- iQpump Micro compact pump drive (MEMOBUS/Modbus RTU)
Variable frequency drive · Modbus register map
Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU) Modbus register map
Updated 19 November 2026
Yaskawa's compact pump drive with built-in pump functions and an RS-485/422 MEMOBUS/Modbus RTU port. Command registers (run bits, frequency reference, PID target, outputs) start at 0001H, status and monitor registers at 0020H, and parameters are reachable at their hex numbers. This map covers the command and status words, key monitors, fault/alarm bits and the b1/H5 setup parameters.
This page lists 36 Modbus registers for the Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU) — 21 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yaskawa’s own free documentation (linked below) and checked against it.
- Manufacturer
- Yaskawa
- Model
- iQpump Micro compact pump drive (MEMOBUS/Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 36 (21 writable)
- Transport
- Modbus RTU
- Default unit ID
- 31
- Default serial
- 9600 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- CIMR-PW (iQpump Micro), iQpump Micro AC Drive, iQpump Micro Compact Intelligent Pump Controller
- Source document
- YASKAWA AC Drive iQpump Micro User Manual · TOEP YAIQPM 03B
Integration notes: Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU)
Set H5-01..H5-03 and power-cycle, then b1-01 = 2 and b1-02 = 2 so the frequency reference and Run come from Modbus. Write 0001H (run bits) and 0002H (frequency reference) with function 10H and poll 0020H, 0021H, 002AH and 002CH.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1 | Operation commands and multi-function inputs | BITMAP16 | Run/stop, direction, fault reset | Read/write |
| HR 2 | Frequency reference | UINT16 | Frequency reference (o1-03 units) | Read/write |
| HR 32 | Drive status 1 | BITMAP16 | Drive status 1 | Read |
| HR 33 | Fault contents 1 | BITMAP16 | Fault contents 1 | Read |
| HR 36 | Output frequency | UINT16 | Output frequency | Read |
| HR 42 | Alarm contents 1 | BITMAP16 | Alarm contents 1 | Read |
| HR 44 | Drive status 2 | BITMAP16 | Drive status 2 incl. comm timeout | Read |
Enable Modbus control & writes
Set H5-01 node address (default 1FH), H5-02 speed (default 3 = 9600 bps) and H5-03 parity (default 0 = none), then cycle power. For control set b1-01 = 2 and b1-02 = 2. H5-12 decides whether 0001H bits 0/1 are FWD/REV run or Run plus direction.
Communication loss & watchdog
H5-05 = 1 (default) enables CE detection after H5-09 (0.0-10.0 s, default 2.0 s) without data; H5-04 sets the reaction (0 ramp, 1 coast, 2 fast stop with C1-09, 3 alarm only and continue - default).
Byte order & addressing
- Registers are hex and 0-based: 0020H is sent as 00 20.
- No function 06H; use 10H.
- Parameter writes need the Enter command unless H5-11 = 1.
Network setup
- Wire the MEMOBUS/Modbus terminals R+, R-, S+, S-; keep H5-07 = 1 (RTS control) for RS-485.
- Power-cycle after changing the H5 communication settings.
Watch out for
- Network inputs in 0001H are ORed with the physical terminals.
- Section C.5 limits node addresses to 0-20H (the parameter list says FFH); stay at 20H or below to be safe.
Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 0001H | Operation commands and multi-function inputs | Run bits follow H5-12; bits 4-A drive multi-function inputs 1-7. | BITMAP16 | Read/write | bit 0 = H5-12=0: forward run (1) / stop; H5-12=1: run (1) / stop; bit 1 = H5-12=0: reverse run (1) / stop; H5-12=1: reverse (1) / forward; bit 2 = External fault EF0; bit 3 = Fault reset; bit 4 = Multi-function input 1 (ComRef when H1-01 = 40); bit 5 = Multi-function input 2 (ComCtrl when H1-02 = 41); bit 6 = Multi-function input 3; bit 7 = Multi-function input 4; bit 8 = Multi-function input 5; bit 9 = Multi-function input 6; bit 10 = Multi-function input 7 | |||
| HR | 2doc 0002H | Frequency reference | Units set by o1-03. | UINT16 | Read/write | ||||
| HR | 3doc 0003H | Output voltage gain | 20-2000 (2.0-200.0 %), 1000 at power-up. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 6doc 0006H | PID target | Signed; enable with 000FH bit 1. | INT16 | × 0.01 | % | Read/write | ||
| HR | 9doc 0009H | Multi-function digital output settings | Drive the outputs from the network. | BITMAP16 | Read/write | bit 0 = Contact output MA/MB-MC; bit 1 = Photocoupler output 1 P1-PC; bit 2 = Photocoupler output 2 P2-PC | |||
| HR | 15doc 000FH | Control selection setting | Enables network setpoints and broadcast terminal inputs. | BITMAP16 | Read/write | bit 1 = PID target input; bit 12 = Broadcast terminal S5 input; bit 13 = Broadcast terminal S6 input; bit 14 = Broadcast terminal S7 input | |||
| HR | 32doc 0020H | Drive status 1 | BITMAP16 | Read | bit 0 = During run; bit 1 = During reverse; bit 2 = Drive ready; bit 3 = Fault; bit 4 = Data setting error; bit 5 = Contact output MA/MB-MC; bit 6 = Photocoupler output 1 P1-PC; bit 7 = Photocoupler output 2 P2-PC; bit 14 = ComRef enabled; bit 15 = ComCtrl enabled | ||||
| HR | 33doc 0021H | Fault contents 1 | BITMAP16 | Read | bit 0 = oC overcurrent / GF ground fault / SC IGBT short circuit; bit 1 = ov overvoltage; bit 2 = oL2 drive overload; bit 3 = oH1 overheat / oH2 drive overheat warning; bit 4 = rr braking transistor / rH braking resistor overheat; bit 6 = FbL / FbH PID feedback loss; bit 7 = EF0 to EF7 external fault; bit 8 = CPFxx hardware fault (incl. oFAxx); bit 9 = oL1 motor overload, oL3/oL4 overtorque, UL3/UL4 undertorque; bit 10 = oS overspeed; bit 11 = Uv main circuit undervoltage; bit 12 = Uv1/Uv2/Uv3 undervoltage; bit 13 = LF output / PF input phase loss; bit 14 = CE Modbus / bUS option communication error; bit 15 = oPr operator connection fault | ||||
| HR | 34doc 0022H | Data link status | Errors from the last write. | BITMAP16 | Read | bit 0 = Writing data or switching motors; bit 3 = Upper or lower limit error; bit 4 = Data conformity error; bit 5 = Writing to EEPROM | |||
| HR | 35doc 0023H | Frequency reference monitor | Units set by o1-03. | UINT16 | Read | ||||
| HR | 36doc 0024H | Output frequency | Units set by o1-03. | UINT16 | Read | ||||
| HR | 41doc 0029H | Fault contents 2 | BITMAP16 | Read | bit 0 = SC IGBT short circuit or ground fault; bit 1 = GF ground fault; bit 2 = PF input phase loss; bit 3 = LF output phase loss; bit 4 = rH braking resistor overheat; bit 6 = oH4 motor overheat 2 (PTC) | ||||
| HR | 42doc 002AH | Alarm contents 1 | Alarms that do not trip the drive. | BITMAP16 | Read | bit 2 = EF run command input error; bit 3 = bb baseblock; bit 4 = oL3 overtorque 1; bit 5 = oH heatsink overheat; bit 6 = ov overvoltage; bit 7 = Uv undervoltage; bit 9 = CE Modbus communication error; bit 10 = bUS option communication error; bit 11 = UL3/UL4 undertorque; bit 12 = oH3 motor overheat; bit 15 = CALL serial transmission error | |||
| HR | 43doc 002BH | Input terminal status | BITMAP16 | Read | bit 0 = Terminal S1 closed; bit 1 = Terminal S2 closed; bit 2 = Terminal S3 closed; bit 3 = Terminal S4 closed; bit 4 = Terminal S5 closed; bit 5 = Terminal S6 closed; bit 6 = Terminal S7 closed | ||||
