Variable frequency drive · Modbus register map
Danfoss VLT AutomationDrive FC 360 (Modbus RTU) Modbus register map
Updated 17 November 2026
The FC 360 is Danfoss's compact general-purpose AC drive with a built-in RS-485 port that can run Modbus RTU. Control and status words are exchanged as coils (control bits 1-16, status bits 33-48), and every drive parameter is a holding register at ten times its parameter number. This map lists the control/status coils, the communication parameters, the main readouts and the alarm/warning words.
This page lists 79 Modbus registers for the Danfoss VLT AutomationDrive FC 360 (Modbus RTU) — 31 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Danfoss’s own free documentation (linked below) and checked against it.
- Manufacturer
- Danfoss
- Model
- VLT AutomationDrive FC 360 (Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 79 (31 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 8E1
- Documented addressing
- derived from parameter numbers
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- FC360, FC-360, VLT AutomationDrive FC 360
Integration notes: Danfoss VLT AutomationDrive FC 360 (Modbus RTU)
Set 8-30 = Modbus RTU and the port settings, make sure 8-02 is FC port, then write the 16 control bits (coils 1-16) and the reference (coils 17-32) with function 15 and read status coils 33-48. Read readouts from the 16-xx registers at parameter number x 10, minus 1 on the wire.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| CO 6 | CTW bit 6 (coil 7) | BIT | CTW bit 6: start / ramp stop | Read/write |
| CO 10 | CTW bit 10 (coil 11) | BIT | CTW bit 10: data valid | Read/write |
| CO 43 | STW bit 11 (coil 44) | BIT | Running | Read |
| CO 35 | STW bit 3 (coil 36) | BIT | Alarm | Read |
| HR 16129 | 16-13 Frequency | UINT32 ABCD | 16-13 Frequency | Read |
| HR 16139 | 16-14 Motor current | UINT16 | 16-14 Motor current | Read |
| HR 16899 | 16-90 Alarm Word | UINT32 ABCD | 16-90 Alarm word | Read |
Enable Modbus control & writes
8-30 Protocol = [2] Modbus RTU, 8-31 Address 1-247, 8-32 Baud Rate (2400-115200), 8-33 Parity/Stop Bits (default even, 1 stop bit). 8-02 Control Source must be [1] FC port and 8-01 Control Site decides whether digital inputs, the control word or both are used.
Communication loss & watchdog
8-03 Control Timeout Time (0.1-6000 s, default 1 s) and 8-04 Control Timeout Function (default Off; Freeze output, Stop, Jogging, Max. speed, Stop and trip) act when the control word stops being updated.
Byte order & addressing
- Control word bit 10 (coil 11) must be 1 or the drive ignores the control word.
- Parameter writes go to RAM only unless coil 65 is 1.
Network setup
- 8-35 Minimum Response Delay can be raised for slow masters or converters.
- Array parameters need the index written to holding register 9 first.
Watch out for
- Register numbers in the manual are 1-based; subtract 1 in the request.
