- Home
- Modbus register maps
- Yaskawa
- U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU)
Variable frequency drive · Modbus register map
Yaskawa U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU) Modbus register map
Updated 17 November 2026
Yaskawa's U1000 is a regenerative matrix-converter variable frequency drive with a built-in MEMOBUS/Modbus RTU port. Commands go to hex registers 0001H-000FH, status, faults and monitors are read from 0020H, and each parameter has its own hex address in the parameter list. This map covers the command block, status, fault and alarm words, fixed-unit monitors and the b1/H5 communication parameters.
This page lists 41 Modbus registers for the Yaskawa U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU) — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yaskawa’s own free documentation (linked below) and checked against it.
- Manufacturer
- Yaskawa
- Model
- U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 41 (12 writable)
- Transport
- Modbus RTU
- Default unit ID
- 31
- Default serial
- 9600 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- CIMR-UU, U1000 Industrial MATRIX Drive
Integration notes: Yaskawa U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU)
Set H5-01..H5-03 and power-cycle, set b1-01 = 2 and b1-02 = 2, then write 0001H (run bits) and 0002H (frequency reference) with function 10H and poll 0020H-002DH.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1 | Operation commands / multi-function inputs | BITMAP16 | Run/stop, direction, fault reset | Read/write |
| HR 2 | Frequency reference | UINT16 | Frequency reference (o1-03 units) | Read/write |
| HR 32 | Drive status 1 | BITMAP16 | Drive status 1 | Read |
| HR 33 | Fault contents 1 | BITMAP16 | Fault contents 1 | Read |
| HR 36 | Output frequency | UINT16 | Output frequency | Read |
| HR 44 | Drive status 2 | BITMAP16 | Drive status 2 incl. comm timeout | Read |
| HR 49 | Control circuit voltage | UINT16 | Control circuit voltage (1 Vdc, as printed) | Read |
Enable Modbus control & writes
Set H5-01 node address (default 1FH), H5-02 speed (default 3 = 9600 bps) and H5-03 parity (default 0 = none), then cycle power. For Modbus control set b1-01 = 2 and b1-02 = 2; H5-12 selects how 0001H bits 0/1 are read.
Communication loss & watchdog
H5-05 = 1 (default) enables CE detection after H5-09 (default 2.0 s, 0.0-10.0 s) without traffic; H5-04 selects the reaction (0 ramp, 1 coast, 2 fast stop, 3 alarm only - default). 002CH bit F flags the timeout.
Byte order & addressing
- Hex 0-based registers.
- No function 06H.
- Parameter writes need the Enter command unless H5-11 = 1.
Network setup
- RS-422/485 on terminals R+, R-, S+, S-; 8 data bits and 1 stop bit are fixed.
- Use DIP switch S2 to switch on the termination resistor at the last drive.
- H5-07 RTS control defaults to enabled.
Watch out for
- H5-01 = 0 makes the drive ignore Modbus.
- H5 changes need a power cycle on this drive.
