NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

NORD's SK 540E/545E inverters answer Modbus RTU on the same RS485 interface as USS, switching protocol automatically. Every parameter is reached at (parameter number x 64 + array index), so the hidden process-data arrays P050 (control word and setpoints) and P051 (status word and actual values) give the cyclic control block. This map covers that process data and the bus setup parameters.

This page lists 12 Modbus registers for the NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU) — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from NORD Drivesystems’s own free documentation (linked below) and checked against it.

Manufacturer
NORD Drivesystems
Model
SK 540E / SK 545E frequency inverter (built-in Modbus RTU)
Equipment type
Variable frequency drive
Registers
12 (8 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
38400 baud, 8E1
Documented addressing
hexadecimal, 0-based
32-bit word order
ABCD high word first (big-endian)
Also known as
SK 540E, SK 545E, SK 54xE, NORDAC SK 500E series (SK 540E and above)
Source document
BU 0050 USS Bus modules and MODBUS RTU - Supplementary manual for NORD frequency inverters · BU 0050 GB-3111 · rev. 2011-08
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU)

Integration in brief

Set P509 = 2 and P510[-01] = 2, P512 to 1 or 3-30, P511 to 38400 or less, then write 0x047E and next 0x047F to P050[-01] (0x0C80) with setpoint 1 at 0x0C81 (16384 = P105). Poll 0x0CC0-0x0CC3 for status word and actual values.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 3200Process data IN: control word (STW)BITMAP16Control word STWRead/write
HR 3201Process data IN: setpoint 1INT16Setpoint 1 (16384 = 100 %)Read/write
HR 3264Process data OUT: status word (ZSW)BITMAP16Status word ZSWRead
HR 3265Process data OUT: actual value 1INT16Actual value 1 (frequency %)Read
HR 32576P509 Control word sourceUINT16P509 control word sourceRead/write
HR 32768P512 USS / Modbus addressUINT16P512 bus addressRead/write

Enable Modbus control & writes

Set P509 = 2 (USS control word; Modbus is detected automatically on SK 540E+) and P510[-01] = 2 for the setpoint. Set P512 to 1 or 3-30 (factory 0 is the broadcast address, and address 2 must not be used: it stops the automatic switch to Modbus) and P511 baud (Modbus max 38400). The format is fixed at 8 data bits, even parity, 1 stop bit.

Communication loss & watchdog

P513 telegram downtime: monitoring starts with the first valid telegram; if no new telegram arrives in time the inverter trips with E010 (error 10.0 Bus Time Out). 0.0 = off (factory); -0.1 = no error even if communication is lost.