Danfoss VLT AutomationDrive FC 360 (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 1 | CTW bit 0 (coil 1) | Preset reference LSB. | BIT | Read/write | ||||
| CO | 1doc 2 | CTW bit 1 (coil 2) | Preset reference MSB. | BIT | Read/write | ||||
| CO | 2doc 3 | CTW bit 2 (coil 3) | 0 = DC brake, 1 = no DC brake. | BIT | Read/write | ||||
| CO | 3doc 4 | CTW bit 3 (coil 4) | 0 = coast stop, 1 = no coast stop. | BIT | Read/write | ||||
| CO | 4doc 5 | CTW bit 4 (coil 5) | 0 = quick stop, 1 = no quick stop. | BIT | Read/write | ||||
| CO | 5doc 6 | CTW bit 5 (coil 6) | 0 = freeze frequency, 1 = no freeze. | BIT | Read/write | ||||
| CO | 6doc 7 | CTW bit 6 (coil 7) | 0 = ramp stop, 1 = start. | BIT | Read/write | ||||
| CO | 7doc 8 | CTW bit 7 (coil 8) | 1 = reset. | BIT | Read/write | ||||
| CO | 8doc 9 | CTW bit 8 (coil 9) | 1 = jog. | BIT | Read/write | ||||
| CO | 9doc 10 | CTW bit 9 (coil 10) | 0 = ramp 1, 1 = ramp 2. | BIT | Read/write | ||||
| CO | 10doc 11 | CTW bit 10 (coil 11) | 1 = data valid. | BIT | Read/write | ||||
| CO | 11doc 12 | CTW bit 11 (coil 12) | 1 = relay 1 on. | BIT | Read/write | ||||
| CO | 12doc 13 | CTW bit 12 (coil 13) | 1 = relay 2 on. | BIT | Read/write | ||||
| CO | 13doc 14 | CTW bit 13 (coil 14) | Set-up select LSB. | BIT | Read/write | ||||
| CO | 15doc 16 | CTW bit 15 (coil 16) | 1 = reversing. | BIT | Read/write | ||||
| CO | 32doc 33 | STW bit 0 (coil 33) | 1 = control ready. | BIT | Read | ||||
| CO | 33doc 34 | STW bit 1 (coil 34) | 1 = drive ready. | BIT | Read | ||||
| CO | 34doc 35 | STW bit 2 (coil 35) | 0 = coasting stop, 1 = safety closed. | BIT | Read | ||||
| CO | 35doc 36 | STW bit 3 (coil 36) | 1 = alarm. | BIT | Read | ||||
| CO | 39doc 40 | STW bit 7 (coil 40) | 1 = warning. | BIT | Read | ||||
| CO | 40doc 41 | STW bit 8 (coil 41) | 1 = at reference. | BIT | Read | ||||
| CO | 41doc 42 | STW bit 9 (coil 42) | 0 = hand mode, 1 = auto mode. | BIT | Read | ||||
| CO | 42doc 43 | STW bit 10 (coil 43) | 1 = in frequency range. | BIT | Read | ||||
| CO | 43doc 44 | STW bit 11 (coil 44) | 0 = stopped, 1 = running. | BIT | Read | ||||
| CO | 45doc 46 | STW bit 13 (coil 46) | 1 = voltage warning. | BIT | Read | ||||
| CO | 46doc 47 | STW bit 14 (coil 47) | 1 = current limit. | BIT | Read | ||||
| CO | 47doc 48 | STW bit 15 (coil 48) | 1 = thermal warning. | BIT | Read | ||||
| CO | 64doc 65 | Parameter write control | 0 = writes go to RAM, 1 = RAM and EEPROM. | BIT | Read/write | ||||
| HR | 6doc 7 | Last error code | Error from the parameter database. | UINT16 | Read | ||||
| HR | 7doc 8 | Last error register | Register where the last error happened. | UINT16 | Read | ||||
| HR | 8doc 9 | Index pointer (IND) | Sub-index for array parameters. | UINT16 | Read/write | ||||
| HR | 3019doc 3020 | 3-02 Minimum Reference | INT32 | ABCD | × 0.001 | Read/write | |||
| HR | 3029doc 3030 | 3-03 Maximum Reference | INT32 | ABCD | × 0.001 | Read/write | |||
| HR | 3409doc 3410 | 3-41 Ramp 1 Ramp Up Time | UINT32 | ABCD | × 0.01 | s | Read/write | ||
| HR | 3419doc 3420 | 3-42 Ramp 1 Ramp Down Time | UINT32 | ABCD | × 0.01 | s | Read/write | ||
