Variable frequency drive · Modbus register map

Danfoss iC2-Micro frequency converter (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

Danfoss's compact drive with a built-in RS-485 port. In Modbus RTU mode the FC-profile control word, bus reference, status word and main actual value sit at holding registers 50000-50210, and every parameter is reachable at ten times its parameter number (PNU). This map covers the control block, the speed limits and ramp-up time, the fault/warning words and the communication and watchdog settings.

This page lists 29 Modbus registers for the Danfoss iC2-Micro frequency converter (Modbus RTU) — 16 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Danfoss’s own free documentation (linked below) and checked against it.

Manufacturer
Danfoss
Model
iC2-Micro frequency converter (Modbus RTU)
Equipment type
Variable frequency drive
Registers
29 (16 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8E1
Documented addressing
derived from parameter numbers
32-bit word order
ABCD high word first (big-endian)
Also known as
iC2-Micro, iC2 Micro, Danfoss iC2
Source document
Application Guide iC2-Micro Frequency Converters · AB413939445838en-000401 (130R1254) · rev. 2025-12
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Danfoss iC2-Micro frequency converter (Modbus RTU)

Integration in brief

Set P 10.1.1 = [2] Modbus RTU with the address, baud and parity in P 10.1.2-10.1.4, keep P 5.5.1.2 Control Source = FC Port, then write CTW to 50000 (bit 10 = 1) and the reference to 50010 and poll 50200/50210. Readouts sit at PNU x 10 (minus 1 on the wire), 32-bit values high word first.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 49999Control word (CTW)BITMAP16CTW: start/stop/resetRead/write
HR 50009Bus reference (REF)INT16REF: speed reference, 4000h = 100%Read/write
HR 50199Status word (STW)BITMAP16STW: ready/running/trip/warningRead
HR 50209Main actual value (MAV)INT16MAV: output frequency, 4000h = 100%Read
HR 16899P 5.1.1 Fault Word 1UINT32 ABCDP 5.1.1 Fault word 1Read
HR 16919P 5.1.4 Warning Word 1UINT32 ABCDP 5.1.4 Warning word 1Read
HR 18549P 5.1.11 Active Fault NumberUINT16P 5.1.11 Active fault numberRead

Enable Modbus control & writes

P 10.1.1 Protocol = [2] Modbus RTU ([26] emulates the VLT Micro Drive FC 51 parameter format), P 10.1.2 address 1-247, P 10.1.3 baud, P 10.1.4 parity. P 5.5.1.1 Control Place Selection decides whether digital inputs, the control word or both are used; P 5.5.1.2 Control Source must be FC Port. STW bit 9 must be 1 (not local) for bus control.

Communication loss & watchdog

P 5.2.16 Watchdog Response (default Off; Freeze output, Stop, Jogging, Max. speed, Stop and trip, Qstop and trip, set-up select, Trip) runs when no telegram arrives within P 5.2.17 Watchdog Delay (0.5-6000.0 s, default 1.0 s).

Byte order & addressing

Network setup

Watch out for

Danfoss iC2-Micro frequency converter (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

