Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

Yaskawa's compact pump drive with built-in pump functions and an RS-485/422 MEMOBUS/Modbus RTU port. Command registers (run bits, frequency reference, PID target, outputs) start at 0001H, status and monitor registers at 0020H, and parameters are reachable at their hex numbers. This map covers the command and status words, key monitors, fault/alarm bits and the b1/H5 setup parameters.

This page lists 36 Modbus registers for the Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU) — 21 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yaskawa’s own free documentation (linked below) and checked against it.

Manufacturer
Yaskawa
Model
iQpump Micro compact pump drive (MEMOBUS/Modbus RTU)
Equipment type
Variable frequency drive
Registers
36 (21 writable)
Transport
Modbus RTU
Default unit ID
31
Default serial
9600 baud, 8N1
Documented addressing
hexadecimal, 0-based
Also known as
CIMR-PW (iQpump Micro), iQpump Micro AC Drive, iQpump Micro Compact Intelligent Pump Controller
Source document
YASKAWA AC Drive iQpump Micro User Manual · TOEP YAIQPM 03B
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU)

Integration in brief

Set H5-01..H5-03 and power-cycle, then b1-01 = 2 and b1-02 = 2 so the frequency reference and Run come from Modbus. Write 0001H (run bits) and 0002H (frequency reference) with function 10H and poll 0020H, 0021H, 002AH and 002CH.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1Operation commands and multi-function inputsBITMAP16Run/stop, direction, fault resetRead/write
HR 2Frequency referenceUINT16Frequency reference (o1-03 units)Read/write
HR 32Drive status 1BITMAP16Drive status 1Read
HR 33Fault contents 1BITMAP16Fault contents 1Read
HR 36Output frequencyUINT16Output frequencyRead
HR 42Alarm contents 1BITMAP16Alarm contents 1Read
HR 44Drive status 2BITMAP16Drive status 2 incl. comm timeoutRead

Enable Modbus control & writes

Set H5-01 node address (default 1FH), H5-02 speed (default 3 = 9600 bps) and H5-03 parity (default 0 = none), then cycle power. For control set b1-01 = 2 and b1-02 = 2. H5-12 decides whether 0001H bits 0/1 are FWD/REV run or Run plus direction.

Communication loss & watchdog

H5-05 = 1 (default) enables CE detection after H5-09 (0.0-10.0 s, default 2.0 s) without data; H5-04 sets the reaction (0 ramp, 1 coast, 2 fast stop with C1-09, 3 alarm only and continue - default).

