Variable frequency drive · Modbus register map
Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU) Modbus register map
Updated 19 November 2026
Yaskawa's FP605 fan and pump drive packaged with a bypass contactor board. The bypass board's RS-485 port speaks MEMOBUS/Modbus RTU (or N2, P1, BACnet). Drive command and monitor registers start at 0001H and 0020H, and the bypass adds its own command word and digital I/O registers at 8400H-8403H. This map covers drive and bypass control, status, fault bits and the b1/H5/Z3-12 setup parameters.
This page lists 35 Modbus registers for the Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU) — 26 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yaskawa’s own free documentation (linked below) and checked against it.
- Manufacturer
- Yaskawa
- Model
- FP605 enclosed bypass (MEMOBUS/Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 35 (26 writable)
- Transport
- Modbus RTU
- Default unit ID
- 31
- Default serial
- 9600 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- FP605 Enclosed Bypass, FP605 bypass package
- Source document
- FP605 Enclosed Bypass Technical Reference · SIEPYAIF6B01C
Integration notes: Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU)
Set H5-08 = 0, H5-01..H5-03 and cycle power (or H5-20 = 1); set b1-01 = 2 and b1-02 = 2 for serial reference and run. Write 0001H and 0002H with function 10H, use 8400H for drive/bypass selection and emergency override, and poll 0020H, 0021H and 002CH.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1 | Run command / drive MFDI command | BITMAP16 | Run/stop, direction, fault reset | Read/write |
| HR 2 | Frequency reference | UINT16 | Frequency reference (o1-03 units) | Read/write |
| HR 33792 | Bypass command word | BITMAP16 | Bypass command word (drive/bypass select) | Read/write |
| HR 32 | Drive status 1 | BITMAP16 | Drive/bypass status 1 | Read |
| HR 33 | Fault description 1 | BITMAP16 | Fault description 1 | Read |
| HR 36 | U1-02 Output frequency | UINT16 | U1-02 output frequency | Read |
| HR 44 | Drive status 2 | BITMAP16 | Drive status 2 incl. comm timeout | Read |
Enable Modbus control & writes
H5-08 = 0 selects Modbus (default 3 = BACnet). Set H5-01 address (default 1FH), H5-02 speed (default 3 = 9600 bps), H5-03 parity (default 0 = none), then cycle power or set H5-20 = 1. Set b1-01 = 2 and b1-02 = 2 for serial control; Z3-12 = 1 lets 0001H bits 4-B and 8402H drive the digital inputs.
Communication loss & watchdog
H5-05 = 1 (default) enables CE detection after H5-09 (0.0-10.0 s, default 2.0 s); H5-04 sets the reaction (0 ramp, 1 coast, 2 fast stop, 3 alarm only - default, 4 run at H5-34 with H5-35 as an optional timeout). Drive status 2 (002CH) bit F shows a timeout.
Byte order & addressing
- Registers are hex and 0-based: 0020H is sent as 00 20.
- No function 06H; use 10H.
- 8403H bits only act on outputs whose Z2-xx function is 99 (not used).
Network setup
- RS-485 on bypass terminal TB3; 8 data bits fixed.
- Enable the RS-485 termination resistor (bypass board DIP switch, see the switch table) only on the bypass at the end of the line.
Watch out for
- Out of the box the bypass talks BACnet (H5-08 = 3), not Modbus.
- With Z3-12 = 0 (default) the network digital-input bits are ignored.
Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 0001H | Run command / drive MFDI command | Bits 4-B drive the drive digital inputs when Z3-12 = 1. | BITMAP16 | Read/write | bit 0 = 1 = forward run (or run), 0 = stop; bit 1 = 1 = reverse run (or reverse), 0 = stop / forward; bit 2 = External fault EF0; bit 3 = Fault reset; bit 4 = Drive digital input bit 4 (Z3-12 = 1); bit 5 = Drive digital input bit 5 (Z3-12 = 1); bit 6 = Drive digital input bit 6 (Z3-12 = 1); bit 7 = Drive digital input bit 7 (Z3-12 = 1); bit 8 = Drive digital input bit 8 (Z3-12 = 1); bit 9 = Drive digital input bit 9 (Z3-12 = 1); bit 10 = Drive digital input bit 10 (Z3-12 = 1); bit 11 = Drive digital input bit 11 (Z3-12 = 1) | |||
| HR | 2doc 0002H | Frequency reference | Unsigned; units set by o1-03. | UINT16 | Read/write | ||||
| HR | 3doc 0003H | Output voltage gain | 20-2000 (2.0-200.0 %), 1000 at power-up. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 6doc 0006H | PID setpoint | Signed; enable with 000FH bit 1. | INT16 | × 0.01 | % | Read/write | ||
| HR | 9doc 0009H | MFDO setting | Drive the drive digital outputs from the network. | BITMAP16 | Read/write | bit 0 = Drive MFDO M1-M2; bit 1 = Drive MFDO M3-M4; bit 2 = Drive MFDO MD-ME-MF; bit 6 = Enable bit 7; bit 7 = Drive fault relay MA/MB-MC | |||
| HR | 13doc 000DH | PI2 control setpoint | -100.00 to +100.00 %; enable with 000FH bit 4. | INT16 | × 0.01 | % | Read/write | ||
| HR | 15doc 000FH | Command selection setting | Enables network setpoints and broadcast terminal inputs. | BITMAP16 | Read/write | bit 1 = PID target from Modbus; bit 4 = PI2 target from Modbus; bit 5 = PID feedback from Modbus (15FFH); bit 12 = Broadcast terminal S5 input; bit 13 = Broadcast terminal S6 input; bit 14 = Broadcast terminal S7 input; bit 15 = Broadcast terminal S8 input | |||
| HR | 32doc 0020H | Drive status 1 | Covers drive and bypass. | BITMAP16 | Read | bit 0 = Drive run or bypass run; bit 1 = During reverse; bit 2 = System ready; bit 3 = Drive or bypass faulted; bit 4 = oPE fault on drive or bypass; bit 5 = MFDO M1-M2 on; bit 6 = MFDO M3-M4 on; bit 7 = MFDO MD-ME-MF on; bit 12 = Safe Torque OFF hardware; bit 13 = Safe Torque OFF; bit 14 = Bypass ComRef enabled; bit 15 = Bypass ComCtrl enabled | |||
| HR | 33doc 0021H | Fault description 1 | BITMAP16 | Read | bit 0 = oC overcurrent / GF ground fault; bit 1 = ov overvoltage; bit 2 = oL2 drive overload; bit 3 = oH1 heatsink / oH2 external overheat; bit 7 = EF0-EF7 external fault; bit 8 = CPFxx hardware fault (incl. oFx); bit 9 = oL1 motor overload, oL3/oL4 overtorque, UL3/UL4 undertorque; bit 10 = oS overspeed / dEv speed deviation; bit 11 = During Uv detection; bit 12 = Uv1/Uv2/Uv3 undervoltage; bit 13 = LF output / PF input phase loss; bit 14 = CE / bUS communication error; bit 15 = oPr keypad connection fault | ||||
| HR | 34doc 0022H | Fault contents (data link) | Errors from the last write. | BITMAP16 | Read | bit 0 = During data write / motor switching; bit 3 = Upper/lower limit fault; bit 4 = Data integrity fault; bit 5 = During EEPROM write | |||
| HR | 35doc 0023H | U1-01 Frequency reference | Units set by o1-03. | UINT16 | Read | ||||
| HR | 36doc 0024H | U1-02 Output frequency | Units set by o1-03. | UINT16 | Read | ||||
| HR | 41doc 0029H | Fault description 2 | BITMAP16 | Read | bit 1 = GF ground fault; bit 2 = PF input phase loss; bit 3 = LF output phase loss; bit 6 = oH4 motor overheat fault (PTC) | ||||
| HR | 42doc 002AH | Minor fault description 1 | Alarms that do not trip the drive. | BITMAP16 | Read | bit 2 = EF run command input error; bit 3 = bb baseblock; bit 4 = oL3 overtorque 1; bit 5 = oH heatsink overheat; bit 6 = ov overvoltage; bit 7 = Uv undervoltage; bit 9 = CE: running at H5-34 go-to frequency; bit 10 = bUS option communication error; bit 11 = UL3/UL4 undertorque; bit 12 = oH3 motor overheat (PTC); bit 15 = CALL serial transmission error | |||
| HR | 43doc 002BH | Drive input terminal status | BITMAP16 | Read | bit 0 = Drive terminal S1 on; bit 1 = Drive terminal S2 on; bit 2 = Drive terminal S3 on; bit 3 = Drive terminal S4 on; bit 4 = Drive terminal S5 on; bit 5 = Drive terminal S6 on; bit 6 = Drive terminal S7 on; bit 7 = Drive terminal S8 on | ||||