| HR | 44doc 002CH | Drive status 2 | BITMAP16 | Read | bit 0 = During run; bit 1 = Zero speed; bit 2 = Speed agree; bit 3 = User speed agree; bit 4 = Frequency detection 1; bit 5 = Frequency detection 2; bit 6 = Drive ready; bit 7 = During undervoltage; bit 8 = During baseblock; bit 9 = Frequency reference (as printed); bit 10 = Run command (as printed); bit 11 = Over/undertorque 1, 2; bit 12 = Frequency reference loss; bit 13 = During fault restart; bit 14 = Fault; bit 15 = Communication timeout | ||||
| HR | 45doc 002DH | Output terminal status | BITMAP16 | Read | bit 0 = Contact output MA/MB-MC; bit 1 = Photocoupler output 1 P1-PC; bit 2 = Photocoupler output 2 P2-PC | ||||
| HR | 49doc 0031H | DC bus voltage | UINT16 | V | Read | ||||
| HR | 56doc 0038H | PID feedback | Unsigned; 100 % = max. output frequency. | UINT16 | × 0.1 | % | Read | ||
| HR | 57doc 0039H | PID input | Signed; 100 % = max. output frequency. | INT16 | × 0.1 | % | Read | ||
| HR | 58doc 003AH | PID output | Signed; 100 % = max. output frequency. | INT16 | × 0.1 | % | Read | ||
| HR | 61doc 003DH | Communications error contents | BITMAP16 | Read | bit 0 = CRC error; bit 1 = Data length error; bit 3 = Parity error; bit 4 = Overrun error; bit 5 = Framing error; bit 6 = Timeout | ||||
| HR | 384doc 0180H | b1-01 Frequency reference selection 1 | Set 2 (serial communication) for a Modbus frequency reference. | UINT16 | Read/write | 0 = Operator (keypad); 1 = Analog input terminals; 2 = MEMOBUS/Modbus communications; 3 = Option PCB; 4 = Pulse input (terminal RP) | |||
| HR | 385doc 0181H | b1-02 Run command selection 1 | Set 2 to take Run from Modbus. | UINT16 | Read/write | 0 = HOA keypad; 1 = Digital input terminals; 2 = MEMOBUS/Modbus communications; 3 = Option PCB | |||
| HR | 1061doc 0425H | H5-01 Drive node address | Default 1FH; 0 = no response. C.5 gives 0-20H, parameter list up to FFH. | UINT16 | Read/write | ||||
| HR | 1062doc 0426H | H5-02 Communication speed selection | Default 3. | UINT16 | Read/write | 0 = 1200 bps; 1 = 2400 bps; 2 = 4800 bps; 3 = 9600 bps; 4 = 19.2 kbps; 5 = 38.4 kbps | |||
| HR | 1063doc 0427H | H5-03 Communication parity selection | Default 0. | UINT16 | Read/write | 0 = No parity; 1 = Even parity; 2 = Odd parity | |||
| HR | 1064doc 0428H | H5-04 Stopping method after CE | Default 3. | UINT16 | Read/write | 0 = Ramp to stop; 1 = Coast to stop; 2 = Fast stop (C1-09); 3 = Alarm only, continue | |||
| HR | 1065doc 0429H | H5-05 Communication fault detection selection | Default 1. | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | |||
| HR | 1066doc 042AH | H5-06 Drive transmit wait time | 5-65 ms, default 5 ms. | UINT16 | ms | Read/write | |||
| HR | 1067doc 042BH | H5-07 RTS control selection | Default 1; 0 only for point-to-point RS-422. | UINT16 | Read/write | 0 = Disabled (RTS always on); 1 = Enabled | |||
| HR | 1077doc 0435H | H5-09 Communications fault detection time | 0.0-10.0 s, default 2.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 1078doc 0436H | H5-10 Unit selection for register 0025H | UINT16 | Read/write | 0 = 0.1 V units; 1 = 1 V units | ||||
| HR | 1084doc 043CH | H5-11 Communications enter function selection | Default 0. | UINT16 | Read/write | 0 = Enter command necessary; 1 = Enter command not necessary | |||
| HR | 1085doc 043DH | H5-12 Run command method selection | Meaning of 0001H bits 0/1; default 0. | UINT16 | Read/write | 0 = FWD/Stop, REV/Stop; 1 = Run/Stop, FWD/REV | |||
| HR | 2304doc 0900H | Enter command (save to EEPROM) | Write 0 to store written parameters in EEPROM. | UINT16 | Write | ||||
| HR | 2320doc 0910H | Enter command (RAM only) | Write 0 to apply written parameters without saving. | UINT16 | Write |
Notes on this map
- Frequency registers 0002H, 0023H and 0024H use the units chosen in o1-03, so they are left unscaled.
