- V7 / V74X compact drive (legacy) - Modbus RTU
Variable frequency drive · Modbus register map
Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU Modbus register map
Updated 17 November 2026
The V7 and its NEMA 4X twin V74X are Yaskawa's legacy compact drives with built-in Modbus RTU. Commands go to hex registers 0001h, 0002h and 0009h, status, fault and monitors are read from 0020h-003Dh, and parameters n001-n179 sit at 0101h-01B3h. This map covers the command and monitor registers with published units, and the run/reference source and Modbus setup parameters.
This page lists 26 Modbus registers for the Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yaskawa’s own free documentation (linked below) and checked against it.
- Manufacturer
- Yaskawa
- Model
- V7 / V74X compact drive (legacy) - Modbus RTU
- Equipment type
- Variable frequency drive
- Registers
- 26 (14 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- CIMR-V7AM, CIMR-V7CU, V74X
Integration notes: Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU
Set n153 (address), n154 (baud) and n155 (parity), then n003 = 2 and n004 = 6 to take run and reference from Modbus. Write 0001h/0002h and poll 0020h-0031h.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1 | Digital input command | BITMAP16 | Run/stop, direction, reset | Read/write |
| HR 2 | Frequency reference | UINT16 | Frequency reference | Read/write |
| HR 32 | Status signal 1 | BITMAP16 | Run/ready/fault | Read |
| HR 33 | Fault content 1 | BITMAP16 | Fault content | Read |
| HR 36 | Output frequency (U-02) | UINT16 | Output frequency | Read |
| HR 39 | Output current (U-03) | UINT16 | Output current | Read |
| HR 44 | Status signal 2 | BITMAP16 | Status incl. comm timeout | Read |
Enable Modbus control & writes
n153 slave address 1-31 (default 0), n154 baud (default 2 = 9600), n155 parity (default 2 = none). n003 = 2 and n004 = 6 select built-in Modbus RTU for run/stop and frequency reference. n157 = 0 for 2-wire RS-485.
Communication loss & watchdog
n151 selects the time-out response: 0 coast (default), 1 ramp with n020, 2 ramp with n022, 3 continue with alarm, 4 disabled. 002Ch bit F shows a communication timeout.
Byte order & addressing
- Registers and addresses are hex.
- 1-8 registers per 03h read.
- Parameter writes (0101h-01B3h) go to an off-line area until 0 is written to 0910h (ACCEPT) or 0900h (ENTER, about 100,000 writes).
- Network digital inputs are ORed with the physical terminals.
Network setup
- Modbus is available on the keypad RJ-45 jack or the R+/R-/S+/S- terminals.
- Slave address 1-20h (1-32) per the protocol chapter; n153 accepts 0-31.
- Baud 2400-19200.
Watch out for
- Factory default n153 = 0 means the drive does not answer reads until an address is set.
Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 0001h | Digital input command | Run, direction, external fault, reset, network inputs S1-S7. | BITMAP16 | Read/write | bit 0 = Run command (0 stop, 1 run); bit 1 = Reverse (0 forward, 1 reverse); bit 2 = External fault; bit 3 = Fault reset; bit 4 = Terminal S1 (n050); bit 5 = Terminal S2 (n051); bit 6 = Terminal S3 (n052); bit 7 = Terminal S4 (n053); bit 8 = Terminal S5 (n054); bit 9 = Terminal S6 (n055); bit 10 = Terminal S7 (n056) | |||
| HR | 2doc 0002h | Frequency reference | Unit set by n152 (0.1 Hz default). | UINT16 | Read/write | ||||
| HR | 9doc 0009h | Digital output command | BITMAP16 | Read/write | bit 0 = Output MA/MB/MC; bit 1 = Output P1-PC; bit 2 = Output P2-PC | ||||
| HR | 32doc 0020h | Status signal 1 | BITMAP16 | Read | bit 0 = During run; bit 1 = Reverse direction; bit 2 = Inverter ready; bit 3 = Fault; bit 4 = Data set error; bit 5 = Output MA-MC closed; bit 6 = Output P1-PC closed; bit 7 = Output P2-PC closed | ||||
