Variable frequency drive · Modbus register map
SEW-EURODRIVE MOVITRAC LTP-B standard inverter (built-in Modbus RTU) Modbus register map
Updated 17 November 2026
SEW-EURODRIVE's standard inverter with Modbus RTU on the RJ45 communication socket. Registers 1-4 carry the process output words and 6-9 the process input words; words 2-4 and 7-9 are freely assignable in parameter group P5. Other parameters sit at register = parameter number (101 = P1-01), except the P0 monitoring group, which has its own register numbers.
This page lists 24 Modbus registers for the SEW-EURODRIVE MOVITRAC LTP-B standard inverter (built-in Modbus RTU) — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from SEW-EURODRIVE’s own free documentation (linked below) and checked against it.
- Manufacturer
- SEW-EURODRIVE
- Model
- MOVITRAC LTP-B standard inverter (built-in Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 24 (17 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 115200 baud, 8N1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- MOVITRAC LTP-B, LTP-B, MC LTP B
Integration notes: SEW-EURODRIVE MOVITRAC LTP-B standard inverter (built-in Modbus RTU)
Set P1-14 = 201, P1-12 = 7 and P1-15 per the manual, then write register 1 = 0x0006 with register 2 = speed (16384 = P1-01). Poll registers 6-9 for status, speed, current and power.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | PO1 Control word | BITMAP16 | PO1 control word | Read/write |
| HR 1 | PO2 (default: speed setpoint %) | INT16 | PO2 speed setpoint (16384 = P1-01) | Read/write |
| HR 5 | PI1 Status word | BITMAP16 | PI1 status word | Read |
| HR 6 | PI2 (default: actual speed %) | INT16 | PI2 actual speed | Read |
| HR 7 | PI3 (default: actual current) | UINT16 | PI3 current, 0.1 % | Read |
| HR 8 | PI4 (default: power) | UINT16 | PI4 power, 0.1 % | Read |
| HR 111 | P1-12 Control signal source | UINT16 | P1-12 control signal source | Read/write |
Enable Modbus control & writes
Set P1-14 = 201 (extended menu), P1-12 = 7 (Modbus RTU or fieldbus) and P1-15 as given in the manual's fieldbus table. P5-01 sets the address (factory 1), P5-03 the baud rate (factory 115200) and P5-04 the format (factory no parity, 1 stop bit). The enable inputs must still be wired.
Communication loss & watchdog
P5-06 sets the communication-failure time (0.0-5.0 s, factory 1.0 s; 0.0 keeps running). P5-05 sets the reaction: 0 fault and coast, 1 stop ramp and fault, 2 stop ramp without fault (factory), 3 run at fixed setpoint speed 8.
Byte order & addressing
- Register numbers are 1-based: subtract 1 for the wire address.
- Control word bit 0 = 1 inhibits the output stage; 0x0006 runs, 0x0000 is a rapid stop.
- Process words 2-4 and 7-9 are reassignable: always check P5-09 to P5-14 before trusting a scale.
Network setup
- Wire RS485- (Modbus) to RJ45 pin 7 and RS485+ to pin 8.
- Up to 32 nodes; 1200 m at 115200 bit/s with 0.5 mm2 cable.
Watch out for
- Fitting a fieldbus or encoder option card disables Modbus on the RJ45 port.
- The P0 monitoring group does not follow the register = parameter number rule.