Byte order & addressing

Network setup

Watch out for

NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

12 of 12 shown
NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR3200doc 0x0C80 (P050[-01])Process data IN: control word (STW)Needs P509 = 2. 0x047E = ready, 0x047F = run.BITMAP16Read/writebit 0 = 1 = ON (ready), 0 = OFF1 ramp stop; bit 1 = 0 = OFF2 (output off, switch-on disabled); bit 2 = 0 = OFF3 quick stop; bit 3 = 1 = enable operation; bit 4 = 1 = enable ramp generator (0 = ramp to zero); bit 5 = 1 = release ramp (0 = hold frequency); bit 6 = 1 = enable setpoint; bit 7 = Fault acknowledge on 0->1; bit 8 = Bus bit 8 (function in P480); bit 9 = Bus bit 9 (function in P480); bit 10 = 1 = process data valid; bit 11 = Rotation right; bit 12 = Rotation left; bit 14 = Parameter set select bit 0; bit 15 = Parameter set select bit 1
HR3201doc 0x0C81 (P050[-02])Process data IN: setpoint 1Default setpoint frequency: 16384 = 100 % of P105 max frequency.INT16Read/write
HR3202doc 0x0C82 (P050[-03])Process data IN: setpoint 2Function set in P546[-02].INT16Read/write
HR3203doc 0x0C83 (P050[-04])Process data IN: setpoint 3Function set in P546[-03].INT16Read/write
HR3264doc 0x0CC0 (P051[-01])Process data OUT: status word (ZSW)0x0B31 = ready for switch-on.BITMAP16Readbit 0 = Ready to start; bit 1 = Ready for operation; bit 2 = Operation enabled; bit 3 = Fault; bit 4 = 0 = OFF2 active; bit 5 = 0 = OFF3 active; bit 6 = Starting disabled; bit 7 = Warning; bit 8 = Actual value OK (setpoint reached); bit 9 = Guidance requested from master; bit 10 = Bus bit 10 (function in P481); bit 11 = Rotation right; bit 12 = Rotation left; bit 13 = Bus bit 13 (function in P481); bit 14 = Active parameter set bit 0; bit 15 = Active parameter set bit 1
HR3265doc 0x0CC1 (P051[-02])Process data OUT: actual value 1Default actual frequency: 16384 = 100 % of nominal.INT16Read
HR3266doc 0x0CC2 (P051[-03])Process data OUT: actual value 2Function set in P543[-02].INT16Read
HR3267doc 0x0CC3 (P051[-04])Process data OUT: actual value 3Function set in P543[-03].INT16Read
HR32576doc P509P509 Control word sourceSet 2 for Modbus (protocol detected automatically).UINT16Read/write0 = Control terminals or keypad; 1 = Control terminals only; 2 = USS / Modbus RTU control word
HR32640doc P510[-01]P510[-01] Main setpoint sourceUINT16Read/write0 = Auto (follows P509); 1 = Control terminals; 2 = USS / Modbus RTU; 3 = CAN; 4 = Profibus; 5 = InterBus; 6 = CANopen; 7 = DeviceNet; 8 = EtherCAT; 9 = CAN broadcast; 10 = CANopen broadcast
HR32704doc P511P511 USS / Modbus baud rateFactory 3 = 38400; Modbus allows 38400 max.UINT16Read/write0 = 4800; 1 = 9600; 2 = 19200; 3 = 38400; 4 = 57600 (SK 54xE); 5 = 115200 (SK 54xE); 6 = 230400 (SK 54xE); 7 = 460800 (SK 54xE)
HR32768doc P512P512 USS / Modbus address0-30, factory 0 (broadcast); use 1 or 3-30, never 2.UINT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU)

What Modbus registers does the NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU) have?

This map lists 12 registers: 12 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The start address is the parameter number in bits 6-15 and the array index (or parameter set) in bits 0-5, sent as-is: P102 parameter set 1 = 0x1980, set 2 = 0x1981; P510 array element 2 = 0x7F81. The manual's examples read P051 from 0x0CC0 (status word + 3 actual values) and write setpoints 1-3 from 0x0C81. Registers here use index 0 (first element / parameter set 1).

What are the minimum Modbus registers to integrate the NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU)?

Start with HR 3200 Process data IN: control word (STW) (Control word STW); HR 3201 Process data IN: setpoint 1 (Setpoint 1 (16384 = 100 %)); HR 3264 Process data OUT: status word (ZSW) (Status word ZSW); HR 3265 Process data OUT: actual value 1 (Actual value 1 (frequency %)); HR 32576 P509 Control word source (P509 control word source); HR 32768 P512 USS / Modbus address (P512 bus address).

How do I enable Modbus control of the NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU)?

Set P509 = 2 (USS control word; Modbus is detected automatically on SK 540E+) and P510[-01] = 2 for the setpoint. Set P512 to 1 or 3-30 (factory 0 is the broadcast address, and address 2 must not be used: it stops the automatic switch to Modbus) and P511 baud (Modbus max 38400). The format is fixed at 8 data bits, even parity, 1 stop bit.

What happens when the NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU) loses Modbus communication?

P513 telegram downtime: monitoring starts with the first valid telegram; if no new telegram arrives in time the inverter trips with E010 (error 10.0 Bus Time Out). 0.0 = off (factory); -0.1 = no error even if communication is lost.

Where is the official NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU) Modbus documentation?

The source is BU 0050 USS Bus modules and MODBUS RTU - Supplementary manual for NORD frequency inverters (BU 0050 GB-3111), revision 2011-08, published free by NORD Drivesystems at https://media.nord.com/res/Document/60557.pdf.

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: BU 0050 USS Bus modules and MODBUS RTU - Supplementary manual for NORD frequency inverters · BU 0050 GB-3111 · rev. 2011-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.