Danfoss VLT Midi Drive FC 280 (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The FC 280 is Danfoss's compact general-purpose (Midi) drive with a built-in RS-485 port that can run Modbus RTU. Control and status words are exchanged as coils (control bits 1-16, status bits 33-48), and every drive parameter is a holding register at ten times its parameter number. This map lists the control/status coils, the communication parameters, the main readouts and the alarm/warning words.

This page lists 89 Modbus registers for the Danfoss VLT Midi Drive FC 280 (Modbus RTU) — 31 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Danfoss’s own free documentation (linked below) and checked against it.

Manufacturer
Danfoss
Model
VLT Midi Drive FC 280 (Modbus RTU)
Equipment type
Variable frequency drive
Registers
89 (31 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8E1
Documented addressing
derived from parameter numbers
32-bit word order
ABCD high word first (big-endian)
Also known as
FC280, FC-280, VLT Midi Drive FC 280, VLT Midi Drive
Source document
VLT Midi Drive FC 280 Design Guide (chapter 5 RS485 Installation and Set-up, Modbus RTU) · MG07B302 · rev. 2017-05
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Danfoss VLT Midi Drive FC 280 (Modbus RTU)

Integration in brief

Set 8-30 = Modbus RTU and the port settings, make sure 8-02 is FC port, then write the 16 control bits (coils 1-16) and the reference (coils 17-32) with function 15 and read status coils 33-48. Read readouts from the 16-xx registers at parameter number x 10, minus 1 on the wire.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
CO 6CTW bit 6 (coil 7)BITCTW bit 6: start / ramp stopRead/write
CO 10CTW bit 10 (coil 11)BITCTW bit 10: data validRead/write
CO 43STW bit 11 (coil 44)BITRunningRead
CO 35STW bit 3 (coil 36)BITAlarmRead
HR 1612916-13 FrequencyUINT32 ABCD16-13 FrequencyRead
HR 1613916-14 Motor currentUINT1616-14 Motor currentRead
HR 1689916-90 Alarm wordUINT32 ABCD16-90 Alarm wordRead

Enable Modbus control & writes

8-30 Protocol = [2] Modbus RTU, 8-31 Address 1-247, 8-32 Baud Rate (2400-115200, default 9600), 8-33 Parity/Stop Bits (even parity, 1 stop bit by default). 8-02 Control Source must be [1] FC port and 8-10 should be [0] FC profile and 8-01 Control Site decides whether digital inputs, the control word or both are used.

Communication loss & watchdog

8-03 Control Timeout Time (0.5-6000 s, default 1 s) and 8-04 Control Timeout Function (default Off; Freeze output, Stop, Jogging, Max. speed, Stop and trip) act when the control word stops being updated.

Byte order & addressing

Network setup

Watch out for

Danfoss VLT Midi Drive FC 280 (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

