- SK 540E / SK 545E frequency inverter (built-in Modbus RTU)
Variable frequency drive · Modbus register map
NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU) Modbus register map
Updated 17 November 2026
NORD's SK 540E/545E inverters answer Modbus RTU on the same RS485 interface as USS, switching protocol automatically. Every parameter is reached at (parameter number x 64 + array index), so the hidden process-data arrays P050 (control word and setpoints) and P051 (status word and actual values) give the cyclic control block. This map covers that process data and the bus setup parameters.
This page lists 12 Modbus registers for the NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU) — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from NORD Drivesystems’s own free documentation (linked below) and checked against it.
- Manufacturer
- NORD Drivesystems
- Model
- SK 540E / SK 545E frequency inverter (built-in Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 12 (8 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 38400 baud, 8E1
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- SK 540E, SK 545E, SK 54xE, NORDAC SK 500E series (SK 540E and above)
Integration notes: NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU)
Set P509 = 2 and P510[-01] = 2, P512 to 1 or 3-30, P511 to 38400 or less, then write 0x047E and next 0x047F to P050[-01] (0x0C80) with setpoint 1 at 0x0C81 (16384 = P105). Poll 0x0CC0-0x0CC3 for status word and actual values.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 3200 | Process data IN: control word (STW) | BITMAP16 | Control word STW | Read/write |
| HR 3201 | Process data IN: setpoint 1 | INT16 | Setpoint 1 (16384 = 100 %) | Read/write |
| HR 3264 | Process data OUT: status word (ZSW) | BITMAP16 | Status word ZSW | Read |
| HR 3265 | Process data OUT: actual value 1 | INT16 | Actual value 1 (frequency %) | Read |
| HR 32576 | P509 Control word source | UINT16 | P509 control word source | Read/write |
| HR 32768 | P512 USS / Modbus address | UINT16 | P512 bus address | Read/write |
Enable Modbus control & writes
Set P509 = 2 (USS control word; Modbus is detected automatically on SK 540E+) and P510[-01] = 2 for the setpoint. Set P512 to 1 or 3-30 (factory 0 is the broadcast address, and address 2 must not be used: it stops the automatic switch to Modbus) and P511 baud (Modbus max 38400). The format is fixed at 8 data bits, even parity, 1 stop bit.
Communication loss & watchdog
P513 telegram downtime: monitoring starts with the first valid telegram; if no new telegram arrives in time the inverter trips with E010 (error 10.0 Bus Time Out). 0.0 = off (factory); -0.1 = no error even if communication is lost.
Byte order & addressing
- Addresses are parameter x 64 + index, not the parameter number: P509 = 32576.
- Control word follows the USS/PROFIdrive pattern: 0x047E = ready for switch-on, then set bit 0 (0x047F) to run; bit 10 must be 1 or the process data is ignored.
- Address 2 disables Modbus (the port stays USS).
Network setup
- Connect RS485 on terminals X7:73/74 (SK 520E and above) or the RJ12 socket X11; switch on the termination with DIP 1 at the bus ends.
- Up to 32 devices per RS485 segment; RS232 only for point-to-point.
Watch out for
- Baud rates above 38400 exist in P511 but are not valid for Modbus.
- If a digital input is set for fault acknowledge, do not hold control-word bit 7 at 1 from the bus, or the edge detection stops working.
NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 3200doc 0x0C80 (P050[-01]) | Process data IN: control word (STW) | Needs P509 = 2. 0x047E = ready, 0x047F = run. | BITMAP16 | Read/write | bit 0 = 1 = ON (ready), 0 = OFF1 ramp stop; bit 1 = 0 = OFF2 (output off, switch-on disabled); bit 2 = 0 = OFF3 quick stop; bit 3 = 1 = enable operation; bit 4 = 1 = enable ramp generator (0 = ramp to zero); bit 5 = 1 = release ramp (0 = hold frequency); bit 6 = 1 = enable setpoint; bit 7 = Fault acknowledge on 0->1; bit 8 = Bus bit 8 (function in P480); bit 9 = Bus bit 9 (function in P480); bit 10 = 1 = process data valid; bit 11 = Rotation right; bit 12 = Rotation left; bit 14 = Parameter set select bit 0; bit 15 = Parameter set select bit 1 | |||
| HR | 3201doc 0x0C81 (P050[-02]) | Process data IN: setpoint 1 | Default setpoint frequency: 16384 = 100 % of P105 max frequency. | INT16 | Read/write | ||||
| HR | 3202doc 0x0C82 (P050[-03]) | Process data IN: setpoint 2 | Function set in P546[-02]. | INT16 | Read/write | ||||
| HR | 3203doc 0x0C83 (P050[-04]) | Process data IN: setpoint 3 | Function set in P546[-03]. | INT16 | Read/write | ||||
| HR | 3264doc 0x0CC0 (P051[-01]) | Process data OUT: status word (ZSW) | 0x0B31 = ready for switch-on. | BITMAP16 | Read | bit 0 = Ready to start; bit 1 = Ready for operation; bit 2 = Operation enabled; bit 3 = Fault; bit 4 = 0 = OFF2 active; bit 5 = 0 = OFF3 active; bit 6 = Starting disabled; bit 7 = Warning; bit 8 = Actual value OK (setpoint reached); bit 9 = Guidance requested from master; bit 10 = Bus bit 10 (function in P481); bit 11 = Rotation right; bit 12 = Rotation left; bit 13 = Bus bit 13 (function in P481); bit 14 = Active parameter set bit 0; bit 15 = Active parameter set bit 1 | |||
| HR | 3265doc 0x0CC1 (P051[-02]) | Process data OUT: actual value 1 | Default actual frequency: 16384 = 100 % of nominal. | INT16 | Read | ||||
| HR | 3266doc 0x0CC2 (P051[-03]) | Process data OUT: actual value 2 | Function set in P543[-02]. | INT16 | Read | ||||
| HR | 3267doc 0x0CC3 (P051[-04]) | Process data OUT: actual value 3 | Function set in P543[-03]. | INT16 | Read | ||||
| HR | 32576doc P509 | P509 Control word source | Set 2 for Modbus (protocol detected automatically). | UINT16 | Read/write | 0 = Control terminals or keypad; 1 = Control terminals only; 2 = USS / Modbus RTU control word | |||
| HR | 32640doc P510[-01] | P510[-01] Main setpoint source | UINT16 | Read/write | 0 = Auto (follows P509); 1 = Control terminals; 2 = USS / Modbus RTU; 3 = CAN; 4 = Profibus; 5 = InterBus; 6 = CANopen; 7 = DeviceNet; 8 = EtherCAT; 9 = CAN broadcast; 10 = CANopen broadcast | ||||
| HR | 32704doc P511 | P511 USS / Modbus baud rate | Factory 3 = 38400; Modbus allows 38400 max. | UINT16 | Read/write | 0 = 4800; 1 = 9600; 2 = 19200; 3 = 38400; 4 = 57600 (SK 54xE); 5 = 115200 (SK 54xE); 6 = 230400 (SK 54xE); 7 = 460800 (SK 54xE) | |||
| HR | 32768doc P512 | P512 USS / Modbus address | 0-30, factory 0 (broadcast); use 1 or 3-30, never 2. | UINT16 | Read/write |
Notes on this map
- This manual offers Modbus RTU only on SK 540E and SK 545E; the other series it covers (SK 300E, rest of SK 500E, SK 700E/750E) use USS on this interface.
- Each 16-bit parameter is one address; read normally takes one parameter per request, except P050/P051 whose four elements can be read or written together. 32-bit parameters must be written with function 16; the manual's example writes P613 = 0x00123456 as 00 12 then 34 56, i.e. high word first.
- Setpoints and actual values are relative: 16384 (0x4000) = 100 %, 0xC000 = -100 %, range about +/-200 %; setpoint 100 % = P105 maximum frequency of the active parameter set. They are kept raw.
- Bus I/O coils 0x0000-0x0007 (Bus IO In 1-8, R/W) and 0x0008-0x000F (Bus IO Out 1-8, R) work only when P480/P481 assign them and P509/P510 are set to control terminals; they are not listed.
