Easy Modbus
  1. Home
  2. Modbus register maps
  3. Yaskawa
  4. FP605 enclosed bypass (MEMOBUS/Modbus RTU)

Variable frequency drive · Modbus register map

Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

Yaskawa's FP605 fan and pump drive packaged with a bypass contactor board. The bypass board's RS-485 port speaks MEMOBUS/Modbus RTU (or N2, P1, BACnet). Drive command and monitor registers start at 0001H and 0020H, and the bypass adds its own command word and digital I/O registers at 8400H-8403H. This map covers drive and bypass control, status, fault bits and the b1/H5/Z3-12 setup parameters.

This page lists 35 Modbus registers for the Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU) — 26 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yaskawa’s own free documentation (linked below) and checked against it.

Manufacturer
Yaskawa
Model
FP605 enclosed bypass (MEMOBUS/Modbus RTU)
Equipment type
Variable frequency drive
Registers
35 (26 writable)
Transport
Modbus RTU
Default unit ID
31
Default serial
9600 baud, 8N1
Documented addressing
hexadecimal, 0-based
Also known as
FP605 Enclosed Bypass, FP605 bypass package
Source document
FP605 Enclosed Bypass Technical Reference · SIEPYAIF6B01C
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU)

Integration in brief

Set H5-08 = 0, H5-01..H5-03 and cycle power (or H5-20 = 1); set b1-01 = 2 and b1-02 = 2 for serial reference and run. Write 0001H and 0002H with function 10H, use 8400H for drive/bypass selection and emergency override, and poll 0020H, 0021H and 002CH.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1Run command / drive MFDI commandBITMAP16Run/stop, direction, fault resetRead/write
HR 2Frequency referenceUINT16Frequency reference (o1-03 units)Read/write
HR 33792Bypass command wordBITMAP16Bypass command word (drive/bypass select)Read/write
HR 32Drive status 1BITMAP16Drive/bypass status 1Read
HR 33Fault description 1BITMAP16Fault description 1Read
HR 36U1-02 Output frequencyUINT16U1-02 output frequencyRead
HR 44Drive status 2BITMAP16Drive status 2 incl. comm timeoutRead

Enable Modbus control & writes

H5-08 = 0 selects Modbus (default 3 = BACnet). Set H5-01 address (default 1FH), H5-02 speed (default 3 = 9600 bps), H5-03 parity (default 0 = none), then cycle power or set H5-20 = 1. Set b1-01 = 2 and b1-02 = 2 for serial control; Z3-12 = 1 lets 0001H bits 4-B and 8402H drive the digital inputs.

Communication loss & watchdog

H5-05 = 1 (default) enables CE detection after H5-09 (0.0-10.0 s, default 2.0 s); H5-04 sets the reaction (0 ramp, 1 coast, 2 fast stop, 3 alarm only - default, 4 run at H5-34 with H5-35 as an optional timeout). Drive status 2 (002CH) bit F shows a timeout.