| HR | 8009doc 8010 | 8-01 Control Site | UINT16 | Read/write | 0 = Digital and ctrl. word; 1 = Digital only; 2 = Control word only | ||||
| HR | 8019doc 8020 | 8-02 Control Source | UINT16 | Read/write | 0 = None; 1 = FC port | ||||
| HR | 8029doc 8030 | 8-03 Control Timeout Time | 0.1-6000 s, default 1 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 8039doc 8040 | 8-04 Control Timeout Function | UINT16 | Read/write | 0 = Off; 1 = Freeze output; 2 = Stop; 3 = Jogging; 4 = Max. speed; 5 = Stop and trip | ||||
| HR | 8099doc 8100 | 8-10 Control Word Profile | UINT16 | Read/write | 0 = FC profile; 1 = PROFIdrive profile | ||||
| HR | 8299doc 8300 | 8-30 Protocol | UINT16 | Read/write | 0 = FC; 2 = Modbus RTU | ||||
| HR | 8309doc 8310 | 8-31 Address | 1-247 for Modbus. | UINT16 | Read/write | ||||
| HR | 8319doc 8320 | 8-32 Baud Rate | UINT16 | Read/write | 0 = 2400; 1 = 4800; 2 = 9600; 3 = 19200; 4 = 38400; 5 = 57600; 6 = 76800; 7 = 115200 | ||||
| HR | 8329doc 8330 | 8-33 Parity / Stop Bits | UINT16 | Read/write | 0 = Even parity, 1 stop bit; 1 = Odd parity, 1 stop bit; 2 = No parity, 1 stop bit; 3 = No parity, 2 stop bits | ||||
| HR | 8349doc 8350 | 8-35 Minimum Response Delay | UINT16 | × 0.001 | s | Read/write | |||
| HR | 15029doc 15030 | 15-03 Power Up's | UINT32 | ABCD | Read | ||||
| HR | 15039doc 15040 | 15-04 Over Temp's | UINT16 | Read | |||||
| HR | 15049doc 15050 | 15-05 Over Volt's | UINT16 | Read | |||||
| HR | 15999doc 16000 | 16-00 Control Word | Control word as received. | UINT16 | Read | ||||
| HR | 16009doc 16010 | 16-01 Reference [Unit] | INT32 | ABCD | × 0.001 | Read | |||
| HR | 16019doc 16020 | 16-02 Reference [%] | INT16 | × 0.1 | % | Read | |||
| HR | 16029doc 16030 | 16-03 Status Word | Same bits as status coils 33-48. | UINT16 | Read | ||||
| HR | 16099doc 16100 | 16-10 Power [kW] | UINT32 | ABCD | × 0.001 | kW | Read | ||
| HR | 16109doc 16110 | 16-11 Power [hp] | UINT32 | ABCD | × 0.001 | hp | Read | ||
| HR | 16119doc 16120 | 16-12 Motor Voltage | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 16129doc 16130 | 16-13 Frequency | UINT32 | ABCD | × 0.1 | Hz | Read | ||
| HR | 16139doc 16140 | 16-14 Motor current | UINT16 | × 0.01 | A | Read | |||
| HR | 16149doc 16150 | 16-15 Frequency [%] | UINT16 | × 0.1 | % | Read | |||
| HR | 16179doc 16180 | 16-18 Motor Thermal | UINT16 | % | Read | ||||
| HR | 16299doc 16300 | 16-30 DC Link Voltage | UINT32 | ABCD | V | Read | |||
| HR | 16349doc 16350 | 16-35 Inverter Thermal | UINT16 | % | Read | ||||
| HR | 16359doc 16360 | 16-36 Inv. Nom. Current | UINT16 | × 0.01 | A | Read | |||
| HR | 16369doc 16370 | 16-37 Inv. Max. Current | UINT16 | × 0.01 | A | Read | |||
| HR | 16499doc 16500 | 16-50 External Reference | INT16 | × 0.1 | % | Read | |||
| HR | 16519doc 16520 | 16-52 Feedback [Unit] | INT32 | ABCD | × 0.001 | Read | |||
| HR | 16599doc 16600 | 16-60 Digital Input | UINT16 | Read | |||||
| HR | 16649doc 16650 | 16-65 Analog Output 42 [mA] | UINT16 | × 0.01 | mA | Read | |||
| HR | 16709doc 16710 | 16-71 Relay Output | UINT16 | Read | |||||
| HR | 16719doc 16720 | 16-72 Counter A | INT16 | Read | |||||
| HR | 16729doc 16730 | 16-73 Counter B | INT16 | Read | |||||