SEW-EURODRIVE MOVITRAC LTP-B standard inverter (built-in Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | PO1 Control word | 0x0006 = run on ramp; 0x0000 = rapid stop; bit 6 edge = fault reset. | BITMAP16 | Read/write | bit 0 = Output stage inhibit: 0 = start, 1 = stop (coast); bit 1 = 0 = rapid stop on P2-25 ramp, 1 = start; bit 2 = 0 = stop on process ramp (P1-03/P1-04 or PO3), 1 = start; bit 6 = Fault reset on 0->1 edge | |||
| HR | 1doc 2 | PO2 (default: speed setpoint %) | Default P5-09 = 1: 16384 (0x4000) = 100 % of P1-01; negative = CCW. | INT16 | Read/write | ||||
| HR | 2doc 3 | PO3 (default: no function) | Content set by P5-10; raw. | UINT16 | Read/write | ||||
| HR | 3doc 4 | PO4 (default: no function) | Content set by P5-11; raw. | UINT16 | Read/write | ||||
| HR | 5doc 6 | PI1 Status word | High byte: 1 STO, 2 no enable, 5 speed, 6 torque, 0x0A technology, 0x0C reference travel. | BITMAP16 | Read | bit 0 = Output stage enabled; bit 1 = Inverter ready; bit 2 = PO data enabled; bit 5 = Fault/warning (high byte = fault code); bit 6 = Positive limit switch active; bit 7 = Negative limit switch active | |||
| HR | 6doc 7 | PI2 (default: actual speed %) | Default P5-12 = 1: 16384 = 100 % of P1-01. | INT16 | Read | ||||
| HR | 7doc 8 | PI3 (default: actual current) | Default P5-13 = 2: 0.1 % of nominal inverter current. | UINT16 | × 0.1 | % | Read | ||
| HR | 8doc 9 | PI4 (default: power) | Default P5-14 = 4: 0.1 % of rated inverter power. | UINT16 | × 0.1 | % | Read | ||
| HR | 10doc 11 | P0-03 Digital input status | DI5-DI8 need an option module. | BITMAP16 | Read | bit 0 = DI1; bit 1 = DI2; bit 2 = DI3; bit 3 = DI4; bit 4 = DI5; bit 5 = DI6; bit 6 = DI7; bit 7 = DI8 | |||
| HR | 19doc 20 | P0-01 Analog input 1 value | 1000 = 100 % of max input voltage or current. | UINT16 | × 0.1 | % | Read | ||
| HR | 20doc 21 | P0-02 Analog input 2 value | 1000 = 100 % of max input voltage or current. | UINT16 | × 0.1 | % | Read | ||
| HR | 106doc 107 | P1-07 Rated motor voltage | Manual example reads 0x00E6 = 230 V. | UINT16 | V | Read/write | |||
| HR | 111doc 112 | P1-12 Control signal source | Set 7 for Modbus RTU. | UINT16 | Read/write | 0 = Terminal mode; 1 = Keypad, unipolar; 2 = Keypad, bipolar; 3 = PID controller; 4 = Slave mode; 5 = SBus MOVILINK; 6 = CANopen; 7 = Modbus RTU or fieldbus interface; 8 = MultiMotion | |||
| HR | 500doc 501 | P5-01 Inverter address | 0-63, factory 1. | UINT16 | Read/write | ||||
| HR | 502doc 503 | P5-03 Modbus RTU baud rate | Factory 115200. | UINT16 | Read/write | 0 = 9600; 1 = 19200; 2 = 38400; 3 = 57600; 4 = 115200 | |||
| HR | 503doc 504 | P5-04 Modbus RTU data format | Factory n-1. | UINT16 | Read/write | 0 = No parity, 1 stop bit; 1 = No parity, 2 stop bits; 2 = Odd parity, 1 stop bit; 3 = Even parity, 1 stop bit | |||
| HR | 504doc 505 | P5-05 Response to communication failure | Factory 2. | UINT16 | Read/write | 0 = Fault and coast to a stop; 1 = Stop ramp and fault; 2 = Stop ramp without fault; 3 = Fixed setpoint speed 8 | |||
| HR | 506doc 507 | P5-07 Ramp specified via fieldbus | UINT16 | Read/write | 0 = Off (P1-03/P1-04 ramps); 1 = On (ramp from a PO word) | ||||
| HR | 508doc 509 | P5-09 Fieldbus PO2 definition | Factory 1. | UINT16 | Read/write | 0 = Speed in rpm (1 = 0.2 rpm, needs P1-10 > 0); 1 = Speed % (0x4000 = 100 % of P1-01); 2 = Torque setpoint/limit (1 = 0.1 %); 3 = Ramp time (1 = 1 ms, needs P5-07 = 1); 4 = PID reference (0x1000 = 100 %); 5 = Analog output 1 / digital output 1; 6 = Analog output 2 / digital output 2; 7 = No function | |||