Byte order & addressing

Network setup

Watch out for

Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

35 of 35 shown
Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 0001HRun command / drive MFDI commandBits 4-B drive the drive digital inputs when Z3-12 = 1.BITMAP16Read/writebit 0 = 1 = forward run (or run), 0 = stop; bit 1 = 1 = reverse run (or reverse), 0 = stop / forward; bit 2 = External fault EF0; bit 3 = Fault reset; bit 4 = Drive digital input bit 4 (Z3-12 = 1); bit 5 = Drive digital input bit 5 (Z3-12 = 1); bit 6 = Drive digital input bit 6 (Z3-12 = 1); bit 7 = Drive digital input bit 7 (Z3-12 = 1); bit 8 = Drive digital input bit 8 (Z3-12 = 1); bit 9 = Drive digital input bit 9 (Z3-12 = 1); bit 10 = Drive digital input bit 10 (Z3-12 = 1); bit 11 = Drive digital input bit 11 (Z3-12 = 1)
HR2doc 0002HFrequency referenceUnsigned; units set by o1-03.UINT16Read/write
HR3doc 0003HOutput voltage gain20-2000 (2.0-200.0 %), 1000 at power-up.UINT16× 0.1%Read/write
HR6doc 0006HPID setpointSigned; enable with 000FH bit 1.INT16× 0.01%Read/write
HR9doc 0009HMFDO settingDrive the drive digital outputs from the network.BITMAP16Read/writebit 0 = Drive MFDO M1-M2; bit 1 = Drive MFDO M3-M4; bit 2 = Drive MFDO MD-ME-MF; bit 6 = Enable bit 7; bit 7 = Drive fault relay MA/MB-MC
HR13doc 000DHPI2 control setpoint-100.00 to +100.00 %; enable with 000FH bit 4.INT16× 0.01%Read/write
HR15doc 000FHCommand selection settingEnables network setpoints and broadcast terminal inputs.BITMAP16Read/writebit 1 = PID target from Modbus; bit 4 = PI2 target from Modbus; bit 5 = PID feedback from Modbus (15FFH); bit 12 = Broadcast terminal S5 input; bit 13 = Broadcast terminal S6 input; bit 14 = Broadcast terminal S7 input; bit 15 = Broadcast terminal S8 input
HR32doc 0020HDrive status 1Covers drive and bypass.BITMAP16Readbit 0 = Drive run or bypass run; bit 1 = During reverse; bit 2 = System ready; bit 3 = Drive or bypass faulted; bit 4 = oPE fault on drive or bypass; bit 5 = MFDO M1-M2 on; bit 6 = MFDO M3-M4 on; bit 7 = MFDO MD-ME-MF on; bit 12 = Safe Torque OFF hardware; bit 13 = Safe Torque OFF; bit 14 = Bypass ComRef enabled; bit 15 = Bypass ComCtrl enabled
HR33doc 0021HFault description 1BITMAP16Readbit 0 = oC overcurrent / GF ground fault; bit 1 = ov overvoltage; bit 2 = oL2 drive overload; bit 3 = oH1 heatsink / oH2 external overheat; bit 7 = EF0-EF7 external fault; bit 8 = CPFxx hardware fault (incl. oFx); bit 9 = oL1 motor overload, oL3/oL4 overtorque, UL3/UL4 undertorque; bit 10 = oS overspeed / dEv speed deviation; bit 11 = During Uv detection; bit 12 = Uv1/Uv2/Uv3 undervoltage; bit 13 = LF output / PF input phase loss; bit 14 = CE / bUS communication error; bit 15 = oPr keypad connection fault
HR34doc 0022HFault contents (data link)Errors from the last write.BITMAP16Readbit 0 = During data write / motor switching; bit 3 = Upper/lower limit fault; bit 4 = Data integrity fault; bit 5 = During EEPROM write
HR35doc 0023HU1-01 Frequency referenceUnits set by o1-03.UINT16Read
HR36doc 0024HU1-02 Output frequencyUnits set by o1-03.UINT16Read
HR41doc 0029HFault description 2BITMAP16Readbit 1 = GF ground fault; bit 2 = PF input phase loss; bit 3 = LF output phase loss; bit 6 = oH4 motor overheat fault (PTC)
HR42doc 002AHMinor fault description 1Alarms that do not trip the drive.BITMAP16Readbit 2 = EF run command input error; bit 3 = bb baseblock; bit 4 = oL3 overtorque 1; bit 5 = oH heatsink overheat; bit 6 = ov overvoltage; bit 7 = Uv undervoltage; bit 9 = CE: running at H5-34 go-to frequency; bit 10 = bUS option communication error; bit 11 = UL3/UL4 undertorque; bit 12 = oH3 motor overheat (PTC); bit 15 = CALL serial transmission error
HR43doc 002BHDrive input terminal statusBITMAP16Readbit 0 = Drive terminal S1 on; bit 1 = Drive terminal S2 on; bit 2 = Drive terminal S3 on; bit 3 = Drive terminal S4 on; bit 4 = Drive terminal S5 on; bit 5 = Drive terminal S6 on; bit 6 = Drive terminal S7 on; bit 7 = Drive terminal S8 on
HR44doc 002CHDrive status 2BITMAP16Readbit 0 = During run; bit 1 = During zero speed; bit 2 = Speed agree; bit 3 = User-defined speed agree; bit 4 = Frequency detection 1; bit 5 = Frequency detection 2; bit 6 = Run ready; bit 7 = During low-voltage detection; bit 8 = During baseblock; bit 9 = Frequency reference mode (1 = not from communication option); bit 10 = Run command mode (1 = not from communication option); bit 11 = Over/undertorque 1/2 detected; bit 12 = Frequency reference loss; bit 13 = Auto-restart in progress; bit 14 = Fault; bit 15 = Modbus communication timeout
HR384doc 0180Hb1-01 Frequency reference selection 1Set 2 for a serial frequency reference.UINT16Read/write0 = Keypad; 1 = Analog input; 2 = Serial communications; 3 = Option PCB
HR385doc 0181Hb1-02 Run command selection 1Set 2 to take Run from serial.UINT16Read/write0 = Keypad; 1 = Digital input; 2 = Serial communications; 3 = Option PCB
HR1061doc 0425HH5-01 Drive node addressDefault 1FH; range depends on protocol.UINT16Read/write
HR1062doc 0426HH5-02 Communication speed selectionDefault 3.UINT16Read/write0 = 1200 bps; 1 = 2400 bps; 2 = 4800 bps; 3 = 9600 bps; 4 = 19.2 kbps; 5 = 38.4 kbps; 6 = 57.6 kbps; 7 = 76.8 kbps; 8 = 115.2 kbps
HR1063doc 0427HH5-03 Communication parity selectionDefault 0.UINT16Read/write0 = No parity; 1 = Even parity; 2 = Odd parity
HR1064doc 0428HH5-04 Communication error stop methodDefault 3.UINT16Read/write0 = Ramp to stop; 1 = Coast to stop; 2 = Fast stop (C1-09); 3 = Alarm only; 4 = Run at H5-34 (CE go-to frequency)
HR1065doc 0429HH5-05 Comm fault detection selectionDefault 1.UINT16Read/write0 = Disabled; 1 = Enabled
HR1066doc 042AHH5-06 Drive transmit wait time0-65 ms, default 5 ms.UINT16msRead/write
HR1077doc 0435HH5-09 CE detection time0.0-10.0 s, default 2.0 s.UINT16× 0.1sRead/write
HR1078doc 0436HH5-10 Modbus register 0025H unit selectionUINT16Read/write0 = 0.1 V units; 1 = 1 V units
HR1084doc 043CHH5-11 Comm ENTER command modeDefault 0.UINT16Read/write0 = ENTER command required; 1 = ENTER command not required
HR1581doc 062DHH5-08 Communication protocol selectionDefault 3 (BACnet); set 0 for Modbus.UINT16Read/write0 = Modbus/MEMOBUS; 1 = Metasys N2; 2 = APOGEE P1; 3 = BACnet
HR2304doc 0900HEnter command (save to EEPROM)Write 0 to store written parameters.UINT16Write
HR2320doc 0910HEnter command (RAM only)Write 0 to apply written parameters without saving.UINT16Write
HR2903doc 0B57HH5-20 Communication parameters reloadUINT16Read/write0 = Reload at next power cycle; 1 = Reload now
HR33792doc 8400HBypass command wordBITMAP16Read/writebit 3 = Remote transfer; bit 4 = Emergency override bypass; bit 5 = Emergency override (FWD); bit 6 = Motor OR; bit 7 = Motor AND; bit 11 = Drive select (Z1-39); bit 12 = Bypass select (Z1-39); bit 13 = Fault reset; bit 14 = EFB; bit 15 = Emergency override drive (REV)
HR33794doc 8402HBypass MFDI commandBypass digital inputs TB2-1..8 when Z3-12 = 1.BITMAP16Read/writebit 0 = Bypass digital input 1 (TB2-1); bit 1 = Bypass digital input 2 (TB2-2); bit 2 = Bypass digital input 3 (TB2-3); bit 3 = Bypass digital input 4 (TB2-4); bit 4 = Bypass digital input 5 (TB2-5); bit 5 = Bypass digital input 6 (TB2-6); bit 6 = Bypass digital input 7 (TB2-7); bit 7 = Bypass digital input 8 (TB2-8)
HR33795doc 8403HBypass MFDO commandBypass outputs whose Z2-xx function is 99 (not used).BITMAP16Read/writebit 6 = Digital output 7 (TB1 1-3); bit 7 = Digital output 8 (TB1 4-6); bit 8 = Digital output 9 (TB1 7-9); bit 9 = Digital output 10 (TB1 10-12)
HR34059doc 850BHZ3-12 Network digital inputsEnables 0001H bits 4-B and 8402H.UINT16Read/write0 = Disabled; 1 = Enabled

