TECO-Westinghouse E510 Compact (E510N1) inverter (Modbus RTU/ASCII) Modbus register map
Updated 17 November 2026
The E510 Compact is the newer TECO-Westinghouse compact inverter with a built-in RS-485 port speaking Modbus RTU or ASCII (BACnet objects are also described). Commands, frequency, torque and speed limit are written to 2501H-2504H; status, fault and alarm codes and monitors are read from 2520H-252FH. Each parameter nn-mm has its own register, with the group in the high byte and the number in the low byte.
This page lists 15 Modbus registers for the TECO-Westinghouse E510 Compact (E510N1) inverter (Modbus RTU/ASCII) — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from TECO-Westinghouse’s own free documentation (linked below) and checked against it.
- Manufacturer
- TECO-Westinghouse
- Model
- E510 Compact (E510N1) inverter (Modbus RTU/ASCII)
- Equipment type
- Variable frequency drive
- Registers
- 15 (4 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- Not stated
- Documented addressing
- hexadecimal, 0-based
- Also known as
- E510N1, E510s, TECO E510 Compact
Integration notes: TECO-Westinghouse E510 Compact (E510N1) inverter (Modbus RTU/ASCII)
Set the node address and serial parameters and select communication as run/frequency source, then write 2501H and 2502H (0.01 Hz) and poll 2520H-2528H.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 9473 | Operation signal | BITMAP16 | Run/stop, direction, reset | Read/write |
| HR 9474 | Frequency command | UINT16 | Frequency command 0.01 Hz | Read/write |
| HR 9504 | State signal | BITMAP16 | Status bits | Read |
| HR 9505 | Error description | UINT16 | Fault code | Read |
| HR 9508 | Output frequency | UINT16 | Output frequency | Read |
| HR 9511 | Output current | UINT16 | Output current | Read |
| HR 9512 | Alarm description | UINT16 | Alarm code | Read |
Enable Modbus control & writes
Set node address and communication settings at the keypad and select communication as run and frequency source (parameter numbers are in the drive manual, not this addendum). Bit 15 of 2501H with 2503H gives torque control by communication.
Byte order & addressing
- Registers are hex: 2520H is sent as 25 20.
- Functions 03H, 06H, 08H and 10H; maximum frame 80 bytes.
- Node addresses 01H-FEH; 00H is broadcast.
- Write 0 to unused bits and never write reserved registers.
Network setup
- RS-485 on CON2 (RJ45): pin 1 or 3 = S+, pin 2 or 6 = S-.
- 120 ohm, 1/4 W terminators at both ends of the line.
Watch out for
- Exception codes: 01 function, 02 register number, 03 number, 04 data setting, 05 write mode error.
- Inverter response time is about 10 ms.
TECO-Westinghouse E510 Compact (E510N1) inverter (Modbus RTU/ASCII) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 9473doc 2501H | Operation signal | Run, direction, fault, reset, comm inputs S1-S6, inverter/torque mode. | BITMAP16 | Read/write | bit 0 = Run (0 stop); bit 1 = Reverse (0 forward); bit 2 = External fault; bit 3 = Fault reset; bit 6 = Comm input S1; bit 7 = Comm input S2; bit 8 = Comm input S3; bit 9 = Comm input S4; bit 10 = Comm input S5; bit 11 = Comm input S6; bit 14 = Inverter mode; bit 15 = Torque command set by communication | |||
| HR | 9474doc 2502H | Frequency command | UINT16 | × 0.01 | Hz | Read/write | |||
| HR | 9475doc 2503H | Torque command | +/-8192 = +/-100 % of rated torque. | INT16 | × 0.0122070312 | % | Read/write | ||
| HR | 9476doc 2504H | Speed limit | +/-120 = +/-120 %. | INT16 | % | Read/write | |||
| HR | 9504doc 2520H | State signal | BITMAP16 | Read | bit 0 = Running; bit 1 = Reverse; bit 2 = Inverter ready; bit 3 = Fault active; bit 4 = Warning; bit 5 = Zero speed; bit 6 = Is 440 V; bit 7 = Frequency agree; bit 8 = Set frequency agree; bit 9 = Frequency detection 1; bit 10 = Frequency detection 2; bit 11 = Under voltage; bit 12 = Baseblock; bit 13 = Frequency reference not from comm; bit 14 = Sequence not from comm; bit 15 = Over torque | ||||
