Variable frequency drive · Modbus register map
Danfoss VLT Micro Drive FC 51 (Modbus RTU) Modbus register map
Updated 17 November 2026
Danfoss's smallest VLT drive with Modbus RTU on the RS-485 terminals. Control and status run through coils (control word bits at coils 1-16, status bits at coils 33-48), and every parameter is a holding register at 10 x its parameter number. This map covers the control and status coils, the Modbus and timeout settings, counters and the 16-xx readouts.
This page lists 60 Modbus registers for the Danfoss VLT Micro Drive FC 51 (Modbus RTU) — 28 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Danfoss’s own free documentation (linked below) and checked against it.
- Manufacturer
- Danfoss
- Model
- VLT Micro Drive FC 51 (Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 60 (28 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- derived from parameter numbers
- Firmware
- 3.1x
- Also known as
- FC 51, FC51, VLT Micro Drive, VLT Micro Drive FC 51
- Source document
- Design Guide VLT Micro Drive FC 51 · MG02K402 · rev. 2016-01
Integration notes: Danfoss VLT Micro Drive FC 51 (Modbus RTU)
Set 8-30 = Modbus, 8-31 address, 8-32/8-33 baud and parity, keep 8-02 = FC RS485, then drive the unit with coils 1-16 (write coils 3, 4, 5, 7 and 11 = 1 to run) and the reference on coils 17-32. Read coils 33-48 for status and holding registers 16130/16140 for frequency and current.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| CO 6 | CTW bit 6: ramp stop / start | BIT | Start (1) / ramp stop (0) | Read/write |
| CO 10 | CTW bit 10: data valid | BIT | Data valid - must be 1 | Read/write |
| CO 43 | STW bit 11: running | BIT | Running status | Read |
| CO 35 | STW bit 3: alarm | BIT | Alarm status | Read |
| CO 39 | STW bit 7: warning | BIT | Warning status | Read |
| HR 16129 | 16-13 Frequency | UINT16 | 16-13 Frequency, 0.1 Hz | Read |
| HR 16139 | 16-14 Motor Current | UINT16 | 16-14 Motor current, 0.01 A | Read |
| HR 8299 | 8-30 Protocol | UINT16 | 8-30 Protocol | Read/write |
Enable Modbus control & writes
Set 8-30 Protocol = [2] Modbus RTU (takes effect only after the drive is powered off and on), 8-31 Address (1-247, factory 1), 8-32 baud (19200 is the default once Modbus is chosen) and 8-33 parity (factory even, 1 stop bit). 8-02 must stay [1] FC RS485 and 8-01 Control Site decides whether terminals, the control word or both act; 8-50 to 8-56 (factory Logic OR) set how bus and terminal commands combine.
Communication loss & watchdog
8-03 Control Word Timeout Time (0.1-6500 s, factory 1.0 s) with 8-04 Control Word Timeout Function: Off (factory), Freeze output, Stop, Jogging, Max. speed, or Stop and trip.
Byte order & addressing
- Parameter register = 10 x parameter number, wire address = that minus 1 (16-13 -> 16129).
- Control word bits are active-low for stops: coils 3-5 must be 1 (no DC brake, no coast, no quick stop) and coil 7 = 1 starts.
- Coil 11 (data valid) must be 1 or the control word is ignored.
Network setup
- Coil 65 = 1 makes parameter writes go to EEPROM as well as RAM; leave it 0 for cyclic writes.
- Array parameters need holding register 9 (IND) set to the index first.
Watch out for
- With factory 8-04 = Off the drive keeps running if the master stops polling.
- Holding registers 50000-50210 (and 2810-2911) are described in the design guide alongside an instruction to set 8-30 = FC; use the coils for Modbus control.
