- Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005)
Sensor / controller (CO2 condensing unit gateway) · Modbus register map
Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005) Modbus register map
Updated 17 November 2026
The Optyma iCO2 gateway exposes Danfoss's CO2 condensing units to a supervisor over RS-485 Modbus RTU. All values are single 16-bit holding registers addressed by PNU. This map covers the main switch, suction setpoint, day/night clock, high/receiver/suction pressures, temperatures, fan and compressor speed, valve openings and status.
This page lists 36 Modbus registers for the Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005) — 7 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Danfoss’s own free documentation (linked below) and checked against it.
- Manufacturer
- Danfoss
- Model
- Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005)
- Equipment type
- Sensor / controller (CO2 condensing unit gateway)
- Registers
- 36 (7 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 8E1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Firmware
- SW 1.0x
- Also known as
- OP-MPAM015, OP-MPAM005, Optyma iCO2 4.6 kW MT, Optyma iCO2 20 kW MT / 10 kW LT
Integration notes: Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005)
Read the pressures, temperatures and speeds with function 03 and use the summary alarm and control state for status. Write r12 Main switch and r23 suction setpoint with function 06.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 116 | r12 Main switch | INT16 | Main switch | Read/write |
| HR 99 | r23 Ts Ref | INT16 | Suction setpoint | Read/write |
| HR 10029 | u01 Pc bar | INT16 | High pressure | Read |
| HR 10035 | U23 Po | INT16 | Suction pressure | Read |
| HR 10037 | U25 T Ambient | INT16 | Ambient temperature | Read |
| HR 10028 | u 52 CompCap% | UINT16 | Compressor speed % | Read |
| HR 2540 | EKC Error | UINT16 | Summary alarm | Read |
| HR 2006 | Ctrl. State | UINT16 | Control state | Read |
Enable Modbus control & writes
Set the slave address with parameter o03 on the MMILDS display.
Byte order & addressing
- Request PNU - 1 on the wire (PNU 100 = address 99).
- Every value is one 16-bit holding register; one decimal in the list means the raw value is x10, two decimals x100.
Network setup
- Set the slave address with o03 on the MMILDS display.
- Line settings: even parity, 8 data bits, 1 stop bit; the baud rate switches automatically between 19200 and 38400.
Watch out for
- The list remarks 'MBP CDU-ECU can receive only' against r23 Suction pressure setpoint; check the unit variant before relying on writes to it.
- Writes are also accepted by broadcast (address 0).
Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 99doc 100 | r23 Ts Ref | INT16 | × 0.1 | °C | Read/write | |||
| HR | 116doc 117 | r12 Main switch | Main switch for the unit. | INT16 | Read/write | 0 = Standby; 1 = On; 2 = Vacuum mode; -1 = Manual mode | |||
| HR | 119doc 120 | Reference | INT16 | × 0.1 | °C | Read | |||
| HR | 2002doc 2003 | FW Version | Gateway firmware: high byte major, low byte minor. | UINT16 | Read | ||||
| HR | 2006doc 2007 | Ctrl. State | Remote readout of the control state. | UINT16 | Read | 0 = Normal control; 10 = Standby; 25 = Manual mode; 34 = Safety stop; 101 = Restart state (high pressure); 102 = Restart state (fan motor); 103 = Restart state (discharge temp.); 104 = Restart state (receiver pressure) | |||
| HR | 2540doc 2541 | EKC Error | Summary alarm, 1 = active. | UINT16 | Read | ||||
| HR | 10001doc 10002 | u13 NightCond | UINT16 | Read | 0 = Day; 1 = Night | ||||
| HR | 10002doc 10003 | OpCond | Unit operating condition code. | UINT16 | Read | ||||
| HR | 10003doc 10004 | r43 Night Offset | UINT16 | °C | Read/write | ||||
| HR | 10013doc 10014 | F07 Fan Speed% | UINT16 | % | Read | ||||
| HR | 10017doc 10018 | t17 Day start h | UINT16 | h | Read/write | ||||
| HR | 10018doc 10019 | t18 Night start h | UINT16 | h | Read/write | ||||
| HR | 10019doc 10020 | o08 SW version | Software version of the condensing unit. | UINT16 | Read | ||||
| HR | 10025doc 10026 | u10 DI1 Status | UINT16 | Read | |||||
| HR | 10026doc 10027 | u21 Superheat K | INT16 | × 0.1 | K | Read | |||
| HR | 10027doc 10028 | u37 DI2 Status | UINT16 | Read | |||||
| HR | 10028doc 10029 | u 52 CompCap% | UINT16 | % | Read | ||||