- Left out: 0007H analog output and 000AH pulse output settings, 0025H output voltage (unit switched by H5-10), 0026H output current (unit given by a footnote that varies), 0027H output power, 0028H/0032H torque, 002FH frequency reference bias, 003EH/003FH output frequency in r/min or 0.01 % (sign not stated), the U-monitor blocks from 0040H and the real-time-clock registers 3004H-3030H.
- Only function codes 03H (read, max. 16 registers), 08H (loopback) and 10H (write multiple) are supported; use 10H for single writes.
- The manual disagrees on the H5-01 range: section C.5 and the slave-address text give 0-20H, the parameter list gives 0-FFH. H5-02 accepts 0-5 (up to 38400 bps) per C.5 even though the speed table prints settings up to 8.
- With H5-11 = 0 (default), parameter writes take effect only after the Enter command (0900H or 0910H). Command registers do not need Enter.
- Data length 8 bits and 1 stop bit are fixed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU)
What Modbus registers does the Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU) have?
This map lists 36 registers: 36 holding registers. 21 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and sent unchanged: the manual's read example asks slave 2 for starting register 0020H as Starting No. 00H 20H. Parameters use the hex numbers in the parameter list (H5-01 = 0425H).
What are the minimum Modbus registers to integrate the Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU)?
Start with HR 1 Operation commands and multi-function inputs (Run/stop, direction, fault reset); HR 2 Frequency reference (Frequency reference (o1-03 units)); HR 32 Drive status 1 (Drive status 1); HR 33 Fault contents 1 (Fault contents 1); HR 36 Output frequency (Output frequency); HR 42 Alarm contents 1 (Alarm contents 1); HR 44 Drive status 2 (Drive status 2 incl. comm timeout).
How do I enable Modbus control of the Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU)?
Set H5-01 node address (default 1FH), H5-02 speed (default 3 = 9600 bps) and H5-03 parity (default 0 = none), then cycle power. For control set b1-01 = 2 and b1-02 = 2. H5-12 decides whether 0001H bits 0/1 are FWD/REV run or Run plus direction.
What happens when the Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU) loses Modbus communication?
H5-05 = 1 (default) enables CE detection after H5-09 (0.0-10.0 s, default 2.0 s) without data; H5-04 sets the reaction (0 ramp, 1 coast, 2 fast stop with C1-09, 3 alarm only and continue - default).
Where is the official Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU) Modbus documentation?
The source is YASKAWA AC Drive iQpump Micro User Manual (TOEP YAIQPM 03B), published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=TOEPYAIQPM03&cmd=documents&documentName=TOEPYAIQPM03.pdf.
More Yaskawa Modbus register maps
- Variable frequency drive
Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa A1000 drives (CIMR-AU; 200 V, 400 V and 600 V classes) using the built-in RS-422/485 MEMOBUS/Modbus terminals (TB5), per Technical Manual SIEP C710616 41H.
Also known as: CIMR-AU, CIMR-AUA, A1000 High Performance Vector Control Drive - Variable frequency drive (HVAC)
Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU
Yaskawa E7 (CIMR-E7U) HVAC fan and pump drives using the built-in RS-422/485 terminals with H5-08 = 0 (Memobus/Modbus), per Parameter Access Technical Manual TM.E7.11 (rev 3016).
Also known as: CIMR-E7U, E7U, E7 Drive - Variable frequency drive
Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU
Yaskawa F7 (CIMR-F7U) general-purpose drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.F7.01 Appendix D, with parameter and monitor addresses from TM.F7.11.
