Variable frequency drive · Modbus register map
Inovance MD500-PLUS series AC drive Modbus register map
Updated 19 November 2026
Inovance's general-purpose vector drive for asynchronous and permanent-magnet motors. With the MD38TX1 RS-485 card it acts as a Modbus RTU slave. Speed goes to 1000H as a signed percentage of maximum frequency, run commands to 2000H, status and fault codes come from 3000H and 8000H, and every parameter has its own hex address (F/A groups at FxxxH/AxxxH, U0 monitors at 70xxH). This map covers the control block, the core U0 monitors with their data types and units, and the FD communication parameters.
This page lists 55 Modbus registers for the Inovance MD500-PLUS series AC drive — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Inovance’s own free documentation (linked below) and checked against it.
- Manufacturer
- Inovance
- Model
- MD500-PLUS series AC drive
- Equipment type
- Variable frequency drive
- Registers
- 55 (17 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N2
- Documented addressing
- hexadecimal, 0-based
- Also known as
- MD500-PLUS, MD500 PLUS, MD500T-PLUS, Inovance MD500-PLUS
Integration notes: Inovance MD500-PLUS series AC drive
Fit the MD38TX1 card, set F0-02 = 2 and F0-03 = 9, then write a signed percentage of F0-10 to 1000H (10000 = 100.00 %) and a run code to 2000H. Poll 3000H for run state, 8000H for faults and 7000H-7006H for frequency, voltage, current, power and torque.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 8192 | Control command | UINT16 | Run / stop / reset command | Write |
| HR 4096 | Communication reference | INT16 | Speed reference as % of max frequency | Write |
| HR 12288 | AC drive state | UINT16 | Forward / reverse / stopped | Read |
| HR 32768 | AC drive fault | UINT16 | Fault code | Read |
| HR 28672 | U0-00 Running frequency | UINT16 | Running frequency | Read |
| HR 28676 | U0-04 Output current | UINT16 | Output current | Read |
| HR 28674 | U0-02 Bus voltage | UINT16 | DC bus voltage | Read |
Enable Modbus control & writes
RS-485 needs the MD38TX1 extension card. F0-02 = 2 accepts run commands over communication; F0-03 = 9 makes 1000H the main frequency. FD-00..FD-02 set baud, data format and address.
Communication loss & watchdog
FD-04 sets a Modbus timeout (0.0 s = off); when messages stop for longer the drive reports a communication fault (Err16).
Byte order & addressing
- 1000H is a percentage, not Hz: 10000 = +100.00 % of F0-10, negative values reverse.
- Default serial format is 8-N-2 (FD-01 = 0).
- To change F-group parameters without wearing the EEPROM, replace the leading F with 0 (F3-12 -> 030CH); A-group uses 4x. Those RAM addresses are write-only.
Network setup
- FD-02 address (default 1), FD-00 baud (default 5 = 9600 bit/s), FD-01 data format (default 0 = 8-N-2).
- Restore defaults over Modbus by writing the user password to 1F00H, then 1 to 1F01H within 30 s.
Watch out for
- Reads longer than 12 registers, or reads that cross the end of a parameter group, return an error.
- No reply is sent for a frame with a CRC error.
Inovance MD500-PLUS series AC drive Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 4096doc 1000H | Communication reference | -10000 to 10000 = -100.00 to 100.00 % of F0-10 (or torque limit). | INT16 | × 0.01 | % | Write | ||
| HR | 7936doc 1F00H | Password verification | Write the user password before 1F01H; reads 0000H when no password is set. | UINT16 | Read/write | ||||
| HR | 7937doc 1F01H | Parameter initialization | UINT16 | Write | 0 = No operation; 1 = Restore default settings (mode 1); 2 = Clear records; 4 = Back up current user parameters; 501 = Restore user backup parameters; 503 = Restore default settings (mode 2) | ||||