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU)

What Modbus registers does the Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU) have?

This map lists 35 registers: 35 holding registers. 26 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and are sent unchanged: the manual's read example asks for starting register 0020H as bytes 00 20. Parameters use the hex number printed under each parameter (H5-01 = 0425H, Z3-12 = 850BH).

What are the minimum Modbus registers to integrate the Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU)?

Start with HR 1 Run command / drive MFDI command (Run/stop, direction, fault reset); HR 2 Frequency reference (Frequency reference (o1-03 units)); HR 33792 Bypass command word (Bypass command word (drive/bypass select)); HR 32 Drive status 1 (Drive/bypass status 1); HR 33 Fault description 1 (Fault description 1); HR 36 U1-02 Output frequency (U1-02 output frequency); HR 44 Drive status 2 (Drive status 2 incl. comm timeout).

How do I enable Modbus control of the Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU)?

H5-08 = 0 selects Modbus (default 3 = BACnet). Set H5-01 address (default 1FH), H5-02 speed (default 3 = 9600 bps), H5-03 parity (default 0 = none), then cycle power or set H5-20 = 1. Set b1-01 = 2 and b1-02 = 2 for serial control; Z3-12 = 1 lets 0001H bits 4-B and 8402H drive the digital inputs.

What happens when the Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU) loses Modbus communication?

H5-05 = 1 (default) enables CE detection after H5-09 (0.0-10.0 s, default 2.0 s); H5-04 sets the reaction (0 ramp, 1 coast, 2 fast stop, 3 alarm only - default, 4 run at H5-34 with H5-35 as an optional timeout). Drive status 2 (002CH) bit F shows a timeout.

Where is the official Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU) Modbus documentation?

The source is FP605 Enclosed Bypass Technical Reference (SIEPYAIF6B01C), published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=SIEPYAIF6B01&cmd=documents&documentName=SIEPYAIF6B01.pdf.

More Yaskawa Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: FP605 Enclosed Bypass Technical Reference · SIEPYAIF6B01C. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.