Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU Modbus register map

Updated 17 November 2026

Short answer

The V7 and its NEMA 4X twin V74X are Yaskawa's legacy compact drives with built-in Modbus RTU. Commands go to hex registers 0001h, 0002h and 0009h, status, fault and monitors are read from 0020h-003Dh, and parameters n001-n179 sit at 0101h-01B3h. This map covers the command and monitor registers with published units, and the run/reference source and Modbus setup parameters.

This page lists 26 Modbus registers for the Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yaskawa’s own free documentation (linked below) and checked against it.

Manufacturer
Yaskawa
Model
V7 / V74X compact drive (legacy) - Modbus RTU
Equipment type
Variable frequency drive
Registers
26 (14 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
hexadecimal, 0-based
Also known as
CIMR-V7AM, CIMR-V7CU, V74X
Source document
Modbus Communication Manual V7 and V74X Drives · TM.V7.11 Rev 07-01 · rev. 2007-01-05
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU

Integration in brief

Set n153 (address), n154 (baud) and n155 (parity), then n003 = 2 and n004 = 6 to take run and reference from Modbus. Write 0001h/0002h and poll 0020h-0031h.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1Digital input commandBITMAP16Run/stop, direction, resetRead/write
HR 2Frequency referenceUINT16Frequency referenceRead/write
HR 32Status signal 1BITMAP16Run/ready/faultRead
HR 33Fault content 1BITMAP16Fault contentRead
HR 36Output frequency (U-02)UINT16Output frequencyRead
HR 39Output current (U-03)UINT16Output currentRead
HR 44Status signal 2BITMAP16Status incl. comm timeoutRead

Enable Modbus control & writes

n153 slave address 1-31 (default 0), n154 baud (default 2 = 9600), n155 parity (default 2 = none). n003 = 2 and n004 = 6 select built-in Modbus RTU for run/stop and frequency reference. n157 = 0 for 2-wire RS-485.

Communication loss & watchdog

n151 selects the time-out response: 0 coast (default), 1 ramp with n020, 2 ramp with n022, 3 continue with alarm, 4 disabled. 002Ch bit F shows a communication timeout.