| HR | 44doc 002CH | Drive status 2 | BITMAP16 | Read | bit 0 = During run; bit 1 = During zero speed; bit 2 = Speed agree; bit 3 = User-defined speed agree; bit 4 = Frequency detection 1; bit 5 = Frequency detection 2; bit 6 = Run ready; bit 7 = During low-voltage detection; bit 8 = During baseblock; bit 9 = Frequency reference mode (1 = not from communication option); bit 10 = Run command mode (1 = not from communication option); bit 11 = Over/undertorque 1/2 detected; bit 12 = Frequency reference loss; bit 13 = Auto-restart in progress; bit 14 = Fault; bit 15 = Modbus communication timeout | ||||
| HR | 384doc 0180H | b1-01 Frequency reference selection 1 | Set 2 for a serial frequency reference. | UINT16 | Read/write | 0 = Keypad; 1 = Analog input; 2 = Serial communications; 3 = Option PCB | |||
| HR | 385doc 0181H | b1-02 Run command selection 1 | Set 2 to take Run from serial. | UINT16 | Read/write | 0 = Keypad; 1 = Digital input; 2 = Serial communications; 3 = Option PCB | |||
| HR | 1061doc 0425H | H5-01 Drive node address | Default 1FH; range depends on protocol. | UINT16 | Read/write | ||||
| HR | 1062doc 0426H | H5-02 Communication speed selection | Default 3. | UINT16 | Read/write | 0 = 1200 bps; 1 = 2400 bps; 2 = 4800 bps; 3 = 9600 bps; 4 = 19.2 kbps; 5 = 38.4 kbps; 6 = 57.6 kbps; 7 = 76.8 kbps; 8 = 115.2 kbps | |||
| HR | 1063doc 0427H | H5-03 Communication parity selection | Default 0. | UINT16 | Read/write | 0 = No parity; 1 = Even parity; 2 = Odd parity | |||
| HR | 1064doc 0428H | H5-04 Communication error stop method | Default 3. | UINT16 | Read/write | 0 = Ramp to stop; 1 = Coast to stop; 2 = Fast stop (C1-09); 3 = Alarm only; 4 = Run at H5-34 (CE go-to frequency) | |||
| HR | 1065doc 0429H | H5-05 Comm fault detection selection | Default 1. | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | |||
| HR | 1066doc 042AH | H5-06 Drive transmit wait time | 0-65 ms, default 5 ms. | UINT16 | ms | Read/write | |||
| HR | 1077doc 0435H | H5-09 CE detection time | 0.0-10.0 s, default 2.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 1078doc 0436H | H5-10 Modbus register 0025H unit selection | UINT16 | Read/write | 0 = 0.1 V units; 1 = 1 V units | ||||
| HR | 1084doc 043CH | H5-11 Comm ENTER command mode | Default 0. | UINT16 | Read/write | 0 = ENTER command required; 1 = ENTER command not required | |||
| HR | 1581doc 062DH | H5-08 Communication protocol selection | Default 3 (BACnet); set 0 for Modbus. | UINT16 | Read/write | 0 = Modbus/MEMOBUS; 1 = Metasys N2; 2 = APOGEE P1; 3 = BACnet | |||
| HR | 2304doc 0900H | Enter command (save to EEPROM) | Write 0 to store written parameters. | UINT16 | Write | ||||
| HR | 2320doc 0910H | Enter command (RAM only) | Write 0 to apply written parameters without saving. | UINT16 | Write | ||||
| HR | 2903doc 0B57H | H5-20 Communication parameters reload | UINT16 | Read/write | 0 = Reload at next power cycle; 1 = Reload now | ||||
| HR | 33792doc 8400H | Bypass command word | BITMAP16 | Read/write | bit 3 = Remote transfer; bit 4 = Emergency override bypass; bit 5 = Emergency override (FWD); bit 6 = Motor OR; bit 7 = Motor AND; bit 11 = Drive select (Z1-39); bit 12 = Bypass select (Z1-39); bit 13 = Fault reset; bit 14 = EFB; bit 15 = Emergency override drive (REV) | ||||
| HR | 33794doc 8402H | Bypass MFDI command | Bypass digital inputs TB2-1..8 when Z3-12 = 1. | BITMAP16 | Read/write | bit 0 = Bypass digital input 1 (TB2-1); bit 1 = Bypass digital input 2 (TB2-2); bit 2 = Bypass digital input 3 (TB2-3); bit 3 = Bypass digital input 4 (TB2-4); bit 4 = Bypass digital input 5 (TB2-5); bit 5 = Bypass digital input 6 (TB2-6); bit 6 = Bypass digital input 7 (TB2-7); bit 7 = Bypass digital input 8 (TB2-8) | |||
| HR | 33795doc 8403H | Bypass MFDO command | Bypass outputs whose Z2-xx function is 99 (not used). | BITMAP16 | Read/write | bit 6 = Digital output 7 (TB1 1-3); bit 7 = Digital output 8 (TB1 4-6); bit 8 = Digital output 9 (TB1 7-9); bit 9 = Digital output 10 (TB1 10-12) | |||
| HR | 34059doc 850BH | Z3-12 Network digital inputs | Enables 0001H bits 4-B and 8402H. | UINT16 | Read/write | 0 = Disabled; 1 = Enabled |
Notes on this map
- H5-08 defaults to 3 (BACnet) on this package; it must be set to 0 for Modbus.