29 of 29 shown
Danfoss iC2-Micro frequency converter (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO64doc 65Parameter write control0 = parameter writes go to RAM only, 1 = RAM and EEPROM.BITRead/write0 = RAM only; 1 = RAM and EEPROM
HR6doc 40007Last fault codeFault code received from the parameter database.UINT16Read
HR7doc 40008Last error registerAddress of the register where the last error occurred.UINT16Read
HR8doc 40009Index pointerArray index for following array-parameter reads/writes.UINT16Read/write
HR999doc 1000P 5.4.2 Operation ModeUINT16Read/write0 = Speed Open Loop; 3 = Process Closed Loop; 4 = Torque Open Loop
HR3029doc 3030P 5.5.3.3 Reference Maximum35000 reads as 35.000 in the unit set by P 5.5.3.2 (guide example).INT32ABCD× 0.001Read/write
HR3409doc 3410P 5.5.4.2 Ramp 1 Accel. TimeGuide example: raw 1000 = 10.00 s (conversion index -2).UINT32ABCD× 0.01sRead/write
HR4119doc 4120P 5.8.3 Motor Speed Low Limit [Hz]Guide example: conversion factor 0.1, write 100 for 10.0 Hz.UINT16× 0.1HzRead/write
HR4139doc 4140P 5.8.2 Motor Speed High Limit [Hz]Guide example: write 1000 for 100.0 Hz.UINT16× 0.1HzRead/write
HR8009doc 8010P 5.5.1.1 Control Place SelectionUINT16Read/write0 = Digital and ctrl. word; 1 = Digital only; 2 = Control word only
HR8019doc 8020P 5.5.1.2 Control SourceUINT16Read/write0 = None; 1 = FC Port
HR8039doc 8040P 5.2.16 Watchdog ResponseAction when the control word is not updated in time.UINT16Read/write0 = Off; 1 = Freeze output; 2 = Stop; 3 = Jogging; 4 = Max. speed; 5 = Stop and trip; 6 = Qstop and trip; 7 = Select set-up 1; 8 = Select set-up 2; 26 = Trip
HR8299doc 8300P 10.1.1 ProtocolUINT16Read/write0 = FC; 2 = Modbus RTU; 26 = Modbus RTU Legacy FC 51
HR8309doc 8310P 10.1.2 Address1-247 for Modbus; uint8 in one register.UINT16Read/write
HR8319doc 8320P 10.1.3 Baud RateUINT16Read/write0 = 2400; 1 = 4800; 2 = 9600; 3 = 19200; 4 = 38400; 5 = 57600; 6 = 76800; 7 = 115200
HR8329doc 8330P 10.1.4 Parity/Stop BitsUINT16Read/write0 = Even parity, 1 stop bit; 1 = Odd parity, 1 stop bit; 2 = No parity, 1 stop bit; 3 = No parity, 2 stop bits
HR15299doc 15300P 6.1.1 Latest Fault NumberFault log entry 0 (most recent); uint8 in one register.UINT16Read
HR15999doc 16000P 5.1.7 Active Control WordControl word as seen by the drive.UINT16Read
HR16029doc 16030P 5.1.8 Drive Status WordUINT16Read
HR16599doc 16600P 9.3.1 Digital Input StatusBit 0 = T18, 2 = T17, 3 = T15, 4 = T14, 5 = T13.UINT16Read
HR16899doc 16900P 5.1.1 Fault Word 1Raw fault bits.UINT32ABCDRead
HR16919doc 16920P 5.1.4 Warning Word 1Raw warning bits.UINT32ABCDRead
HR16939doc 16940P 5.1.9 Ext. Status WordUINT32ABCDRead
HR18549doc 18550P 5.1.11 Active Fault NumberFirst entry of the active-fault array; 0 = none.UINT16Read
HR18559doc 18560P 5.1.12 Active Warning NumberFirst entry of the active-warning array; 0 = none.UINT16Read
HR49999doc 50000Control word (CTW)FC profile control word.BITMAP16Read/writebit 0 = Preset reference select LSB; bit 1 = Preset reference select MSB; bit 2 = 0 = DC brake, 1 = no DC brake (ramp); bit 3 = 0 = coast stop, 1 = no coast stop; bit 4 = 0 = quick stop, 1 = no quick stop; bit 5 = 0 = freeze output frequency, 1 = no freeze; bit 6 = 0 = ramp stop, 1 = start; bit 7 = Reset (on 0->1 edge); bit 8 = 1 = jog; bit 9 = 0 = ramp 1, 1 = ramp 2; bit 10 = 1 = data valid (0 = control word ignored); bit 11 = 1 = relay 1 on (if relay set to control word bit 11); bit 13 = Set-up select (0 = set-up 1, 1 = set-up 2); bit 15 = 1 = reversing
HR50009doc 50010Bus reference (REF)Signed; 16384 (4000h) = 100% of the reference range.INT16Read/write
HR50199doc 50200Status word (STW)FC profile status word.BITMAP16Readbit 0 = Control ready; bit 1 = Drive ready; bit 2 = 1 = enable (0 = coasting); bit 3 = Trip; bit 4 = Error (no trip); bit 6 = Triplock; bit 7 = Warning; bit 8 = Speed = reference; bit 9 = 1 = bus control (0 = local operation); bit 10 = Frequency within limits; bit 11 = In operation; bit 12 = Stopped, auto start (overtemperature); bit 13 = DC voltage limit exceeded; bit 14 = Current limit exceeded; bit 15 = Thermal timer exceeded
HR50209doc 50210Main actual value (MAV)Actual output frequency, scaled like REF (4000h = 100%).INT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Danfoss iC2-Micro frequency converter (Modbus RTU)

What Modbus registers does the Danfoss iC2-Micro frequency converter (Modbus RTU) have?

This map lists 29 registers: 1 coil, 28 holding registers. 16 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Danfoss iC2-Micro frequency converter (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers derived from parameter numbers. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed 1-based (40001 is sent as 0000). A parameter's register is 10 x its parameter number (PNU), sent minus 1: P 5.5.3.3 (PNU 303) is register 3030, read at address 3029 (0x0BD5) in the guide's own example. CTW 50000, REF 50010, STW 50200 and MAV 50210 follow the same minus-1 rule. Coil 65 is sent as 64.

What byte order does the Danfoss iC2-Micro frequency converter (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Danfoss iC2-Micro frequency converter (Modbus RTU)?

Start with HR 49999 Control word (CTW) (CTW: start/stop/reset); HR 50009 Bus reference (REF) (REF: speed reference, 4000h = 100%); HR 50199 Status word (STW) (STW: ready/running/trip/warning); HR 50209 Main actual value (MAV) (MAV: output frequency, 4000h = 100%); HR 16899 P 5.1.1 Fault Word 1 (P 5.1.1 Fault word 1); HR 16919 P 5.1.4 Warning Word 1 (P 5.1.4 Warning word 1); HR 18549 P 5.1.11 Active Fault Number (P 5.1.11 Active fault number).

How do I enable Modbus control of the Danfoss iC2-Micro frequency converter (Modbus RTU)?

P 10.1.1 Protocol = [2] Modbus RTU ([26] emulates the VLT Micro Drive FC 51 parameter format), P 10.1.2 address 1-247, P 10.1.3 baud, P 10.1.4 parity. P 5.5.1.1 Control Place Selection decides whether digital inputs, the control word or both are used; P 5.5.1.2 Control Source must be FC Port. STW bit 9 must be 1 (not local) for bus control.

What happens when the Danfoss iC2-Micro frequency converter (Modbus RTU) loses Modbus communication?

P 5.2.16 Watchdog Response (default Off; Freeze output, Stop, Jogging, Max. speed, Stop and trip, Qstop and trip, set-up select, Trip) runs when no telegram arrives within P 5.2.17 Watchdog Delay (0.5-6000.0 s, default 1.0 s).

Where is the official Danfoss iC2-Micro frequency converter (Modbus RTU) Modbus documentation?

The source is Application Guide iC2-Micro Frequency Converters (AB413939445838en-000401 (130R1254)), revision 2025-12, published free by Danfoss at https://assets.danfoss.com/documents/560863/AB413939445838en-000401.pdf.