| HR | 10029doc 10030 | u01 Pc bar | INT16 | × 0.1 | bar | Read | |||
| HR | 10030doc 10031 | U05 Sgc Temp | INT16 | × 0.1 | °C | Read | |||
| HR | 10031doc 10032 | U07 Srec2 temp | INT16 | × 0.1 | °C | Read | |||
| HR | 10032doc 10033 | U08 Prec pressure | INT16 | × 0.1 | bar | Read | |||
| HR | 10033doc 10034 | U09 Trec temp | INT16 | × 0.1 | °C | Read | |||
| HR | 10034doc 10035 | U22 Tc | INT16 | × 0.1 | °C | Read | |||
| HR | 10035doc 10036 | U23 Po | INT16 | × 0.1 | bar | Read | |||
| HR | 10036doc 10037 | U24 To | INT16 | × 0.1 | °C | Read | |||
| HR | 10037doc 10038 | U25 T Ambient | INT16 | × 0.1 | °C | Read | |||
| HR | 10038doc 10039 | U26 T Discharge | INT16 | × 0.1 | °C | Read | |||
| HR | 10039doc 10040 | U27 T Suction | INT16 | × 0.1 | °C | Read | |||
| HR | 10040doc 10041 | U62 Alarm Relay | UINT16 | Read | |||||
| HR | 10041doc 10042 | U91 Vhp % | High pressure valve opening. | UINT16 | % | Read | |||
| HR | 10042doc 10043 | U92 Vrec % | Receiver pressure valve opening. | UINT16 | % | Read | |||
| HR | 10043doc 10044 | U80 FW Version | UINT16 | × 0.01 | Read | ||||
| HR | 10053doc 10054 | U78 DynLP OFF | INT16 | × 0.1 | °C | Read | |||
| HR | 10054doc 10055 | U79 DynLP ON | INT16 | × 0.1 | °C | Read | |||
| HR | 15000doc 15001 | t07 Clk Hours | UINT16 | h | Read/write | ||||
| HR | 15001doc 15002 | t08 Clk Minutes | UINT16 | min | Read/write |
Notes on this map
- Scale follows the 'Decimals' column: 1 decimal = value x10 on the wire (127 = 12.7), 2 decimals = x100. The SW version row has no decimals entry and is left unscaled.
- The list header says all values are in °C / bar(g), while the unit column prints °C/°F and bar/PSI. Units here follow the header.
- The alarm list (PNU 20000-20021) is left out: its PDF layout does not pair each alarm code with a PNU unambiguously.
- Baud rate switches automatically between 19200 and 38400; even parity, 8 data bits, 1 stop bit.
- Signedness is not printed; registers with negative minimums are listed as INT16.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005)
What Modbus registers does the Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005) have?
This map lists 36 registers: 36 holding registers. 7 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide states every PNU is the register address plus 1: PNU 100 is requested as 0x63 (99).
What are the minimum Modbus registers to integrate the Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005)?
Start with HR 116 r12 Main switch (Main switch); HR 99 r23 Ts Ref (Suction setpoint); HR 10029 u01 Pc bar (High pressure); HR 10035 U23 Po (Suction pressure); HR 10037 U25 T Ambient (Ambient temperature); HR 10028 u 52 CompCap% (Compressor speed %); HR 2540 EKC Error (Summary alarm); HR 2006 Ctrl. State (Control state).
How do I enable Modbus control of the Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005)?
Set the slave address with parameter o03 on the MMILDS display.
Where is the official Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005) Modbus documentation?
The source is Programming Guide, Basic Modbus parameter list, Optyma iCO2 gateway (OP-MPAM015 and OP-MPAM005), SW Ver. 1.0x (AU459739305217en-000201), revision 2024-08, published free by Danfoss at https://assets.danfoss.com/documents/424639/AU459739305217en-000201.pdf.
More Danfoss Modbus register maps
- Thermostat / heating controller (district heating and HVAC)
Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP)
ECL Comfort 210, 296 and 310 controllers (and B versions) with any application key; many parameters depend on the loaded application.
Also known as: ECL Comfort 210, ECL Comfort 296, ECL Comfort 310, ECL Comfort 210B, ECL Comfort 310B, 087H3020, 087H3024, 087H3030, 087H3034, 087H3040, 087H3044, 087H3050, 087H3054 - Sensor (refrigerant / toxic gas detector)
Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU)
Danfoss GD Basic, Premium and Heavy Duty gas detection units on their own RS-485 Modbus port (Part 2 of the guide). The gas detection controller's X-bus map in Part 1 is not included.
Also known as: GDA, GDC, GDHC, GDHF, GDH, GD Basic, GD Premium, GD Heavy Duty - Variable frequency drive
Danfoss iC2-Micro frequency converter (Modbus RTU)
Danfoss iC2-Micro frequency converters using the built-in RS-485 port with P 10.1.1 Protocol = [2] Modbus RTU and the FC control profile; Application Guide AB413939445838en-000401.