| HR | 33doc 0021h | Fault content 1 | BITMAP16 | Read | bit 0 = Overcurrent (OC); bit 1 = Overvoltage (OV); bit 2 = Inverter overload (OL2); bit 3 = Inverter overheat (OH); bit 6 = PID feedback (FbL); bit 7 = External fault (EF, EF0) or emergency stop (STP); bit 8 = Hardware fault (Fxx); bit 9 = Motor overload (OL1); bit 10 = Overtorque detection; bit 11 = Undertorque detection; bit 12 = Undervoltage (UV1); bit 13 = Control power supply fault (UV2); bit 14 = Modbus communications timeout (CE); bit 15 = Operator connection fault (oPA) | ||||
| HR | 34doc 0022h | Data link status | BITMAP16 | Read | bit 0 = During data write; bit 3 = Limit fault; bit 4 = Matching fault | ||||
| HR | 35doc 0023h | Frequency reference (U-01) | Unit set by n152. | UINT16 | Read | ||||
| HR | 36doc 0024h | Output frequency (U-02) | Unit set by n152. | UINT16 | Read | ||||
| HR | 39doc 0027h | Output current (U-03) | UINT16 | × 0.1 | A | Read | |||
| HR | 40doc 0028h | Output voltage (U-04) | UINT16 | V | Read | ||||
| HR | 43doc 002Bh | Digital input status | Terminals S1-S7 closed. | BITMAP16 | Read | bit 0 = S1 closed; bit 1 = S2 closed; bit 2 = S3 closed; bit 3 = S4 closed; bit 4 = S5 closed; bit 5 = S6 closed; bit 6 = S7 closed | |||
| HR | 44doc 002Ch | Status signal 2 | BITMAP16 | Read | bit 0 = During run; bit 1 = Zero speed; bit 2 = Speed agree; bit 3 = Alarm; bit 4 = Frequency detection 1; bit 5 = Frequency detection 2; bit 6 = Inverter ready; bit 7 = Undervoltage detection; bit 8 = Baseblock; bit 9 = Frequency reference source (0 network, 1 n004); bit 10 = Run command source (0 network, 1 n003); bit 11 = Overtorque detection; bit 12 = Undertorque detection; bit 13 = Fault retry; bit 14 = Fault; bit 15 = Communication timeout | ||||
| HR | 45doc 002Dh | Digital output status | BITMAP16 | Read | bit 0 = MA-MC closed; bit 1 = P1-PC closed; bit 2 = P2-PC closed | ||||
| HR | 49doc 0031h | DC bus voltage (U-05) | UINT16 | V | Read | ||||
| HR | 61doc 003Dh | Modbus error | BITMAP16 | Read | bit 0 = CRC error; bit 1 = Data length error; bit 3 = Parity error; bit 4 = Overrun error; bit 5 = Framing error; bit 6 = Timeout | ||||
| HR | 259doc 0103h | n003 Run/stop source | UINT16 | Read/write | 0 = Keypad; 1 = Terminal strip; 2 = Built-in Modbus RTU; 3 = Option card | ||||
| HR | 260doc 0104h | n004 Frequency reference source | UINT16 | Read/write | 0 = Keypad potentiometer; 1 = Frequency reference 1 (n024); 2 = 0-10 V (FR); 3 = 4-20 mA (FR); 4 = 0-20 mA (FR); 5 = Pulse train (RP); 6 = Built-in Modbus RTU; 7 = Multi-function analog input 0-10 V (keypad CN2); 8 = Multi-function analog input 4-20 mA (keypad CN2); 9 = Option card | ||||
| HR | 407doc 0197h | n151 Modbus time-out detection | UINT16 | Read/write | 0 = Coast to stop; 1 = Ramp to stop (n020); 2 = Ramp to stop (n022); 3 = Continue with alarm; 4 = Disabled | ||||
| HR | 408doc 0198h | n152 Frequency reference unit | Applies to 0002h, 0023h, 0024h. | UINT16 | Read/write | 0 = 1 = 0.1 Hz; 1 = 1 = 0.01 Hz; 2 = 30000 = n011 (max frequency); 3 = 1 = 0.1 % | |||
| HR | 409doc 0199h | n153 Modbus RTU slave address | 0-31 decimal. | UINT16 | Read/write | ||||
| HR | 410doc 019Ah | n154 Modbus RTU baud rate | UINT16 | Read/write | 0 = 2400; 1 = 4800; 2 = 9600; 3 = 19200 | ||||
| HR | 411doc 019Bh | n155 Modbus RTU parity | UINT16 | Read/write | 0 = Even; 1 = Odd; 2 = None | ||||
| HR | 412doc 019Ch | n156 Modbus RTU send delay | 0-65 ms. | UINT16 | ms | Read/write | |||
| HR | 413doc 019Dh | n157 Modbus RTU RTS control | UINT16 | Read/write | 0 = Enabled (RS-485 2-wire); 1 = Disabled (RS-422 / RS-485 4-wire) | ||||
| HR | 2304doc 900 | ENTER | Write 0 to store off-line parameter data in EEPROM (about 100,000 writes). | UINT16 | Write | ||||
| HR | 2320doc 910 | ACCEPT | Write 0 to activate off-line parameter data in RAM. | UINT16 | Write |
Notes on this map
- n153 defaults to 0, so a factory-fresh drive has no valid Modbus slave address; set n153 to 1-31 first. The defaults block shows the printed parameter defaults (n153 = 0, n154 = 2 = 9600, n155 = 2 = none).