Yaskawa U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 0001H | Operation commands / multi-function inputs | Run bits follow H5-12; bits 4-B drive multi-function inputs 1-8. | BITMAP16 | Read/write | bit 0 = H5-12=0: forward run / H5-12=1: run; bit 1 = H5-12=0: reverse run / H5-12=1: reverse direction; bit 2 = External fault EF0; bit 3 = Fault reset; bit 4 = Multi-function input 1; bit 5 = Multi-function input 2; bit 6 = Multi-function input 3; bit 7 = Multi-function input 4; bit 8 = Multi-function input 5; bit 9 = Multi-function input 6; bit 10 = Multi-function input 7; bit 11 = Multi-function input 8 | |||
| HR | 2doc 0002H | Frequency reference | Units set by o1-03. | UINT16 | Read/write | ||||
| HR | 3doc 0003H | Output voltage gain | 20-2000 (2.0-200.0 %), 1000 at power-up. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 4doc 0004H | Torque reference / torque limit | Only when torque control is enabled. | INT16 | × 0.1 | % | Read/write | ||
| HR | 5doc 0005H | Torque compensation | Only when torque control is enabled. | INT16 | × 0.1 | % | Read/write | ||
| HR | 6doc 0006H | PID target | INT16 | × 0.01 | % | Read/write | |||
| HR | 9doc 0009H | Multi-function digital output setting | Drive outputs from the network. | BITMAP16 | Read/write | bit 0 = Contact output M1-M2; bit 1 = Contact output M3-M4; bit 2 = Contact output M5-M6; bit 6 = Enable bit 7; bit 7 = Fault contact MA/MB-MC | |||
| HR | 15doc 000FH | Control selection setting | BITMAP16 | Read/write | bit 1 = PID setpoint input; bit 2 = Torque reference/limit from Modbus; bit 3 = Torque compensation from Modbus; bit 12 = Broadcast terminal S5 input; bit 13 = Broadcast terminal S6 input; bit 14 = Broadcast terminal S7 input; bit 15 = Broadcast terminal S8 input | ||||
| HR | 32doc 0020H | Drive status 1 | BITMAP16 | Read | bit 0 = During run; bit 1 = During reverse; bit 2 = Drive ready; bit 3 = Fault; bit 4 = Data setting error; bit 5 = Contact output 1 M1-M2; bit 6 = Contact output 2 M3-M4; bit 7 = Contact output 3 M5-M6; bit 14 = ComRef enabled; bit 15 = ComCtrl enabled | ||||
| HR | 33doc 0021H | Fault contents 1 | BITMAP16 | Read | bit 0 = oC overcurrent / GF ground fault; bit 1 = ov control circuit overvoltage; bit 2 = oL2 overload; bit 3 = oH1/oH2 overheat; bit 6 = FbL/FbH PID feedback; bit 7 = EF to EF8 external fault; bit 8 = CPF hardware fault (incl. oFx); bit 9 = oL1, oL3/oL4, UL3/UL4; bit 10 = PGo, PGoH, oS, dEv; bit 11 = Uv, AUv, Fdv; bit 12 = Uv1, Uv2, Uv3, Fdv, AUv, SrC; bit 13 = LF output phase loss; bit 14 = CE/bUS communication error; bit 15 = oPr external operator connection fault | ||||
| HR | 34doc 0022H | Data link status | Errors from the last write. | BITMAP16 | Read | bit 0 = Writing data or switching motors; bit 3 = Upper or lower limit error; bit 4 = Data conformity error; bit 5 = Writing to EEPROM; bit 6 = Write to RAM only (H5-17=1) | |||
| HR | 35doc 0023H | Frequency reference (monitor) | Units set by o1-03. | UINT16 | Read | ||||
| HR | 36doc 0024H | Output frequency | Units set by o1-03. | UINT16 | Read | ||||
| HR | 41doc 0029H | Fault contents 2 | BITMAP16 | Read | bit 1 = GF ground fault; bit 3 = LF output phase loss; bit 6 = oH4 motor overheat 2 (PTC) | ||||
| HR | 42doc 002AH | Alarm contents 1 | Alarms that do not trip the drive. | BITMAP16 | Read | bit 2 = EF run command input error; bit 3 = bb drive baseblock; bit 4 = oL3 overtorque 1; bit 5 = oH heatsink overheat; bit 6 = ov control circuit overvoltage; bit 7 = Uv control circuit undervoltage; bit 8 = FAn fan fault; bit 9 = CE Modbus communication error; bit 10 = bUS option communication error; bit 11 = UL3/UL4 undertorque; bit 12 = oH3 motor overheat; bit 13 = FbL/FbH PID feedback loss; bit 15 = CALL serial transmission error | |||
| HR | 43doc 002BH | Input terminal status | BITMAP16 | Read | bit 0 = Terminal S1 closed; bit 1 = Terminal S2 closed; bit 2 = Terminal S3 closed; bit 3 = Terminal S4 closed; bit 4 = Terminal S5 closed; bit 5 = Terminal S6 closed; bit 6 = Terminal S7 closed; bit 7 = Terminal S8 closed | ||||
