Danfoss VLT Micro Drive FC 51 (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

Danfoss's smallest VLT drive with Modbus RTU on the RS-485 terminals. Control and status run through coils (control word bits at coils 1-16, status bits at coils 33-48), and every parameter is a holding register at 10 x its parameter number. This map covers the control and status coils, the Modbus and timeout settings, counters and the 16-xx readouts.

This page lists 60 Modbus registers for the Danfoss VLT Micro Drive FC 51 (Modbus RTU) — 28 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Danfoss’s own free documentation (linked below) and checked against it.

Manufacturer
Danfoss
Model
VLT Micro Drive FC 51 (Modbus RTU)
Equipment type
Variable frequency drive
Registers
60 (28 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
19200 baud, 8E1
Documented addressing
derived from parameter numbers
Firmware
3.1x
Also known as
FC 51, FC51, VLT Micro Drive, VLT Micro Drive FC 51
Source document
Design Guide VLT Micro Drive FC 51 · MG02K402 · rev. 2016-01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Danfoss VLT Micro Drive FC 51 (Modbus RTU)

Integration in brief

Set 8-30 = Modbus, 8-31 address, 8-32/8-33 baud and parity, keep 8-02 = FC RS485, then drive the unit with coils 1-16 (write coils 3, 4, 5, 7 and 11 = 1 to run) and the reference on coils 17-32. Read coils 33-48 for status and holding registers 16130/16140 for frequency and current.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
CO 6CTW bit 6: ramp stop / startBITStart (1) / ramp stop (0)Read/write
CO 10CTW bit 10: data validBITData valid - must be 1Read/write
CO 43STW bit 11: runningBITRunning statusRead
CO 35STW bit 3: alarmBITAlarm statusRead
CO 39STW bit 7: warningBITWarning statusRead
HR 1612916-13 FrequencyUINT1616-13 Frequency, 0.1 HzRead
HR 1613916-14 Motor CurrentUINT1616-14 Motor current, 0.01 ARead
HR 82998-30 ProtocolUINT168-30 ProtocolRead/write

Enable Modbus control & writes

Set 8-30 Protocol = [2] Modbus RTU (takes effect only after the drive is powered off and on), 8-31 Address (1-247, factory 1), 8-32 baud (19200 is the default once Modbus is chosen) and 8-33 parity (factory even, 1 stop bit). 8-02 must stay [1] FC RS485 and 8-01 Control Site decides whether terminals, the control word or both act; 8-50 to 8-56 (factory Logic OR) set how bus and terminal commands combine.

Communication loss & watchdog

8-03 Control Word Timeout Time (0.1-6500 s, factory 1.0 s) with 8-04 Control Word Timeout Function: Off (factory), Freeze output, Stop, Jogging, Max. speed, or Stop and trip.

Byte order & addressing

Network setup

Watch out for

Danfoss VLT Micro Drive FC 51 (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