Also known as: CIMR-F7U, F7U, F7 Drive - Variable frequency drive
Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU)
Yaskawa FP605 enclosed bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (MEMOBUS/Modbus); Technical Reference SIEPYAIF6B01C, section 10.6.
Also known as: FP605 Enclosed Bypass, FP605 bypass package - Variable frequency drive
Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa FP605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per technical reference SIEPC7106171F.
Also known as: CIPR-FP6, FP605 drive, FP605 AC Drive for Industrial Fan and Pump Applications - Variable frequency drive
Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU
Yaskawa G7 (CIMR-G7U) drives using built-in Modbus RTU on terminals R+/R-/S+/S-, per the Modbus Communication Manual G7 TM.G7.11 (rev 07-01).
Also known as: CIMR-G7U, G7U, G7 Drive - Variable frequency drive
Yaskawa GA500 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA500 drives using the built-in RS-485 MEMOBUS/Modbus port (terminal TB4), per technical reference SIEPC71061752 revision C.
Also known as: CIPR-GA50U, GA500 Versatile Compact - Variable frequency drive
Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA800 drives using the built-in RS-485 MEMOBUS/Modbus port, per technical reference SIEPC71061737 revision G.
Also known as: CIPR-GA80, GA800 Industrial AC Microdrive - Variable frequency drive
Yaskawa HV305 HVAC micro drive (MEMOBUS/Modbus RTU)
Yaskawa HV305 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPYAIHV3001B.
Also known as: HV35U, HV305 drive, HV305 Versatile Compact Drive - Variable frequency drive
Yaskawa HV600 HVAC fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa HV600 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPC71061732 revision F.
Also known as: CIPR-HV60, HV600 HVAC drive - Variable frequency drive (HVAC bypass package)
Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)
Yaskawa HV600 Narrow and Enclosed Bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (Modbus); Technical Reference SIEPYAIH6B01F, section 10.6.
Also known as: HV600 Bypass, HV600 Enclosed Bypass, HV600 Narrow Bypass - Variable frequency drive (pump)
Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU
Legacy Yaskawa iQpump drives built on the P7U platform (CIMR-P7U...), per user manual TM.iQp.01, using the built-in RS-422/485 terminals R+/R-/S+/S-.
Also known as: iQpump, CIMR-P7U iQpump, iQpump Drive - Variable frequency drive
Yaskawa iQpump1000 intelligent pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump1000 drives (CIMR-PW) using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEPYAIP1W01G.
Also known as: CIMR-PW, CIMR-PWA, iQpump1000 AC Drive - Variable frequency drive
Yaskawa iQpump605 intelligent pump controller (MEMOBUS/Modbus RTU)
Yaskawa iQpump605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per user manual SIEPYAIWM6502D.
Also known as: WM65W, iQpump605 drive, iQpump605 Intelligent Pump Controller - Variable frequency drive
Yaskawa J1000 compact V/f drive (MEMOBUS/Modbus RTU)
Yaskawa J1000 drives (CIMR-JU/JC) with the optional RS-422/485 MEMOBUS/Modbus interface, per Technical Manual SIEP C710606 31D.
Also known as: CIMR-JU, CIMR-JC, J1000 Compact V/f Control Drive - Variable frequency drive (HVAC bypass package)
Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU)
P1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIP1B 01D, appendix D.
Also known as: P1000 Bypass, P1B - Variable frequency drive
Yaskawa P1000 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa P1000 drives using the built-in RS-485/422 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP YAIP1U 01C.
Also known as: CIMR-PU, P1000 Industrial Fan and Pump Drive - Variable frequency drive (fan / pump)
Yaskawa P7 fan/pump drive (CIMR-P7U, legacy) - Modbus RTU
Yaskawa P7 (CIMR-P7U) fan and pump drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.P7.01 Appendix D.
Also known as: CIMR-P7U, P7U, P7 Drive - Variable frequency drive (fan / pump bypass package)
Yaskawa P7B drive/bypass (legacy) - Modbus RTU
Yaskawa P7B drive/bypass packages (P7 drive CIMR-P7U inside a bypass enclosure, option V native Modbus) using the drive's RS-422/485 terminals, per technical manual TM.P7B.01 Appendix D.