- Left out: P513 telegram timeout (the manual gives 0.1 s steps on the keypad but no bus scaling), P543-P548 function lists, and fault parameters P700/P701 (array format not described in this manual).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU)
What Modbus registers does the NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU) have?
This map lists 12 registers: 12 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The start address is the parameter number in bits 6-15 and the array index (or parameter set) in bits 0-5, sent as-is: P102 parameter set 1 = 0x1980, set 2 = 0x1981; P510 array element 2 = 0x7F81. The manual's examples read P051 from 0x0CC0 (status word + 3 actual values) and write setpoints 1-3 from 0x0C81. Registers here use index 0 (first element / parameter set 1).
What are the minimum Modbus registers to integrate the NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU)?
Start with HR 3200 Process data IN: control word (STW) (Control word STW); HR 3201 Process data IN: setpoint 1 (Setpoint 1 (16384 = 100 %)); HR 3264 Process data OUT: status word (ZSW) (Status word ZSW); HR 3265 Process data OUT: actual value 1 (Actual value 1 (frequency %)); HR 32576 P509 Control word source (P509 control word source); HR 32768 P512 USS / Modbus address (P512 bus address).
How do I enable Modbus control of the NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU)?
Set P509 = 2 (USS control word; Modbus is detected automatically on SK 540E+) and P510[-01] = 2 for the setpoint. Set P512 to 1 or 3-30 (factory 0 is the broadcast address, and address 2 must not be used: it stops the automatic switch to Modbus) and P511 baud (Modbus max 38400). The format is fixed at 8 data bits, even parity, 1 stop bit.
What happens when the NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU) loses Modbus communication?
P513 telegram downtime: monitoring starts with the first valid telegram; if no new telegram arrives in time the inverter trips with E010 (error 10.0 Bus Time Out). 0.0 = off (factory); -0.1 = no error even if communication is lost.
Where is the official NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU) Modbus documentation?
The source is BU 0050 USS Bus modules and MODBUS RTU - Supplementary manual for NORD frequency inverters (BU 0050 GB-3111), revision 2011-08, published free by NORD Drivesystems at https://media.nord.com/res/Document/60557.pdf.
Other variable frequency drives register maps
- Actuator / valve driver (I/O module, 3 analog outputs)
Seneca Z-3AO 3-channel analog output module
Seneca Z-3AO DIN-rail module with three voltage/current outputs and RS-485 Modbus RTU, per user manual MI00260-2-EN.
Also known as: Z-3AO - Variable frequency drive
TECO-Westinghouse E510 Compact (E510N1) inverter (Modbus RTU/ASCII)
TECO-Westinghouse E510 Compact (E510N1) inverters with the built-in RS-485 port (CON2), per communication addendum DOCUMENT-TECO-E510N1-AC002 Ver01 (2017-08).
Also known as: E510N1, E510s, TECO E510 Compact - Variable frequency drive
Vacon VACON 10 AC drive (built-in Modbus RTU)
VACON 10 micro drives on the built-in RS-485 Modbus RTU port, per complete user manual DPD00717F1 (software FW0135V010).
Also known as: VACON 10, Vacon 10, VACON0010 - Variable frequency drive
Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa FP605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per technical reference SIEPC7106171F.
Also known as: CIPR-FP6, FP605 drive, FP605 AC Drive for Industrial Fan and Pump Applications - Variable frequency drive (pump)
Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU
Legacy Yaskawa iQpump drives built on the P7U platform (CIMR-P7U...), per user manual TM.iQp.01, using the built-in RS-422/485 terminals R+/R-/S+/S-.
Also known as: iQpump, CIMR-P7U iQpump, iQpump Drive - Variable frequency drive (fan / pump)
Yaskawa P7 fan/pump drive (CIMR-P7U, legacy) - Modbus RTU
Yaskawa P7 (CIMR-P7U) fan and pump drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.P7.01 Appendix D.
Also known as: CIMR-P7U, P7U, P7 Drive
All variable frequency drives Modbus register maps →
Source: BU 0050 USS Bus modules and MODBUS RTU - Supplementary manual for NORD frequency inverters · BU 0050 GB-3111 · rev. 2011-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.