60 of 60 shown
Danfoss VLT Micro Drive FC 51 (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 1CTW bit 0: preset reference LSBBITRead/write
CO1doc 2CTW bit 1: preset reference MSBBITRead/write
CO2doc 3CTW bit 2: DC brakeBITRead/write0 = DC brake; 1 = No DC brake
CO3doc 4CTW bit 3: coast stopBITRead/write0 = Coast stop; 1 = No coast stop
CO4doc 5CTW bit 4: quick stopBITRead/write0 = Quick stop; 1 = No quick stop
CO5doc 6CTW bit 5: freeze frequencyBITRead/write0 = Freeze frequency; 1 = No freeze frequency
CO6doc 7CTW bit 6: ramp stop / startBITRead/write0 = Ramp stop; 1 = Start
CO7doc 8CTW bit 7: resetBITRead/write0 = No reset; 1 = Reset
CO8doc 9CTW bit 8: jogBITRead/write0 = No jog; 1 = Jog
CO9doc 10CTW bit 9: ramp selectBITRead/write0 = Ramp 1; 1 = Ramp 2
CO10doc 11CTW bit 10: data validBITRead/write0 = Data not valid; 1 = Data valid
CO11doc 12CTW bit 11: relay 1BITRead/write0 = Relay 1 off; 1 = Relay 1 on
CO12doc 13CTW bit 12: relay 2BITRead/write0 = Relay 2 off; 1 = Relay 2 on
CO13doc 14CTW bit 13: set-up select LSBBITRead/write
CO15doc 16CTW bit 15: reversingBITRead/write0 = No reversing; 1 = Reversing
CO32doc 33STW bit 0: control readyBITRead0 = Control not ready; 1 = Control ready
CO33doc 34STW bit 1: drive readyBITRead0 = Not ready; 1 = Ready
CO34doc 35STW bit 2: coast stop / safety closedBITRead0 = Coast stop; 1 = Safety closed
CO35doc 36STW bit 3: alarmBITRead0 = No alarm; 1 = Alarm
CO39doc 40STW bit 7: warningBITRead0 = No warning; 1 = Warning
CO40doc 41STW bit 8: at referenceBITRead0 = Not at reference; 1 = At reference
CO41doc 42STW bit 9: hand/autoBITRead0 = Hand mode; 1 = Auto mode
CO42doc 43STW bit 10: frequency rangeBITRead0 = Out of frequency range; 1 = In frequency range
CO43doc 44STW bit 11: runningBITRead0 = Stopped; 1 = Running
CO45doc 46STW bit 13: voltage warningBITRead0 = No voltage warning; 1 = Voltage warning
CO46doc 47STW bit 14: current limitBITRead0 = Not in current limit; 1 = Current limit
CO47doc 48STW bit 15: thermal warningBITRead0 = No thermal warning; 1 = Thermal warning
CO64doc 65Parameter write controlBITRead/write0 = Writes go to RAM only; 1 = Writes go to RAM and EEPROM
HR6doc 7Last fault codeFault code from the parameter database.UINT16Read
HR8doc 9Index pointer (IND)Array index used for array parameters such as 3-10.UINT16Read/write
HR4119doc 4120 (par. 4-12)4-12 Motor Speed Low Limit [Hz]Write only when stopped.UINT16× 0.1HzRead/write
HR4139doc 4140 (par. 4-14)4-14 Motor Speed High Limit [Hz]Write only when stopped.UINT16× 0.1HzRead/write
HR8009doc 8010 (par. 8-01)8-01 Control SiteUINT16Read/write0 = Digital and control word; 1 = Digital only; 2 = Control word only
HR8019doc 8020 (par. 8-02)8-02 Control Word SourceUINT16Read/write0 = None; 1 = FC RS485
HR8029doc 8030 (par. 8-03)8-03 Control Word Timeout Time0.1-6500 s, factory 1.0 s.UINT16× 0.1sRead/write
HR8039doc 8040 (par. 8-04)8-04 Control Word Timeout FunctionUINT16Read/write0 = Off; 1 = Freeze output; 2 = Stop; 3 = Jogging; 4 = Max. speed; 5 = Stop and trip
HR8299doc 8300 (par. 8-30)8-30 ProtocolUINT16Read/write0 = FC; 2 = Modbus
HR8309doc 8310 (par. 8-31)8-31 Address1-247, factory 1.UINT16Read/write
HR8319doc 8320 (par. 8-32)8-32 FC Port Baud RateUINT16Read/write0 = 2400; 1 = 4800; 2 = 9600 (default with FC protocol); 3 = 19200 (default with Modbus); 4 = 38400
HR8329doc 8330 (par. 8-33)8-33 FC Port ParityUINT16Read/write0 = Even parity, 1 stop bit; 1 = Odd parity, 1 stop bit; 2 = No parity, 1 stop bit; 3 = No parity, 2 stop bits
HR8349doc 8350 (par. 8-35)8-35 Minimum Response Delay0.001-0.5 s, factory 0.010 s.UINT16× 0.001sRead/write
HR15039doc 15040 (par. 15-04)15-04 Over Temp'sUINT16Read
HR15049doc 15050 (par. 15-05)15-05 Over Volt'sUINT16Read
HR15999doc 16000 (par. 16-00)16-00 Control WordLast control word received, hex.UINT16Read
HR16019doc 16020 (par. 16-02)16-02 Reference %INT16× 0.1%Read
HR16029doc 16030 (par. 16-03)16-03 Status WordStatus word, hex; bits as coils 33-48.UINT16Read
HR16099doc 16100 (par. 16-10)16-10 Power [kW]UINT16× 0.001kWRead
HR16119doc 16120 (par. 16-12)16-12 Motor VoltageUINT16VRead
HR16129doc 16130 (par. 16-13)16-13 FrequencyUINT16× 0.1HzRead
HR16139doc 16140 (par. 16-14)16-14 Motor CurrentUINT16× 0.01ARead
HR16179doc 16180 (par. 16-18)16-18 Motor ThermalUINT16%Read
HR16299doc 16300 (par. 16-30)16-30 DC Link VoltageUINT16VRead
HR16339doc 16340 (par. 16-34)16-34 Heatsink Temp.UINT16°CRead
HR16349doc 16350 (par. 16-35)16-35 Inverter ThermalUINT16%Read
HR16359doc 16360 (par. 16-36)16-36 Inv. Nom. CurrentUINT16× 0.01ARead
HR16599doc 16600 (par. 16-60)16-60 Digital input 18,19,27,33UINT16Read
HR16619doc 16620 (par. 16-62)16-62 Analog Input 53 (V)UINT16× 0.01VRead
HR16629doc 16630 (par. 16-63)16-63 Analog Input 53 (mA)UINT16× 0.01mARead
HR16639doc 16640 (par. 16-64)16-64 Analog Input 60UINT16× 0.01mARead
HR16649doc 16650 (par. 16-65)16-65 Analog Output 42 [mA]UINT16× 0.01mARead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Danfoss VLT Micro Drive FC 51 (Modbus RTU)