Danfoss VLT Micro Drive FC 51 (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 1 | CTW bit 0: preset reference LSB | BIT | Read/write | |||||
| CO | 1doc 2 | CTW bit 1: preset reference MSB | BIT | Read/write | |||||
| CO | 2doc 3 | CTW bit 2: DC brake | BIT | Read/write | 0 = DC brake; 1 = No DC brake | ||||
| CO | 3doc 4 | CTW bit 3: coast stop | BIT | Read/write | 0 = Coast stop; 1 = No coast stop | ||||
| CO | 4doc 5 | CTW bit 4: quick stop | BIT | Read/write | 0 = Quick stop; 1 = No quick stop | ||||
| CO | 5doc 6 | CTW bit 5: freeze frequency | BIT | Read/write | 0 = Freeze frequency; 1 = No freeze frequency | ||||
| CO | 6doc 7 | CTW bit 6: ramp stop / start | BIT | Read/write | 0 = Ramp stop; 1 = Start | ||||
| CO | 7doc 8 | CTW bit 7: reset | BIT | Read/write | 0 = No reset; 1 = Reset | ||||
| CO | 8doc 9 | CTW bit 8: jog | BIT | Read/write | 0 = No jog; 1 = Jog | ||||
| CO | 9doc 10 | CTW bit 9: ramp select | BIT | Read/write | 0 = Ramp 1; 1 = Ramp 2 | ||||
| CO | 10doc 11 | CTW bit 10: data valid | BIT | Read/write | 0 = Data not valid; 1 = Data valid | ||||
| CO | 11doc 12 | CTW bit 11: relay 1 | BIT | Read/write | 0 = Relay 1 off; 1 = Relay 1 on | ||||
| CO | 12doc 13 | CTW bit 12: relay 2 | BIT | Read/write | 0 = Relay 2 off; 1 = Relay 2 on | ||||
| CO | 13doc 14 | CTW bit 13: set-up select LSB | BIT | Read/write | |||||
| CO | 15doc 16 | CTW bit 15: reversing | BIT | Read/write | 0 = No reversing; 1 = Reversing | ||||
| CO | 32doc 33 | STW bit 0: control ready | BIT | Read | 0 = Control not ready; 1 = Control ready | ||||
| CO | 33doc 34 | STW bit 1: drive ready | BIT | Read | 0 = Not ready; 1 = Ready | ||||
| CO | 34doc 35 | STW bit 2: coast stop / safety closed | BIT | Read | 0 = Coast stop; 1 = Safety closed | ||||
| CO | 35doc 36 | STW bit 3: alarm | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| CO | 39doc 40 | STW bit 7: warning | BIT | Read | 0 = No warning; 1 = Warning | ||||
| CO | 40doc 41 | STW bit 8: at reference | BIT | Read | 0 = Not at reference; 1 = At reference | ||||
| CO | 41doc 42 | STW bit 9: hand/auto | BIT | Read | 0 = Hand mode; 1 = Auto mode | ||||
| CO | 42doc 43 | STW bit 10: frequency range | BIT | Read | 0 = Out of frequency range; 1 = In frequency range | ||||
| CO | 43doc 44 | STW bit 11: running | BIT | Read | 0 = Stopped; 1 = Running | ||||
| CO | 45doc 46 | STW bit 13: voltage warning | BIT | Read | 0 = No voltage warning; 1 = Voltage warning | ||||
| CO | 46doc 47 | STW bit 14: current limit | BIT | Read | 0 = Not in current limit; 1 = Current limit | ||||
| CO | 47doc 48 | STW bit 15: thermal warning | BIT | Read | 0 = No thermal warning; 1 = Thermal warning | ||||
| CO | 64doc 65 | Parameter write control | BIT | Read/write | 0 = Writes go to RAM only; 1 = Writes go to RAM and EEPROM | ||||
| HR | 6doc 7 | Last fault code | Fault code from the parameter database. | UINT16 | Read | ||||
| HR | 8doc 9 | Index pointer (IND) | Array index used for array parameters such as 3-10. | UINT16 | Read/write | ||||
| HR | 4119doc 4120 (par. 4-12) | 4-12 Motor Speed Low Limit [Hz] | Write only when stopped. | UINT16 | × 0.1 | Hz | Read/write | ||
| HR | 4139doc 4140 (par. 4-14) | 4-14 Motor Speed High Limit [Hz] | Write only when stopped. | UINT16 | × 0.1 | Hz | Read/write | ||
| HR | 8009doc 8010 (par. 8-01) | 8-01 Control Site | UINT16 | Read/write | 0 = Digital and control word; 1 = Digital only; 2 = Control word only | ||||
| HR | 8019doc 8020 (par. 8-02) | 8-02 Control Word Source | UINT16 | Read/write | 0 = None; 1 = FC RS485 | ||||