Also known as: iC2-Micro, iC2 Micro, Danfoss iC2 - Variable frequency drive
Danfoss VLT AQUA Drive FC 202 (Modbus RTU)
VLT AQUA Drive FC 202 using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter data checked against the software 5.4X programming guide.
Also known as: VLT AQUA Drive, FC202, FC-202, AQUA Drive FC 202 - Variable frequency drive
Danfoss VLT AutomationDrive FC 301/302 (Modbus RTU)
VLT AutomationDrive FC 301 and FC 302 (0.25-75 kW design guide; same scheme across sizes) using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter data checked against the software 9.5x / 48.96 programming guide.
Also known as: VLT AutomationDrive, FC 301, FC301, FC302, FC-302, FC-301, FC 300 - Variable frequency drive
Danfoss VLT AutomationDrive FC 360 (Modbus RTU)
VLT AutomationDrive FC 360 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC360, FC-360, VLT AutomationDrive FC 360 - Variable frequency drive
Danfoss VLT Compressor Drive CDS 803 (Modbus RTU)
VLT Compressor Drive CDS 803 (variable-speed compressor drive for HVAC/R) using the built-in RS-485 port with 8-30 Protocol = Modbus RTU; Modbus rules from Design Guide MG18N202 (software 1.20), parameter data from Programming Guide MG18P202 (software 2.0).
Also known as: CDS803, CDS-803, VLT Compressor Drive CDS 803 - Variable frequency drive (HVAC fans and pumps)
Danfoss VLT HVAC Basic Drive FC 101 (Modbus RTU)
VLT HVAC Basic Drive FC 101 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC101, FC-101, VLT HVAC Basic Drive FC 101, VLT HVAC Basic - Variable frequency drive
Danfoss VLT HVAC Drive FC 102 (Modbus RTU)
VLT HVAC Drive FC 102 using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter scaling checked against the software 7.61 programming guide.
Also known as: VLT HVAC Drive, FC102, FC-102 - Variable frequency drive
Danfoss VLT Micro Drive FC 51 (Modbus RTU)
VLT Micro Drive FC 51 on the built-in RS-485 port with 8-30 = Modbus, software 3.1x; registers per design guide MG02K402 and parameter data per programming guide MG02C702.
Also known as: FC 51, FC51, VLT Micro Drive, VLT Micro Drive FC 51 - Variable frequency drive
Danfoss VLT Midi Drive FC 280 (Modbus RTU)
VLT Midi Drive FC 280 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC280, FC-280, VLT Midi Drive FC 280, VLT Midi Drive
Other ac & vrf gateways register maps
- VRF / split AC gateway
Intesis (HMS Networks) IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway
Samsung indoor units on the F3F4 remote-controller bus, gateway set to Modbus RTU (SW1-5 ON); user manual version 1.0.0.
Also known as: IN485SAM001R000, Intesis Samsung BACnet MS/TP Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001I000 Daikin domestic AC to Modbus RTU gateway
Single Daikin domestic (S21-connector) indoor unit via INMBSDAI001I000, user manual v1.0.2.
Also known as: INMBSDAI001I000, Intesis Daikin domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIS016O000 Hisense VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus Server - Hisense VRF, order codes INMBSHIS016O000 / INMBSHIS064O000 (legacy HS-AC-MBS-16 / HS-AC-MBS-64), user manual User Manual r1.0 EN.
Also known as: INMBSHIS016O000, INMBSHIS064O000, HS-AC-MBS-16, HS-AC-MBS-64, Intesis Modbus Server Hisense VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSMID001I000 Midea AC to Modbus RTU gateway
One Midea commercial / VRF indoor unit on the XYE bus, user manual v1.11.
Also known as: INMBSMID001I000, Intesis Midea Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway
Intesis Modbus Server - Panasonic, order codes INMBSPAN016O000 / 064O000 / 128O000 (legacy PA-AC-MBS-16 / -64 / -128), user manual r1.1 (11/2020); Panasonic P-Link systems.
Also known as: INMBSPAN016O000, INMBSPAN064O000, INMBSPAN128O000, PA-AC-MBS-16, PA-AC-MBS-64, PA-AC-MBS-128, Intesis Modbus Server Panasonic VRF - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units
Procon MelcoBEMS MINI (A1M) on the CN105/CN92 connector of a Mitsubishi Electric Air-To-Air indoor unit, installation manual v1.1.11 (firmware 3.0.28 for revision 2-4 hardware, 3.1.1 for revision 5).
Also known as: MelcoBEMS MINI (A1M), A1M, Procon A1M, MelcoBEMS MINI
All ac & vrf gateways Modbus register maps →
Source: Programming Guide, Basic Modbus parameter list, Optyma iCO2 gateway (OP-MPAM015 and OP-MPAM005), SW Ver. 1.0x · AU459739305217en-000201 · rev. 2024-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.