  4. VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU)

Variable frequency drive · Modbus register map

Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

Compact HVAC drive with a Modbus RTU subordinate on its RJ45 PU port. All data are holding registers: reset and parameter-clear commands, a control/status word, the running-frequency command (0.01 Hz), a real-time monitor block (output frequency, current, voltage, power, load factors, PID values, energy), eight fault-history slots with fault codes, and every parameter P.n at register 41000 + n.

This page lists 50 Modbus registers for the Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU) — 20 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Johnson Controls’s own free documentation (linked below) and checked against it.

Manufacturer
Johnson Controls
Model
VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU)
Equipment type
Variable frequency drive
Registers
50 (20 writable)
Transport
Modbus RTU
Default unit ID
0
Default serial
9600 baud, 8E1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
VFD68Bxx, VFD68Cxx, VFD68BDC-2C, VFD68CDF-2C, PENN VFD68
Source document
VFD68 Variable Frequency Drives Technical Bulletin · 24-7664-3051 · rev. 2019-08-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU)

Integration in brief

Set P.549 = 1 (Modbus RTU), a station number in P.117 and the speed/parity in P.118/P.120, then use function 03/06/16 on 4xxxx holding registers: command the drive with 40009 (bit 1 forward, bit 2 reverse) and 40014 (0.01 Hz), and monitor 40201-40214 and 40501.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 8VFD Status / Control Input InstructionBITMAP16Run command (write) / drive status (read)Read/write
HR 13Running Frequency (RAM)UINT16Frequency command in 0.01 HzRead/write
HR 200Output FrequencyUINT16Output frequencyRead
HR 201Output CurrentUINT16Output currentRead
HR 213Output PowerUINT16Output powerRead
HR 500Fault History 1UINT16Latest fault codeRead/write
HR 1VFD ResetUINT16Fault resetWrite

Enable Modbus control & writes

On the operation panel set P.549 = 1 (Modbus RTU) and P.117 = 1-247 (0 means the drive never replies), then P.118/P.120 for speed and parity; these parameters can only be set when P.160 = 0.

Communication loss & watchdog

P.122 (PU communication check time interval: 0, 0.1-999.8 s or 9999, default 9999; the bulletin does not explain the 0 and 9999 settings) and P.502 (stop mode at communication error: coast with E.PUE, decelerate then E.PUE, or decelerate with E.PUE shown but no fault output).