| HR | 44doc 002CH | Drive status 2 | BITMAP16 | Read | bit 0 = During run; bit 1 = Zero speed; bit 2 = Speed agree; bit 3 = User-set speed agree; bit 4 = Frequency detection 1; bit 5 = Frequency detection 2; bit 6 = Drive ready; bit 7 = During undervoltage; bit 8 = During baseblock; bit 9 = Frequency reference from operator keypad; bit 10 = Run command from operator keypad; bit 11 = Over/undertorque 1, 2; bit 12 = Frequency reference loss; bit 13 = During fault restart; bit 14 = Fault; bit 15 = Communication timeout | ||||
| HR | 45doc 002DH | Output terminal status | BITMAP16 | Read | bit 0 = Contact output 1 M1-M2; bit 1 = Contact output 2 M3-M4; bit 2 = Contact output 3 M5-M6; bit 7 = Fault contact MA/MB-MC | ||||
| HR | 49doc 0031H | Control circuit voltage | Printed as control circuit voltage, 1 Vdc units. | UINT16 | V | Read | |||
| HR | 56doc 0038H | PID feedback | 100 % = maximum output frequency. | UINT16 | × 0.1 | % | Read | ||
| HR | 57doc 0039H | PID input | INT16 | × 0.1 | % | Read | |||
| HR | 58doc 003AH | PID output | INT16 | × 0.1 | % | Read | |||
| HR | 61doc 003DH | Communications error contents | BITMAP16 | Read | bit 0 = CRC error; bit 1 = Data length error; bit 3 = Parity error; bit 4 = Overrun error; bit 5 = Framing error; bit 6 = Timeout | ||||
| HR | 75doc 004BH | Drive status (U1-12) | BITMAP16 | Read | bit 0 = During run; bit 1 = During zero speed; bit 2 = During reverse run; bit 3 = During fault reset signal input; bit 4 = During speed agree; bit 5 = Drive ready; bit 6 = Alarm; bit 7 = Fault; bit 8 = During operation error (oPE); bit 9 = During momentary power loss; bit 10 = Motor 2 selected; bit 14 = ComRef / NetRef status; bit 15 = ComCtrl / NetCtrl status | ||||
| HR | 152doc 0098H | U4-01 Accumulated operation time (high word) | 10 h units. | UINT16 | × 10 | h | Read | ||
| HR | 153doc 0099H | U4-01 Accumulated operation time (low word) | 1 h units; add to 0098H x 10. | UINT16 | h | Read | |||
| HR | 384doc 0180H | b1-01 Frequency reference selection 1 | Default 1. | UINT16 | Read/write | 0 = Digital operator; 1 = Analog input terminals; 2 = MEMOBUS/Modbus communications; 3 = Option PCB; 4 = Pulse train input (terminal RP) | |||
| HR | 385doc 0181H | b1-02 Run command selection 1 | Default 1. | UINT16 | Read/write | 0 = Digital operator; 1 = Digital input terminals; 2 = MEMOBUS/Modbus communications; 3 = Option card | |||
| HR | 1061doc 0425H | H5-01 Drive node address | 0-FFH, default 1FH; 0 disables Modbus; cycle power. | UINT16 | Read | ||||
| HR | 1062doc 0426H | H5-02 Communication speed | Default 3; cycle power. | UINT16 | Read | 0 = 1200 bps; 1 = 2400 bps; 2 = 4800 bps; 3 = 9600 bps; 4 = 19200 bps; 5 = 38400 bps; 6 = 57600 bps; 7 = 76800 bps; 8 = 115200 bps | |||
| HR | 1063doc 0427H | H5-03 Communication parity | Default 0; cycle power. | UINT16 | Read | 0 = No parity; 1 = Even parity; 2 = Odd parity | |||
| HR | 1064doc 0428H | H5-04 Stopping method after CE | Default 3. | UINT16 | Read | 0 = Ramp to stop; 1 = Coast to stop; 2 = Fast stop; 3 = Alarm only | |||
| HR | 1065doc 0429H | H5-05 Communication fault detection | Default 1. | UINT16 | Read | 0 = Disabled; 1 = Enabled | |||
| HR | 1066doc 042AH | H5-06 Drive transmit wait time | 5-65 ms, default 5 ms. | UINT16 | ms | Read | |||
| HR | 1067doc 042BH | H5-07 RTS control selection | Default 1. | UINT16 | Read | 0 = Disabled (RTS always on); 1 = Enabled (RTS on only when sending) | |||
| HR | 1077doc 0435H | H5-09 CE detection time | 0.0-10.0 s, default 2.0 s. | UINT16 | × 0.1 | s | Read | ||
| HR | 1078doc 0436H | H5-10 Unit for register 0025H | UINT16 | Read | 0 = 0.1 V units; 1 = 1 V units | ||||
| HR | 1084doc 043CH | H5-11 Communications ENTER function | Default 0. | UINT16 | Read | 0 = Enter command required; 1 = Changes active without Enter | |||
| HR | 1085doc 043DH | H5-12 Run command method | Meaning of 0001H bits 0/1; default 0. | UINT16 | Read | 0 = FWD/Stop, REV/Stop; 1 = Run/Stop, FWD/REV | |||
| HR | 2304doc 0900H | Enter command (save to EEPROM) | Write 0 to store written parameters. | UINT16 | Write | ||||
| HR | 2320doc 0910H | Enter command (RAM only) | Write 0 to apply written parameters without saving. | UINT16 | Write |
Notes on this map
- Frequency registers 0002H, 0023H and 0024H use the units chosen in o1-03, so they are left unscaled.