Byte order & addressing

Network setup

Watch out for

Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

36 of 36 shown
Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 0001HOperation commands and multi-function inputsRun bits follow H5-12; bits 4-A drive multi-function inputs 1-7.BITMAP16Read/writebit 0 = H5-12=0: forward run (1) / stop; H5-12=1: run (1) / stop; bit 1 = H5-12=0: reverse run (1) / stop; H5-12=1: reverse (1) / forward; bit 2 = External fault EF0; bit 3 = Fault reset; bit 4 = Multi-function input 1 (ComRef when H1-01 = 40); bit 5 = Multi-function input 2 (ComCtrl when H1-02 = 41); bit 6 = Multi-function input 3; bit 7 = Multi-function input 4; bit 8 = Multi-function input 5; bit 9 = Multi-function input 6; bit 10 = Multi-function input 7
HR2doc 0002HFrequency referenceUnits set by o1-03.UINT16Read/write
HR3doc 0003HOutput voltage gain20-2000 (2.0-200.0 %), 1000 at power-up.UINT16× 0.1%Read/write
HR6doc 0006HPID targetSigned; enable with 000FH bit 1.INT16× 0.01%Read/write
HR9doc 0009HMulti-function digital output settingsDrive the outputs from the network.BITMAP16Read/writebit 0 = Contact output MA/MB-MC; bit 1 = Photocoupler output 1 P1-PC; bit 2 = Photocoupler output 2 P2-PC
HR15doc 000FHControl selection settingEnables network setpoints and broadcast terminal inputs.BITMAP16Read/writebit 1 = PID target input; bit 12 = Broadcast terminal S5 input; bit 13 = Broadcast terminal S6 input; bit 14 = Broadcast terminal S7 input
HR32doc 0020HDrive status 1BITMAP16Readbit 0 = During run; bit 1 = During reverse; bit 2 = Drive ready; bit 3 = Fault; bit 4 = Data setting error; bit 5 = Contact output MA/MB-MC; bit 6 = Photocoupler output 1 P1-PC; bit 7 = Photocoupler output 2 P2-PC; bit 14 = ComRef enabled; bit 15 = ComCtrl enabled
HR33doc 0021HFault contents 1BITMAP16Readbit 0 = oC overcurrent / GF ground fault / SC IGBT short circuit; bit 1 = ov overvoltage; bit 2 = oL2 drive overload; bit 3 = oH1 overheat / oH2 drive overheat warning; bit 4 = rr braking transistor / rH braking resistor overheat; bit 6 = FbL / FbH PID feedback loss; bit 7 = EF0 to EF7 external fault; bit 8 = CPFxx hardware fault (incl. oFAxx); bit 9 = oL1 motor overload, oL3/oL4 overtorque, UL3/UL4 undertorque; bit 10 = oS overspeed; bit 11 = Uv main circuit undervoltage; bit 12 = Uv1/Uv2/Uv3 undervoltage; bit 13 = LF output / PF input phase loss; bit 14 = CE Modbus / bUS option communication error; bit 15 = oPr operator connection fault
HR34doc 0022HData link statusErrors from the last write.BITMAP16Readbit 0 = Writing data or switching motors; bit 3 = Upper or lower limit error; bit 4 = Data conformity error; bit 5 = Writing to EEPROM
HR35doc 0023HFrequency reference monitorUnits set by o1-03.UINT16Read
HR36doc 0024HOutput frequencyUnits set by o1-03.UINT16Read
HR41doc 0029HFault contents 2BITMAP16Readbit 0 = SC IGBT short circuit or ground fault; bit 1 = GF ground fault; bit 2 = PF input phase loss; bit 3 = LF output phase loss; bit 4 = rH braking resistor overheat; bit 6 = oH4 motor overheat 2 (PTC)
HR42doc 002AHAlarm contents 1Alarms that do not trip the drive.BITMAP16Readbit 2 = EF run command input error; bit 3 = bb baseblock; bit 4 = oL3 overtorque 1; bit 5 = oH heatsink overheat; bit 6 = ov overvoltage; bit 7 = Uv undervoltage; bit 9 = CE Modbus communication error; bit 10 = bUS option communication error; bit 11 = UL3/UL4 undertorque; bit 12 = oH3 motor overheat; bit 15 = CALL serial transmission error
HR43doc 002BHInput terminal statusBITMAP16Readbit 0 = Terminal S1 closed; bit 1 = Terminal S2 closed; bit 2 = Terminal S3 closed; bit 3 = Terminal S4 closed; bit 4 = Terminal S5 closed; bit 5 = Terminal S6 closed; bit 6 = Terminal S7 closed
HR44doc 002CHDrive status 2BITMAP16Readbit 0 = During run; bit 1 = Zero speed; bit 2 = Speed agree; bit 3 = User speed agree; bit 4 = Frequency detection 1; bit 5 = Frequency detection 2; bit 6 = Drive ready; bit 7 = During undervoltage; bit 8 = During baseblock; bit 9 = Frequency reference (as printed); bit 10 = Run command (as printed); bit 11 = Over/undertorque 1, 2; bit 12 = Frequency reference loss; bit 13 = During fault restart; bit 14 = Fault; bit 15 = Communication timeout
HR45doc 002DHOutput terminal statusBITMAP16Readbit 0 = Contact output MA/MB-MC; bit 1 = Photocoupler output 1 P1-PC; bit 2 = Photocoupler output 2 P2-PC
HR49doc 0031HDC bus voltageUINT16VRead
HR56doc 0038HPID feedbackUnsigned; 100 % = max. output frequency.UINT16× 0.1%Read
HR57doc 0039HPID inputSigned; 100 % = max. output frequency.INT16× 0.1%Read
HR58doc 003AHPID outputSigned; 100 % = max. output frequency.INT16× 0.1%Read
HR61doc 003DHCommunications error contentsBITMAP16Readbit 0 = CRC error; bit 1 = Data length error; bit 3 = Parity error; bit 4 = Overrun error; bit 5 = Framing error; bit 6 = Timeout
HR384doc 0180Hb1-01 Frequency reference selection 1Set 2 (serial communication) for a Modbus frequency reference.UINT16Read/write0 = Operator (keypad); 1 = Analog input terminals; 2 = MEMOBUS/Modbus communications; 3 = Option PCB; 4 = Pulse input (terminal RP)
HR385doc 0181Hb1-02 Run command selection 1Set 2 to take Run from Modbus.UINT16Read/write0 = HOA keypad; 1 = Digital input terminals; 2 = MEMOBUS/Modbus communications; 3 = Option PCB
HR1061doc 0425HH5-01 Drive node addressDefault 1FH; 0 = no response. C.5 gives 0-20H, parameter list up to FFH.UINT16Read/write
HR1062doc 0426HH5-02 Communication speed selectionDefault 3.UINT16Read/write0 = 1200 bps; 1 = 2400 bps; 2 = 4800 bps; 3 = 9600 bps; 4 = 19.2 kbps; 5 = 38.4 kbps
HR1063doc 0427HH5-03 Communication parity selectionDefault 0.UINT16Read/write0 = No parity; 1 = Even parity; 2 = Odd parity
HR1064doc 0428HH5-04 Stopping method after CEDefault 3.UINT16Read/write0 = Ramp to stop; 1 = Coast to stop; 2 = Fast stop (C1-09); 3 = Alarm only, continue
HR1065doc 0429HH5-05 Communication fault detection selectionDefault 1.UINT16Read/write0 = Disabled; 1 = Enabled
HR1066doc 042AHH5-06 Drive transmit wait time5-65 ms, default 5 ms.UINT16msRead/write
HR1067doc 042BHH5-07 RTS control selectionDefault 1; 0 only for point-to-point RS-422.UINT16Read/write0 = Disabled (RTS always on); 1 = Enabled
HR1077doc 0435HH5-09 Communications fault detection time0.0-10.0 s, default 2.0 s.UINT16× 0.1sRead/write
HR1078doc 0436HH5-10 Unit selection for register 0025HUINT16Read/write0 = 0.1 V units; 1 = 1 V units
HR1084doc 043CHH5-11 Communications enter function selectionDefault 0.UINT16Read/write0 = Enter command necessary; 1 = Enter command not necessary
HR1085doc 043DHH5-12 Run command method selectionMeaning of 0001H bits 0/1; default 0.UINT16Read/write0 = FWD/Stop, REV/Stop; 1 = Run/Stop, FWD/REV
HR2304doc 0900HEnter command (save to EEPROM)Write 0 to store written parameters in EEPROM.UINT16Write
HR2320doc 0910HEnter command (RAM only)Write 0 to apply written parameters without saving.UINT16Write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU)