| HR | 8029doc 8030 (par. 8-03) | 8-03 Control Word Timeout Time | 0.1-6500 s, factory 1.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 8039doc 8040 (par. 8-04) | 8-04 Control Word Timeout Function | UINT16 | Read/write | 0 = Off; 1 = Freeze output; 2 = Stop; 3 = Jogging; 4 = Max. speed; 5 = Stop and trip | ||||
| HR | 8299doc 8300 (par. 8-30) | 8-30 Protocol | UINT16 | Read/write | 0 = FC; 2 = Modbus | ||||
| HR | 8309doc 8310 (par. 8-31) | 8-31 Address | 1-247, factory 1. | UINT16 | Read/write | ||||
| HR | 8319doc 8320 (par. 8-32) | 8-32 FC Port Baud Rate | UINT16 | Read/write | 0 = 2400; 1 = 4800; 2 = 9600 (default with FC protocol); 3 = 19200 (default with Modbus); 4 = 38400 | ||||
| HR | 8329doc 8330 (par. 8-33) | 8-33 FC Port Parity | UINT16 | Read/write | 0 = Even parity, 1 stop bit; 1 = Odd parity, 1 stop bit; 2 = No parity, 1 stop bit; 3 = No parity, 2 stop bits | ||||
| HR | 8349doc 8350 (par. 8-35) | 8-35 Minimum Response Delay | 0.001-0.5 s, factory 0.010 s. | UINT16 | × 0.001 | s | Read/write | ||
| HR | 15039doc 15040 (par. 15-04) | 15-04 Over Temp's | UINT16 | Read | |||||
| HR | 15049doc 15050 (par. 15-05) | 15-05 Over Volt's | UINT16 | Read | |||||
| HR | 15999doc 16000 (par. 16-00) | 16-00 Control Word | Last control word received, hex. | UINT16 | Read | ||||
| HR | 16019doc 16020 (par. 16-02) | 16-02 Reference % | INT16 | × 0.1 | % | Read | |||
| HR | 16029doc 16030 (par. 16-03) | 16-03 Status Word | Status word, hex; bits as coils 33-48. | UINT16 | Read | ||||
| HR | 16099doc 16100 (par. 16-10) | 16-10 Power [kW] | UINT16 | × 0.001 | kW | Read | |||
| HR | 16119doc 16120 (par. 16-12) | 16-12 Motor Voltage | UINT16 | V | Read | ||||
| HR | 16129doc 16130 (par. 16-13) | 16-13 Frequency | UINT16 | × 0.1 | Hz | Read | |||
| HR | 16139doc 16140 (par. 16-14) | 16-14 Motor Current | UINT16 | × 0.01 | A | Read | |||
| HR | 16179doc 16180 (par. 16-18) | 16-18 Motor Thermal | UINT16 | % | Read | ||||
| HR | 16299doc 16300 (par. 16-30) | 16-30 DC Link Voltage | UINT16 | V | Read | ||||
| HR | 16339doc 16340 (par. 16-34) | 16-34 Heatsink Temp. | UINT16 | °C | Read | ||||
| HR | 16349doc 16350 (par. 16-35) | 16-35 Inverter Thermal | UINT16 | % | Read | ||||
| HR | 16359doc 16360 (par. 16-36) | 16-36 Inv. Nom. Current | UINT16 | × 0.01 | A | Read | |||
| HR | 16599doc 16600 (par. 16-60) | 16-60 Digital input 18,19,27,33 | UINT16 | Read | |||||
| HR | 16619doc 16620 (par. 16-62) | 16-62 Analog Input 53 (V) | UINT16 | × 0.01 | V | Read | |||
| HR | 16629doc 16630 (par. 16-63) | 16-63 Analog Input 53 (mA) | UINT16 | × 0.01 | mA | Read | |||
| HR | 16639doc 16640 (par. 16-64) | 16-64 Analog Input 60 | UINT16 | × 0.01 | mA | Read | |||
| HR | 16649doc 16650 (par. 16-65) | 16-65 Analog Output 42 [mA] | UINT16 | × 0.01 | mA | Read |
Notes on this map
- Parameter data (type, conversion index, defaults, option lists) come from the VLT Micro Drive FC 51 Programming Guide MG02C702 (12/2014, software 3.1x), https://assets.danfoss.com/documents/273489/AU361182403098en-000901.pdf, section 5.2 parameter lists. Conversion index -1 = x0.1, -2 = x0.01, -3 = x0.001, 0 = x1.
- Left out: all 32-bit parameters (3-02, 3-03, 3-41, 3-42, 15-00 to 15-03, 16-01, 16-52, 16-90, 16-92, 16-94). The FC 51 guides only say they take 2 registers; the design guide's generic examples are inconsistent (3-14 at 3410, and a 3-03 read whose bytes 00 16 E3 60 are described as 000088B8 = 35 Hz), and Danfoss's general Modbus RTU instructions MG92B102 are written for software 6.4x and do not name the FC 51, so the word order is not settled for this drive.
- The design guide's 32-bit example names 3-14 at registers 3410/3411; by the x10 rule 3-14 is register 3140, and the programming guide types 3-14 as Int16. Treat that example as a typo.