89 of 89 shown
Danfoss VLT Midi Drive FC 280 (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 1CTW bit 0 (coil 1)Preset reference LSB.BITRead/write
CO1doc 2CTW bit 1 (coil 2)Preset reference MSB.BITRead/write
CO2doc 3CTW bit 2 (coil 3)0 = DC brake, 1 = no DC brake.BITRead/write
CO3doc 4CTW bit 3 (coil 4)0 = coast stop, 1 = no coast stop.BITRead/write
CO4doc 5CTW bit 4 (coil 5)0 = quick stop, 1 = no quick stop.BITRead/write
CO5doc 6CTW bit 5 (coil 6)0 = freeze frequency, 1 = no freeze.BITRead/write
CO6doc 7CTW bit 6 (coil 7)0 = ramp stop, 1 = start.BITRead/write
CO7doc 8CTW bit 7 (coil 8)1 = reset.BITRead/write
CO8doc 9CTW bit 8 (coil 9)1 = jog.BITRead/write
CO9doc 10CTW bit 9 (coil 10)0 = ramp 1, 1 = ramp 2.BITRead/write
CO10doc 11CTW bit 10 (coil 11)1 = data valid.BITRead/write
CO11doc 12CTW bit 11 (coil 12)1 = relay 1 on.BITRead/write
CO12doc 13CTW bit 12 (coil 13)1 = relay 2 on.BITRead/write
CO13doc 14CTW bit 13 (coil 14)Set-up select LSB.BITRead/write
CO15doc 16CTW bit 15 (coil 16)1 = reversing.BITRead/write
CO32doc 33STW bit 0 (coil 33)1 = control ready.BITRead
CO33doc 34STW bit 1 (coil 34)1 = drive ready.BITRead
CO34doc 35STW bit 2 (coil 35)0 = coasting stop, 1 = safety closed.BITRead
CO35doc 36STW bit 3 (coil 36)1 = alarm.BITRead
CO39doc 40STW bit 7 (coil 40)1 = warning.BITRead
CO40doc 41STW bit 8 (coil 41)1 = at reference.BITRead
CO41doc 42STW bit 9 (coil 42)0 = hand mode, 1 = auto mode.BITRead
CO42doc 43STW bit 10 (coil 43)1 = in frequency range.BITRead
CO43doc 44STW bit 11 (coil 44)0 = stopped, 1 = running.BITRead
CO45doc 46STW bit 13 (coil 46)1 = voltage warning.BITRead
CO46doc 47STW bit 14 (coil 47)1 = current limit.BITRead
CO47doc 48STW bit 15 (coil 48)1 = thermal warning.BITRead
CO64doc 65Parameter write control0 = writes go to RAM, 1 = RAM and EEPROM.BITRead/write
HR6doc 7Last error codeError from the parameter database.UINT16Read
HR7doc 8Last error registerRegister where the last error happened.UINT16Read
HR8doc 9Index pointer (IND)Sub-index for array parameters.UINT16Read/write
HR3019doc 30203-02 Minimum ReferenceINT32ABCD× 0.001Read/write
HR3029doc 30303-03 Maximum ReferenceINT32ABCD× 0.001Read/write
HR3409doc 34103-41 Ramp 1 Ramp Up TimeUINT32ABCD× 0.01sRead/write
HR3419doc 34203-42 Ramp 1 Ramp Down TimeUINT32ABCD× 0.01sRead/write
HR8009doc 80108-01 Control SiteUINT16Read/write0 = Digital and ctrl. word; 1 = Digital only; 2 = Control word only
HR8019doc 80208-02 Control SourceUINT16Read/write0 = None; 1 = FC port; 2 = FC USB; 3 = Option A
HR8029doc 80308-03 Control Timeout Time0.5-6000 s, default 1 s.UINT16× 0.1sRead/write
HR8039doc 80408-04 Control Timeout FunctionUINT16Read/write0 = Off; 1 = Freeze output; 2 = Stop; 3 = Jogging; 4 = Max. speed; 5 = Stop and trip
HR8099doc 81008-10 Control Word ProfileUINT16Read/write0 = FC profile; 1 = PROFIdrive profile; 5 = ODVA; 7 = CANopen DSP 402
HR8299doc 83008-30 ProtocolUINT16Read/write0 = FC; 2 = Modbus RTU
HR8309doc 83108-31 Address1-247 for Modbus.UINT16Read/write
HR8319doc 83208-32 Baud RateUINT16Read/write0 = 2400; 1 = 4800; 2 = 9600; 3 = 19200; 4 = 38400; 5 = 57600; 6 = 76800; 7 = 115200
HR8329doc 83308-33 Parity / Stop BitsUINT16Read/write0 = Even parity, 1 stop bit; 1 = Odd parity, 1 stop bit; 2 = No parity, 1 stop bit; 3 = No parity, 2 stop bits
HR8349doc 83508-35 Minimum Response DelayUINT16× 0.001sRead/write
HR14999doc 1500015-00 Operating hoursUINT32ABCDhRead
HR15009doc 1501015-01 Running hoursUINT32ABCDhRead
HR15019doc 1502015-02 kWh counterUINT32ABCDkWhRead
HR15029doc 1503015-03 Power up'sUINT32ABCDRead
HR15039doc 1504015-04 Over temp'sUINT16Read
HR15049doc 1505015-05 Over volt'sUINT16Read
HR15999doc 1600016-00 Control wordControl word as received.UINT16Read
HR16009doc 1601016-01 Reference [unit]INT32ABCD× 0.001Read
HR16019doc 1602016-02 Reference [%]INT16× 0.1%Read
HR16029doc 1603016-03 Status wordSame bits as status coils 33-48.UINT16Read
HR16099doc 1610016-10 Power [kW]UINT32ABCD× 0.001kWRead
HR16109doc 1611016-11 Power [hp]UINT32ABCD× 0.001hpRead
HR16119doc 1612016-12 Motor voltageUINT32ABCD× 0.1VRead
HR16129doc 1613016-13 FrequencyUINT32ABCD× 0.1HzRead
HR16139doc 1614016-14 Motor currentUINT16× 0.01ARead
HR16149doc 1615016-15 Frequency [%]UINT16× 0.1%Read
HR16159doc 1616016-16 Torque [Nm]INT32ABCD× 0.1NmRead
HR16169doc 1617016-17 Speed [RPM]INT32ABCDRPMRead
HR16179doc 1618016-18 Motor thermalUINT16%Read
HR16219doc 1622016-22 Torque [%]INT16%Read
HR16299doc 1630016-30 DC link voltageUINT32ABCDVRead
HR16339doc 1634016-34 Heatsink temperatureInt8 in the list, carried in one register.INT16°CRead
HR16349doc 1635016-35 Inverter thermalUINT16%Read
HR16359doc 1636016-36 Inverter nominal currentUINT16× 0.01ARead
HR16369doc 1637016-37 Inverter maximum currentUINT16× 0.01ARead
HR16389doc 1639016-39 Control Card Temp.UINT16°CRead
HR16499doc 1650016-50 External referenceINT16× 0.1%Read
HR16519doc 1652016-52 Feedback [Unit]INT32ABCD× 0.001Read
HR16569doc 1657016-57 Feedback [RPM]INT32ABCDRPMRead
HR16599doc 1660016-60 Digital inputUINT16Read
HR16649doc 1665016-65 Analog output AO42 [mA]UINT16× 0.01mARead
HR16709doc 1671016-71 Relay output [bin]UINT16Read
HR16719doc 1672016-72 Counter AINT16Read
HR16729doc 1673016-73 Counter BINT16Read
HR16849doc 1685016-85 FC Port CTW 1Control word received on the FC port.UINT16Read
HR16859doc 1686016-86 FC port REF 1Reference received on the FC port; 4000h = 100 %.INT16Read
HR16899doc 1690016-90 Alarm wordBit meanings in the programming guide.UINT32ABCDRead
HR16909doc 1691016-91 Alarm word 2Bit meanings in the programming guide.UINT32ABCDRead
HR16919doc 1692016-92 Warning wordBit meanings in the programming guide.UINT32ABCDRead
HR16929doc 1693016-93 Warning word 2Bit meanings in the programming guide.UINT32ABCDRead
HR16939doc 1694016-94 External status wordBit meanings in the programming guide.UINT32ABCDRead
HR16949doc 1695016-95 External status word 2Bit meanings in the programming guide.UINT32ABCDRead
HR16969doc 1697016-97 Alarm word 3Bit meanings in the programming guide.UINT32ABCDRead
HR16979doc 1698016-98 Warning word 3Bit meanings in the programming guide.UINT32ABCDRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Danfoss VLT Midi Drive FC 280 (Modbus RTU)