- Frequency registers 0002H, 0023H and 0024H use the units chosen in o1-03, so they are left unscaled.
- Left out: 0007H/0008H analog outputs, 0025H output voltage (unit switched by H5-10), 0026H/0027H output current and power, 002DH and later monitors not checked row by row, the U-monitor, fault-trace and fault-description blocks from 0040H, 15FFH (no unit given), the clock registers 3004H-3030H and emergency-override registers 3A93H-3A96H.
- The command table prints run bits 0/1 with both meanings (forward run / run and reverse run / reverse) without naming the selecting parameter; on the drive this is H5-12, which is not in the bypass H5 list.
- Supported function codes are 03H, 08H, 10H, 5AH and 67H; there is no 06H, so use 10H even for a single register.
- With H5-11 = 0 (default), parameter writes take effect only after the Enter command (0900H or 0910H).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU)
What Modbus registers does the Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU) have?
This map lists 35 registers: 35 holding registers. 26 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and are sent unchanged: the manual's read example asks for starting register 0020H as bytes 00 20. Parameters use the hex number printed under each parameter (H5-01 = 0425H, Z3-12 = 850BH).
What are the minimum Modbus registers to integrate the Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU)?
Start with HR 1 Run command / drive MFDI command (Run/stop, direction, fault reset); HR 2 Frequency reference (Frequency reference (o1-03 units)); HR 33792 Bypass command word (Bypass command word (drive/bypass select)); HR 32 Drive status 1 (Drive/bypass status 1); HR 33 Fault description 1 (Fault description 1); HR 36 U1-02 Output frequency (U1-02 output frequency); HR 44 Drive status 2 (Drive status 2 incl. comm timeout).
How do I enable Modbus control of the Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU)?
H5-08 = 0 selects Modbus (default 3 = BACnet). Set H5-01 address (default 1FH), H5-02 speed (default 3 = 9600 bps), H5-03 parity (default 0 = none), then cycle power or set H5-20 = 1. Set b1-01 = 2 and b1-02 = 2 for serial control; Z3-12 = 1 lets 0001H bits 4-B and 8402H drive the digital inputs.
What happens when the Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU) loses Modbus communication?
H5-05 = 1 (default) enables CE detection after H5-09 (0.0-10.0 s, default 2.0 s); H5-04 sets the reaction (0 ramp, 1 coast, 2 fast stop, 3 alarm only - default, 4 run at H5-34 with H5-35 as an optional timeout). Drive status 2 (002CH) bit F shows a timeout.
Where is the official Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU) Modbus documentation?
The source is FP605 Enclosed Bypass Technical Reference (SIEPYAIF6B01C), published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=SIEPYAIF6B01&cmd=documents&documentName=SIEPYAIF6B01.pdf.
More Yaskawa Modbus register maps
- Variable frequency drive
Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa A1000 drives (CIMR-AU; 200 V, 400 V and 600 V classes) using the built-in RS-422/485 MEMOBUS/Modbus terminals (TB5), per Technical Manual SIEP C710616 41H.
Also known as: CIMR-AU, CIMR-AUA, A1000 High Performance Vector Control Drive - Variable frequency drive (HVAC)
Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU
Yaskawa E7 (CIMR-E7U) HVAC fan and pump drives using the built-in RS-422/485 terminals with H5-08 = 0 (Memobus/Modbus), per Parameter Access Technical Manual TM.E7.11 (rev 3016).