| HR | 16789doc 16790 | 16-79 Analog Output AO45 | UINT16 | × 0.01 | mA | Read | |||
| HR | 16849doc 16850 | 16-85 FC Port CTW 1 | Control word received on the FC port. | UINT16 | Read | ||||
| HR | 16859doc 16860 | 16-86 FC Port REF 1 | Reference received on the FC port; 4000h = 100 %. | INT16 | Read | ||||
| HR | 16899doc 16900 | 16-90 Alarm Word | Bit meanings in the programming guide. | UINT32 | ABCD | Read | |||
| HR | 16909doc 16910 | 16-91 Alarm Word 2 | Bit meanings in the programming guide. | UINT32 | ABCD | Read | |||
| HR | 16919doc 16920 | 16-92 Warning Word | Bit meanings in the programming guide. | UINT32 | ABCD | Read | |||
| HR | 16929doc 16930 | 16-93 Warning Word 2 | Bit meanings in the programming guide. | UINT32 | ABCD | Read | |||
| HR | 16939doc 16940 | 16-94 Ext. Status Word | Bit meanings in the programming guide. | UINT32 | ABCD | Read | |||
| HR | 16949doc 16950 | 16-95 Ext. Status Word 2 | Bit meanings in the programming guide. | UINT32 | ABCD | Read |
Notes on this map
- 32-bit values are high word first: the design guide's example reads 3-03 at registers 3030/3031 and gets 0x0016 0xE360 = 1500000, and its preset-multiple example writes 1-24 = 738 as 0x0000 0x02E2.
- Scale comes from each parameter's conversion index in the programming guide (-1 = x0.1, -2 = x0.01, -3 = x0.001, 0 = x1).
- Left out because the FC 360 programming guide leaves the factor for conversion indices 67, 74, 75 and 100 blank: 15-00 Operating hours, 15-01 Running Hours, 15-02 kWh Counter, 16-34 Heatsink Temp., 16-39 Control Card Temp., 16-57 Feedback [RPM]. Also left out: 16-05 Main Actual Value [%] (normalised), 16-62/16-64 analog inputs (unit not given), 16-66 Digital Output (text), text and array parameters.
- The design guide for this drive lists no 50000/50200 control registers; bus control uses coils 1-16 (control word), 17-32 (16-bit speed reference, 4000h = 100 %, negative in two's complement), 33-48 (status word) and 49-64 (output frequency, or feedback in closed loop).
- Uint8 parameters are read and written as one 16-bit register.
- Bit-by-bit coil names follow the FC profile tables; coil 15 has no function and STW coils 37-39 and 45 are unused.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Danfoss VLT AutomationDrive FC 360 (Modbus RTU)
What Modbus registers does the Danfoss VLT AutomationDrive FC 360 (Modbus RTU) have?
This map lists 79 registers: 28 coils, 51 holding registers. 31 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Danfoss VLT AutomationDrive FC 360 (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers derived from parameter numbers. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Coils and registers are numbered from 1 and sent minus 1 (coil 65 = address 64, register 40001 = address 0). A parameter's register is 10 x its parameter number (16-13 -> 16130) and the request uses that minus 1; the design guide reads 3-03 (register 3030) with start address 0x0BD5 = 3029.
What byte order does the Danfoss VLT AutomationDrive FC 360 (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Danfoss VLT AutomationDrive FC 360 (Modbus RTU)?
