- VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU)
Variable frequency drive · Modbus register map
Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU) Modbus register map
Updated 17 November 2026
Compact HVAC drive with a Modbus RTU subordinate on its RJ45 PU port. All data are holding registers: reset and parameter-clear commands, a control/status word, the running-frequency command (0.01 Hz), a real-time monitor block (output frequency, current, voltage, power, load factors, PID values, energy), eight fault-history slots with fault codes, and every parameter P.n at register 41000 + n.
This page lists 50 Modbus registers for the Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU) — 20 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Johnson Controls’s own free documentation (linked below) and checked against it.
- Manufacturer
- Johnson Controls
- Model
- VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 50 (20 writable)
- Transport
- Modbus RTU
- Default unit ID
- 0
- Default serial
- 9600 baud, 8E1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- VFD68Bxx, VFD68Cxx, VFD68BDC-2C, VFD68CDF-2C, PENN VFD68
Integration notes: Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU)
Set P.549 = 1 (Modbus RTU), a station number in P.117 and the speed/parity in P.118/P.120, then use function 03/06/16 on 4xxxx holding registers: command the drive with 40009 (bit 1 forward, bit 2 reverse) and 40014 (0.01 Hz), and monitor 40201-40214 and 40501.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 8 | VFD Status / Control Input Instruction | BITMAP16 | Run command (write) / drive status (read) | Read/write |
| HR 13 | Running Frequency (RAM) | UINT16 | Frequency command in 0.01 Hz | Read/write |
| HR 200 | Output Frequency | UINT16 | Output frequency | Read |
| HR 201 | Output Current | UINT16 | Output current | Read |
| HR 213 | Output Power | UINT16 | Output power | Read |
| HR 500 | Fault History 1 | UINT16 | Latest fault code | Read/write |
| HR 1 | VFD Reset | UINT16 | Fault reset | Write |
Enable Modbus control & writes
On the operation panel set P.549 = 1 (Modbus RTU) and P.117 = 1-247 (0 means the drive never replies), then P.118/P.120 for speed and parity; these parameters can only be set when P.160 = 0.
Communication loss & watchdog
P.122 (PU communication check time interval: 0, 0.1-999.8 s or 9999, default 9999; the bulletin does not explain the 0 and 9999 settings) and P.502 (stop mode at communication error: coast with E.PUE, decelerate then E.PUE, or decelerate with E.PUE shown but no fault output).
Byte order & addressing
- Register numbers are 4xxxx; subtract 40001 for the PDU address.
- Default station number 0 means broadcast-only: the drive will not answer until P.117 is set.
- Parity and stop bits are linked: no parity forces 2 stop bits, odd/even use 1.
- Writing to 40014 changes the RAM value only; 40015 writes the frequency to EEPROM.
Network setup
- RJ45 PU port pins (Table 87): 1 and 7 SG (ground), 3 RDA, 4 SDB, 5 SDA, 6 RDB. Do not connect pins 2 and 8 (drive power supply).
- Speeds 4800/9600/19200/38400 bps, 8 data bits, up to 32 drives per segment.
Watch out for
- Supported function codes are 03, 06, 08, 16 and 70 (H46 access log).
- Reading a non-existent register in a block returns 0 instead of an error unless every register in the block is invalid.
Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 40002 | VFD Reset | Write any value to reset the drive. | UINT16 | Write | ||||
| HR | 2doc 40003 | Parameter Clear | Write H965A. | UINT16 | Write | ||||
| HR | 3doc 40004 | All Parameters Clear | Write H965A. | UINT16 | Write | ||||
| HR | 5doc 40006 | Parameter Clear (keeps communication settings) | Write H965A. Communication parameters are not cleared. | UINT16 | Write | ||||
| HR | 6doc 40007 | All Parameters Clear (keeps communication settings) | Write H965A. Communication parameters are not cleared. | UINT16 | Write | ||||
| HR | 8doc 40009 | VFD Status / Control Input Instruction | Write control bits (Table 125: 1 FWD, 2 REV, 10 MRS ...); read returns status bits. | BITMAP16 | Read/write | bit 0 = RUN (drive running); bit 1 = Forward rotation; bit 2 = Reverse rotation; bit 3 = SU up to frequency; bit 4 = OL overload; bit 6 = FU frequency detection; bit 7 = ABC fault; bit 15 = Fault occurrence | |||
| HR | 9doc 40010 | Operation Mode / VFD Setting | Write sets the operation mode; read returns the mode status. | UINT16 | Read/write | ||||
| HR | 13doc 40014 | Running Frequency (RAM) | Frequency command, not stored. 6000 = 60.00 Hz (P.37 can change it to speed). | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 14doc 40015 | Running Frequency (EEPROM) | Frequency command stored in EEPROM. | UINT16 | × 0.01 | Hz | Write | ||
| HR | 200doc 40201 | Output Frequency | UINT16 | × 0.01 | Hz | Read | |||
| HR | 201doc 40202 | Output Current | UINT16 | × 0.01 | A | Read | |||
| HR | 202doc 40203 | Output Voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 204doc 40205 | Frequency Setting | UINT16 | × 0.01 | Hz | Read | |||
| HR | 207doc 40208 | Converter Output Voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 208doc 40209 | Regenerative Brake Duty | UINT16 | × 0.1 | % | Read | |||
| HR | 209doc 40210 | Electronic Thermal Relay Load Factor | UINT16 | × 0.1 | % | Read | |||
| HR | 210doc 40211 | Output Current Peak | UINT16 | × 0.01 | A | Read | |||
| HR | 211doc 40212 | Converter Output Voltage Peak | UINT16 | × 0.1 | V | Read | |||
| HR | 213doc 40214 | Output Power | UINT16 | × 0.01 | kW | Read | |||
| HR | 214doc 40215 | Input Terminal Status | BITMAP16 | Read | bit 0 = STF; bit 1 = STR; bit 4 = RL; bit 5 = RM; bit 6 = RH | ||||
| HR | 215doc 40216 | Output Terminal Status | BITMAP16 | Read | bit 0 = RUN; bit 5 = ABC | ||||
| HR | 219doc 40220 | Cumulative Energization Time | UINT16 | h | Read | ||||
| HR | 222doc 40223 | Actual Operation Time | UINT16 | h | Read | ||||
| HR | 223doc 40224 | Motor Load Factor | UINT16 | × 0.1 | % | Read | |||
| HR | 224doc 40225 | Cumulative Power | UINT16 | kWh | Read | ||||
| HR | 251doc 40252 | PID Setpoint | UINT16 | × 0.1 | % | Read | |||
| HR | 252doc 40253 | PID Measured Value | UINT16 | × 0.1 | % | Read | |||
| HR | 260doc 40261 | Motor Thermal Load Factor | UINT16 | × 0.1 | % | Read | |||
| HR | 261doc 40262 | VFD Thermal Load Factor | UINT16 | × 0.1 | % | Read | |||
| HR | 262doc 40263 | Cumulative Power 2 | UINT16 | × 0.01 | kWh | Read | |||
| HR | 263doc 40264 | PTC Thermistor Resistance | UINT16 | × 0.01 | kΩ | Read | |||
| HR | 500doc 40501 | Fault History 1 | Fault code in the low byte. Writing any value clears the history. | UINT16 | Read/write | 0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 192 = E.CPU; 196 = E.CDO; 197 = E.IOH; 199 = E.AIE; 201 = E.SAF; 245 = E.5 | |||
| HR | 501doc 40502 | Fault History 2 | Fault code in the low byte. | UINT16 | Read | 0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 192 = E.CPU; 196 = E.CDO; 197 = E.IOH; 199 = E.AIE; 201 = E.SAF; 245 = E.5 | |||
| HR | 502doc 40503 | Fault History 3 | Fault code in the low byte. | UINT16 | Read | 0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 192 = E.CPU; 196 = E.CDO; 197 = E.IOH; 199 = E.AIE; 201 = E.SAF; 245 = E.5 | |||
| HR | 503doc 40504 | Fault History 4 | Fault code in the low byte. | UINT16 | Read | 0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 192 = E.CPU; 196 = E.CDO; 197 = E.IOH; 199 = E.AIE; 201 = E.SAF; 245 = E.5 | |||
| HR | 504doc 40505 | Fault History 5 | Fault code in the low byte. | UINT16 | Read | 0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 192 = E.CPU; 196 = E.CDO; 197 = E.IOH; 199 = E.AIE; 201 = E.SAF; 245 = E.5 | |||
| HR | 505doc 40506 | Fault History 6 | Fault code in the low byte. | UINT16 | Read | 0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 192 = E.CPU; 196 = E.CDO; 197 = E.IOH; 199 = E.AIE; 201 = E.SAF; 245 = E.5 | |||
| HR | 506doc 40507 | Fault History 7 | Fault code in the low byte. | UINT16 | Read | 0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 192 = E.CPU; 196 = E.CDO; 197 = E.IOH; 199 = E.AIE; 201 = E.SAF; 245 = E.5 | |||
