TECO-Westinghouse L510 inverter (Modbus RTU/ASCII) Modbus register map

Updated 17 November 2026

Short answer

The L510 is TECO-Westinghouse's micro inverter; with its RS-485 option card it speaks Modbus RTU or ASCII. Run/stop and frequency are written to hex registers 2501H/2502H, status and monitors are read from 2520H-252FH, and each parameter nn-mm has its own register (group in the high byte, number in the low byte). This map covers the command and monitor tables.

This page lists 12 Modbus registers for the TECO-Westinghouse L510 inverter (Modbus RTU/ASCII) — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from TECO-Westinghouse’s own free documentation (linked below) and checked against it.

Manufacturer
TECO-Westinghouse
Model
L510 inverter (Modbus RTU/ASCII)
Equipment type
Variable frequency drive
Registers
12 (2 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
Not stated
Documented addressing
hexadecimal, 0-based
Also known as
TECO L510, L510 Communication Addendum
Source document
L510 Communication Addendum Modbus RTU/ASCII · DOCUMENT-TECO-L510-AC001 Ver01 · rev. 2015-06
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: TECO-Westinghouse L510 inverter (Modbus RTU/ASCII)

Integration in brief

Fit the RS-485 option card, set node address and serial settings and select communication as run/frequency source in the L510 parameters, then write 2501H and 2502H and poll 2520H-2527H.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 9473Operation signalBITMAP16Run/stop, direction, resetRead/write
HR 9474Frequency commandUINT16Frequency commandRead/write
HR 9504State signalBITMAP16Run/ready/fault statusRead
HR 9505Error descriptionUINT16Error codeRead
HR 9508Output frequencyUINT16Output frequencyRead
HR 9511Output currentUINT16Output currentRead

Enable Modbus control & writes

Install the RS-485 option card, then set the node address, communication parameters and run/frequency source at the keypad (parameter numbers are in the L510 manual, not this addendum).

Byte order & addressing

Network setup

Watch out for

TECO-Westinghouse L510 inverter (Modbus RTU/ASCII) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

12 of 12 shown
TECO-Westinghouse L510 inverter (Modbus RTU/ASCII) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR9473doc 2501HOperation signalRun/stop, direction, EFO, reset, jog, comm inputs S1-S5, relay R1.BITMAP16Read/writebit 0 = Run (0 stop); bit 1 = Reverse (0 forward); bit 2 = Abnormal (EFO); bit 3 = Fault reset; bit 4 = Jog forward; bit 5 = Jog reverse; bit 6 = Comm input S1; bit 7 = Comm input S2; bit 8 = Comm input S3; bit 9 = Comm input S4; bit 10 = Comm input S5; bit 12 = Relay R1 on
HR9474doc 2502HFrequency commandScale not printed in the command table.UINT16Read/write
HR9504doc 2520HState signalBITMAP16Readbit 0 = Running (0 stopped); bit 1 = Reverse (0 forward); bit 2 = Inverter ready; bit 3 = Fault; bit 4 = Data setting error
HR9505doc 2521HError descriptionActive error code.UINT16Read0 = Inverter OK; 1 = OH; 2 = OC; 3 = LV; 4 = OV; 6 = External BB (bb); 7 = CTER; 8 = PDER; 9 = EPR; 10 = ATER; 11 = OL3; 12 = OL510 inverter overload; 13 = OL1 motor overload; 14 = EFO; 15 = External bb (E.S.); 16 = LOC; 18 = OC-C; 19 = OC-A; 20 = OC-D; 21 = OC-S; 23 = LV-C; 24 = OV-C; 25 = OH-C; 26 = STP0; 27 = STP1; 28 = STP2; 29 = Err1; 30 = Err2; 31 = Err4; 32 = Err5; 33 = Err6; 34 = Err7; 35 = Err8; 38 = EPR1; 39 = EPR2; 40 = OVSP
HR9506doc 2522HDI stateBITMAP16Readbit 0 = Comm S1 on; bit 1 = Comm S2 on; bit 2 = Comm S3 on; bit 3 = Comm S4 on; bit 4 = Comm S5 on; bit 6 = Relay R1Y on
HR9507doc 2523HFrequency command100 = 1 Hz.UINT16× 0.01HzRead
HR9508doc 2524HOutput frequency100 = 1 Hz.UINT16× 0.01HzRead
HR9509doc 2525HOutput voltage10 = 1 V.UINT16× 0.1VRead
HR9510doc 2526HDC voltage1 = 1 V.UINT16VRead
HR9511doc 2527HOutput current10 = 1 A.UINT16× 0.1ARead
HR9514doc 252AHPID feedback10 = 1 %, 100 % = fmax.UINT16× 0.1%Read
HR9519doc 252FHL510 identificationReads 0x0110 (272).UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the TECO-Westinghouse L510 inverter (Modbus RTU/ASCII)

What Modbus registers does the TECO-Westinghouse L510 inverter (Modbus RTU/ASCII) have?

This map lists 12 registers: 12 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the TECO-Westinghouse L510 inverter (Modbus RTU/ASCII) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and sent unchanged: the 06H example writes start register 01 02 (0102H) and the 03H example reads 01 23 (0123H). Parameters map as group in the high byte and number in the low byte, e.g. 00-10 = 000AH, 01-17 = 0111H.

What are the minimum Modbus registers to integrate the TECO-Westinghouse L510 inverter (Modbus RTU/ASCII)?

Start with HR 9473 Operation signal (Run/stop, direction, reset); HR 9474 Frequency command (Frequency command); HR 9504 State signal (Run/ready/fault status); HR 9505 Error description (Error code); HR 9508 Output frequency (Output frequency); HR 9511 Output current (Output current).

How do I enable Modbus control of the TECO-Westinghouse L510 inverter (Modbus RTU/ASCII)?

Install the RS-485 option card, then set the node address, communication parameters and run/frequency source at the keypad (parameter numbers are in the L510 manual, not this addendum).

Where is the official TECO-Westinghouse L510 inverter (Modbus RTU/ASCII) Modbus documentation?

The source is L510 Communication Addendum Modbus RTU/ASCII (DOCUMENT-TECO-L510-AC001 Ver01), revision 2015-06, published free by TECO-Westinghouse at https://tecowestinghouse.com/PDF/L510_comm_addendum.pdf.

More TECO-Westinghouse Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: L510 Communication Addendum Modbus RTU/ASCII · DOCUMENT-TECO-L510-AC001 Ver01 · rev. 2015-06. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.