- Register 0031H is printed as Control Circuit Voltage (1 Vdc units).
- Left out: 0025H output voltage (unit switched by H5-10), 0026H output current (0.1 A in the table, but the manual gives model-dependent current units elsewhere), 0027H output power and 0028H torque reference (no unit given), 0032H torque reference (sign not stated), 002FH frequency reference bias, 003EH/003FH output frequency in r/min and % (sign not stated), 00ABH rated current, and the U1/U2/U3/U4 blocks at 0040H-0097H.
- Only function codes 03H (max 16 registers), 08H and 10H are supported, so use 10H even for one register.
- With H5-11 = 0, parameter writes take effect only after writing 0 to 0900H (EEPROM) or 0910H (RAM). Reading 0900H/0910H returns an error.
- The manual's list of Modbus operations allows reading and writing parameters except H5-xx, so the H5 entries here are marked read-only for reference; set them from the keypad.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Yaskawa U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU)
What Modbus registers does the Yaskawa U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU) have?
This map lists 41 registers: 41 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Yaskawa U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and sent unchanged: the manual's read example uses starting number 00H 20H for 0020H. Parameters use the hex address printed under each parameter in the parameter list (H5-01 (425) = 0425H).
What are the minimum Modbus registers to integrate the Yaskawa U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU)?
Start with HR 1 Operation commands / multi-function inputs (Run/stop, direction, fault reset); HR 2 Frequency reference (Frequency reference (o1-03 units)); HR 32 Drive status 1 (Drive status 1); HR 33 Fault contents 1 (Fault contents 1); HR 36 Output frequency (Output frequency); HR 44 Drive status 2 (Drive status 2 incl. comm timeout); HR 49 Control circuit voltage (Control circuit voltage (1 Vdc, as printed)).
How do I enable Modbus control of the Yaskawa U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU)?
Set H5-01 node address (default 1FH), H5-02 speed (default 3 = 9600 bps) and H5-03 parity (default 0 = none), then cycle power. For Modbus control set b1-01 = 2 and b1-02 = 2; H5-12 selects how 0001H bits 0/1 are read.
What happens when the Yaskawa U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU) loses Modbus communication?
H5-05 = 1 (default) enables CE detection after H5-09 (default 2.0 s, 0.0-10.0 s) without traffic; H5-04 selects the reaction (0 ramp, 1 coast, 2 fast stop, 3 alarm only - default). 002CH bit F flags the timeout.
Where is the official Yaskawa U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU) Modbus documentation?
The source is YASKAWA U1000 Industrial MATRIX Drive Technical Manual (SIEP C710636 04E), revision 2024-03, published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=SIEPC71063604&cmd=documents&documentName=SIEPC71063604.pdf.
More Yaskawa Modbus register maps
- Variable frequency drive
Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa A1000 drives (CIMR-AU; 200 V, 400 V and 600 V classes) using the built-in RS-422/485 MEMOBUS/Modbus terminals (TB5), per Technical Manual SIEP C710616 41H.
