Variable frequency drive (HVAC bypass package) · Modbus register map

Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The Z1000 Bypass pairs the drive with a bypass controller board that has its own RS-485 port. Over Modbus RTU the bypass passes through the drive command and monitor registers and adds a bypass command word (run, AUTO select, BYPASS select, smoke purge, Motor AND/OR, fault reset), a bypass frequency reference, network control of the bypass inputs and outputs, and UB bypass monitors.

This page lists 38 Modbus registers for the Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU) — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yaskawa’s own free documentation (linked below) and checked against it.

Manufacturer
Yaskawa
Model
Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU)
Equipment type
Variable frequency drive (HVAC bypass package)
Registers
38 (17 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N1
Documented addressing
hexadecimal, 0-based
Also known as
Z1000 Bypass, Z1B1
Source document
Z1000 Bypass for HVAC fans and pumps Technical Manual · SIEP YAIZ1B 01F · rev. 2018-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU)

Integration in brief

Set Z3-01 = 0 (Modbus), Z3-02 address, Z3-03/Z3-04 line settings and restart. Set Z1-07 = 2 and Z1-08 = 2 to take speed and run from the bypass serial port, then write 8401H (frequency) and 8400H (run bit 0, AUTO select bit 10, BYPASS select bit 12); poll 0020H, 0021H, 0024H and UB-09 (8788H).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 33792Bypass command (BYP Command)BITMAP16Bypass command 8400HRead/write
HR 33793Bypass frequency referenceUINT16Bypass frequency reference 8401HRead/write
HR 32Drive status 1BITMAP16Drive status 1Read
HR 33Fault contents 1BITMAP16Fault contents 1Read
HR 36Output frequencyUINT16Output frequencyRead
HR 34696UB-09 bypass current faultUINT16Bypass current fault UB-09Read
HR 49DC bus voltageUINT16DC bus voltageRead

Enable Modbus control & writes

Set Z3-01 = 0, then Z1-07 = 2 [Bypass Serial] for the speed reference and Z1-08 = 2 [Bypass Serial] for the AUTO run command. Set Z3-12 = 1 if the bypass digital inputs are to be driven from 8402H.

Communication loss & watchdog

Z3-11 enables comm-fault detection; Z3-06 sets the timeout (default 2.0 s) and Z3-05 the action: ignore, alarm, EF0 fault, EF0 fault and open contactors, or run at the Z3-10 preset speed.