Start with CO 6 CTW bit 6 (coil 7) (CTW bit 6: start / ramp stop); CO 10 CTW bit 10 (coil 11) (CTW bit 10: data valid); CO 43 STW bit 11 (coil 44) (Running); CO 35 STW bit 3 (coil 36) (Alarm); HR 16129 16-13 Frequency (16-13 Frequency); HR 16139 16-14 Motor current (16-14 Motor current); HR 16899 16-90 Alarm Word (16-90 Alarm word).
How do I enable Modbus control of the Danfoss VLT AutomationDrive FC 360 (Modbus RTU)?
8-30 Protocol = [2] Modbus RTU, 8-31 Address 1-247, 8-32 Baud Rate (2400-115200), 8-33 Parity/Stop Bits (default even, 1 stop bit). 8-02 Control Source must be [1] FC port and 8-01 Control Site decides whether digital inputs, the control word or both are used.
What happens when the Danfoss VLT AutomationDrive FC 360 (Modbus RTU) loses Modbus communication?
8-03 Control Timeout Time (0.1-6000 s, default 1 s) and 8-04 Control Timeout Function (default Off; Freeze output, Stop, Jogging, Max. speed, Stop and trip) act when the control word stops being updated.
Where is the official Danfoss VLT AutomationDrive FC 360 (Modbus RTU) Modbus documentation?
The source is VLT AutomationDrive FC 360 Design Guide (chapter 5 RS485 Installation and Set-up, Modbus RTU) (MG06B402), revision 2014-09, published free by Danfoss at https://files.danfoss.com/download/Drives/MG06B402.pdf.
More Danfoss Modbus register maps
- Thermostat / heating controller (district heating and HVAC)
Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP)
ECL Comfort 210, 296 and 310 controllers (and B versions) with any application key; many parameters depend on the loaded application.
Also known as: ECL Comfort 210, ECL Comfort 296, ECL Comfort 310, ECL Comfort 210B, ECL Comfort 310B, 087H3020, 087H3024, 087H3030, 087H3034, 087H3040, 087H3044, 087H3050, 087H3054 - Sensor (refrigerant / toxic gas detector)
Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU)
Danfoss GD Basic, Premium and Heavy Duty gas detection units on their own RS-485 Modbus port (Part 2 of the guide). The gas detection controller's X-bus map in Part 1 is not included.
Also known as: GDA, GDC, GDHC, GDHF, GDH, GD Basic, GD Premium, GD Heavy Duty - Variable frequency drive
Danfoss iC2-Micro frequency converter (Modbus RTU)
Danfoss iC2-Micro frequency converters using the built-in RS-485 port with P 10.1.1 Protocol = [2] Modbus RTU and the FC control profile; Application Guide AB413939445838en-000401.
Also known as: iC2-Micro, iC2 Micro, Danfoss iC2 - Sensor / controller (CO2 condensing unit gateway)
Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005)
Danfoss Optyma iCO2 CO2 condensing units (4.6 kW MT and 20 kW MT / 10 kW LT) through their Modbus gateway, software 1.0x.
Also known as: OP-MPAM015, OP-MPAM005, Optyma iCO2 4.6 kW MT, Optyma iCO2 20 kW MT / 10 kW LT - Variable frequency drive
Danfoss VLT AQUA Drive FC 202 (Modbus RTU)
VLT AQUA Drive FC 202 using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter data checked against the software 5.4X programming guide.
Also known as: VLT AQUA Drive, FC202, FC-202, AQUA Drive FC 202 - Variable frequency drive
Danfoss VLT AutomationDrive FC 301/302 (Modbus RTU)
VLT AutomationDrive FC 301 and FC 302 (0.25-75 kW design guide; same scheme across sizes) using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter data checked against the software 9.5x / 48.96 programming guide.
