Variable frequency drive · Modbus register map

SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

SEW-EURODRIVE's compact frequency inverter with Modbus RTU on the RJ45 communication socket. Registers 1-3 carry the SEW process output words (control word, speed setpoint, ramp time), registers 6-8 the process input words (status, actual speed, actual current), and the monitoring and setup parameters have fixed Modbus register numbers listed in the parameter overview. This map covers the process data and the monitoring values whose scaling the manual states.

This page lists 14 Modbus registers for the SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from SEW-EURODRIVE’s own free documentation (linked below) and checked against it.

Manufacturer
SEW-EURODRIVE
Model
MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU)
Equipment type
Variable frequency drive
Registers
14 (5 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
115200 baud, 8N1
Documented addressing
1-based (subtract 1 for the wire address)
Also known as
MOVITRAC LTE-B+, LTE-B+, MC LTE B+, MOVITRAC LTE B plus
Source document
Product Manual - Frequency Inverters MOVITRAC LTE-B+ · 31965822/EN · rev. 2024-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU)

Integration in brief

Set P-14 = 101, P-12 = 5 (or 6 to send ramp times in register 3) and P-15 per the fieldbus table, then write register 1 = 0x0006 with register 2 = speed (16384 = P-01). Poll register 6 for status, 7 for actual speed and 8 for current.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0PO1 Control wordBITMAP16PO1 control wordRead/write
HR 1PO2 Setpoint speedINT16PO2 speed setpoint (16384 = P-01)Read/write
HR 5PI1 Status wordBITMAP16PI1 status wordRead
HR 6PI2 Actual speedINT16PI2 actual speedRead
HR 7PI3 Actual currentUINT16PI3 actual currentRead
HR 22P00-08 DC link voltageUINT16DC link voltageRead
HR 23P00-09 Heat sink temperatureINT16Heat sink temperatureRead
HR 139P-12 Control signal sourceUINT16P-12 control signal sourceRead/write

Enable Modbus control & writes

Set P-14 = 101 for extended parameter access, P-12 = 5 (Modbus RTU, internal ramps P-03/P-04) or 6 (ramps from PO3), and P-15 as the manual's Modbus table shows. P-36 level 1 sets the address (1-63, factory 1) and level 2 the Modbus baud rate (0 = 9.6, 1 = 115.2 (factory), 2 = 19.2, 3 = 38.4, 4 = 57.6, 5 = 76.8 kbit/s). The digital inputs must still be wired so the inverter is enabled.

Communication loss & watchdog

P-36 level 3 sets the reaction to a communication failure: 0 = keep the last setpoint (no fault), 1-4 = coast to a stop after 30/100/1000/3000 ms, 5-8 = rapid stop on P-24 after 30/100/1000/3000 ms. The fault list has fault 50 for a Modbus communication error (0x2B in the PI1 high byte).