| HR | 9505doc 2521H | Error description | Active fault code. | UINT16 | Read | 1 = UV; 2 = OC; 3 = OV; 4 = OH1; 5 = OL1; 6 = OL2; 7 = OT; 8 = UT; 9 = SC; 10 = Ground OC; 12 = Input phase loss; 13 = Output phase loss; 17 = External fault 01; 18 = External fault 02; 19 = External fault 03; 20 = External fault 04; 21 = External fault 05; 22 = External fault 06; 25 = PID feedback error; 26 = Keypad removed; 28 = CE; 29 = STO1; 30 = Over torque 2; 37 = LSCFT (Rtry); 38 = CF07; 41 = OLDOP; 44 = FBLSS; 46 = OH4; 47 = SS1; 48 = CF20; 49 = MtrSw DI motor switch fault; 50 = OC_A; 51 = OC_D; 52 = OC_C; 53 = UD_C; 54 = CF_08; 55 = STO2; 56 = STO3; 57 = PO | |||
| HR | 9506doc 2522H | DI state | BITMAP16 | Read | bit 0 = Comm S1 on; bit 1 = Comm S2 on; bit 2 = Comm S3 on; bit 3 = Comm S4 on; bit 4 = Comm S5 on; bit 5 = Comm S6 on | ||||
| HR | 9507doc 2523H | Frequency command | UINT16 | × 0.01 | Hz | Read | |||
| HR | 9508doc 2524H | Output frequency | UINT16 | × 0.01 | Hz | Read | |||
| HR | 9510doc 2526H | DC voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 9511doc 2527H | Output current | UINT16 | × 0.1 | A | Read | |||
| HR | 9512doc 2528H | Alarm description | Active warning code. | UINT16 | Read | 0 = No alarm; 1 = OV; 2 = UV; 3 = OL2; 4 = OH2; 6 = OT; 9 = UT; 10 = OS; 11 = PGO; 12 = DEV; 13 = CE; 14 = CALL; 16 = EF0; 17 = EF1; 18 = EF2; 19 = EF3; 20 = EF4; 21 = EF5; 22 = EF6; 23 = EF7; 24 = EF8; 26 = CLB; 28 = CT; 29 = USP; 30 = RDE; 31 = WRE; 32 = FB; 33 = VRYE; 34 = SE01; 35 = SE02; 36 = SE03; 38 = SE05; 39 = HPERR; 40 = EF; 43 = RDP; 45 = OL1; 46 = HP_ER; 47 = SE10; 49 = BB1; 50 = BB2; 51 = BB3; 52 = BB4; 53 = BB5; 54 = BB6; 55 = BB7; 56 = BB8 | |||
| HR | 9516doc 252CH | AI1 input | UINT16 | × 0.1 | % | Read | |||
| HR | 9517doc 252DH | AI2 input | UINT16 | × 0.1 | % | Read | |||
| HR | 9519doc 252FH | Model check | Identifies L510(s)/E510(s)/A510(s)/F510. | UINT16 | Read |
Notes on this map
- The addendum does not name the drive parameters for node address, baud rate, parity or run/frequency source; set those per the E510 Compact manual.
- 2521H (faults) and 2528H (alarms) are code tables, mapped as enums.
- Left out: 2505H/252AH AO1 (range 0.00-10.00 V given, raw scale not stated), 2507H DO and 2529H digital output state (no bit list), 252FH value list.
- Parameter 12-00 is 32-bit (2510H high word, 2511H low word) but is a parameter, not a monitor, and is not listed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the TECO-Westinghouse E510 Compact (E510N1) inverter (Modbus RTU/ASCII)
What Modbus registers does the TECO-Westinghouse E510 Compact (E510N1) inverter (Modbus RTU/ASCII) have?
This map lists 15 registers: 15 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the TECO-Westinghouse E510 Compact (E510N1) inverter (Modbus RTU/ASCII) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and sent unchanged: the 03H example reads start register 01 23 (0123H) and the 06H example writes 01 02. Parameters map group to the high byte and number to the low byte (13-00 = 0D00H), except 12-00 which is a 32-bit value at 2510H (high word) / 2511H (low word).
What are the minimum Modbus registers to integrate the TECO-Westinghouse E510 Compact (E510N1) inverter (Modbus RTU/ASCII)?
Start with HR 9473 Operation signal (Run/stop, direction, reset); HR 9474 Frequency command (Frequency command 0.01 Hz); HR 9504 State signal (Status bits); HR 9505 Error description (Fault code); HR 9508 Output frequency (Output frequency); HR 9511 Output current (Output current); HR 9512 Alarm description (Alarm code).