What Modbus registers does the Danfoss VLT Midi Drive FC 280 (Modbus RTU) have?

This map lists 89 registers: 28 coils, 61 holding registers. 31 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Danfoss VLT Midi Drive FC 280 (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers derived from parameter numbers. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Coils and registers are numbered from 1 and sent minus 1 (coil 65 = address 64, register 40001 = address 0). A parameter's register is 10 x its parameter number (16-13 -> 16130) and the request uses that minus 1; the design guide reads 3-03 (register 3030) at register address 3029.

What byte order does the Danfoss VLT Midi Drive FC 280 (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Danfoss VLT Midi Drive FC 280 (Modbus RTU)?

Start with CO 6 CTW bit 6 (coil 7) (CTW bit 6: start / ramp stop); CO 10 CTW bit 10 (coil 11) (CTW bit 10: data valid); CO 43 STW bit 11 (coil 44) (Running); CO 35 STW bit 3 (coil 36) (Alarm); HR 16129 16-13 Frequency (16-13 Frequency); HR 16139 16-14 Motor current (16-14 Motor current); HR 16899 16-90 Alarm word (16-90 Alarm word).

How do I enable Modbus control of the Danfoss VLT Midi Drive FC 280 (Modbus RTU)?

8-30 Protocol = [2] Modbus RTU, 8-31 Address 1-247, 8-32 Baud Rate (2400-115200, default 9600), 8-33 Parity/Stop Bits (even parity, 1 stop bit by default). 8-02 Control Source must be [1] FC port and 8-10 should be [0] FC profile and 8-01 Control Site decides whether digital inputs, the control word or both are used.

What happens when the Danfoss VLT Midi Drive FC 280 (Modbus RTU) loses Modbus communication?

8-03 Control Timeout Time (0.5-6000 s, default 1 s) and 8-04 Control Timeout Function (default Off; Freeze output, Stop, Jogging, Max. speed, Stop and trip) act when the control word stops being updated.

Where is the official Danfoss VLT Midi Drive FC 280 (Modbus RTU) Modbus documentation?

The source is VLT Midi Drive FC 280 Design Guide (chapter 5 RS485 Installation and Set-up, Modbus RTU) (MG07B302), revision 2017-05, published free by Danfoss at https://files.danfoss.com/download/Drives/MG07B302.pdf.

More Danfoss Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: VLT Midi Drive FC 280 Design Guide (chapter 5 RS485 Installation and Set-up, Modbus RTU) · MG07B302 · rev. 2017-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.