- Uint8 parameters are read and written as one 16-bit register.
- Section 8.11 lists CTW/REF at holding registers 50000/50010 and STW/MAV at 50200/50210 (and, from software 2.32, 2810/2811 and 2910/2911), but the same section says to set 8-30 = [0] FC, so their use with Modbus is unclear and they are not listed. Coils 1-16 carry the control word, 17-32 the bus reference (16-bit, 0x0-0xFFFF = -200 %..~200 %), 33-48 the status word and 49-64 output frequency (open loop) or feedback (closed loop); the reference and actual-value coil groups are not listed bit by bit.
- Coil 15 (control word bit 14) is unused in the FC profile table and is not listed; status coils 37-39 and 45 are 'not used'.
- Alarm and warning words (16-90/16-92) are 32-bit and left out for the word-order reason above; use status coil 36 (alarm) and 40 (warning) instead.
- Left out: 16-05 and 16-15 (normalised percentages), 16-50/16-51 external and pulse references, text parameters (15-4x), the fault log arrays (15-30, need IND) and Smart Logic groups.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Danfoss VLT Micro Drive FC 51 (Modbus RTU)
What Modbus registers does the Danfoss VLT Micro Drive FC 51 (Modbus RTU) have?
This map lists 60 registers: 28 coils, 32 holding registers. 28 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Danfoss VLT Micro Drive FC 51 (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers derived from parameter numbers. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The design guide says Modbus addresses are referenced to 0: coil 1 is coil 0 on the wire and holding register 40001 is register 0. A parameter's register number is 10 x its parameter number (16-13 -> 16130; 3-12 is read in holding register 3120) and the request carries that number minus 1 (16-13 at address 16129). Coil n is address n - 1.
What are the minimum Modbus registers to integrate the Danfoss VLT Micro Drive FC 51 (Modbus RTU)?
Start with CO 6 CTW bit 6: ramp stop / start (Start (1) / ramp stop (0)); CO 10 CTW bit 10: data valid (Data valid - must be 1); CO 43 STW bit 11: running (Running status); CO 35 STW bit 3: alarm (Alarm status); CO 39 STW bit 7: warning (Warning status); HR 16129 16-13 Frequency (16-13 Frequency, 0.1 Hz); HR 16139 16-14 Motor Current (16-14 Motor current, 0.01 A); HR 8299 8-30 Protocol (8-30 Protocol).
How do I enable Modbus control of the Danfoss VLT Micro Drive FC 51 (Modbus RTU)?
Set 8-30 Protocol = [2] Modbus RTU (takes effect only after the drive is powered off and on), 8-31 Address (1-247, factory 1), 8-32 baud (19200 is the default once Modbus is chosen) and 8-33 parity (factory even, 1 stop bit). 8-02 must stay [1] FC RS485 and 8-01 Control Site decides whether terminals, the control word or both act; 8-50 to 8-56 (factory Logic OR) set how bus and terminal commands combine.
What happens when the Danfoss VLT Micro Drive FC 51 (Modbus RTU) loses Modbus communication?
8-03 Control Word Timeout Time (0.1-6500 s, factory 1.0 s) with 8-04 Control Word Timeout Function: Off (factory), Freeze output, Stop, Jogging, Max. speed, or Stop and trip.
Where is the official Danfoss VLT Micro Drive FC 51 (Modbus RTU) Modbus documentation?
The source is Design Guide VLT Micro Drive FC 51 (MG02K402), revision 2016-01, published free by Danfoss at https://assets.danfoss.com/documents/273509/AJ361178983102en-000401.pdf.
More Danfoss Modbus register maps
- Thermostat / heating controller (district heating and HVAC)
Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP)
ECL Comfort 210, 296 and 310 controllers (and B versions) with any application key; many parameters depend on the loaded application.
Also known as: ECL Comfort 210, ECL Comfort 296, ECL Comfort 310, ECL Comfort 210B, ECL Comfort 310B, 087H3020, 087H3024, 087H3030, 087H3034, 087H3040, 087H3044, 087H3050, 087H3054 - Sensor (refrigerant / toxic gas detector)
Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU)
Danfoss GD Basic, Premium and Heavy Duty gas detection units on their own RS-485 Modbus port (Part 2 of the guide). The gas detection controller's X-bus map in Part 1 is not included.
Also known as: GDA, GDC, GDHC, GDHF, GDH, GD Basic, GD Premium, GD Heavy Duty - Variable frequency drive
Danfoss iC2-Micro frequency converter (Modbus RTU)
Danfoss iC2-Micro frequency converters using the built-in RS-485 port with P 10.1.1 Protocol = [2] Modbus RTU and the FC control profile; Application Guide AB413939445838en-000401.
