Variable frequency drive · Modbus register map
TECO-Westinghouse L510 inverter (Modbus RTU/ASCII) Modbus register map
Updated 17 November 2026
The L510 is TECO-Westinghouse's micro inverter; with its RS-485 option card it speaks Modbus RTU or ASCII. Run/stop and frequency are written to hex registers 2501H/2502H, status and monitors are read from 2520H-252FH, and each parameter nn-mm has its own register (group in the high byte, number in the low byte). This map covers the command and monitor tables.
This page lists 12 Modbus registers for the TECO-Westinghouse L510 inverter (Modbus RTU/ASCII) — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from TECO-Westinghouse’s own free documentation (linked below) and checked against it.
- Manufacturer
- TECO-Westinghouse
- Model
- L510 inverter (Modbus RTU/ASCII)
- Equipment type
- Variable frequency drive
- Registers
- 12 (2 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- Not stated
- Documented addressing
- hexadecimal, 0-based
- Also known as
- TECO L510, L510 Communication Addendum
Integration notes: TECO-Westinghouse L510 inverter (Modbus RTU/ASCII)
Fit the RS-485 option card, set node address and serial settings and select communication as run/frequency source in the L510 parameters, then write 2501H and 2502H and poll 2520H-2527H.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 9473 | Operation signal | BITMAP16 | Run/stop, direction, reset | Read/write |
| HR 9474 | Frequency command | UINT16 | Frequency command | Read/write |
| HR 9504 | State signal | BITMAP16 | Run/ready/fault status | Read |
| HR 9505 | Error description | UINT16 | Error code | Read |
| HR 9508 | Output frequency | UINT16 | Output frequency | Read |
| HR 9511 | Output current | UINT16 | Output current | Read |
Enable Modbus control & writes
Install the RS-485 option card, then set the node address, communication parameters and run/frequency source at the keypad (parameter numbers are in the L510 manual, not this addendum).
Byte order & addressing
- Registers are hex: 2520H is sent as 25 20.
- Functions 03H, 06H, 08H and 10H; maximum frame 80 bytes.
- Node addresses 01H-FEH; 00H is broadcast.
- Write 0 to unused bits and never write reserved registers.
Network setup
- RS-485 via the L510 option card, S+ / S-.
- Up to 31 inverters per network; 120 ohm terminators at both ends.
Watch out for
- Exception codes: 01 function, 02 register number, 03 number, 04 data setting error.
- Inverter response time is about 10 ms.
TECO-Westinghouse L510 inverter (Modbus RTU/ASCII) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 9473doc 2501H | Operation signal | Run/stop, direction, EFO, reset, jog, comm inputs S1-S5, relay R1. | BITMAP16 | Read/write | bit 0 = Run (0 stop); bit 1 = Reverse (0 forward); bit 2 = Abnormal (EFO); bit 3 = Fault reset; bit 4 = Jog forward; bit 5 = Jog reverse; bit 6 = Comm input S1; bit 7 = Comm input S2; bit 8 = Comm input S3; bit 9 = Comm input S4; bit 10 = Comm input S5; bit 12 = Relay R1 on | |||
| HR | 9474doc 2502H | Frequency command | Scale not printed in the command table. | UINT16 | Read/write | ||||
| HR | 9504doc 2520H | State signal | BITMAP16 | Read | bit 0 = Running (0 stopped); bit 1 = Reverse (0 forward); bit 2 = Inverter ready; bit 3 = Fault; bit 4 = Data setting error | ||||
| HR | 9505doc 2521H | Error description | Active error code. | UINT16 | Read | 0 = Inverter OK; 1 = OH; 2 = OC; 3 = LV; 4 = OV; 6 = External BB (bb); 7 = CTER; 8 = PDER; 9 = EPR; 10 = ATER; 11 = OL3; 12 = OL510 inverter overload; 13 = OL1 motor overload; 14 = EFO; 15 = External bb (E.S.); 16 = LOC; 18 = OC-C; 19 = OC-A; 20 = OC-D; 21 = OC-S; 23 = LV-C; 24 = OV-C; 25 = OH-C; 26 = STP0; 27 = STP1; 28 = STP2; 29 = Err1; 30 = Err2; 31 = Err4; 32 = Err5; 33 = Err6; 34 = Err7; 35 = Err8; 38 = EPR1; 39 = EPR2; 40 = OVSP | |||
| HR | 9506doc 2522H | DI state | BITMAP16 | Read | bit 0 = Comm S1 on; bit 1 = Comm S2 on; bit 2 = Comm S3 on; bit 3 = Comm S4 on; bit 4 = Comm S5 on; bit 6 = Relay R1Y on | ||||
| HR | 9507doc 2523H | Frequency command | 100 = 1 Hz. | UINT16 | × 0.01 | Hz | Read | ||
| HR | 9508doc 2524H | Output frequency | 100 = 1 Hz. | UINT16 | × 0.01 | Hz | Read | ||
| HR | 9509doc 2525H | Output voltage | 10 = 1 V. | UINT16 | × 0.1 | V | Read | ||
| HR | 9510doc 2526H | DC voltage | 1 = 1 V. | UINT16 | V | Read | |||
| HR | 9511doc 2527H | Output current | 10 = 1 A. | UINT16 | × 0.1 | A | Read | ||
| HR | 9514doc 252AH | PID feedback | 10 = 1 %, 100 % = fmax. | UINT16 | × 0.1 | % | Read | ||
| HR | 9519doc 252FH | L510 identification | Reads 0x0110 (272). | UINT16 | Read |
Notes on this map
- The addendum does not name the drive parameters for node address, baud rate, parity or remote run/frequency source; set those per the L510 instruction manual.