Byte order & addressing

Network setup

Watch out for

Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

26 of 26 shown
Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 0001hDigital input commandRun, direction, external fault, reset, network inputs S1-S7.BITMAP16Read/writebit 0 = Run command (0 stop, 1 run); bit 1 = Reverse (0 forward, 1 reverse); bit 2 = External fault; bit 3 = Fault reset; bit 4 = Terminal S1 (n050); bit 5 = Terminal S2 (n051); bit 6 = Terminal S3 (n052); bit 7 = Terminal S4 (n053); bit 8 = Terminal S5 (n054); bit 9 = Terminal S6 (n055); bit 10 = Terminal S7 (n056)
HR2doc 0002hFrequency referenceUnit set by n152 (0.1 Hz default).UINT16Read/write
HR9doc 0009hDigital output commandBITMAP16Read/writebit 0 = Output MA/MB/MC; bit 1 = Output P1-PC; bit 2 = Output P2-PC
HR32doc 0020hStatus signal 1BITMAP16Readbit 0 = During run; bit 1 = Reverse direction; bit 2 = Inverter ready; bit 3 = Fault; bit 4 = Data set error; bit 5 = Output MA-MC closed; bit 6 = Output P1-PC closed; bit 7 = Output P2-PC closed
HR33doc 0021hFault content 1BITMAP16Readbit 0 = Overcurrent (OC); bit 1 = Overvoltage (OV); bit 2 = Inverter overload (OL2); bit 3 = Inverter overheat (OH); bit 6 = PID feedback (FbL); bit 7 = External fault (EF, EF0) or emergency stop (STP); bit 8 = Hardware fault (Fxx); bit 9 = Motor overload (OL1); bit 10 = Overtorque detection; bit 11 = Undertorque detection; bit 12 = Undervoltage (UV1); bit 13 = Control power supply fault (UV2); bit 14 = Modbus communications timeout (CE); bit 15 = Operator connection fault (oPA)
HR34doc 0022hData link statusBITMAP16Readbit 0 = During data write; bit 3 = Limit fault; bit 4 = Matching fault
HR35doc 0023hFrequency reference (U-01)Unit set by n152.UINT16Read
HR36doc 0024hOutput frequency (U-02)Unit set by n152.UINT16Read
HR39doc 0027hOutput current (U-03)UINT16× 0.1ARead
HR40doc 0028hOutput voltage (U-04)UINT16VRead
HR43doc 002BhDigital input statusTerminals S1-S7 closed.BITMAP16Readbit 0 = S1 closed; bit 1 = S2 closed; bit 2 = S3 closed; bit 3 = S4 closed; bit 4 = S5 closed; bit 5 = S6 closed; bit 6 = S7 closed
HR44doc 002ChStatus signal 2BITMAP16Readbit 0 = During run; bit 1 = Zero speed; bit 2 = Speed agree; bit 3 = Alarm; bit 4 = Frequency detection 1; bit 5 = Frequency detection 2; bit 6 = Inverter ready; bit 7 = Undervoltage detection; bit 8 = Baseblock; bit 9 = Frequency reference source (0 network, 1 n004); bit 10 = Run command source (0 network, 1 n003); bit 11 = Overtorque detection; bit 12 = Undertorque detection; bit 13 = Fault retry; bit 14 = Fault; bit 15 = Communication timeout
HR45doc 002DhDigital output statusBITMAP16Readbit 0 = MA-MC closed; bit 1 = P1-PC closed; bit 2 = P2-PC closed
HR49doc 0031hDC bus voltage (U-05)UINT16VRead
HR61doc 003DhModbus errorBITMAP16Readbit 0 = CRC error; bit 1 = Data length error; bit 3 = Parity error; bit 4 = Overrun error; bit 5 = Framing error; bit 6 = Timeout
HR259doc 0103hn003 Run/stop sourceUINT16Read/write0 = Keypad; 1 = Terminal strip; 2 = Built-in Modbus RTU; 3 = Option card
HR260doc 0104hn004 Frequency reference sourceUINT16Read/write0 = Keypad potentiometer; 1 = Frequency reference 1 (n024); 2 = 0-10 V (FR); 3 = 4-20 mA (FR); 4 = 0-20 mA (FR); 5 = Pulse train (RP); 6 = Built-in Modbus RTU; 7 = Multi-function analog input 0-10 V (keypad CN2); 8 = Multi-function analog input 4-20 mA (keypad CN2); 9 = Option card
HR407doc 0197hn151 Modbus time-out detectionUINT16Read/write0 = Coast to stop; 1 = Ramp to stop (n020); 2 = Ramp to stop (n022); 3 = Continue with alarm; 4 = Disabled
HR408doc 0198hn152 Frequency reference unitApplies to 0002h, 0023h, 0024h.UINT16Read/write0 = 1 = 0.1 Hz; 1 = 1 = 0.01 Hz; 2 = 30000 = n011 (max frequency); 3 = 1 = 0.1 %
HR409doc 0199hn153 Modbus RTU slave address0-31 decimal.UINT16Read/write
HR410doc 019Ahn154 Modbus RTU baud rateUINT16Read/write0 = 2400; 1 = 4800; 2 = 9600; 3 = 19200
HR411doc 019Bhn155 Modbus RTU parityUINT16Read/write0 = Even; 1 = Odd; 2 = None
HR412doc 019Chn156 Modbus RTU send delay0-65 ms.UINT16msRead/write
HR413doc 019Dhn157 Modbus RTU RTS controlUINT16Read/write0 = Enabled (RS-485 2-wire); 1 = Disabled (RS-422 / RS-485 4-wire)
HR2304doc 900ENTERWrite 0 to store off-line parameter data in EEPROM (about 100,000 writes).UINT16Write
HR2320doc 910ACCEPTWrite 0 to activate off-line parameter data in RAM.UINT16Write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU

What Modbus registers does the Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU have?

This map lists 26 registers: 26 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are hex and go on the wire unchanged: the read example asks for starting register 00h 20h (0020h-0023h). Parameter nXXX lives at its hex address in Table 4.4 (n003 = 0103h, n153 = 0199h); ENTER/ACCEPT are printed as 900/910.

What are the minimum Modbus registers to integrate the Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU?

Start with HR 1 Digital input command (Run/stop, direction, reset); HR 2 Frequency reference (Frequency reference); HR 32 Status signal 1 (Run/ready/fault); HR 33 Fault content 1 (Fault content); HR 36 Output frequency (U-02) (Output frequency); HR 39 Output current (U-03) (Output current); HR 44 Status signal 2 (Status incl. comm timeout).

How do I enable Modbus control of the Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU?

n153 slave address 1-31 (default 0), n154 baud (default 2 = 9600), n155 parity (default 2 = none). n003 = 2 and n004 = 6 select built-in Modbus RTU for run/stop and frequency reference. n157 = 0 for 2-wire RS-485.

What happens when the Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU loses Modbus communication?

n151 selects the time-out response: 0 coast (default), 1 ramp with n020, 2 ramp with n022, 3 continue with alarm, 4 disabled. 002Ch bit F shows a communication timeout.

Where is the official Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU Modbus documentation?

The source is Modbus Communication Manual V7 and V74X Drives (TM.V7.11 Rev 07-01), revision 2007-01-05, published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=TM.V7.11&cmd=documents&documentName=TM.V7.11.pdf.