Also known as: CIMR-E7U, E7U, E7 Drive - Variable frequency drive
Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU
Yaskawa F7 (CIMR-F7U) general-purpose drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.F7.01 Appendix D, with parameter and monitor addresses from TM.F7.11.
Also known as: CIMR-F7U, F7U, F7 Drive - Variable frequency drive
Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa FP605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per technical reference SIEPC7106171F.
Also known as: CIPR-FP6, FP605 drive, FP605 AC Drive for Industrial Fan and Pump Applications - Variable frequency drive
Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU
Yaskawa G7 (CIMR-G7U) drives using built-in Modbus RTU on terminals R+/R-/S+/S-, per the Modbus Communication Manual G7 TM.G7.11 (rev 07-01).
Also known as: CIMR-G7U, G7U, G7 Drive - Variable frequency drive
Yaskawa GA500 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA500 drives using the built-in RS-485 MEMOBUS/Modbus port (terminal TB4), per technical reference SIEPC71061752 revision C.
Also known as: CIPR-GA50U, GA500 Versatile Compact - Variable frequency drive
Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA800 drives using the built-in RS-485 MEMOBUS/Modbus port, per technical reference SIEPC71061737 revision G.
Also known as: CIPR-GA80, GA800 Industrial AC Microdrive - Variable frequency drive
Yaskawa HV305 HVAC micro drive (MEMOBUS/Modbus RTU)
Yaskawa HV305 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPYAIHV3001B.
Also known as: HV35U, HV305 drive, HV305 Versatile Compact Drive - Variable frequency drive
Yaskawa HV600 HVAC fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa HV600 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPC71061732 revision F.
Also known as: CIPR-HV60, HV600 HVAC drive - Variable frequency drive (HVAC bypass package)
Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)
Yaskawa HV600 Narrow and Enclosed Bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (Modbus); Technical Reference SIEPYAIH6B01F, section 10.6.
Also known as: HV600 Bypass, HV600 Enclosed Bypass, HV600 Narrow Bypass - Variable frequency drive (pump)
Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU
Legacy Yaskawa iQpump drives built on the P7U platform (CIMR-P7U...), per user manual TM.iQp.01, using the built-in RS-422/485 terminals R+/R-/S+/S-.
Also known as: iQpump, CIMR-P7U iQpump, iQpump Drive - Variable frequency drive
Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump Micro drives using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEP YAIQPM 03B.
Also known as: CIMR-PW (iQpump Micro), iQpump Micro AC Drive, iQpump Micro Compact Intelligent Pump Controller - Variable frequency drive
Yaskawa iQpump1000 intelligent pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump1000 drives (CIMR-PW) using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEPYAIP1W01G.
Also known as: CIMR-PW, CIMR-PWA, iQpump1000 AC Drive - Variable frequency drive
Yaskawa iQpump605 intelligent pump controller (MEMOBUS/Modbus RTU)
Yaskawa iQpump605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per user manual SIEPYAIWM6502D.
Also known as: WM65W, iQpump605 drive, iQpump605 Intelligent Pump Controller - Variable frequency drive
Yaskawa J1000 compact V/f drive (MEMOBUS/Modbus RTU)
Yaskawa J1000 drives (CIMR-JU/JC) with the optional RS-422/485 MEMOBUS/Modbus interface, per Technical Manual SIEP C710606 31D.
Also known as: CIMR-JU, CIMR-JC, J1000 Compact V/f Control Drive - Variable frequency drive (HVAC bypass package)
Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU)
P1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIP1B 01D, appendix D.
Also known as: P1000 Bypass, P1B - Variable frequency drive
Yaskawa P1000 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa P1000 drives using the built-in RS-485/422 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP YAIP1U 01C.
Also known as: CIMR-PU, P1000 Industrial Fan and Pump Drive - Variable frequency drive (fan / pump)
Yaskawa P7 fan/pump drive (CIMR-P7U, legacy) - Modbus RTU
Yaskawa P7 (CIMR-P7U) fan and pump drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.P7.01 Appendix D.
Also known as: CIMR-P7U, P7U, P7 Drive - Variable frequency drive (fan / pump bypass package)
Yaskawa P7B drive/bypass (legacy) - Modbus RTU
Yaskawa P7B drive/bypass packages (P7 drive CIMR-P7U inside a bypass enclosure, option V native Modbus) using the drive's RS-422/485 terminals, per technical manual TM.P7B.01 Appendix D.