| HR | 509doc 510 | P5-10 Fieldbus PO3 definition | Factory 7. | UINT16 | Read/write | 0 = Speed in rpm (1 = 0.2 rpm, needs P1-10 > 0); 1 = Speed % (0x4000 = 100 % of P1-01); 2 = Torque setpoint/limit (1 = 0.1 %); 3 = Ramp time (1 = 1 ms, needs P5-07 = 1); 4 = PID reference (0x1000 = 100 %); 5 = Analog output 1 / digital output 1; 6 = Analog output 2 / digital output 2; 7 = No function | |||
| HR | 510doc 511 | P5-11 Fieldbus PO4 definition | Factory 7. | UINT16 | Read/write | 0 = Speed in rpm (1 = 0.2 rpm, needs P1-10 > 0); 1 = Speed % (0x4000 = 100 % of P1-01); 2 = Torque setpoint/limit (1 = 0.1 %); 3 = Ramp time (1 = 1 ms, needs P5-07 = 1); 4 = PID reference (0x1000 = 100 %); 5 = Analog output 1 / digital output 1; 6 = Analog output 2 / digital output 2; 7 = No function | |||
| HR | 511doc 512 | P5-12 Fieldbus PI2 definition | Factory 1. | UINT16 | Read/write | 0 = Speed in rpm (1 = 0.2 rpm, needs P1-10 > 0); 1 = Speed % (0x4000 = 100 % of P1-01); 2 = Current (1 = 0.1 % of nominal inverter current); 3 = Torque (1 = 0.1 % of nominal motor torque); 4 = Power (1 = 0.1 % of rated inverter power); 5 = Power electronics temperature (1 = 0.01 °C); 6 = DC link voltage (1 = 1 V); 7 = Analog input 1 (0x1000 = 100 %); 8 = Analog input 2 (0x1000 = 100 %); 9 = I/O status of basic device and option; 10 = LTX position low byte (increments within one revolution, LTX module only); 11 = LTX position high byte (revolutions, LTX module only) | |||
| HR | 512doc 513 | P5-13 Fieldbus PI3 definition | Factory 2. | UINT16 | Read/write | 0 = Speed in rpm (1 = 0.2 rpm, needs P1-10 > 0); 1 = Speed % (0x4000 = 100 % of P1-01); 2 = Current (1 = 0.1 % of nominal inverter current); 3 = Torque (1 = 0.1 % of nominal motor torque); 4 = Power (1 = 0.1 % of rated inverter power); 5 = Power electronics temperature (1 = 0.01 °C); 6 = DC link voltage (1 = 1 V); 7 = Analog input 1 (0x1000 = 100 %); 8 = Analog input 2 (0x1000 = 100 %); 9 = I/O status of basic device and option; 10 = LTX position low byte (increments within one revolution, LTX module only); 11 = LTX position high byte (revolutions, LTX module only) | |||
| HR | 513doc 514 | P5-14 Fieldbus PI4 definition | Factory 4. | UINT16 | Read/write | 0 = Speed in rpm (1 = 0.2 rpm, needs P1-10 > 0); 1 = Speed % (0x4000 = 100 % of P1-01); 2 = Current (1 = 0.1 % of nominal inverter current); 3 = Torque (1 = 0.1 % of nominal motor torque); 4 = Power (1 = 0.1 % of rated inverter power); 5 = Power electronics temperature (1 = 0.01 °C); 6 = DC link voltage (1 = 1 V); 7 = Analog input 1 (0x1000 = 100 %); 8 = Analog input 2 (0x1000 = 100 %); 9 = I/O status of basic device and option; 10 = LTX position low byte (increments within one revolution, LTX module only); 11 = LTX position high byte (revolutions, LTX module only) |
Notes on this map
- Registers 2-4 and 7-9 change meaning with P5-09 to P5-14; the scaling given is for the factory assignment. Each option's scaling is listed in the P5-09 to P5-14 value lists.
- Speed values are relative (16384 = 100 % of P1-01) and are kept raw.
- Left out: P0 monitor registers whose layout in the manual's table could not be read unambiguously (speed setpoint 22, torque 41, DC link 23, heat sink 24, kWh/MWh counters 30-33); P5-06 communication timeout (register scaling not stated); most P1-P4 parameters because the Modbus scaling of each is not given.
- The manual's example reads P1-08 (register 108) as 0x2B = 43, a percentage of the inverter current, so P1-08 is not in amperes; it is left out.
- Function code 16 (write multiple) works for the PO words; 03 and 06 work on all registers.