| HR | 8192doc 2000H | Control command | Needs F0-02 = 2. | UINT16 | Write | 1 = Forward running; 2 = Reverse running; 3 = Forward jogging; 4 = Reverse jogging; 5 = Coast to stop; 6 = Decelerate to stop; 7 = Fault reset | |||
| HR | 8193doc 2001H | DO control | Outputs must be assigned function 20 (communication). | BITMAP16 | Write | bit 0 = DO1; bit 1 = DO2; bit 2 = RELAY1; bit 3 = RELAY2; bit 4 = FMR; bit 5 = VDO1; bit 6 = VDO2; bit 7 = VDO3; bit 8 = VDO4; bit 9 = VDO5 | |||
| HR | 8194doc 2002H | AO1 control | 0-7FFF = 0-100 %; AO1 must be assigned function 12. | UINT16 | Write | ||||
| HR | 8195doc 2003H | AO2 control | 0-7FFF = 0-100 %. | UINT16 | Write | ||||
| HR | 8196doc 2004H | Pulse output (FMP) control | 0-7FFF = 0-100 %. | UINT16 | Write | ||||
| HR | 12288doc 3000H | AC drive state | UINT16 | Read | 1 = Forward running; 2 = Reverse running; 3 = Stop | ||||
| HR | 28672doc U0-00 (0x7000) | U0-00 Running frequency | UINT16 | × 0.01 | Hz | Read | |||
| HR | 28673doc U0-01 (0x7001) | U0-01 Frequency reference | UINT16 | × 0.01 | Hz | Read | |||
| HR | 28674doc U0-02 (0x7002) | U0-02 Bus voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 28675doc U0-03 (0x7003) | U0-03 Output voltage | UINT16 | V | Read | ||||
| HR | 28676doc U0-04 (0x7004) | U0-04 Output current | UINT16 | × 0.1 | A | Read | |||
| HR | 28677doc U0-05 (0x7005) | U0-05 Output power | INT16 | × 0.1 | kW | Read | |||
| HR | 28678doc U0-06 (0x7006) | U0-06 Output torque | INT16 | × 0.1 | % | Read | |||
| HR | 28679doc U0-07 (0x7007) | U0-07 DI state | BITMAP16 | Read | |||||
| HR | 28680doc U0-08 (0x7008) | U0-08 DO state | BITMAP16 | Read | |||||
| HR | 28681doc U0-09 (0x7009) | U0-09 AI1 voltage | INT16 | × 0.01 | V | Read | |||
| HR | 28682doc U0-10 (0x700A) | U0-10 AI2 voltage | INT16 | × 0.01 | V | Read | |||
| HR | 28683doc U0-11 (0x700B) | U0-11 AI3 voltage | INT16 | × 0.01 | V | Read | |||
| HR | 28684doc U0-12 (0x700C) | U0-12 Count value | UINT16 | Read | |||||
| HR | 28685doc U0-13 (0x700D) | U0-13 Length value | UINT16 | Read | |||||
| HR | 28687doc U0-15 (0x700F) | U0-15 PID reference | UINT16 | % | Read | ||||
| HR | 28688doc U0-16 (0x7010) | U0-16 PID feedback | UINT16 | % | Read | ||||
| HR | 28689doc U0-17 (0x7011) | U0-17 PLC stage | UINT16 | Read | |||||
| HR | 28690doc U0-18 (0x7012) | U0-18 Pulse input frequency | UINT16 | × 0.01 | kHz | Read | |||
| HR | 28691doc U0-19 (0x7013) | U0-19 Feedback speed | INT16 | × 0.01 | Hz | Read | |||
| HR | 28692doc U0-20 (0x7014) | U0-20 Remaining running time | UINT16 | × 0.1 | min | Read | |||
| HR | 28693doc U0-21 (0x7015) | U0-21 AI1 voltage before correction | INT16 | × 0.001 | V | Read | |||
| HR | 28697doc U0-25 (0x7019) | U0-25 Current power-on time | UINT16 | min | Read | ||||
| HR | 28698doc U0-26 (0x701A) | U0-26 Current running time | UINT16 | × 0.1 | min | Read | |||
| HR | 28699doc U0-27 (0x701B) | U0-27 Pulse input frequency | UINT16 | Hz | Read | ||||
| HR | 28700doc U0-28 (0x701C) | U0-28 Communication reference read-back | INT16 | × 0.01 | % | Read | |||
| HR | 28701doc U0-29 (0x701D) | U0-29 Encoder feedback speed | INT16 | × 0.01 | Hz | Read | |||
| HR | 28702doc U0-30 (0x701E) | U0-30 Main frequency X | INT16 | × 0.01 | Hz | Read | |||
| HR | 28703doc U0-31 (0x701F) | U0-31 Auxiliary frequency Y | INT16 | × 0.01 | Hz | Read | |||
| HR | 28706doc U0-34 (0x7022) | U0-34 Motor temperature | INT16 | °C | Read | ||||
| HR | 28707doc U0-35 (0x7023) | U0-35 Target torque | INT16 | × 0.1 | % | Read | |||
| HR | 28709doc U0-37 (0x7025) | U0-37 Power factor angle | INT16 | × 0.1 | ° | Read | |||
| HR | 28711doc U0-39 (0x7027) | U0-39 Target voltage upon V/f separation | UINT16 | V | Read | ||||
