Variable frequency drive · Modbus register map
SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU) Modbus register map
Updated 17 November 2026
SEW-EURODRIVE's compact frequency inverter with Modbus RTU on the RJ45 communication socket. Registers 1-3 carry the SEW process output words (control word, speed setpoint, ramp time), registers 6-8 the process input words (status, actual speed, actual current), and the monitoring and setup parameters have fixed Modbus register numbers listed in the parameter overview. This map covers the process data and the monitoring values whose scaling the manual states.
This page lists 14 Modbus registers for the SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from SEW-EURODRIVE’s own free documentation (linked below) and checked against it.
- Manufacturer
- SEW-EURODRIVE
- Model
- MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 14 (5 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 115200 baud, 8N1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- MOVITRAC LTE-B+, LTE-B+, MC LTE B+, MOVITRAC LTE B plus
Integration notes: SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU)
Set P-14 = 101, P-12 = 5 (or 6 to send ramp times in register 3) and P-15 per the fieldbus table, then write register 1 = 0x0006 with register 2 = speed (16384 = P-01). Poll register 6 for status, 7 for actual speed and 8 for current.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | PO1 Control word | BITMAP16 | PO1 control word | Read/write |
| HR 1 | PO2 Setpoint speed | INT16 | PO2 speed setpoint (16384 = P-01) | Read/write |
| HR 5 | PI1 Status word | BITMAP16 | PI1 status word | Read |
| HR 6 | PI2 Actual speed | INT16 | PI2 actual speed | Read |
| HR 7 | PI3 Actual current | UINT16 | PI3 actual current | Read |
| HR 22 | P00-08 DC link voltage | UINT16 | DC link voltage | Read |
| HR 23 | P00-09 Heat sink temperature | INT16 | Heat sink temperature | Read |
| HR 139 | P-12 Control signal source | UINT16 | P-12 control signal source | Read/write |
Enable Modbus control & writes
Set P-14 = 101 for extended parameter access, P-12 = 5 (Modbus RTU, internal ramps P-03/P-04) or 6 (ramps from PO3), and P-15 as the manual's Modbus table shows. P-36 level 1 sets the address (1-63, factory 1) and level 2 the Modbus baud rate (0 = 9.6, 1 = 115.2 (factory), 2 = 19.2, 3 = 38.4, 4 = 57.6, 5 = 76.8 kbit/s). The digital inputs must still be wired so the inverter is enabled.
Communication loss & watchdog
P-36 level 3 sets the reaction to a communication failure: 0 = keep the last setpoint (no fault), 1-4 = coast to a stop after 30/100/1000/3000 ms, 5-8 = rapid stop on P-24 after 30/100/1000/3000 ms. The fault list has fault 50 for a Modbus communication error (0x2B in the PI1 high byte).
Byte order & addressing
- Register numbers are 1-based: subtract 1 for the wire address.
- Control word logic is inverted against most drives: bit 0 = 1 inhibits the output stage; 0x0006 runs, 0x0000 rapid-stops, 0x0001 coasts.
- Speed is a signed relative value: 16384 = +100 % of P-01, -16384 = -100 % (CCW).
Network setup
- Wire RS485- (Modbus) to RJ45 pin 7 and RS485+ to pin 8; pins 4/5 are the engineering port.
- Up to 32 stations; 1200 m at 115200 bit/s with 0.5 mm2 cable.
- Framing is fixed at 8 data bits, no parity, 1 stop bit.
Watch out for
- Parameters above P-15 are only reachable after P-14 = 101 (or the code set in P-37).
- With P-36 level 3 = 0 the inverter keeps running on the last setpoint if the master disappears.
SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | PO1 Control word | 0x0006 = run; 0x0000 = rapid stop; 0x0001 = coast; bit 6 edge = reset. | BITMAP16 | Read/write | bit 0 = Output stage inhibit: 0 = start, 1 = stop (coast); bit 1 = 0 = rapid stop on P-24 ramp, 1 = start; bit 2 = 0 = stop on process ramp (P-03/P-04 or PO3), 1 = start; bit 6 = Fault reset on 0->1 edge | |||
| HR | 1doc 2 | PO2 Setpoint speed | Raw: 16384 (0x4000) = 100 % of P-01; negative (two's complement) = CCW. | INT16 | Read/write | ||||
| HR | 2doc 3 | PO3 Ramp time | 1 digit = 1 ms (100-65535 ms); used when P-12 = 6. | UINT16 | × 0.001 | s | Read/write | ||
| HR | 5doc 6 | PI1 Status word | High byte: 1 inhibited, 2 not enabled, 4 running, 5 factory set; else fault code. | BITMAP16 | Read | bit 0 = Output stage enabled; bit 1 = Inverter ready; bit 2 = PO data enabled; bit 5 = Fault/warning; bit 8 = High byte (bits 8-15): status code, or fault code when bit 5 = 1 (see description) | |||
| HR | 6doc 7 | PI2 Actual speed | Same raw scaling as PO2 (16384 = 100 % of P-01). | INT16 | Read | ||||
| HR | 7doc 8 | PI3 Actual current | Raw: 16384 (0x4000) = 100 % of P-08 rated motor current. | UINT16 | Read | ||||
| HR | 10doc 11 | P00-04 Digital input status | BITMAP16 | Read | bit 0 = DI1; bit 1 = DI2; bit 2 = DI3; bit 3 = DI4 | ||||
| HR | 19doc 20 | P00-01 Analog input 1 value | 1000 = 100 % of max input voltage or current. | UINT16 | × 0.1 | % | Read | ||
| HR | 20doc 21 | P00-02 Analog input 2 value | 1000 = 100 % of max input voltage or current. | UINT16 | × 0.1 | % | Read | ||
| HR | 22doc 23 | P00-08 DC link voltage | 600 = 600 V. | UINT16 | V | Read | |||
| HR | 23doc 24 | P00-09 Heat sink temperature | Power electronics; -20 to 100 °C. | INT16 | °C | Read | |||
| HR | 38doc 39 | P00-05 Control electronics temperature | -25 to 125 °C. | INT16 | °C | Read | |||
| HR | 134doc 135 | P-07 Rated motor voltage | Manual example reads 0x00E6 = 230 V. | UINT16 | V | Read/write | |||
| HR | 139doc 140 | P-12 Control signal source | 5 or 6 for Modbus RTU. | UINT16 | Read/write | 0 = Terminal mode; 1 = Keypad, unipolar; 2 = Keypad, bipolar; 3 = SBus MOVILINK, internal ramps; 4 = SBus MOVILINK, ramps via PO3; 5 = Modbus RTU, internal ramps P-03/P-04; 6 = Modbus RTU, ramps via PO3 (register 3); 7 = CANopen, internal ramps; 8 = CANopen, ramps via PO3; 9 = PI controller; 10 = PI controller + analog input 1; 11 = Slave mode |
Notes on this map
- PO2/PI2 speed and PI3 current are relative values (16384 = 100 % of P-01 or of P-08), so they are kept raw; multiply by P-01/16384 or P-08/16384 in the master.
- Left out: PI4 motor torque (register 9) because no scaling is given; P00-03 speed setpoint (22/40) because its unit switches between Hz and rpm with P-10 and the resolution is not stated; P00-07 motor voltage (43), the kWh/MWh counters (32/33, resolution not stated) and the hours/minutes counters (25/26, 28) because the register format is not described.
- Parameter registers follow 128 + parameter number (P-01 = 129 ... P-60 = 188), but the manual does not give the Modbus scaling for most of them; only P-07 (confirmed by the frame example) and P-12 are listed. P-36 (address, baud, timeout) has three levels behind one register number and is left out.
- The manual's own example reads P-08 (register 136) as 0x2B = 43 % of the nominal inverter current, i.e. not in amperes; it is left out because the scaling is only shown by that one example.
- The PI1 high byte holds the 'fault code status word' column of the fault list (e.g. 0x2B = fault 50 Modbus communication error) when bit 5 = 1.
- Only function codes 03 (read holding registers) and 06 (write single register) are named in the Modbus chapter.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU)
What Modbus registers does the SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU) have?