Byte order & addressing

Network setup

Watch out for

Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

50 of 50 shown
Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 40002VFD ResetWrite any value to reset the drive.UINT16Write
HR2doc 40003Parameter ClearWrite H965A.UINT16Write
HR3doc 40004All Parameters ClearWrite H965A.UINT16Write
HR5doc 40006Parameter Clear (keeps communication settings)Write H965A. Communication parameters are not cleared.UINT16Write
HR6doc 40007All Parameters Clear (keeps communication settings)Write H965A. Communication parameters are not cleared.UINT16Write
HR8doc 40009VFD Status / Control Input InstructionWrite control bits (Table 125: 1 FWD, 2 REV, 10 MRS ...); read returns status bits.BITMAP16Read/writebit 0 = RUN (drive running); bit 1 = Forward rotation; bit 2 = Reverse rotation; bit 3 = SU up to frequency; bit 4 = OL overload; bit 6 = FU frequency detection; bit 7 = ABC fault; bit 15 = Fault occurrence
HR9doc 40010Operation Mode / VFD SettingWrite sets the operation mode; read returns the mode status.UINT16Read/write
HR13doc 40014Running Frequency (RAM)Frequency command, not stored. 6000 = 60.00 Hz (P.37 can change it to speed).UINT16× 0.01HzRead/write
HR14doc 40015Running Frequency (EEPROM)Frequency command stored in EEPROM.UINT16× 0.01HzWrite
HR200doc 40201Output FrequencyUINT16× 0.01HzRead
HR201doc 40202Output CurrentUINT16× 0.01ARead
HR202doc 40203Output VoltageUINT16× 0.1VRead
HR204doc 40205Frequency SettingUINT16× 0.01HzRead
HR207doc 40208Converter Output VoltageUINT16× 0.1VRead
HR208doc 40209Regenerative Brake DutyUINT16× 0.1%Read
HR209doc 40210Electronic Thermal Relay Load FactorUINT16× 0.1%Read
HR210doc 40211Output Current PeakUINT16× 0.01ARead
HR211doc 40212Converter Output Voltage PeakUINT16× 0.1VRead
HR213doc 40214Output PowerUINT16× 0.01kWRead
HR214doc 40215Input Terminal StatusBITMAP16Readbit 0 = STF; bit 1 = STR; bit 4 = RL; bit 5 = RM; bit 6 = RH
HR215doc 40216Output Terminal StatusBITMAP16Readbit 0 = RUN; bit 5 = ABC
HR219doc 40220Cumulative Energization TimeUINT16hRead
HR222doc 40223Actual Operation TimeUINT16hRead
HR223doc 40224Motor Load FactorUINT16× 0.1%Read
HR224doc 40225Cumulative PowerUINT16kWhRead
HR251doc 40252PID SetpointUINT16× 0.1%Read
HR252doc 40253PID Measured ValueUINT16× 0.1%Read
HR260doc 40261Motor Thermal Load FactorUINT16× 0.1%Read
HR261doc 40262VFD Thermal Load FactorUINT16× 0.1%Read
HR262doc 40263Cumulative Power 2UINT16× 0.01kWhRead
HR263doc 40264PTC Thermistor ResistanceUINT16× 0.01kΩRead
HR500doc 40501Fault History 1Fault code in the low byte. Writing any value clears the history.UINT16Read/write0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 192 = E.CPU; 196 = E.CDO; 197 = E.IOH; 199 = E.AIE; 201 = E.SAF; 245 = E.5
HR501doc 40502Fault History 2Fault code in the low byte.UINT16Read0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 192 = E.CPU; 196 = E.CDO; 197 = E.IOH; 199 = E.AIE; 201 = E.SAF; 245 = E.5
HR502doc 40503Fault History 3Fault code in the low byte.UINT16Read0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 192 = E.CPU; 196 = E.CDO; 197 = E.IOH; 199 = E.AIE; 201 = E.SAF; 245 = E.5
HR503doc 40504Fault History 4Fault code in the low byte.UINT16Read0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 192 = E.CPU; 196 = E.CDO; 197 = E.IOH; 199 = E.AIE; 201 = E.SAF; 245 = E.5
HR504doc 40505Fault History 5Fault code in the low byte.UINT16Read0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 192 = E.CPU; 196 = E.CDO; 197 = E.IOH; 199 = E.AIE; 201 = E.SAF; 245 = E.5
HR505doc 40506Fault History 6Fault code in the low byte.UINT16Read0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 192 = E.CPU; 196 = E.CDO; 197 = E.IOH; 199 = E.AIE; 201 = E.SAF; 245 = E.5
HR506doc 40507Fault History 7Fault code in the low byte.UINT16Read0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 192 = E.CPU; 196 = E.CDO; 197 = E.IOH; 199 = E.AIE; 201 = E.SAF; 245 = E.5
HR507doc 40508Fault History 8Fault code in the low byte.UINT16Read0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 192 = E.CPU; 196 = E.CDO; 197 = E.IOH; 199 = E.AIE; 201 = E.SAF; 245 = E.5
HR1003doc 41004P.4 High speedMulti-speed RH setting; manual example reads 6000 = 60.00 Hz.UINT16× 0.01HzRead/write
HR1004doc 41005P.5 Middle speedMulti-speed RM setting; example 3000 = 30.00 Hz.UINT16× 0.01HzRead/write
HR1005doc 41006P.6 Low speedMulti-speed RL setting; example 1000 = 10.00 Hz.UINT16× 0.01HzRead/write
HR1006doc 41007P.7 Acceleration timeParameter P.7; example writes 5 = 0.5 s.UINT16× 0.1sRead/write
HR1007doc 41008P.8 Deceleration timeParameter P.8; example writes 10 = 1 s.UINT16× 0.1sRead/write
HR1116doc 41117P.117 PU communication station number0 = no reply; 1-247 station number.UINT16Read/write
HR1117doc 41118P.118 PU communication speedValue x 100 = bit/s (48, 96, 192, 384).UINT16Read/write
HR1119doc 41120P.120 PU communication parity checkUINT16Read/write0 = No parity, 2 stop bits; 1 = Odd parity, 1 stop bit; 2 = Even parity, 1 stop bit
HR1342doc 41343P.343 Communication error countCommunication errors since power-up (read only).UINT16Read
HR1501doc 41502P.502 Stop mode selection at communication errorUINT16Read/write0 = Coast to stop (E.PUE); 1 = Decelerate to stop, then E.PUE; 2 = Decelerate to stop, E.PUE shown, no fault output
HR1548doc 41549P.549 Protocol selectionUINT16Read/write0 = VFD computer link protocol; 1 = Modbus RTU

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU)

What Modbus registers does the Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU) have?

This map lists 50 registers: 50 holding registers. 20 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as 4xxxx. The bulletin states the address in the frame is the register number minus 40001 and shows it in examples (41004 is sent as H03EB = 1003).

What are the minimum Modbus registers to integrate the Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU)?

Start with HR 8 VFD Status / Control Input Instruction (Run command (write) / drive status (read)); HR 13 Running Frequency (RAM) (Frequency command in 0.01 Hz); HR 200 Output Frequency (Output frequency); HR 201 Output Current (Output current); HR 213 Output Power (Output power); HR 500 Fault History 1 (Latest fault code); HR 1 VFD Reset (Fault reset).

How do I enable Modbus control of the Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU)?

On the operation panel set P.549 = 1 (Modbus RTU) and P.117 = 1-247 (0 means the drive never replies), then P.118/P.120 for speed and parity; these parameters can only be set when P.160 = 0.

What happens when the Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU) loses Modbus communication?

P.122 (PU communication check time interval: 0, 0.1-999.8 s or 9999, default 9999; the bulletin does not explain the 0 and 9999 settings) and P.502 (stop mode at communication error: coast with E.PUE, decelerate then E.PUE, or decelerate with E.PUE shown but no fault output).

Where is the official Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU) Modbus documentation?

The source is VFD68 Variable Frequency Drives Technical Bulletin (24-7664-3051), revision 2019-08-09, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/r/PENN-Controls/en-US/VFD68-Variable-Frequency-Drives-Technical-Bulletin/C.

More Johnson Controls Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: VFD68 Variable Frequency Drives Technical Bulletin · 24-7664-3051 · rev. 2019-08-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.