Byte order & addressing

Network setup

Watch out for

Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

38 of 38 shown
Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 0001HDrive operation command / multi-function inputsDrive-level command word.BITMAP16Read/writebit 2 = External fault EF0; bit 3 = Fault reset; bit 6 = Multi-function input 3; bit 7 = Multi-function input 4; bit 8 = Multi-function input 5; bit 9 = Multi-function input 6; bit 10 = Multi-function input 7
HR6doc 0006HPI target0.01 % units, signed.INT16× 0.01%Read/write
HR15doc 000FHControl selection settingBITMAP16Read/writebit 1 = PI setpoint input from Modbus; bit 4 = PI2 target input from Modbus; bit 12 = Terminal S5 input for broadcast; bit 13 = Terminal S6 input for broadcast; bit 14 = Terminal S7 input for broadcast
HR32doc 0020HDrive status 1BITMAP16Readbit 0 = During run; bit 1 = During reverse; bit 2 = Drive ready; bit 3 = Fault; bit 4 = Data setting error; bit 5 = MFDO M1-M2; bit 6 = MFDO M3-M4; bit 7 = MFDO M5-M6; bit 14 = ComRef status; bit 15 = ComCtrl status
HR33doc 0021HFault contents 1BITMAP16Readbit 0 = oC overcurrent / GF ground fault; bit 1 = ov overvoltage; bit 2 = oL2 drive overload; bit 3 = oH1 / oH2 overheat; bit 6 = FbL / FbH PI feedback loss; bit 7 = EF to EF7 external fault; bit 8 = CPF hardware fault (incl. oFx); bit 9 = oL1 / oL3 / UL3; bit 11 = Uv main circuit undervoltage; bit 12 = Uv1 / Uv2 / Uv3; bit 13 = LF / PF phase loss; bit 14 = CE / bUS communication error; bit 15 = oPr operator connection fault
HR34doc 0022HData link statusBITMAP16Readbit 0 = Writing data or switching motors; bit 3 = Upper or lower limit error; bit 4 = Data conformity error; bit 5 = Writing to EEPROM
HR35doc 0023HFrequency referenceUnits set by o1-03.UINT16Read
HR36doc 0024HOutput frequencyUnits set by o1-03.UINT16Read
HR42doc 002AHAlarm contents 1BITMAP16Readbit 2 = EF run command input error; bit 3 = bb baseblock; bit 4 = oL3 overtorque 1; bit 5 = oH heatsink overheat; bit 6 = ov overvoltage; bit 7 = Uv undervoltage; bit 8 = FAn cooling fan error; bit 9 = CE Modbus communication error; bit 10 = bUS option communication error; bit 11 = UL3 undertorque 1; bit 12 = oH3 motor overheat; bit 13 = FbL / FbH PI feedback loss; bit 15 = CALL transmission error
HR44doc 002CHDrive status 2BITMAP16Readbit 0 = During run; bit 1 = Zero speed; bit 2 = Speed agree; bit 3 = User speed agree; bit 4 = Frequency detection 1; bit 5 = Frequency detection 2; bit 6 = Drive ready; bit 7 = During undervoltage; bit 8 = During baseblock; bit 9 = Frequency reference from keypad; bit 10 = Run command from keypad; bit 11 = Over/undertorque 1; bit 12 = Frequency reference loss; bit 13 = During fault restart; bit 14 = Fault; bit 15 = Communication timeout
HR49doc 0031HDC bus voltageUINT16VRead
HR52doc 0034HProduct code 1ASCII product type (Z0 for Z1000).UINT16Read
HR56doc 0038HPI feedbackUnsigned; 100 % = maximum output frequency.UINT16× 0.1%Read
HR57doc 0039HPI inputSigned.INT16× 0.1%Read
HR58doc 003AHPI outputSigned.INT16× 0.1%Read
HR61doc 003DHCommunications error contentsHeld until the fault is reset.BITMAP16Readbit 0 = CRC error; bit 1 = Data length error; bit 3 = Parity error; bit 4 = Overrun error; bit 5 = Framing error; bit 6 = Timeout
HR75doc 004BHDrive status (U1-12)BITMAP16Readbit 0 = During run; bit 1 = Zero speed; bit 2 = Reverse run; bit 3 = Fault reset signal input; bit 4 = Speed agree; bit 5 = Drive ready; bit 6 = Alarm; bit 7 = Fault; bit 8 = Operation error oPE; bit 9 = Momentary power loss; bit 14 = ComRef / NetRef; bit 15 = ComCtrl / NetCtrl
HR127doc 007FHAlarm codeCode list in the manual's alarm register table.UINT16Read
HR152doc 0098HAccumulated operation time, high word (U4-01)10 h units; total = high x 10 + low.UINT16× 10hRead
HR153doc 0099HAccumulated operation time, low word (U4-01)1 h units.UINT16hRead
HR33792doc 8400HBypass command (BYP Command)OR-ed with the physical inputs.BITMAP16Read/writebit 0 = Run; bit 1 = Run reverse; bit 3 = Transfer to bypass; bit 4 = Smoke purge bypass; bit 5 = Smoke purge drive; bit 6 = Motor OR select; bit 7 = Motor AND select; bit 10 = AUTO select; bit 12 = BYPASS select; bit 13 = Fault reset; bit 14 = External fault (EFB)
HR33793doc 8401HBypass frequency referenceSent to the drive when Z1-07 = 2; units set by o1-03.UINT16Read/write
HR33794doc 8402HBypass digital input commandOR-ed with DI-1 to DI-8; needs Z3-12 = 1.BITMAP16Read/writebit 0 = DI-1; bit 1 = DI-2; bit 2 = DI-3; bit 3 = DI-4; bit 4 = DI-5; bit 5 = DI-6; bit 6 = DI-7; bit 7 = DI-8
HR33795doc 8403HBypass digital output commandOnly outputs whose function is unused.BITMAP16Read/writebit 6 = DO-7; bit 7 = DO-8; bit 8 = DO-9; bit 9 = DO-10
HR34048doc 8500HZ3-01 serial communications protocolDefault 3 (BACnet).UINT16Read/write0 = Modbus; 1 = N2; 2 = P1; 3 = BACnet
HR34049doc 8501HZ3-02 serial communications node address0-127, default 1.UINT16Read/write
HR34050doc 8502HZ3-03 baud rateDefault 3.UINT16Read/write0 = 1200 bps; 1 = 2400 bps; 2 = 4800 bps; 3 = 9600 bps; 4 = 19200 bps; 5 = 38400 bps; 6 = 57600 bps; 7 = 76800 bps; 8 = 115200 bps
HR34051doc 8503HZ3-04 parityDefault 0.UINT16Read/write0 = No parity; 1 = Even parity; 2 = Odd parity
HR34052doc 8504HZ3-05 serial communications fault actionDefault 1.UINT16Read/write0 = Ignore; 1 = Alarm only; 2 = Fault with EF0; 3 = Fault with EF0 and open contactors; 4 = Alarm and run at Z3-10 preset speed
HR34053doc 8505HZ3-06 serial communications fault time0.0-99.9 s, default 2.0 s; 0.0 = never.UINT16× 0.1sRead/write
HR34054doc 8506HZ3-07 receive-to-transmit wait time0-99 ms, default 5 ms.UINT16msRead/write
HR34059doc 850BHZ3-12 network digital input select1 enables 8402H.UINT16Read/write0 = Disable; 1 = Enable
HR34252doc 85CCHZ1-07 speed reference selectDefault 1.UINT16Read/write0 = Operator; 1 = Analog input; 2 = Bypass serial; 3 = Option board (CN5)
HR34253doc 85CDHZ1-08 run command selectDefault 1.UINT16Read/write0 = Operator; 1 = Bypass controller digital input; 2 = Bypass serial; 3 = Option board (CN5)
HR34696doc 8788HUB-09 bypass current faultBypass fault code.UINT16Read
HR34700doc 878CHUB-13 bypass previous faultBypass fault code.UINT16Read
HR34704doc 8790HUB-17 contactor coil voltage (120 VAC)UINT16VRead
HR34705doc 8791HUB-18 bypass software versionUINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU)

