Sensor / controller (CO2 condensing unit gateway) · Modbus register map

Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005) Modbus register map

Updated 17 November 2026

Short answer

The Optyma iCO2 gateway exposes Danfoss's CO2 condensing units to a supervisor over RS-485 Modbus RTU. All values are single 16-bit holding registers addressed by PNU. This map covers the main switch, suction setpoint, day/night clock, high/receiver/suction pressures, temperatures, fan and compressor speed, valve openings and status.

This page lists 36 Modbus registers for the Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005) — 7 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Danfoss’s own free documentation (linked below) and checked against it.

Manufacturer
Danfoss
Model
Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005)
Equipment type
Sensor / controller (CO2 condensing unit gateway)
Registers
36 (7 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
8E1
Documented addressing
1-based (subtract 1 for the wire address)
Firmware
SW 1.0x
Also known as
OP-MPAM015, OP-MPAM005, Optyma iCO2 4.6 kW MT, Optyma iCO2 20 kW MT / 10 kW LT
Source document
Programming Guide, Basic Modbus parameter list, Optyma iCO2 gateway (OP-MPAM015 and OP-MPAM005), SW Ver. 1.0x · AU459739305217en-000201 · rev. 2024-08
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005)

Integration in brief

Read the pressures, temperatures and speeds with function 03 and use the summary alarm and control state for status. Write r12 Main switch and r23 suction setpoint with function 06.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 116r12 Main switchINT16Main switchRead/write
HR 99r23 Ts RefINT16Suction setpointRead/write
HR 10029u01 Pc barINT16High pressureRead
HR 10035U23 PoINT16Suction pressureRead
HR 10037U25 T AmbientINT16Ambient temperatureRead
HR 10028u 52 CompCap%UINT16Compressor speed %Read
HR 2540EKC ErrorUINT16Summary alarmRead
HR 2006Ctrl. StateUINT16Control stateRead

Enable Modbus control & writes

Set the slave address with parameter o03 on the MMILDS display.

Byte order & addressing

Network setup

Watch out for

Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

36 of 36 shown
Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR99doc 100r23 Ts RefINT16× 0.1°CRead/write
HR116doc 117r12 Main switchMain switch for the unit.INT16Read/write0 = Standby; 1 = On; 2 = Vacuum mode; -1 = Manual mode
HR119doc 120ReferenceINT16× 0.1°CRead
HR2002doc 2003FW VersionGateway firmware: high byte major, low byte minor.UINT16Read
HR2006doc 2007Ctrl. StateRemote readout of the control state.UINT16Read0 = Normal control; 10 = Standby; 25 = Manual mode; 34 = Safety stop; 101 = Restart state (high pressure); 102 = Restart state (fan motor); 103 = Restart state (discharge temp.); 104 = Restart state (receiver pressure)
HR2540doc 2541EKC ErrorSummary alarm, 1 = active.UINT16Read
HR10001doc 10002u13 NightCondUINT16Read0 = Day; 1 = Night
HR10002doc 10003OpCondUnit operating condition code.UINT16Read
HR10003doc 10004r43 Night OffsetUINT16°CRead/write
HR10013doc 10014F07 Fan Speed%UINT16%Read
HR10017doc 10018t17 Day start hUINT16hRead/write
HR10018doc 10019t18 Night start hUINT16hRead/write
HR10019doc 10020o08 SW versionSoftware version of the condensing unit.UINT16Read
HR10025doc 10026u10 DI1 StatusUINT16Read
HR10026doc 10027u21 Superheat KINT16× 0.1KRead
HR10027doc 10028u37 DI2 StatusUINT16Read
HR10028doc 10029u 52 CompCap%UINT16%Read
HR10029doc 10030u01 Pc barINT16× 0.1barRead
HR10030doc 10031U05 Sgc TempINT16× 0.1°CRead
HR10031doc 10032U07 Srec2 tempINT16× 0.1°CRead
HR10032doc 10033U08 Prec pressureINT16× 0.1barRead
HR10033doc 10034U09 Trec tempINT16× 0.1°CRead
HR10034doc 10035U22 TcINT16× 0.1°CRead
HR10035doc 10036U23 PoINT16× 0.1barRead
HR10036doc 10037U24 ToINT16× 0.1°CRead
HR10037doc 10038U25 T AmbientINT16× 0.1°CRead
HR10038doc 10039U26 T DischargeINT16× 0.1°CRead
HR10039doc 10040U27 T SuctionINT16× 0.1°CRead
HR10040doc 10041U62 Alarm RelayUINT16Read
HR10041doc 10042U91 Vhp %High pressure valve opening.UINT16%Read
HR10042doc 10043U92 Vrec %Receiver pressure valve opening.UINT16%Read
HR10043doc 10044U80 FW VersionUINT16× 0.01Read
HR10053doc 10054U78 DynLP OFFINT16× 0.1°CRead
HR10054doc 10055U79 DynLP ONINT16× 0.1°CRead
HR15000doc 15001t07 Clk HoursUINT16hRead/write
HR15001doc 15002t08 Clk MinutesUINT16minRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005)

What Modbus registers does the Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005) have?

This map lists 36 registers: 36 holding registers. 7 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide states every PNU is the register address plus 1: PNU 100 is requested as 0x63 (99).

What are the minimum Modbus registers to integrate the Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005)?

Start with HR 116 r12 Main switch (Main switch); HR 99 r23 Ts Ref (Suction setpoint); HR 10029 u01 Pc bar (High pressure); HR 10035 U23 Po (Suction pressure); HR 10037 U25 T Ambient (Ambient temperature); HR 10028 u 52 CompCap% (Compressor speed %); HR 2540 EKC Error (Summary alarm); HR 2006 Ctrl. State (Control state).

How do I enable Modbus control of the Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005)?

Set the slave address with parameter o03 on the MMILDS display.

Where is the official Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005) Modbus documentation?

The source is Programming Guide, Basic Modbus parameter list, Optyma iCO2 gateway (OP-MPAM015 and OP-MPAM005), SW Ver. 1.0x (AU459739305217en-000201), revision 2024-08, published free by Danfoss at https://assets.danfoss.com/documents/424639/AU459739305217en-000201.pdf.

More Danfoss Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: Programming Guide, Basic Modbus parameter list, Optyma iCO2 gateway (OP-MPAM015 and OP-MPAM005), SW Ver. 1.0x · AU459739305217en-000201 · rev. 2024-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.