| HR | 28712doc U0-40 (0x7028) | U0-40 Output voltage upon V/f separation | UINT16 | V | Read | ||||
| HR | 28717doc U0-45 (0x702D) | U0-45 Fault subcode | UINT16 | Read | |||||
| HR | 28718doc U0-46 (0x702E) | U0-46 Inverter unit temperature | INT16 | °C | Read | ||||
| HR | 32768doc 8000H | AC drive fault | Fault code; codes printed in hex in the guide. | UINT16 | Read | 0 = No fault; 2 = Overcurrent during acceleration; 3 = Overcurrent during deceleration; 4 = Overcurrent during operation at constant speed; 5 = Overvoltage during acceleration; 6 = Overvoltage during deceleration; 7 = Overvoltage during operation at constant speed; 8 = Snubber resistor overload; 9 = Undervoltage fault; 10 = AC drive overload; 11 = Motor overload; 12 = Input phase loss; 13 = Output phase loss; 14 = IGBT overtemperature; 15 = External fault; 16 = Communication fault; 17 = Contactor fault; 18 = Current detection fault; 19 = Motor auto-tuning fault; 20 = Encoder/PG card fault; 21 = Parameter read-write error; 22 = AC drive hardware fault; 23 = Motor short circuit to ground; 26 = Running time reached; 27 = User-defined fault 1; 28 = User-defined fault 2; 29 = Power-on time reached; 30 = Load lost; 31 = PID feedback loss during operation; 40 = Fast current limit timeout; 41 = Motor switchover fault during operation; 42 = Excessive speed deviation; 43 = Motor overspeed; 45 = Motor overtemperature; 90 = Encoder PPR reference error; 91 = Encoder not connected; 92 = Initial position error; 94 = Speed feedback error | |||
| HR | 61442doc F0-02 (0xF002) | F0-02 Command source selection | Set 2 so 2000H commands are accepted. | UINT16 | Read/write | 0 = Operating panel / software; 1 = Terminal; 2 = Communication | |||
| HR | 61443doc F0-03 (0xF003) | F0-03 Main frequency source X | Set 9 so 1000H sets the speed. | UINT16 | Read/write | 0 = Digital setting (non-retentive); 1 = Digital setting (retentive); 2 = AI1; 3 = AI2; 4 = AI3; 5 = Pulse reference (DI5); 6 = Multi-reference; 7 = Simple PLC; 8 = PID; 9 = Communication | |||
| HR | 61450doc F0-10 (0xF00A) | F0-10 Maximum frequency | 5.00-599.00 Hz; 1000H is a percentage of this. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 63758doc F9-14 (0xF90E) | F9-14 1st fault type | 0-99; most recent fault, same codes as 8000H. | UINT16 | Read | ||||
| HR | 64768doc FD-00 (0xFD00) | FD-00 Baud rate | Default 5 (9600 bit/s). | UINT16 | Read/write | 0 = 300 bit/s; 1 = 600 bit/s; 2 = 1200 bit/s; 3 = 2400 bit/s; 4 = 4800 bit/s; 5 = 9600 bit/s; 6 = 19200 bit/s; 7 = 38400 bit/s; 8 = 57600 bit/s; 9 = 115200 bit/s | |||
| HR | 64769doc FD-01 (0xFD01) | FD-01 Modbus data format | UINT16 | Read/write | 0 = No check (8-N-2); 1 = Even parity (8-E-1); 2 = Odd parity (8-O-1); 3 = No check (8-N-1) | ||||
| HR | 64770doc FD-02 (0xFD02) | FD-02 Local address | 1-247, default 1. | UINT16 | Read/write | ||||
| HR | 64771doc FD-03 (0xFD03) | FD-03 Response delay | 0-20 ms, default 2. | UINT16 | ms | Read/write | |||
| HR | 64772doc FD-04 (0xFD04) | FD-04 Modbus communication timeout | 0.0-60.0 s; 0.0 = off. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 64774doc FD-06 (0xFD06) | FD-06 Communication fault reset | UINT16 | Read/write | 0 = Disabled; 1 = Enabled |
Notes on this map
- Every register is one 16-bit word. Scales come from the 'Basic Unit' column of Table 1-1; signedness comes from the data type printed in each U0 parameter description.
- Left out: U0-14 (unit printed differently in the two tables), U0-22/U0-23, U0-32/U0-33/U0-36/U0-38 (position/debug values) and everything from U0-58 on, because Table 1-1 and the parameter descriptions give different addresses for those rows (e.g. U0-59 at 0x7035 vs 0x703B).