Also known as: CIMR-AU, CIMR-AUA, A1000 High Performance Vector Control Drive - Variable frequency drive (HVAC)
Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU
Yaskawa E7 (CIMR-E7U) HVAC fan and pump drives using the built-in RS-422/485 terminals with H5-08 = 0 (Memobus/Modbus), per Parameter Access Technical Manual TM.E7.11 (rev 3016).
Also known as: CIMR-E7U, E7U, E7 Drive - Variable frequency drive
Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU
Yaskawa F7 (CIMR-F7U) general-purpose drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.F7.01 Appendix D, with parameter and monitor addresses from TM.F7.11.
Also known as: CIMR-F7U, F7U, F7 Drive - Variable frequency drive
Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU)
Yaskawa FP605 enclosed bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (MEMOBUS/Modbus); Technical Reference SIEPYAIF6B01C, section 10.6.
Also known as: FP605 Enclosed Bypass, FP605 bypass package - Variable frequency drive
Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa FP605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per technical reference SIEPC7106171F.
Also known as: CIPR-FP6, FP605 drive, FP605 AC Drive for Industrial Fan and Pump Applications - Variable frequency drive
Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU
Yaskawa G7 (CIMR-G7U) drives using built-in Modbus RTU on terminals R+/R-/S+/S-, per the Modbus Communication Manual G7 TM.G7.11 (rev 07-01).
Also known as: CIMR-G7U, G7U, G7 Drive - Variable frequency drive
Yaskawa GA500 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA500 drives using the built-in RS-485 MEMOBUS/Modbus port (terminal TB4), per technical reference SIEPC71061752 revision C.
Also known as: CIPR-GA50U, GA500 Versatile Compact - Variable frequency drive
Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA800 drives using the built-in RS-485 MEMOBUS/Modbus port, per technical reference SIEPC71061737 revision G.
Also known as: CIPR-GA80, GA800 Industrial AC Microdrive - Variable frequency drive
Yaskawa HV305 HVAC micro drive (MEMOBUS/Modbus RTU)
Yaskawa HV305 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPYAIHV3001B.
Also known as: HV35U, HV305 drive, HV305 Versatile Compact Drive - Variable frequency drive
Yaskawa HV600 HVAC fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa HV600 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPC71061732 revision F.
Also known as: CIPR-HV60, HV600 HVAC drive - Variable frequency drive (HVAC bypass package)
Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)
Yaskawa HV600 Narrow and Enclosed Bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (Modbus); Technical Reference SIEPYAIH6B01F, section 10.6.
Also known as: HV600 Bypass, HV600 Enclosed Bypass, HV600 Narrow Bypass - Variable frequency drive (pump)
Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU
Legacy Yaskawa iQpump drives built on the P7U platform (CIMR-P7U...), per user manual TM.iQp.01, using the built-in RS-422/485 terminals R+/R-/S+/S-.
Also known as: iQpump, CIMR-P7U iQpump, iQpump Drive - Variable frequency drive
Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump Micro drives using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEP YAIQPM 03B.
Also known as: CIMR-PW (iQpump Micro), iQpump Micro AC Drive, iQpump Micro Compact Intelligent Pump Controller - Variable frequency drive
Yaskawa iQpump1000 intelligent pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump1000 drives (CIMR-PW) using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEPYAIP1W01G.
Also known as: CIMR-PW, CIMR-PWA, iQpump1000 AC Drive - Variable frequency drive
Yaskawa iQpump605 intelligent pump controller (MEMOBUS/Modbus RTU)
Yaskawa iQpump605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per user manual SIEPYAIWM6502D.
Also known as: WM65W, iQpump605 drive, iQpump605 Intelligent Pump Controller - Variable frequency drive
Yaskawa J1000 compact V/f drive (MEMOBUS/Modbus RTU)
Yaskawa J1000 drives (CIMR-JU/JC) with the optional RS-422/485 MEMOBUS/Modbus interface, per Technical Manual SIEP C710606 31D.
Also known as: CIMR-JU, CIMR-JC, J1000 Compact V/f Control Drive - Variable frequency drive (HVAC bypass package)
Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU)
P1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIP1B 01D, appendix D.
Also known as: P1000 Bypass, P1B - Variable frequency drive
Yaskawa P1000 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa P1000 drives using the built-in RS-485/422 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP YAIP1U 01C.
