC Fan and Pump - Variable frequency drive
Yaskawa Z1000U HVAC matrix drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000U HVAC matrix drives using the built-in serial terminals with H5-08 = 0 (MEMOBUS/Modbus), per programming manual SIEP C710636 10D.
Also known as: Z1000U HVAC MATRIX Drive, Z1000U Matrix
Other variable frequency drives register maps
- Variable frequency drive
ABB ACH480 HVAC drive (embedded Modbus RTU)
ACH480 drives running the ACH480 HVAC control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000247134 Rev E.
Also known as: ACH480-04, ACH480 HVAC control program - Variable frequency drive
ABB ACS380 machinery drive (embedded Modbus RTU)
ACS380 drives running the machinery control program with the BMIO-01 I/O and Modbus RTU module, embedded fieldbus (EFB), addressing mode 0 (default); firmware manual 3AXD50000029275 Rev J.
Also known as: ACS380-04, ACS380 machinery control program, BMIO-01 - Pump (vertical in-line with integrated VFD)
Armstrong Fluid Technology Design Envelope 4300 / 4380 with DEPM IVS / DE IVS drive (map v2)
Armstrong Design Envelope 4300 and 4380 vertical in-line pumps with DEPM IVS or DE IVS drive, controller firmware v1.17 and newer (Modbus register map version 2).
Also known as: Design Envelope 4300, Design Envelope 4380, DEPM IVS, DE IVS, Design Envelope pump controller, DEPC - Variable frequency drive
Bonfiglioli Agile frequency inverter (Modbus RTU/ASCII)
Bonfiglioli Agile 230 V / 400 V frequency inverters, Modbus on the X21 RJ45 connection or a CM-232/CM-485 module, per Modbus communication manual VEC 691 R1 (02/2011).
Also known as: Agile, AGL, Bonfiglioli Agile - Variable frequency drive
Danfoss VLT HVAC Drive FC 102 (Modbus RTU)
VLT HVAC Drive FC 102 using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter scaling checked against the software 7.61 programming guide.
Also known as: VLT HVAC Drive, FC102, FC-102 - Variable frequency drive
Eaton PowerXL DC1 compact drive (Modbus RTU)
Eaton PowerXL DC1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DC1, PowerXL DC1, DC1-1D, DC1-12, DC1-32, DC1-34, DC1-S2
All variable frequency drives Modbus register maps →
Source: Modbus Communication Manual G7 · TM.G7.11 Rev 07-01 · rev. 2007-01-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.