- 2502H frequency command has no scale in the command table, so it is left unscaled (the read-back 2523H uses 100 = 1 Hz).
- 2521H is a code table (0-40), mapped as an enum.
- Left out: 252BH PID input (sign not stated) and 252CH/252DH AVI/ACI inputs (footnote *1 not explained). 2526H is labelled 'DC voltage command' in the table.
- The parameter register rule (group high byte, number low byte, hex) is not expanded into individual registers.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the TECO-Westinghouse L510 inverter (Modbus RTU/ASCII)
What Modbus registers does the TECO-Westinghouse L510 inverter (Modbus RTU/ASCII) have?
This map lists 12 registers: 12 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the TECO-Westinghouse L510 inverter (Modbus RTU/ASCII) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and sent unchanged: the 06H example writes start register 01 02 (0102H) and the 03H example reads 01 23 (0123H). Parameters map as group in the high byte and number in the low byte, e.g. 00-10 = 000AH, 01-17 = 0111H.
What are the minimum Modbus registers to integrate the TECO-Westinghouse L510 inverter (Modbus RTU/ASCII)?
Start with HR 9473 Operation signal (Run/stop, direction, reset); HR 9474 Frequency command (Frequency command); HR 9504 State signal (Run/ready/fault status); HR 9505 Error description (Error code); HR 9508 Output frequency (Output frequency); HR 9511 Output current (Output current).
How do I enable Modbus control of the TECO-Westinghouse L510 inverter (Modbus RTU/ASCII)?
Install the RS-485 option card, then set the node address, communication parameters and run/frequency source at the keypad (parameter numbers are in the L510 manual, not this addendum).
Where is the official TECO-Westinghouse L510 inverter (Modbus RTU/ASCII) Modbus documentation?
The source is L510 Communication Addendum Modbus RTU/ASCII (DOCUMENT-TECO-L510-AC001 Ver01), revision 2015-06, published free by TECO-Westinghouse at https://tecowestinghouse.com/PDF/L510_comm_addendum.pdf.
More TECO-Westinghouse Modbus register maps
- Variable frequency drive
TECO-Westinghouse A510 inverter (Modbus RTU/ASCII)
TECO-Westinghouse A510 inverters using the built-in RS-485 port (CN6), per communication addendum DOCUMENT-TECO-A510-AC001 Ver01 (2015-04).
Also known as: TECO A510, A510s - Variable frequency drive
TECO-Westinghouse E510 Compact (E510N1) inverter (Modbus RTU/ASCII)
TECO-Westinghouse E510 Compact (E510N1) inverters with the built-in RS-485 port (CON2), per communication addendum DOCUMENT-TECO-E510N1-AC002 Ver01 (2017-08).
Also known as: E510N1, E510s, TECO E510 Compact - Variable frequency drive
TECO-Westinghouse E510 inverter (Modbus RTU/ASCII)
TECO-Westinghouse E510 inverters using the built-in RS-485 port (CON2), per communication addendum DOCUMENT-TECO-E510-AC001 Ver01 (2015-03).
Also known as: TECO E510, E510 Communication Addendum - Variable frequency drive
TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII)
TECO-Westinghouse EV series micro inverters with the RS-485 option card, per the EV Inverter Series Modbus Communication Manual.
Also known as: TECO EV, EV Inverter Series - Variable frequency drive (HVAC fan / pump)
TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII)
TECO-Westinghouse F510 HVAC inverters using the built-in RS-485 port (CN6) in Modbus mode, per communication addendum DOCUMENT-TECO-F510-AC001 Ver01 (2015-03).
Also known as: TECO F510, F510 HVAC drive
Other variable frequency drives register maps
- Variable frequency drive (HVAC)
Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU
Yaskawa E7 (CIMR-E7U) HVAC fan and pump drives using the built-in RS-422/485 terminals with H5-08 = 0 (Memobus/Modbus), per Parameter Access Technical Manual TM.E7.11 (rev 3016).
Also known as: CIMR-E7U, E7U, E7 Drive - Variable frequency drive
Yaskawa HV305 HVAC micro drive (MEMOBUS/Modbus RTU)
Yaskawa HV305 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPYAIHV3001B.
Also known as: HV35U, HV305 drive, HV305 Versatile Compact Drive - Variable frequency drive
Yaskawa J1000 compact V/f drive (MEMOBUS/Modbus RTU)
Yaskawa J1000 drives (CIMR-JU/JC) with the optional RS-422/485 MEMOBUS/Modbus interface, per Technical Manual SIEP C710606 31D.
Also known as: CIMR-JU, CIMR-JC, J1000 Compact V/f Control Drive - Variable frequency drive
Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU
Yaskawa V7 (CIMR-V7AM) and V74X (CIMR-V7CU) compact drives with built-in Modbus RTU (keypad RJ-45 or R+/R-/S+/S- terminals), per TM.V7.11 Rev 07-01.
Also known as: CIMR-V7AM, CIMR-V7CU, V74X - Variable frequency drive
ABB ACQ580 water and wastewater drive (embedded Modbus RTU)
ACQ580 drives running the ACQ580 pump control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000035867 Rev H.
Also known as: ACQ580-01, ACQ580-04, ACQ580-07, ACQ580-31, ACQ580-34, ACQ580 pump control program - Variable frequency drive
ABB ACS580 general purpose drive (embedded Modbus RTU)
ACS580 drives running the ACS580 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default).
Also known as: ACS580-01, ACS580-04, ACS580-07, ACS580 standard control program
All variable frequency drives Modbus register maps →
Source: L510 Communication Addendum Modbus RTU/ASCII · DOCUMENT-TECO-L510-AC001 Ver01 · rev. 2015-06. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.