Also known as: CIMR-PU, P1000 Industrial Fan and Pump Drive - Variable frequency drive (fan / pump)
Yaskawa P7 fan/pump drive (CIMR-P7U, legacy) - Modbus RTU
Yaskawa P7 (CIMR-P7U) fan and pump drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.P7.01 Appendix D.
Also known as: CIMR-P7U, P7U, P7 Drive - Variable frequency drive (fan / pump bypass package)
Yaskawa P7B drive/bypass (legacy) - Modbus RTU
Yaskawa P7B drive/bypass packages (P7 drive CIMR-P7U inside a bypass enclosure, option V native Modbus) using the drive's RS-422/485 terminals, per technical manual TM.P7B.01 Appendix D.
Also known as: P7B, P7 Bypass - Variable frequency drive
Yaskawa V1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa V1000 drives (CIMR-VU; 200 V single/three-phase and 400 V three-phase, 0.1-18.5 kW) using the built-in RS-422/485 MEMOBUS/Modbus terminals, per Technical Manual SIEP C710606 18F.
Also known as: CIMR-VU, V1000 Compact Vector Control Drive - Variable frequency drive
Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU
Yaskawa V7 (CIMR-V7AM) and V74X (CIMR-V7CU) compact drives with built-in Modbus RTU (keypad RJ-45 or R+/R-/S+/S- terminals), per TM.V7.11 Rev 07-01.
Also known as: CIMR-V7AM, CIMR-V7CU, V74X - Variable frequency drive (HVAC bypass package)
Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU)
Z1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIZ1B 01F, appendix D.
Also known as: Z1000 Bypass, Z1B1 - Variable frequency drive (HVAC fan / pump)
Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000 HVAC drives (CIMR-ZU) using the built-in RS-485 terminals with H5-08 = 0, per Programming Manual SIEP YAIZ1U 03C (the copy covers the 600 V class models 5A0007-5A0242).
Also known as: CIMR-ZU, Z1000 AC Drive for HVAC Fan and Pump - Variable frequency drive
Yaskawa Z1000U HVAC matrix drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000U HVAC matrix drives using the built-in serial terminals with H5-08 = 0 (MEMOBUS/Modbus), per programming manual SIEP C710636 10D.
Also known as: Z1000U HVAC MATRIX Drive, Z1000U Matrix
Other variable frequency drives register maps
- Variable frequency drive
ABB ACH550-UH HVAC drive (embedded Modbus RTU)
ACH550-UH HVAC drives using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AUA0000081823 Rev F.
Also known as: ACH550-UH, ACH550 - Variable frequency drive
ABB ACS480 general purpose drive (embedded Modbus RTU)
ACS480 drives running the ACS480 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000047399 Rev G.
Also known as: ACS480-04, ACS480 standard control program - Variable frequency drive
AutomationDirect DURApulse GS10 AC drive
GS10 drives (built-in RS-485 port) per the GS10 user manual, 1st edition rev. C, chapter 5.
Also known as: DURApulse GS10, GS10 micro drive - Variable frequency drive
Danfoss iC2-Micro frequency converter (Modbus RTU)
Danfoss iC2-Micro frequency converters using the built-in RS-485 port with P 10.1.1 Protocol = [2] Modbus RTU and the FC control profile; Application Guide AB413939445838en-000401.
Also known as: iC2-Micro, iC2 Micro, Danfoss iC2 - Variable frequency drive
Danfoss VLT Micro Drive FC 51 (Modbus RTU)
VLT Micro Drive FC 51 on the built-in RS-485 port with 8-30 = Modbus, software 3.1x; registers per design guide MG02K402 and parameter data per programming guide MG02C702.
Also known as: FC 51, FC51, VLT Micro Drive, VLT Micro Drive FC 51 - Variable frequency drive (variable speed starter)
Eaton PowerXL DE1 variable speed starter (Modbus RTU)
Eaton PowerXL DE1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DE1, DE11, PowerXL DE1, PowerXL DE11, DE1-12, DE1-34, DE11-12, DE11-34
All variable frequency drives Modbus register maps →
Source: YASKAWA U1000 Industrial MATRIX Drive Technical Manual · SIEP C710636 04E · rev. 2024-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.