| HR | 507doc 40508 | Fault History 8 | Fault code in the low byte. | UINT16 | Read | 0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 192 = E.CPU; 196 = E.CDO; 197 = E.IOH; 199 = E.AIE; 201 = E.SAF; 245 = E.5 | |||
| HR | 1003doc 41004 | P.4 High speed | Multi-speed RH setting; manual example reads 6000 = 60.00 Hz. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 1004doc 41005 | P.5 Middle speed | Multi-speed RM setting; example 3000 = 30.00 Hz. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 1005doc 41006 | P.6 Low speed | Multi-speed RL setting; example 1000 = 10.00 Hz. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 1006doc 41007 | P.7 Acceleration time | Parameter P.7; example writes 5 = 0.5 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 1007doc 41008 | P.8 Deceleration time | Parameter P.8; example writes 10 = 1 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 1116doc 41117 | P.117 PU communication station number | 0 = no reply; 1-247 station number. | UINT16 | Read/write | ||||
| HR | 1117doc 41118 | P.118 PU communication speed | Value x 100 = bit/s (48, 96, 192, 384). | UINT16 | Read/write | ||||
| HR | 1119doc 41120 | P.120 PU communication parity check | UINT16 | Read/write | 0 = No parity, 2 stop bits; 1 = Odd parity, 1 stop bit; 2 = Even parity, 1 stop bit | ||||
| HR | 1342doc 41343 | P.343 Communication error count | Communication errors since power-up (read only). | UINT16 | Read | ||||
| HR | 1501doc 41502 | P.502 Stop mode selection at communication error | UINT16 | Read/write | 0 = Coast to stop (E.PUE); 1 = Decelerate to stop, then E.PUE; 2 = Decelerate to stop, E.PUE shown, no fault output | ||||
| HR | 1548doc 41549 | P.549 Protocol selection | UINT16 | Read/write | 0 = VFD computer link protocol; 1 = Modbus RTU |
Notes on this map
- Source is Johnson Controls' documentation portal; the bulletin's PDF attachment is 24-7664-3051.pdf.
- Scaling comes from the unit column of Table 126 and the worked examples (H1770 = 60.00 Hz written to 40014; P.4-P.6 read as 6000/3000/1000 = 60/30/10 Hz; 0.5 s written to P.7 as 5).
- Parameters: register = 41000 + parameter number for P.0-P.999 (C2-C7 calibration values also have 42xxx/43xxx analog-value registers). Only the parameters whose scaling the bulletin shows or that set up communication are listed; see the drive parameter lists for the rest.
- Communication defaults from Table 88: P.117 station number 0 (no reply - must be set 1-247), P.118 = 96 (9600 bps), P.120 = 2 (even parity, 1 stop bit), P.549 = 0 (computer link). The VFD68 parameter table (Table 34) instead lists P.549 = 1 (Modbus RTU) as the VFD68 default, so check P.549 on the drive. Communication parameters can only be set when P.160 = 0.
- Operation-mode values for 40010 and the control/status bit assignments can change with P.180-P.182 and P.190-P.192; the bits listed are the initial settings.
- PID Deviation (40254, 0.1 %) is left out: a deviation can be negative but the bulletin does not say whether the register is signed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU)
What Modbus registers does the Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU) have?
This map lists 50 registers: 50 holding registers. 20 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as 4xxxx. The bulletin states the address in the frame is the register number minus 40001 and shows it in examples (41004 is sent as H03EB = 1003).
What are the minimum Modbus registers to integrate the Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU)?
Start with HR 8 VFD Status / Control Input Instruction (Run command (write) / drive status (read)); HR 13 Running Frequency (RAM) (Frequency command in 0.01 Hz); HR 200 Output Frequency (Output frequency); HR 201 Output Current (Output current); HR 213 Output Power (Output power); HR 500 Fault History 1 (Latest fault code); HR 1 VFD Reset (Fault reset).
How do I enable Modbus control of the Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU)?
On the operation panel set P.549 = 1 (Modbus RTU) and P.117 = 1-247 (0 means the drive never replies), then P.118/P.120 for speed and parity; these parameters can only be set when P.160 = 0.
What happens when the Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU) loses Modbus communication?
P.122 (PU communication check time interval: 0, 0.1-999.8 s or 9999, default 9999; the bulletin does not explain the 0 and 9999 settings) and P.502 (stop mode at communication error: coast with E.PUE, decelerate then E.PUE, or decelerate with E.PUE shown but no fault output).
Where is the official Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU) Modbus documentation?
The source is VFD68 Variable Frequency Drives Technical Bulletin (24-7664-3051), revision 2019-08-09, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/r/PENN-Controls/en-US/VFD68-Variable-Frequency-Drives-Technical-Bulletin/C.