Also known as: VLT AutomationDrive, FC 301, FC301, FC302, FC-302, FC-301, FC 300 - Variable frequency drive
Danfoss VLT Compressor Drive CDS 803 (Modbus RTU)
VLT Compressor Drive CDS 803 (variable-speed compressor drive for HVAC/R) using the built-in RS-485 port with 8-30 Protocol = Modbus RTU; Modbus rules from Design Guide MG18N202 (software 1.20), parameter data from Programming Guide MG18P202 (software 2.0).
Also known as: CDS803, CDS-803, VLT Compressor Drive CDS 803 - Variable frequency drive (HVAC fans and pumps)
Danfoss VLT HVAC Basic Drive FC 101 (Modbus RTU)
VLT HVAC Basic Drive FC 101 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC101, FC-101, VLT HVAC Basic Drive FC 101, VLT HVAC Basic - Variable frequency drive
Danfoss VLT HVAC Drive FC 102 (Modbus RTU)
VLT HVAC Drive FC 102 using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter scaling checked against the software 7.61 programming guide.
Also known as: VLT HVAC Drive, FC102, FC-102 - Variable frequency drive
Danfoss VLT Micro Drive FC 51 (Modbus RTU)
VLT Micro Drive FC 51 on the built-in RS-485 port with 8-30 = Modbus, software 3.1x; registers per design guide MG02K402 and parameter data per programming guide MG02C702.
Also known as: FC 51, FC51, VLT Micro Drive, VLT Micro Drive FC 51 - Variable frequency drive
Danfoss VLT Midi Drive FC 280 (Modbus RTU)
VLT Midi Drive FC 280 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC280, FC-280, VLT Midi Drive FC 280, VLT Midi Drive
Other variable frequency drives register maps
- Variable frequency drive (HVAC)
Eaton H-Max HVAC drive (embedded Modbus RTU / TCP)
H-Max HVAC drives with the application described in application manual MN04008006E (January 2012).
Also known as: HMX, H-Max HVAC, HMX32, HMX34 - Pump (circulator / E-pump / pump drive)
Grundfos E-pumps (MAGNA3, TPE, CRE, CUE) via CIM 200 / CIM 500
Grundfos E-pumps (CRE/CRNE/CRIE, MTRE, CHIE, CME, TPE, TPE Series 2000, NBE/NKE), CUE drives and MAGNA3 with a CIM/CIU 200, CIM/CIU 500 or built-in SoftCIM.
Also known as: MAGNA3, TPE, TPE Series 2000, CRE, CRNE, CRIE, MTRE, CHIE, CME, NBE, NKE, CUE, MGE, CIM 200, CIU 200, CIM 500, CIU 500, SoftCIM Modbus RTU - Variable frequency drive
Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU)
Invertek Optidrive E3 (ODE-3) IP20 drives on the RJ45 Modbus RTU port, per user guide 82-E3I20-IN V1.05.
Also known as: ODE-3, Optidrive E3, ODE-3 IP20, Optidrive ODE-3 - Variable frequency drive
INVT Goodrive270 (GD270) fan and pump VFD
INVT Goodrive270 fan and pump drives using the built-in RS-485 Modbus RTU port, per the GD270 manual V1.4 (chapter 9).
Also known as: GD270, Goodrive270, GD270 fan and pump drive, GD270 HVAC drive - Variable frequency drive
Lenze MC Series drives MC1000 / MC3000 (Modbus RTU)
Lenze AC Tech MC1000 and MC3000 Series drives, software 213-083 rev 13 (parameter configurations 188-190); reference guide RG-MCMOD.
Also known as: MC1000, MC3000, MC Series, Lenze AC Tech MC, RG-MCMOD - Variable frequency drive
Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU)
FR-A800 series inverters (FR-A820/A840/A842/A846, incl. -GF) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision P.
Also known as: FR-A820, FR-A840, FR-A842, FR-A846, FR-A800-GF, FR-A800 series
All variable frequency drives Modbus register maps →
Source: VLT AutomationDrive FC 360 Design Guide (chapter 5 RS485 Installation and Set-up, Modbus RTU) · MG06B402 · rev. 2014-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.