- Left out because the sign is not stated: 002Fh frequency reference bias, 0032h torque monitor, 0037h output power, 0038h-003Ah PID feedback/input/output.
- Frequency registers follow n152 (default 0 = 0.1 Hz) and are left unscaled.
- The CM091/CM092 Modbus TCP/IP option card uses a different command layout (Table 4.5) that is not covered here.
- Broadcast (slave 0): 0001h bit 0 run, bit 1 reverse, bit 4 external fault, bit 5 fault reset; 0002h fixed at 30000 = 100 % of n011.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU
What Modbus registers does the Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU have?
This map lists 26 registers: 26 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are hex and go on the wire unchanged: the read example asks for starting register 00h 20h (0020h-0023h). Parameter nXXX lives at its hex address in Table 4.4 (n003 = 0103h, n153 = 0199h); ENTER/ACCEPT are printed as 900/910.
What are the minimum Modbus registers to integrate the Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU?
Start with HR 1 Digital input command (Run/stop, direction, reset); HR 2 Frequency reference (Frequency reference); HR 32 Status signal 1 (Run/ready/fault); HR 33 Fault content 1 (Fault content); HR 36 Output frequency (U-02) (Output frequency); HR 39 Output current (U-03) (Output current); HR 44 Status signal 2 (Status incl. comm timeout).
How do I enable Modbus control of the Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU?
n153 slave address 1-31 (default 0), n154 baud (default 2 = 9600), n155 parity (default 2 = none). n003 = 2 and n004 = 6 select built-in Modbus RTU for run/stop and frequency reference. n157 = 0 for 2-wire RS-485.
What happens when the Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU loses Modbus communication?
n151 selects the time-out response: 0 coast (default), 1 ramp with n020, 2 ramp with n022, 3 continue with alarm, 4 disabled. 002Ch bit F shows a communication timeout.
Where is the official Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU Modbus documentation?
The source is Modbus Communication Manual V7 and V74X Drives (TM.V7.11 Rev 07-01), revision 2007-01-05, published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=TM.V7.11&cmd=documents&documentName=TM.V7.11.pdf.
More Yaskawa Modbus register maps
- Variable frequency drive
Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa A1000 drives (CIMR-AU; 200 V, 400 V and 600 V classes) using the built-in RS-422/485 MEMOBUS/Modbus terminals (TB5), per Technical Manual SIEP C710616 41H.
Also known as: CIMR-AU, CIMR-AUA, A1000 High Performance Vector Control Drive - Variable frequency drive (HVAC)
Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU
Yaskawa E7 (CIMR-E7U) HVAC fan and pump drives using the built-in RS-422/485 terminals with H5-08 = 0 (Memobus/Modbus), per Parameter Access Technical Manual TM.E7.11 (rev 3016).
Also known as: CIMR-E7U, E7U, E7 Drive - Variable frequency drive
Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU
Yaskawa F7 (CIMR-F7U) general-purpose drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.F7.01 Appendix D, with parameter and monitor addresses from TM.F7.11.