This map lists 14 registers: 14 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual's register numbers start at 1 and it warns that zero-based masters must subtract 1. Its frame examples confirm this: reading registers 135/136 (P-07/P-08) sends start address 0x0086 = 134, and writing register 2 (setpoint speed) sends start address 0x0001.
What are the minimum Modbus registers to integrate the SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU)?
Start with HR 0 PO1 Control word (PO1 control word); HR 1 PO2 Setpoint speed (PO2 speed setpoint (16384 = P-01)); HR 5 PI1 Status word (PI1 status word); HR 6 PI2 Actual speed (PI2 actual speed); HR 7 PI3 Actual current (PI3 actual current); HR 22 P00-08 DC link voltage (DC link voltage); HR 23 P00-09 Heat sink temperature (Heat sink temperature); HR 139 P-12 Control signal source (P-12 control signal source).
How do I enable Modbus control of the SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU)?
Set P-14 = 101 for extended parameter access, P-12 = 5 (Modbus RTU, internal ramps P-03/P-04) or 6 (ramps from PO3), and P-15 as the manual's Modbus table shows. P-36 level 1 sets the address (1-63, factory 1) and level 2 the Modbus baud rate (0 = 9.6, 1 = 115.2 (factory), 2 = 19.2, 3 = 38.4, 4 = 57.6, 5 = 76.8 kbit/s). The digital inputs must still be wired so the inverter is enabled.
What happens when the SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU) loses Modbus communication?
P-36 level 3 sets the reaction to a communication failure: 0 = keep the last setpoint (no fault), 1-4 = coast to a stop after 30/100/1000/3000 ms, 5-8 = rapid stop on P-24 after 30/100/1000/3000 ms. The fault list has fault 50 for a Modbus communication error (0x2B in the PI1 high byte).
Where is the official SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU) Modbus documentation?
The source is Product Manual - Frequency Inverters MOVITRAC LTE-B+ (31965822/EN), revision 2024-03, published free by SEW-EURODRIVE at https://download.sew-eurodrive.com/download/pdf/31965822.pdf.
More SEW-EURODRIVE Modbus register maps
Other variable frequency drives register maps
- Variable frequency drive
TECO-Westinghouse E510 inverter (Modbus RTU/ASCII)
TECO-Westinghouse E510 inverters using the built-in RS-485 port (CON2), per communication addendum DOCUMENT-TECO-E510-AC001 Ver01 (2015-03).
Also known as: TECO E510, E510 Communication Addendum - Variable frequency drive
Vacon VACON 20 AC drive (built-in Modbus RTU)
VACON 20 compact drives with the standard Vacon 20 application on the built-in RS-485 Modbus RTU port, per complete user manual DPD00716H1 (software FW0107V012).
Also known as: VACON 20, Vacon 20, VACON0020 - Variable frequency drive
Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU
Yaskawa G7 (CIMR-G7U) drives using built-in Modbus RTU on terminals R+/R-/S+/S-, per the Modbus Communication Manual G7 TM.G7.11 (rev 07-01).
Also known as: CIMR-G7U, G7U, G7 Drive - Variable frequency drive
Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump Micro drives using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEP YAIQPM 03B.
Also known as: CIMR-PW (iQpump Micro), iQpump Micro AC Drive, iQpump Micro Compact Intelligent Pump Controller - Variable frequency drive (fan / pump bypass package)
Yaskawa P7B drive/bypass (legacy) - Modbus RTU
Yaskawa P7B drive/bypass packages (P7 drive CIMR-P7U inside a bypass enclosure, option V native Modbus) using the drive's RS-422/485 terminals, per technical manual TM.P7B.01 Appendix D.
Also known as: P7B, P7 Bypass - Variable frequency drive
ABB ACH480 HVAC drive (embedded Modbus RTU)
ACH480 drives running the ACH480 HVAC control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000247134 Rev E.
Also known as: ACH480-04, ACH480 HVAC control program
All variable frequency drives Modbus register maps →
Source: Product Manual - Frequency Inverters MOVITRAC LTE-B+ · 31965822/EN · rev. 2024-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.