- Modbus is not available once a communication option or an encoder card is fitted in the option slot.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the SEW-EURODRIVE MOVITRAC LTP-B standard inverter (built-in Modbus RTU)
What Modbus registers does the SEW-EURODRIVE MOVITRAC LTP-B standard inverter (built-in Modbus RTU) have?
This map lists 24 registers: 24 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the SEW-EURODRIVE MOVITRAC LTP-B standard inverter (built-in Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual's register numbers start at 1 and it warns that zero-based masters must subtract 1. Its frame example reads registers 107/108 (P1-07/P1-08) with start address 0x006A = 106. Parameters use register = parameter number (P5-03 = 503 = wire address 502).
What are the minimum Modbus registers to integrate the SEW-EURODRIVE MOVITRAC LTP-B standard inverter (built-in Modbus RTU)?
Start with HR 0 PO1 Control word (PO1 control word); HR 1 PO2 (default: speed setpoint %) (PO2 speed setpoint (16384 = P1-01)); HR 5 PI1 Status word (PI1 status word); HR 6 PI2 (default: actual speed %) (PI2 actual speed); HR 7 PI3 (default: actual current) (PI3 current, 0.1 %); HR 8 PI4 (default: power) (PI4 power, 0.1 %); HR 111 P1-12 Control signal source (P1-12 control signal source).
How do I enable Modbus control of the SEW-EURODRIVE MOVITRAC LTP-B standard inverter (built-in Modbus RTU)?
Set P1-14 = 201 (extended menu), P1-12 = 7 (Modbus RTU or fieldbus) and P1-15 as given in the manual's fieldbus table. P5-01 sets the address (factory 1), P5-03 the baud rate (factory 115200) and P5-04 the format (factory no parity, 1 stop bit). The enable inputs must still be wired.
What happens when the SEW-EURODRIVE MOVITRAC LTP-B standard inverter (built-in Modbus RTU) loses Modbus communication?
P5-06 sets the communication-failure time (0.0-5.0 s, factory 1.0 s; 0.0 keeps running). P5-05 sets the reaction: 0 fault and coast, 1 stop ramp and fault, 2 stop ramp without fault (factory), 3 run at fixed setpoint speed 8.
Where is the official SEW-EURODRIVE MOVITRAC LTP-B standard inverter (built-in Modbus RTU) Modbus documentation?
The source is Product Manual - Standard Inverters MOVITRAC LTP-B (31554814/EN), revision 2023-10, published free by SEW-EURODRIVE at https://download.sew-eurodrive.com/download/pdf/31554814.pdf.
More SEW-EURODRIVE Modbus register maps
Other variable frequency drives register maps
- Variable frequency drive
TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII)
TECO-Westinghouse EV series micro inverters with the RS-485 option card, per the EV Inverter Series Modbus Communication Manual.
Also known as: TECO EV, EV Inverter Series - Variable frequency drive
WEG CFW500 frequency inverter (Modbus RTU)
WEG CFW500 drives as a Modbus RTU slave on the RS-485 port of the plug-in module (Modbus RTU User's Guide 10002253377 rev 04); parameter scaling from the V2.2X programming manual.
Also known as: CFW500 VFD, CFW500-IOS, CFW500-CRS485, CFW500-CUSB, CFW500-CRS232 - Variable frequency drive
Yaskawa GA500 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA500 drives using the built-in RS-485 MEMOBUS/Modbus port (terminal TB4), per technical reference SIEPC71061752 revision C.
Also known as: CIPR-GA50U, GA500 Versatile Compact - Variable frequency drive
Yaskawa iQpump1000 intelligent pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump1000 drives (CIMR-PW) using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEPYAIP1W01G.
Also known as: CIMR-PW, CIMR-PWA, iQpump1000 AC Drive - Variable frequency drive
Yaskawa U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU)
Yaskawa U1000 matrix drives using the built-in RS-422/485 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP C710636 04E.
Also known as: CIMR-UU, U1000 Industrial MATRIX Drive - Variable frequency drive
ABB ACH550-UH HVAC drive (embedded Modbus RTU)
ACH550-UH HVAC drives using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AUA0000081823 Rev F.
Also known as: ACH550-UH, ACH550
All variable frequency drives Modbus register maps →
Source: Product Manual - Standard Inverters MOVITRAC LTP-B · 31554814/EN · rev. 2023-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.