Also known as: CIMR-F7U, F7U, F7 Drive - Variable frequency drive
Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU)
Yaskawa FP605 enclosed bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (MEMOBUS/Modbus); Technical Reference SIEPYAIF6B01C, section 10.6.
Also known as: FP605 Enclosed Bypass, FP605 bypass package - Variable frequency drive
Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa FP605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per technical reference SIEPC7106171F.
Also known as: CIPR-FP6, FP605 drive, FP605 AC Drive for Industrial Fan and Pump Applications - Variable frequency drive
Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU
Yaskawa G7 (CIMR-G7U) drives using built-in Modbus RTU on terminals R+/R-/S+/S-, per the Modbus Communication Manual G7 TM.G7.11 (rev 07-01).
Also known as: CIMR-G7U, G7U, G7 Drive - Variable frequency drive
Yaskawa GA500 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA500 drives using the built-in RS-485 MEMOBUS/Modbus port (terminal TB4), per technical reference SIEPC71061752 revision C.
Also known as: CIPR-GA50U, GA500 Versatile Compact - Variable frequency drive
Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA800 drives using the built-in RS-485 MEMOBUS/Modbus port, per technical reference SIEPC71061737 revision G.
Also known as: CIPR-GA80, GA800 Industrial AC Microdrive - Variable frequency drive
Yaskawa HV305 HVAC micro drive (MEMOBUS/Modbus RTU)
Yaskawa HV305 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPYAIHV3001B.
Also known as: HV35U, HV305 drive, HV305 Versatile Compact Drive - Variable frequency drive
Yaskawa HV600 HVAC fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa HV600 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPC71061732 revision F.
Also known as: CIPR-HV60, HV600 HVAC drive - Variable frequency drive (HVAC bypass package)
Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)
Yaskawa HV600 Narrow and Enclosed Bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (Modbus); Technical Reference SIEPYAIH6B01F, section 10.6.
Also known as: HV600 Bypass, HV600 Enclosed Bypass, HV600 Narrow Bypass - Variable frequency drive (pump)
Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU
Legacy Yaskawa iQpump drives built on the P7U platform (CIMR-P7U...), per user manual TM.iQp.01, using the built-in RS-422/485 terminals R+/R-/S+/S-.
Also known as: iQpump, CIMR-P7U iQpump, iQpump Drive - Variable frequency drive
Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump Micro drives using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEP YAIQPM 03B.
Also known as: CIMR-PW (iQpump Micro), iQpump Micro AC Drive, iQpump Micro Compact Intelligent Pump Controller - Variable frequency drive
Yaskawa iQpump1000 intelligent pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump1000 drives (CIMR-PW) using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEPYAIP1W01G.
Also known as: CIMR-PW, CIMR-PWA, iQpump1000 AC Drive - Variable frequency drive
Yaskawa iQpump605 intelligent pump controller (MEMOBUS/Modbus RTU)
Yaskawa iQpump605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per user manual SIEPYAIWM6502D.
Also known as: WM65W, iQpump605 drive, iQpump605 Intelligent Pump Controller - Variable frequency drive
Yaskawa J1000 compact V/f drive (MEMOBUS/Modbus RTU)
Yaskawa J1000 drives (CIMR-JU/JC) with the optional RS-422/485 MEMOBUS/Modbus interface, per Technical Manual SIEP C710606 31D.
Also known as: CIMR-JU, CIMR-JC, J1000 Compact V/f Control Drive - Variable frequency drive (HVAC bypass package)
Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU)
P1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIP1B 01D, appendix D.
Also known as: P1000 Bypass, P1B - Variable frequency drive
Yaskawa P1000 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa P1000 drives using the built-in RS-485/422 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP YAIP1U 01C.
Also known as: CIMR-PU, P1000 Industrial Fan and Pump Drive - Variable frequency drive (fan / pump)
Yaskawa P7 fan/pump drive (CIMR-P7U, legacy) - Modbus RTU
Yaskawa P7 (CIMR-P7U) fan and pump drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.P7.01 Appendix D.