How do I enable Modbus control of the TECO-Westinghouse E510 Compact (E510N1) inverter (Modbus RTU/ASCII)?
Set node address and communication settings at the keypad and select communication as run and frequency source (parameter numbers are in the drive manual, not this addendum). Bit 15 of 2501H with 2503H gives torque control by communication.
Where is the official TECO-Westinghouse E510 Compact (E510N1) inverter (Modbus RTU/ASCII) Modbus documentation?
The source is E510 Communication Addendum Modbus RTU/ASCII (E510N1) (DOCUMENT-TECO-E510N1-AC002 Ver01), revision 2017-08, published free by TECO-Westinghouse at https://tecowestinghouse.com/PDF/E510_Compact_comm_addendum.pdf.
More TECO-Westinghouse Modbus register maps
- Variable frequency drive
TECO-Westinghouse A510 inverter (Modbus RTU/ASCII)
TECO-Westinghouse A510 inverters using the built-in RS-485 port (CN6), per communication addendum DOCUMENT-TECO-A510-AC001 Ver01 (2015-04).
Also known as: TECO A510, A510s - Variable frequency drive
TECO-Westinghouse E510 inverter (Modbus RTU/ASCII)
TECO-Westinghouse E510 inverters using the built-in RS-485 port (CON2), per communication addendum DOCUMENT-TECO-E510-AC001 Ver01 (2015-03).
Also known as: TECO E510, E510 Communication Addendum - Variable frequency drive
TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII)
TECO-Westinghouse EV series micro inverters with the RS-485 option card, per the EV Inverter Series Modbus Communication Manual.
Also known as: TECO EV, EV Inverter Series - Variable frequency drive (HVAC fan / pump)
TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII)
TECO-Westinghouse F510 HVAC inverters using the built-in RS-485 port (CN6) in Modbus mode, per communication addendum DOCUMENT-TECO-F510-AC001 Ver01 (2015-03).
Also known as: TECO F510, F510 HVAC drive - Variable frequency drive
TECO-Westinghouse L510 inverter (Modbus RTU/ASCII)
TECO-Westinghouse L510 micro inverters with the RS-485 option card, per communication addendum DOCUMENT-TECO-L510-AC001 Ver01 (2015-06).
Also known as: TECO L510, L510 Communication Addendum
Other variable frequency drives register maps
- Variable frequency drive
Vacon VACON 10 AC drive (built-in Modbus RTU)
VACON 10 micro drives on the built-in RS-485 Modbus RTU port, per complete user manual DPD00717F1 (software FW0135V010).
Also known as: VACON 10, Vacon 10, VACON0010 - Variable frequency drive
Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa FP605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per technical reference SIEPC7106171F.
Also known as: CIPR-FP6, FP605 drive, FP605 AC Drive for Industrial Fan and Pump Applications - Variable frequency drive (pump)
Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU
Legacy Yaskawa iQpump drives built on the P7U platform (CIMR-P7U...), per user manual TM.iQp.01, using the built-in RS-422/485 terminals R+/R-/S+/S-.
Also known as: iQpump, CIMR-P7U iQpump, iQpump Drive - Variable frequency drive (fan / pump)
Yaskawa P7 fan/pump drive (CIMR-P7U, legacy) - Modbus RTU
Yaskawa P7 (CIMR-P7U) fan and pump drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.P7.01 Appendix D.
Also known as: CIMR-P7U, P7U, P7 Drive - Variable frequency drive
Yaskawa Z1000U HVAC matrix drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000U HVAC matrix drives using the built-in serial terminals with H5-08 = 0 (MEMOBUS/Modbus), per programming manual SIEP C710636 10D.
Also known as: Z1000U HVAC MATRIX Drive, Z1000U Matrix - Variable frequency drive
ABB ACS355 machinery drive (embedded Modbus RTU)
ACS355 drives with firmware 5.110 or later using the embedded fieldbus (Modbus RTU) over an FMBA-01 adapter on terminal X3 (EIA-485) or the panel port (RS-232).
Also known as: ACS355-01E, ACS355-03E, ACS355-01U, ACS355-03U, ACS355 with FMBA-01
All variable frequency drives Modbus register maps →
Source: E510 Communication Addendum Modbus RTU/ASCII (E510N1) · DOCUMENT-TECO-E510N1-AC002 Ver01 · rev. 2017-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.