Also known as: P7B, P7 Bypass - Variable frequency drive
Yaskawa U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU)
Yaskawa U1000 matrix drives using the built-in RS-422/485 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP C710636 04E.
Also known as: CIMR-UU, U1000 Industrial MATRIX Drive - Variable frequency drive
Yaskawa V1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa V1000 drives (CIMR-VU; 200 V single/three-phase and 400 V three-phase, 0.1-18.5 kW) using the built-in RS-422/485 MEMOBUS/Modbus terminals, per Technical Manual SIEP C710606 18F.
Also known as: CIMR-VU, V1000 Compact Vector Control Drive - Variable frequency drive
Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU
Yaskawa V7 (CIMR-V7AM) and V74X (CIMR-V7CU) compact drives with built-in Modbus RTU (keypad RJ-45 or R+/R-/S+/S- terminals), per TM.V7.11 Rev 07-01.
Also known as: CIMR-V7AM, CIMR-V7CU, V74X - Variable frequency drive (HVAC bypass package)
Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU)
Z1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIZ1B 01F, appendix D.
Also known as: Z1000 Bypass, Z1B1 - Variable frequency drive (HVAC fan / pump)
Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000 HVAC drives (CIMR-ZU) using the built-in RS-485 terminals with H5-08 = 0, per Programming Manual SIEP YAIZ1U 03C (the copy covers the 600 V class models 5A0007-5A0242).
Also known as: CIMR-ZU, Z1000 AC Drive for HVAC Fan and Pump - Variable frequency drive
Yaskawa Z1000U HVAC matrix drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000U HVAC matrix drives using the built-in serial terminals with H5-08 = 0 (MEMOBUS/Modbus), per programming manual SIEP C710636 10D.
Also known as: Z1000U HVAC MATRIX Drive, Z1000U Matrix
Other variable frequency drives register maps
- Variable frequency drive
ABB ACS310 pump and fan drive (embedded Modbus RTU)
ACS310 drives (01E/01U/03E/03U) using the embedded fieldbus: Modbus RTU on the built-in EIA-485 terminals 23-26 or RS-232 on the panel connector; user's manual 3AUA0000044201 Rev D.
Also known as: ACS310-01E, ACS310-01U, ACS310-03E, ACS310-03U - Variable frequency drive
ABB ACS880 industrial drive, primary control program (embedded Modbus RTU)
ACS880 drives running the primary control program (AINLX) 3.4x or later, embedded fieldbus (EFB) Modbus RTU on terminal XD2D, 58.33 Addressing mode = Mode 0 (default).
Also known as: ACS880-01, ACS880-04, ACS880-07, ACS880-11, ACS880-17, ACS880-31, ACS880-37, AINLX, ACS880 primary control program - Variable frequency drive
AutomationDirect GS2 series AC drive
All GS2 drives; status addresses and P9.xx serial-communication parameters from chapter 5 of the user manual.
Also known as: GS2-10P2, GS2-10P5, GS2-11P0, GS2-20P5, GS2-21P0, GS2-22P0, GS2-23P0, GS2-25P0, GS2-27P5, GS2-41P0, GS2-42P0, GS2-43P0, GS2-45P0, GS2-47P5 - Variable frequency drive
Danfoss VLT Compressor Drive CDS 803 (Modbus RTU)
VLT Compressor Drive CDS 803 (variable-speed compressor drive for HVAC/R) using the built-in RS-485 port with 8-30 Protocol = Modbus RTU; Modbus rules from Design Guide MG18N202 (software 1.20), parameter data from Programming Guide MG18P202 (software 2.0).
Also known as: CDS803, CDS-803, VLT Compressor Drive CDS 803 - Variable frequency drive
Eaton PowerXL DA1 variable frequency drive (Modbus RTU)
Eaton PowerXL DA1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DA1, PowerXL DA1, DA1-12, DA1-32, DA1-34, DA1-35 - Variable frequency drive
Hitachi SJ-P1 series inverter (Modbus RTU, firmware Ver. 2.00)
Hitachi SJ-P1 inverters on the built-in RS485 port in Modbus-RTU mode, register layout of firmware Ver. 2.00 (User's Guide NT251BX-2, Rev. 6).
Also known as: SJ-P1, P1-xxxxx-L, P1-xxxxx-H
All variable frequency drives Modbus register maps →
Source: FP605 Enclosed Bypass Technical Reference · SIEPYAIF6B01C. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.