Also known as: CIMR-P7U, P7U, P7 Drive - Variable frequency drive (fan / pump bypass package)
Yaskawa P7B drive/bypass (legacy) - Modbus RTU
Yaskawa P7B drive/bypass packages (P7 drive CIMR-P7U inside a bypass enclosure, option V native Modbus) using the drive's RS-422/485 terminals, per technical manual TM.P7B.01 Appendix D.
Also known as: P7B, P7 Bypass - Variable frequency drive
Yaskawa U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU)
Yaskawa U1000 matrix drives using the built-in RS-422/485 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP C710636 04E.
Also known as: CIMR-UU, U1000 Industrial MATRIX Drive - Variable frequency drive
Yaskawa V1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa V1000 drives (CIMR-VU; 200 V single/three-phase and 400 V three-phase, 0.1-18.5 kW) using the built-in RS-422/485 MEMOBUS/Modbus terminals, per Technical Manual SIEP C710606 18F.
Also known as: CIMR-VU, V1000 Compact Vector Control Drive - Variable frequency drive (HVAC bypass package)
Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU)
Z1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIZ1B 01F, appendix D.
Also known as: Z1000 Bypass, Z1B1 - Variable frequency drive (HVAC fan / pump)
Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000 HVAC drives (CIMR-ZU) using the built-in RS-485 terminals with H5-08 = 0, per Programming Manual SIEP YAIZ1U 03C (the copy covers the 600 V class models 5A0007-5A0242).
Also known as: CIMR-ZU, Z1000 AC Drive for HVAC Fan and Pump - Variable frequency drive
Yaskawa Z1000U HVAC matrix drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000U HVAC matrix drives using the built-in serial terminals with H5-08 = 0 (MEMOBUS/Modbus), per programming manual SIEP C710636 10D.
Also known as: Z1000U HVAC MATRIX Drive, Z1000U Matrix
Other variable frequency drives register maps
- Variable frequency drive
ABB ACQ580 water and wastewater drive (embedded Modbus RTU)
ACQ580 drives running the ACQ580 pump control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000035867 Rev H.
Also known as: ACQ580-01, ACQ580-04, ACQ580-07, ACQ580-31, ACQ580-34, ACQ580 pump control program - Variable frequency drive
ABB ACS580 general purpose drive (embedded Modbus RTU)
ACS580 drives running the ACS580 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default).
Also known as: ACS580-01, ACS580-04, ACS580-07, ACS580 standard control program - Variable frequency drive
AutomationDirect DURApulse GS3 AC drive
All GS3 drives; status addresses and P9.xx serial-communication parameters from chapter 5 of the user manual.
Also known as: DURApulse GS3, GS3-21P0, GS3-22P0, GS3-23P0, GS3-25P0, GS3-27P5, GS3-2010, GS3-2015, GS3-2020, GS3-2025 - Variable frequency drive
Danfoss VLT AutomationDrive FC 301/302 (Modbus RTU)
VLT AutomationDrive FC 301 and FC 302 (0.25-75 kW design guide; same scheme across sizes) using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter data checked against the software 9.5x / 48.96 programming guide.
Also known as: VLT AutomationDrive, FC 301, FC301, FC302, FC-302, FC-301, FC 300 - Variable frequency drive
Danfoss VACON VACON 100 family (built-in Modbus RTU / Modbus TCP)
VACON 100 INDUSTRIAL, FLOW, HVAC and 100 X drives using the built-in RS-485 Modbus RTU or Ethernet Modbus TCP/UDP (manual DPD00156D); application IDs per the VACON 100 INDUSTRIAL application guide DPD00927L (FW0072V037).
Also known as: VACON 100 INDUSTRIAL, VACON 100 FLOW, VACON 100 HVAC, VACON 100 X, VACON0100 - Variable frequency drive (HVAC / pump)
Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU)
Fuji Electric FRENIC-HVAC (AR) and FRENIC-AQUA (AQ) inverters on the RS-485 port in Modbus RTU mode (y10 = 0); RS-485 Communication User's Manual 24A7-E-0021b.
Also known as: FRENIC-HVAC, FRENIC-AQUA, FRN-AR, FRN-AQ
All variable frequency drives Modbus register maps →
Source: Modbus Communication Manual V7 and V74X Drives · TM.V7.11 Rev 07-01 · rev. 2007-01-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.