Also known as: P7B, P7 Bypass - Variable frequency drive
Yaskawa U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU)
Yaskawa U1000 matrix drives using the built-in RS-422/485 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP C710636 04E.
Also known as: CIMR-UU, U1000 Industrial MATRIX Drive - Variable frequency drive
Yaskawa V1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa V1000 drives (CIMR-VU; 200 V single/three-phase and 400 V three-phase, 0.1-18.5 kW) using the built-in RS-422/485 MEMOBUS/Modbus terminals, per Technical Manual SIEP C710606 18F.
Also known as: CIMR-VU, V1000 Compact Vector Control Drive - Variable frequency drive
Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU
Yaskawa V7 (CIMR-V7AM) and V74X (CIMR-V7CU) compact drives with built-in Modbus RTU (keypad RJ-45 or R+/R-/S+/S- terminals), per TM.V7.11 Rev 07-01.
Also known as: CIMR-V7AM, CIMR-V7CU, V74X - Variable frequency drive (HVAC bypass package)
Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU)
Z1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIZ1B 01F, appendix D.
Also known as: Z1000 Bypass, Z1B1 - Variable frequency drive (HVAC fan / pump)
Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000 HVAC drives (CIMR-ZU) using the built-in RS-485 terminals with H5-08 = 0, per Programming Manual SIEP YAIZ1U 03C (the copy covers the 600 V class models 5A0007-5A0242).
Also known as: CIMR-ZU, Z1000 AC Drive for HVAC Fan and Pump - Variable frequency drive
Yaskawa Z1000U HVAC matrix drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000U HVAC matrix drives using the built-in serial terminals with H5-08 = 0 (MEMOBUS/Modbus), per programming manual SIEP C710636 10D.
Also known as: Z1000U HVAC MATRIX Drive, Z1000U Matrix
Other variable frequency drives register maps
- Variable frequency drive
ABB ACH480 HVAC drive (embedded Modbus RTU)
ACH480 drives running the ACH480 HVAC control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000247134 Rev E.
Also known as: ACH480-04, ACH480 HVAC control program - Variable frequency drive
ABB ACS380 machinery drive (embedded Modbus RTU)
ACS380 drives running the machinery control program with the BMIO-01 I/O and Modbus RTU module, embedded fieldbus (EFB), addressing mode 0 (default); firmware manual 3AXD50000029275 Rev J.
Also known as: ACS380-04, ACS380 machinery control program, BMIO-01 - Pump (vertical in-line with integrated VFD)
Armstrong Fluid Technology Design Envelope 4300 / 4380 with DEPM IVS / DE IVS drive (map v2)
Armstrong Design Envelope 4300 and 4380 vertical in-line pumps with DEPM IVS or DE IVS drive, controller firmware v1.17 and newer (Modbus register map version 2).
Also known as: Design Envelope 4300, Design Envelope 4380, DEPM IVS, DE IVS, Design Envelope pump controller, DEPC - Variable frequency drive
Bonfiglioli Agile frequency inverter (Modbus RTU/ASCII)
Bonfiglioli Agile 230 V / 400 V frequency inverters, Modbus on the X21 RJ45 connection or a CM-232/CM-485 module, per Modbus communication manual VEC 691 R1 (02/2011).
Also known as: Agile, AGL, Bonfiglioli Agile - Variable frequency drive
Danfoss VLT HVAC Drive FC 102 (Modbus RTU)
VLT HVAC Drive FC 102 using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter scaling checked against the software 7.61 programming guide.
Also known as: VLT HVAC Drive, FC102, FC-102 - Variable frequency drive
Eaton PowerXL DC1 compact drive (Modbus RTU)
Eaton PowerXL DC1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DC1, PowerXL DC1, DC1-1D, DC1-12, DC1-32, DC1-34, DC1-S2
All variable frequency drives Modbus register maps →
Source: YASKAWA AC Drive iQpump Micro User Manual · TOEP YAIQPM 03B. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.