Byte order & addressing

Network setup

Watch out for

SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

14 of 14 shown
SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1PO1 Control word0x0006 = run; 0x0000 = rapid stop; 0x0001 = coast; bit 6 edge = reset.BITMAP16Read/writebit 0 = Output stage inhibit: 0 = start, 1 = stop (coast); bit 1 = 0 = rapid stop on P-24 ramp, 1 = start; bit 2 = 0 = stop on process ramp (P-03/P-04 or PO3), 1 = start; bit 6 = Fault reset on 0->1 edge
HR1doc 2PO2 Setpoint speedRaw: 16384 (0x4000) = 100 % of P-01; negative (two's complement) = CCW.INT16Read/write
HR2doc 3PO3 Ramp time1 digit = 1 ms (100-65535 ms); used when P-12 = 6.UINT16× 0.001sRead/write
HR5doc 6PI1 Status wordHigh byte: 1 inhibited, 2 not enabled, 4 running, 5 factory set; else fault code.BITMAP16Readbit 0 = Output stage enabled; bit 1 = Inverter ready; bit 2 = PO data enabled; bit 5 = Fault/warning; bit 8 = High byte (bits 8-15): status code, or fault code when bit 5 = 1 (see description)
HR6doc 7PI2 Actual speedSame raw scaling as PO2 (16384 = 100 % of P-01).INT16Read
HR7doc 8PI3 Actual currentRaw: 16384 (0x4000) = 100 % of P-08 rated motor current.UINT16Read
HR10doc 11P00-04 Digital input statusBITMAP16Readbit 0 = DI1; bit 1 = DI2; bit 2 = DI3; bit 3 = DI4
HR19doc 20P00-01 Analog input 1 value1000 = 100 % of max input voltage or current.UINT16× 0.1%Read
HR20doc 21P00-02 Analog input 2 value1000 = 100 % of max input voltage or current.UINT16× 0.1%Read
HR22doc 23P00-08 DC link voltage600 = 600 V.UINT16VRead
HR23doc 24P00-09 Heat sink temperaturePower electronics; -20 to 100 °C.INT16°CRead
HR38doc 39P00-05 Control electronics temperature-25 to 125 °C.INT16°CRead
HR134doc 135P-07 Rated motor voltageManual example reads 0x00E6 = 230 V.UINT16VRead/write
HR139doc 140P-12 Control signal source5 or 6 for Modbus RTU.UINT16Read/write0 = Terminal mode; 1 = Keypad, unipolar; 2 = Keypad, bipolar; 3 = SBus MOVILINK, internal ramps; 4 = SBus MOVILINK, ramps via PO3; 5 = Modbus RTU, internal ramps P-03/P-04; 6 = Modbus RTU, ramps via PO3 (register 3); 7 = CANopen, internal ramps; 8 = CANopen, ramps via PO3; 9 = PI controller; 10 = PI controller + analog input 1; 11 = Slave mode

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU)

What Modbus registers does the SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU) have?

This map lists 14 registers: 14 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual's register numbers start at 1 and it warns that zero-based masters must subtract 1. Its frame examples confirm this: reading registers 135/136 (P-07/P-08) sends start address 0x0086 = 134, and writing register 2 (setpoint speed) sends start address 0x0001.

What are the minimum Modbus registers to integrate the SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU)?

Start with HR 0 PO1 Control word (PO1 control word); HR 1 PO2 Setpoint speed (PO2 speed setpoint (16384 = P-01)); HR 5 PI1 Status word (PI1 status word); HR 6 PI2 Actual speed (PI2 actual speed); HR 7 PI3 Actual current (PI3 actual current); HR 22 P00-08 DC link voltage (DC link voltage); HR 23 P00-09 Heat sink temperature (Heat sink temperature); HR 139 P-12 Control signal source (P-12 control signal source).

How do I enable Modbus control of the SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU)?

Set P-14 = 101 for extended parameter access, P-12 = 5 (Modbus RTU, internal ramps P-03/P-04) or 6 (ramps from PO3), and P-15 as the manual's Modbus table shows. P-36 level 1 sets the address (1-63, factory 1) and level 2 the Modbus baud rate (0 = 9.6, 1 = 115.2 (factory), 2 = 19.2, 3 = 38.4, 4 = 57.6, 5 = 76.8 kbit/s). The digital inputs must still be wired so the inverter is enabled.

What happens when the SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU) loses Modbus communication?

P-36 level 3 sets the reaction to a communication failure: 0 = keep the last setpoint (no fault), 1-4 = coast to a stop after 30/100/1000/3000 ms, 5-8 = rapid stop on P-24 after 30/100/1000/3000 ms. The fault list has fault 50 for a Modbus communication error (0x2B in the PI1 high byte).

Where is the official SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU) Modbus documentation?

The source is Product Manual - Frequency Inverters MOVITRAC LTE-B+ (31965822/EN), revision 2024-03, published free by SEW-EURODRIVE at https://download.sew-eurodrive.com/download/pdf/31965822.pdf.

More SEW-EURODRIVE Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: Product Manual - Frequency Inverters MOVITRAC LTE-B+ · 31965822/EN · rev. 2024-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.