What Modbus registers does the Danfoss VLT Micro Drive FC 51 (Modbus RTU) have?

This map lists 60 registers: 28 coils, 32 holding registers. 28 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Danfoss VLT Micro Drive FC 51 (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers derived from parameter numbers. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The design guide says Modbus addresses are referenced to 0: coil 1 is coil 0 on the wire and holding register 40001 is register 0. A parameter's register number is 10 x its parameter number (16-13 -> 16130; 3-12 is read in holding register 3120) and the request carries that number minus 1 (16-13 at address 16129). Coil n is address n - 1.

What are the minimum Modbus registers to integrate the Danfoss VLT Micro Drive FC 51 (Modbus RTU)?

Start with CO 6 CTW bit 6: ramp stop / start (Start (1) / ramp stop (0)); CO 10 CTW bit 10: data valid (Data valid - must be 1); CO 43 STW bit 11: running (Running status); CO 35 STW bit 3: alarm (Alarm status); CO 39 STW bit 7: warning (Warning status); HR 16129 16-13 Frequency (16-13 Frequency, 0.1 Hz); HR 16139 16-14 Motor Current (16-14 Motor current, 0.01 A); HR 8299 8-30 Protocol (8-30 Protocol).

How do I enable Modbus control of the Danfoss VLT Micro Drive FC 51 (Modbus RTU)?

Set 8-30 Protocol = [2] Modbus RTU (takes effect only after the drive is powered off and on), 8-31 Address (1-247, factory 1), 8-32 baud (19200 is the default once Modbus is chosen) and 8-33 parity (factory even, 1 stop bit). 8-02 must stay [1] FC RS485 and 8-01 Control Site decides whether terminals, the control word or both act; 8-50 to 8-56 (factory Logic OR) set how bus and terminal commands combine.

What happens when the Danfoss VLT Micro Drive FC 51 (Modbus RTU) loses Modbus communication?

8-03 Control Word Timeout Time (0.1-6500 s, factory 1.0 s) with 8-04 Control Word Timeout Function: Off (factory), Freeze output, Stop, Jogging, Max. speed, or Stop and trip.

Where is the official Danfoss VLT Micro Drive FC 51 (Modbus RTU) Modbus documentation?

The source is Design Guide VLT Micro Drive FC 51 (MG02K402), revision 2016-01, published free by Danfoss at https://assets.danfoss.com/documents/273509/AJ361178983102en-000401.pdf.

More Danfoss Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: Design Guide VLT Micro Drive FC 51 · MG02K402 · rev. 2016-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.