- The 1000H-1020H 'stop/run parameter' block is listed without units, so it is left out; read the U0 group instead.
- F9-14 holds the same fault code as 8000H; the guide prints the 8000H codes in hex (001AH = 26).
- Function codes: 03H read, 06H write, 10H multi-write; up to 12 consecutive registers per request, and a request must not run past the end of a parameter group.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Inovance MD500-PLUS series AC drive
What Modbus registers does the Inovance MD500-PLUS series AC drive have?
This map lists 55 registers: 55 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Inovance MD500-PLUS series AC drive Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are hex and go on the wire unchanged: the guide's reverse-run example is 01 06 20 00 00 02, writing 2 to 2000H. Parameter addresses are the group code (F0-FE, A0-AC, 70 for U0) followed by the parameter number in hex (F3-12 = 0xF30C).
What are the minimum Modbus registers to integrate the Inovance MD500-PLUS series AC drive?
Start with HR 8192 Control command (Run / stop / reset command); HR 4096 Communication reference (Speed reference as % of max frequency); HR 12288 AC drive state (Forward / reverse / stopped); HR 32768 AC drive fault (Fault code); HR 28672 U0-00 Running frequency (Running frequency); HR 28676 U0-04 Output current (Output current); HR 28674 U0-02 Bus voltage (DC bus voltage).
How do I enable Modbus control of the Inovance MD500-PLUS series AC drive?
RS-485 needs the MD38TX1 extension card. F0-02 = 2 accepts run commands over communication; F0-03 = 9 makes 1000H the main frequency. FD-00..FD-02 set baud, data format and address.
What happens when the Inovance MD500-PLUS series AC drive loses Modbus communication?
FD-04 sets a Modbus timeout (0.0 s = off); when messages stop for longer the drive reports a communication fault (Err16).
Where is the official Inovance MD500-PLUS series AC drive Modbus documentation?
The source is MD500-PLUS Series General-Purpose AC Drive Software Guide (19011580 A04), revision 2021-11, published free by Inovance at https://inovance.eu/fileadmin/downloads/Manuals/EN/MD500-PLUS/MD500-PLUS_Software_Guide_EN_A04_19011580.pdf.
More Inovance Modbus register maps
Other variable frequency drives register maps
- Variable frequency drive
INVT Goodrive20 (GD20) general-purpose VFD
INVT Goodrive20 drives using the built-in RS-485 Modbus port, per the GD20 VFD manual V2.1 (chapter 7, communication protocol).
Also known as: GD20, Goodrive20, GD20-EU, GD20-UL, GD20 vector VFD - Variable frequency drive
Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU)
Johnson Controls / PENN VFD68Bxx (200-240 V) and VFD68Cxx (380-480 V) drives on their RJ45 PU port with Modbus RTU selected (P.549 = 1), per the VFD68 Variable Frequency Drives Technical Bulletin, Appendix 4.
Also known as: VFD68Bxx, VFD68Cxx, VFD68BDC-2C, VFD68CDF-2C, PENN VFD68 - Variable frequency drive
LS Electric LSLV-S100 AC drive (built-in RS-485 Modbus RTU)
LS Electric S100 drives (0.4-75 kW, including IP66) using the built-in RS-485 terminals S+/S-/SG with CM.02 = Modbus-RTU, per S100 User Manual V4.3.
Also known as: LSLV-S100, LSIS S100, LS S100, LSLV0075S100-4EOFNS - Variable frequency drive (HVAC fans and pumps)
Schneider Electric Altivar 212 (embedded Modbus RTU)
ATV212H (IP21) and ATV212W (IP55) drives on the built-in Modbus RTU ports (RJ45 and open-style terminal), per Modbus manual S1A53844.
Also known as: ATV212, Altivar 212, ATV212H, ATV212W, ATV212HU15N4, ATV212WD11N4 - Variable frequency drive
SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU)
SEW-EURODRIVE MOVITRAC LTE-B+ inverters on the RJ45 Modbus RTU port, per product manual 31965822/EN edition 03/2024.
Also known as: MOVITRAC LTE-B+, LTE-B+, MC LTE B+, MOVITRAC LTE B plus - Variable frequency drive
TECO-Westinghouse E510 inverter (Modbus RTU/ASCII)
TECO-Westinghouse E510 inverters using the built-in RS-485 port (CON2), per communication addendum DOCUMENT-TECO-E510-AC001 Ver01 (2015-03).
Also known as: TECO E510, E510 Communication Addendum
All variable frequency drives Modbus register maps →
Source: MD500-PLUS Series General-Purpose AC Drive Software Guide · 19011580 A04 · rev. 2021-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.