  4. iQpump drive (P7U-based, legacy) - Modbus RTU

Variable frequency drive (pump) · Modbus register map

Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU Modbus register map

Updated 17 November 2026

Short answer

The original Yaskawa iQpump is a pump-application drive based on the P7 platform with an embedded Modbus RTU slave on terminals R+/R-/S+/S-. Commands go to hex registers 0001H-000FH, status and fault words are read from 0020H upward, and parameters have their own hex Modbus addresses in Appendix A. This map covers the command block, status/fault words, PI levels, pump monitors, fault history codes and the b1/H5 setup parameters.

This page lists 44 Modbus registers for the Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU — 19 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yaskawa’s own free documentation (linked below) and checked against it.

Manufacturer
Yaskawa
Model
iQpump drive (P7U-based, legacy) - Modbus RTU
Equipment type
Variable frequency drive (pump)
Registers
44 (19 writable)
Transport
Modbus RTU
Default unit ID
31
Default serial
9600 baud, 8N1
Documented addressing
hexadecimal, 0-based
Also known as
iQpump, CIMR-P7U iQpump, iQpump Drive
Source document
iQpump Drive User Manual · TM.iQp.01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU

Integration in brief

Set H5-01..H5-03 at the keypad and power-cycle, set b1-01 = 2 and b1-02 = 2 for Modbus reference and run, then write 0001H and 0002H with function 10H and poll 0020H-002DH for status and faults.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1Operation commandBITMAP16Run/stop and fault resetRead/write
HR 2Frequency referenceUINT16Frequency referenceRead/write
HR 32Drive statusBITMAP16Drive statusRead
HR 33Fault detailsBITMAP16Fault detailsRead
HR 36Output frequency (U1-02)UINT16Output frequencyRead
HR 44Drive status 2BITMAP16Drive status 2 incl. comm timeoutRead
HR 1825Pump feedback (U1-91)UINT16Pump feedbackRead
HR 128Current fault (U2-01)UINT16Current fault codeRead

Enable Modbus control & writes

Set H5-01 address (default 1F hex), H5-02 baud (default 3 = 9600) and H5-03 parity (default none), then cycle power. b1-01 = 2 and b1-02 = 2 hand the frequency reference and run command to Modbus. Status reads, parameter access, fault reset and multi-function inputs work regardless of b1-01/b1-02.

Communication loss & watchdog

H5-05 = 1 (default) enables CE detection after H5-09 seconds (default 2.0 s) without messages; H5-04 sets the reaction: 0 ramp, 1 coast, 2 fast-stop, 3 alarm only (default). 002CH bit F shows a comm time-out.