What Modbus registers does the Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU) have?

This map lists 38 registers: 38 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and are sent unchanged: the manual's read example asks for starting register 0020H as 00 20. Bypass parameters and monitors use the hex number printed under each one (Z3-01 = 8500H, UB-09 = 8788H).

What are the minimum Modbus registers to integrate the Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU)?

Start with HR 33792 Bypass command (BYP Command) (Bypass command 8400H); HR 33793 Bypass frequency reference (Bypass frequency reference 8401H); HR 32 Drive status 1 (Drive status 1); HR 33 Fault contents 1 (Fault contents 1); HR 36 Output frequency (Output frequency); HR 34696 UB-09 bypass current fault (Bypass current fault UB-09); HR 49 DC bus voltage (DC bus voltage).

How do I enable Modbus control of the Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU)?

Set Z3-01 = 0, then Z1-07 = 2 [Bypass Serial] for the speed reference and Z1-08 = 2 [Bypass Serial] for the AUTO run command. Set Z3-12 = 1 if the bypass digital inputs are to be driven from 8402H.

What happens when the Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU) loses Modbus communication?

Z3-11 enables comm-fault detection; Z3-06 sets the timeout (default 2.0 s) and Z3-05 the action: ignore, alarm, EF0 fault, EF0 fault and open contactors, or run at the Z3-10 preset speed.

Where is the official Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU) Modbus documentation?

The source is Z1000 Bypass for HVAC fans and pumps Technical Manual (SIEP YAIZ1B 01F), revision 2018-03, published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=SIEPYAIZ1B01&cmd=documents&documentName=SIEPYAIZ1B01.pdf.

More Yaskawa Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: Z1000 Bypass for HVAC fans and pumps Technical Manual · SIEP YAIZ1B 01F · rev. 2018-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.