Also known as: iC2-Micro, iC2 Micro, Danfoss iC2 - Sensor / controller (CO2 condensing unit gateway)
Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005)
Danfoss Optyma iCO2 CO2 condensing units (4.6 kW MT and 20 kW MT / 10 kW LT) through their Modbus gateway, software 1.0x.
Also known as: OP-MPAM015, OP-MPAM005, Optyma iCO2 4.6 kW MT, Optyma iCO2 20 kW MT / 10 kW LT - Variable frequency drive
Danfoss VLT AQUA Drive FC 202 (Modbus RTU)
VLT AQUA Drive FC 202 using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter data checked against the software 5.4X programming guide.
Also known as: VLT AQUA Drive, FC202, FC-202, AQUA Drive FC 202 - Variable frequency drive
Danfoss VLT AutomationDrive FC 301/302 (Modbus RTU)
VLT AutomationDrive FC 301 and FC 302 (0.25-75 kW design guide; same scheme across sizes) using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter data checked against the software 9.5x / 48.96 programming guide.
Also known as: VLT AutomationDrive, FC 301, FC301, FC302, FC-302, FC-301, FC 300 - Variable frequency drive
Danfoss VLT AutomationDrive FC 360 (Modbus RTU)
VLT AutomationDrive FC 360 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC360, FC-360, VLT AutomationDrive FC 360 - Variable frequency drive
Danfoss VLT Compressor Drive CDS 803 (Modbus RTU)
VLT Compressor Drive CDS 803 (variable-speed compressor drive for HVAC/R) using the built-in RS-485 port with 8-30 Protocol = Modbus RTU; Modbus rules from Design Guide MG18N202 (software 1.20), parameter data from Programming Guide MG18P202 (software 2.0).
Also known as: CDS803, CDS-803, VLT Compressor Drive CDS 803 - Variable frequency drive (HVAC fans and pumps)
Danfoss VLT HVAC Basic Drive FC 101 (Modbus RTU)
VLT HVAC Basic Drive FC 101 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC101, FC-101, VLT HVAC Basic Drive FC 101, VLT HVAC Basic - Variable frequency drive
Danfoss VLT HVAC Drive FC 102 (Modbus RTU)
VLT HVAC Drive FC 102 using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter scaling checked against the software 7.61 programming guide.
Also known as: VLT HVAC Drive, FC102, FC-102 - Variable frequency drive
Danfoss VLT Midi Drive FC 280 (Modbus RTU)
VLT Midi Drive FC 280 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC280, FC-280, VLT Midi Drive FC 280, VLT Midi Drive
Other variable frequency drives register maps
- Variable frequency drive (variable speed starter)
Eaton PowerXL DE1 variable speed starter (Modbus RTU)
Eaton PowerXL DE1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DE1, DE11, PowerXL DE1, PowerXL DE11, DE1-12, DE1-34, DE11-12, DE11-34 - Variable frequency drive
Inovance MD200 series compact AC drive
Inovance MD200 single- and three-phase compact drives using the RS-485 Modbus RTU port, per user guide 19012113 rev. C02.
Also known as: MD200, MD200T, MD200S, MD200-NC, Inovance MD200 - Variable frequency drive
INVT Goodrive10 (GD10) mini VFD
INVT Goodrive10 mini drives using the built-in RS-485 Modbus RTU port, per the GD10 VFD manual V2.9 (chapter 7).
Also known as: GD10, Goodrive10, GD10 mini VFD - Variable frequency drive
INVT Goodrive350A (GD350A) high-performance multifunction VFD
INVT Goodrive350A drives using the built-in RS-485 Modbus RTU port, per the GD350A manual V1.3 (chapter 9).
Also known as: GD350A, Goodrive350A, GD350A series - Variable frequency drive
Lovato Electric VT1 series variable speed drives (Modbus RTU / ASCII)
Lovato VT1 series drives on the built-in RS-485 port, per communication manual I646 GB I 02 21 (Modbus part).
Also known as: VT1, Lovato VT1, VT1 series - Variable frequency drive
NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU)
NORD SK 500E-series inverters from SK 540E up (SK 540E, SK 545E) on the RS485 interface, per supplementary manual BU 0050 (GB-3111).
Also known as: SK 540E, SK 545E, SK 54xE, NORDAC SK 500E series (SK 540E and above)
All variable frequency drives Modbus register maps →
Source: Design Guide VLT Micro Drive FC 51 · MG02K402 · rev. 2016-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.