Byte order & addressing

Network setup

Watch out for

Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

44 of 44 shown
Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 0001HOperation commandRun forward/reverse, external fault, fault reset, virtual inputs.BITMAP16Read/writebit 0 = Run forward; bit 1 = Run reverse; bit 2 = External fault (EFO); bit 3 = Fault reset; bit 4 = ComNet; bit 5 = ComCtrl; bit 6 = Multi-function input command 3; bit 7 = Multi-function input command 4; bit 8 = Multi-function input command 5; bit 9 = Multi-function input command 6; bit 10 = Multi-function input command 7
HR2doc 0002HFrequency referenceUnits set by o1-03; unscaled here.UINT16Read/write
HR6doc 0006HPI setpointUsed when 000FH bit 1 is set.UINT16Read/write
HR7doc 0007HAnalog output 1 setting-11 V = -726 ... 11 V = 726 (10 V = 660).INT16Read/write
HR8doc 0008HAnalog output 2 setting-11 V = -726 ... 11 V = 726 (10 V = 660).INT16Read/write
HR9doc 0009HMulti-function contact output settingNetwork control of M1-M2, M3-M4 and fault contact.BITMAP16Read/writebit 0 = Digital output 1 (M1-M2) on; bit 1 = Digital output 2 (M3-M4) on; bit 6 = Use bit 7 to drive fault contact MA-MC; bit 7 = Fault contact (MA-MC) on
HR15doc 000FHReference selection settingsEnables network PI setpoint and broadcast S5-S7 inputs.BITMAP16Read/writebit 1 = Input PI setpoint (0006H) enabled; bit 12 = Broadcast terminal S5 input enabled; bit 13 = Broadcast terminal S6 input enabled; bit 14 = Broadcast terminal S7 input enabled
HR32doc 0020HDrive statusBITMAP16Readbit 0 = Running; bit 1 = Reverse operation; bit 2 = Drive startup complete; bit 3 = Fault; bit 4 = Data setting error; bit 5 = Multi-function output 1 (M1-M2) on; bit 6 = Multi-function output 2 (M3-M4) on
HR33doc 0021HFault detailsBITMAP16Readbit 0 = Overcurrent (OC) / ground fault (GF); bit 1 = Main circuit overvoltage (OV); bit 2 = Drive overload (OL2); bit 3 = Drive overheat (OH1, OH2); bit 5 = Fuse blown (PUF); bit 6 = PI feedback reference lost (FbL); bit 7 = External error (EF, EFO); bit 8 = Hardware error (CPF); bit 9 = Motor overload (OL1) or overtorque 1 (OL3); bit 10 = PG broken wire (PGO), overspeed (OS), speed deviation (DEV); bit 11 = Main circuit undervoltage (UV) detected; bit 12 = Undervoltage UV1, control power UV2, inrush circuit UV3, power loss; bit 13 = Missing output phase (LF); bit 14 = Modbus communications error (CE); bit 15 = Operator disconnected (OPR)
HR34doc 0022HData link statusBITMAP16Readbit 0 = Writing data; bit 3 = Upper/lower limit error; bit 4 = Data integrity error
HR35doc 0023HFrequency reference (U1-01)Raw; units follow o1-03/P1-02.UINT16Read
HR36doc 0024HOutput frequency (U1-02)Raw value; the data table gives no resolution.UINT16Read
HR43doc 002BHSequence input statusTerminals S1-S7.BITMAP16Readbit 0 = S1 on; bit 1 = S2 on; bit 2 = S3 on; bit 3 = S4 on; bit 4 = S5 on; bit 5 = S6 on; bit 6 = S7 on
HR44doc 002CHDrive status 2BITMAP16Readbit 0 = Operating; bit 1 = Zero speed; bit 2 = Frequency agree; bit 3 = Desired frequency agree; bit 4 = Frequency detection 1 (output <= L4-01); bit 5 = Frequency detection 2 (output >= L4-01); bit 6 = Drive startup completed; bit 7 = Low voltage detected; bit 8 = Baseblock; bit 9 = Frequency reference not from communication; bit 10 = Run command not from communication; bit 11 = Overtorque detected; bit 12 = Frequency reference lost; bit 13 = Retrying error; bit 14 = Error (incl. Modbus time-out); bit 15 = Modbus communications time-out
HR45doc 002DHMulti-function digital output statusBITMAP16Readbit 0 = Output 1 (M1-M2) on; bit 1 = Output 2 (M3-M4) on
HR56doc 0038HPI feedback levelUnsigned, 10 = 1 % of max output frequency.UINT16× 0.1%Read
HR57doc 0039HPI input levelSigned, 10 = 1 % of max output frequency.INT16× 0.1%Read
HR58doc 003AHPI output levelSigned, 10 = 1 % of max output frequency.INT16× 0.1%Read
HR59doc 003BHCPU software numberUINT16Read
HR60doc 003CHFlash software numberUINT16Read
HR61doc 003DHCommunication error detailsLatched until a fault reset.BITMAP16Readbit 0 = CRC error; bit 1 = Invalid data length; bit 3 = Parity error; bit 4 = Overrun error; bit 5 = Framing error; bit 6 = Time-out
HR62doc 003EHkVA settingUINT16Read
HR63doc 003FHControl methodUINT16Read
HR128doc 0080HCurrent fault (U2-01)Fault code of the active fault.UINT16Read
HR129doc 0081HPrevious fault (U2-02)UINT16Read
HR144doc 0090HMost recent fault (U3-01)UINT16Read
HR145doc 0091H2nd most recent fault (U3-02)UINT16Read
HR146doc 0092H3rd most recent fault (U3-03)UINT16Read
HR147doc 0093H4th most recent fault (U3-04)UINT16Read
HR384doc 0180Hb1-01 Frequency reference selectionUINT16Read/write0 = Operator; 1 = Terminals; 2 = Serial com (R+/R-/S+/S-); 3 = Option PCB
HR385doc 0181Hb1-02 Run command selectionUINT16Read/write0 = Operator; 1 = Terminals; 2 = Serial com (R+/R-/S+/S-); 3 = Option PCB
HR1061doc 0425HH5-01 Drive node addressDefault 1F hex; power-cycle after change.UINT16Read/write
HR1062doc 0426HH5-02 Communication speedPower-cycle after change.UINT16Read/write0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200
HR1063doc 0427HH5-03 Communication parityPower-cycle after change.UINT16Read/write0 = None; 1 = Even; 2 = Odd
HR1064doc 0428HH5-04 Stopping method after comm errorUINT16Read/write0 = Ramp to stop; 1 = Coast to stop; 2 = Fast-stop; 3 = Alarm only
HR1065doc 0429HH5-05 Comm error detectionUINT16Read/write0 = Disabled; 1 = Enabled
HR1066doc 042AHH5-06 Drive transmit wait time5-65 ms.UINT16msRead/write
HR1067doc 042BHH5-07 RTS controlUINT16Read/write0 = Disabled (RTS always on); 1 = Enabled (RTS on only when sending)
HR1077doc 0435HH5-09 Comm error detection time0.0-10.0 s in Modbus mode.UINT16× 0.1sRead/write
HR1824doc 0720HPump setpoint (U1-90)Excludes setpoint compensation; system units (P1-02).UINT16× 0.1Read
HR1825doc 0721HPump feedback (U1-91)Scaled feedback in system units (P1-02).UINT16× 0.1Read
HR1826doc 0722HPump status (U1-92)BITMAP16Readbit 0 = Drive (pump 1) running; bit 1 = Pump 2 on; bit 2 = Pump 3 on
HR2304doc 0900HEnter command (EEPROM)Write 0 to store written parameters in EEPROM and RAM.UINT16Write
HR2320doc 0910HEnter command (RAM only)Write 0 to activate written parameters in RAM only.UINT16Write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU

What Modbus registers does the Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU have?

This map lists 44 registers: 44 holding registers. 19 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and are sent unchanged: the 03H example reads from start address 00 20 (drive status), and the 10H example writes 0001H (run forward) and 0002H (0258H = 600 for 60.0 Hz) starting at 00 01. Parameters use the hex Modbus address in Appendix A (b1-01 = 0180H, H5-01 = 0425H).

What are the minimum Modbus registers to integrate the Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU?

Start with HR 1 Operation command (Run/stop and fault reset); HR 2 Frequency reference (Frequency reference); HR 32 Drive status (Drive status); HR 33 Fault details (Fault details); HR 36 Output frequency (U1-02) (Output frequency); HR 44 Drive status 2 (Drive status 2 incl. comm timeout); HR 1825 Pump feedback (U1-91) (Pump feedback); HR 128 Current fault (U2-01) (Current fault code).

How do I enable Modbus control of the Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU?

Set H5-01 address (default 1F hex), H5-02 baud (default 3 = 9600) and H5-03 parity (default none), then cycle power. b1-01 = 2 and b1-02 = 2 hand the frequency reference and run command to Modbus. Status reads, parameter access, fault reset and multi-function inputs work regardless of b1-01/b1-02.

What happens when the Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU loses Modbus communication?

H5-05 = 1 (default) enables CE detection after H5-09 seconds (default 2.0 s) without messages; H5-04 sets the reaction: 0 ramp, 1 coast, 2 fast-stop, 3 alarm only (default). 002CH bit F shows a comm time-out.

Where is the official Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU Modbus documentation?

The source is iQpump Drive User Manual (TM.iQp.01), published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=TM.iQp.01&cmd=documents&documentName=TM.iQp.01.pdf.

More Yaskawa Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: iQpump Drive User Manual · TM.iQp.01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.