What Modbus registers does the Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU) have?

This map lists 36 registers: 36 holding registers. 21 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and sent unchanged: the manual's read example asks slave 2 for starting register 0020H as Starting No. 00H 20H. Parameters use the hex numbers in the parameter list (H5-01 = 0425H).

What are the minimum Modbus registers to integrate the Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU)?

Start with HR 1 Operation commands and multi-function inputs (Run/stop, direction, fault reset); HR 2 Frequency reference (Frequency reference (o1-03 units)); HR 32 Drive status 1 (Drive status 1); HR 33 Fault contents 1 (Fault contents 1); HR 36 Output frequency (Output frequency); HR 42 Alarm contents 1 (Alarm contents 1); HR 44 Drive status 2 (Drive status 2 incl. comm timeout).

How do I enable Modbus control of the Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU)?

Set H5-01 node address (default 1FH), H5-02 speed (default 3 = 9600 bps) and H5-03 parity (default 0 = none), then cycle power. For control set b1-01 = 2 and b1-02 = 2. H5-12 decides whether 0001H bits 0/1 are FWD/REV run or Run plus direction.

What happens when the Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU) loses Modbus communication?

H5-05 = 1 (default) enables CE detection after H5-09 (0.0-10.0 s, default 2.0 s) without data; H5-04 sets the reaction (0 ramp, 1 coast, 2 fast stop with C1-09, 3 alarm only and continue - default).

Where is the official Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU) Modbus documentation?

The source is YASKAWA AC Drive iQpump Micro User Manual (TOEP YAIQPM 03B), published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=TOEPYAIQPM03&cmd=documents&documentName=TOEPYAIQPM03.pdf.

More Yaskawa Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: YASKAWA AC Drive iQpump Micro User Manual · TOEP YAIQPM 03B. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.