More Johnson Controls Modbus register maps
- Sensor
Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter
Johnson Controls GS3000 / GS3001 electrochemical CO transmitters with RS-485 Modbus RTU, per installation guide 24-11484-00021 (2020-10-01).
Also known as: GS3000, GS3001, 24-11484-00021 - Thermostat
Johnson Controls PENN System 450 with C450CRN-1 Modbus communications control module
PENN System 450 modular temperature, pressure and humidity control systems built around a C450CRN-1 Modbus RTU control module (up to 3 sensors and 10 relay/analog outputs), per LIT-12011826 (2021-01-14).
Also known as: C450CRN-1, C450CRN, System 450, PENN System 450, LIT-12011826 - Thermostat
Johnson Controls PENN TC3221 refrigeration temperature controller (Modbus RTU)
PENN TC3221 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3221, TC3, PENN TC3, LIT-12013523 - Thermostat
Johnson Controls PENN TC3222 refrigeration temperature controller (Modbus RTU)
PENN TC3222 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3222, TC3, PENN TC3, LIT-12013523 - Thermostat
Johnson Controls PENN TC3223 refrigeration temperature controller (Modbus RTU)
PENN TC3223 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3223, TC3, PENN TC3, LIT-12013523 - Thermostat
Johnson Controls PENN TC3224N9V refrigeration temperature controller (Modbus RTU)
PENN TC3224N9V electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3224N9V, TC3, PENN TC3, LIT-12013523, TC3224N9R, TC3224 - Thermostat (fan coil)
Johnson Controls T7000 series fan coil thermostat (Modbus RTU)
Johnson Controls T7000 series Modbus thermostats listed in the data table: T7600-TF21, T7601-TF20 (ECM fan), T7600-TF20 (relay), T7603-T000 (single-stage heating) and T7600-TB21 (with AI); data table revision 2.4 (2019-12-23).
Also known as: T7600-TF21-9JS0, T7601-TF20-9JS0, T7600-TF20-9JS0, T7603-T000-9JF0, T7600-TF21-1JS0, T7601-TF20-1JS0, T7600-TF20-1JS0, T7603-T000-1JF0, T7600-TB21-9JA0, T7600, T7601, T7603
Other variable frequency drives register maps
- Variable frequency drive
LS Electric LSLV-S100 AC drive (built-in RS-485 Modbus RTU)
LS Electric S100 drives (0.4-75 kW, including IP66) using the built-in RS-485 terminals S+/S-/SG with CM.02 = Modbus-RTU, per S100 User Manual V4.3.
Also known as: LSLV-S100, LSIS S100, LS S100, LSLV0075S100-4EOFNS - Variable frequency drive (HVAC fans and pumps)
Schneider Electric Altivar 212 (embedded Modbus RTU)
ATV212H (IP21) and ATV212W (IP55) drives on the built-in Modbus RTU ports (RJ45 and open-style terminal), per Modbus manual S1A53844.
Also known as: ATV212, Altivar 212, ATV212H, ATV212W, ATV212HU15N4, ATV212WD11N4 - Variable frequency drive
SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU)
SEW-EURODRIVE MOVITRAC LTE-B+ inverters on the RJ45 Modbus RTU port, per product manual 31965822/EN edition 03/2024.
Also known as: MOVITRAC LTE-B+, LTE-B+, MC LTE B+, MOVITRAC LTE B plus - Variable frequency drive
TECO-Westinghouse E510 inverter (Modbus RTU/ASCII)
TECO-Westinghouse E510 inverters using the built-in RS-485 port (CON2), per communication addendum DOCUMENT-TECO-E510-AC001 Ver01 (2015-03).
Also known as: TECO E510, E510 Communication Addendum - Variable frequency drive
Vacon VACON 20 AC drive (built-in Modbus RTU)
VACON 20 compact drives with the standard Vacon 20 application on the built-in RS-485 Modbus RTU port, per complete user manual DPD00716H1 (software FW0107V012).
Also known as: VACON 20, Vacon 20, VACON0020 - Variable frequency drive
Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU
Yaskawa G7 (CIMR-G7U) drives using built-in Modbus RTU on terminals R+/R-/S+/S-, per the Modbus Communication Manual G7 TM.G7.11 (rev 07-01).
Also known as: CIMR-G7U, G7U, G7 Drive
All variable frequency drives Modbus register maps →
Source: VFD68 Variable Frequency Drives Technical Bulletin · 24-7664-3051 · rev. 2019-08-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.