Variable frequency drive (HVAC fan / pump) · Modbus register map

TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII) Modbus register map

Updated 17 November 2026

Short answer

The F510 is TECO-Westinghouse's HVAC fan and pump inverter; its RS-485 port supports Modbus RTU/ASCII as well as BACnet MS/TP and Metasys N2. Run/stop and frequency (0.01 Hz) are written to 2501H/2502H, and status, fault and warning codes and monitors are read from 2520H-252FH. Each parameter nn-mm has its own register, with the group in the high byte and the number in the low byte.

This page lists 15 Modbus registers for the TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII) — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from TECO-Westinghouse’s own free documentation (linked below) and checked against it.

Manufacturer
TECO-Westinghouse
Model
F510 HVAC fan/pump inverter (Modbus RTU/ASCII)
Equipment type
Variable frequency drive (HVAC fan / pump)
Registers
15 (4 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
Not stated
Documented addressing
hexadecimal, 0-based
Also known as
TECO F510, F510 HVAC drive
Source document
F510 Communication Addendum Modbus RTU/ASCII, BACnet, Metasys N2 · DOCUMENT-TECO-F510-AC001 Ver01 · rev. 2015-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII)

Integration in brief

Set the RS-485 protocol to Modbus, the node address and serial parameters, and select communication as run/frequency source, then write 2501H and 2502H (0.01 Hz) and poll 2520H-2528H.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 9473Operation signalBITMAP16Run/stop, direction, resetRead/write
HR 9474Frequency commandUINT16Frequency command 0.01 HzRead/write
HR 9504State signalBITMAP16Status bitsRead
HR 9505Error descriptionUINT16Fault codeRead
HR 9508Output frequencyUINT16Output frequencyRead
HR 9512Warning descriptionUINT16Warning codeRead

Enable Modbus control & writes

Select Modbus as the communication protocol (the port also does BACnet and Metasys N2), then set node address, serial settings and run/frequency source at the keypad per the F510 manual.

Byte order & addressing

Network setup

Watch out for

TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

15 of 15 shown
TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR9473doc 2501HOperation signalRun, direction, fault, reset, comm inputs S1-S6, inverter mode.BITMAP16Read/writebit 0 = Run (0 stop); bit 1 = Reverse (0 forward); bit 2 = External fault; bit 3 = Fault reset; bit 6 = Comm input S1; bit 7 = Comm input S2; bit 8 = Comm input S3; bit 9 = Comm input S4; bit 10 = Comm input S5; bit 11 = Comm input S6; bit 14 = Inverter mode
HR9474doc 2502HFrequency commandUINT16× 0.01HzRead/write
HR9477doc 2505HAO1 command0-1000 = 0.00-10.00 V or 4-20 mA.UINT16Read/write
HR9478doc 2506HAO2 command0-1000 = 0.00-10.00 V or 4-20 mA.UINT16Read/write
HR9504doc 2520HState signalBITMAP16Readbit 0 = Running; bit 1 = Reverse; bit 2 = Inverter ready; bit 3 = Fault; bit 4 = Warning; bit 5 = Zero speed; bit 6 = Is 440 V; bit 7 = Frequency agree; bit 8 = Set frequency agree; bit 9 = Frequency detection 1; bit 10 = Frequency detection 2; bit 11 = Under voltage; bit 12 = Baseblock; bit 13 = Frequency reference not from comm; bit 14 = Sequence not from comm; bit 15 = Over torque
HR9505doc 2521HError descriptionActive fault code.UINT16Read1 = UV; 2 = OC; 3 = OV; 4 = OH1; 5 = OL1; 6 = OL2; 7 = OT; 8 = UT; 9 = SC; 10 = Ground OC; 11 = Fuse blown; 12 = Input phase loss; 13 = Output phase loss; 17 = External fault 01; 18 = External fault 02; 19 = External fault 03; 20 = External fault 04; 21 = External fault 05; 22 = External fault 06; 25 = Feedback fault; 26 = Keypad removed; 27 = Modbus external fault; 28 = CE; 29 = STO; 36 = Low suction fault; 37 = Low suction fault (with retry); 38 = CF07; 39 = Low flow fault; 40 = High flow fault; 42 = Low pressure fault; 43 = High pressure fault; 44 = Feedback loss; 46 = Motor overheat (OH4)
HR9506doc 2522HDI stateBITMAP16Readbit 0 = Comm S1; bit 1 = Comm S2; bit 2 = Comm S3; bit 3 = Comm S4; bit 4 = Comm S5; bit 5 = Comm S6
HR9507doc 2523HFrequency commandRaw; unit not printed in the monitor table.UINT16Read
HR9508doc 2524HOutput frequencyRaw; unit not printed in the monitor table.UINT16Read
HR9510doc 2526HDC voltage commandRaw; unit not printed in the monitor table.UINT16Read
HR9511doc 2527HOutput currentRaw; unit not printed in the monitor table.UINT16Read
HR9512doc 2528HWarning descriptionActive warning code.UINT16Read0 = No alarm; 1 = OV; 2 = UV; 3 = OL2; 4 = OH2; 6 = OT; 9 = UT; 13 = CE; 16 = EF0; 17 = EF1; 18 = EF2; 19 = EF3; 20 = EF4; 21 = EF5; 22 = EF6; 25 = CLA; 26 = CLB; 29 = USP; 30 = RDE; 31 = WRE; 32 = FB; 33 = VRYE; 34 = SE01; 35 = SE02; 36 = SE03; 37 = SE04; 38 = SE05; 39 = HPERR; 40 = EF; 41 = CTRLE; 42 = SUME; 43 = RDP; 45 = OL1; 47 = SE10; 49 = BB1; 50 = BB2; 51 = BB3; 52 = BB4; 53 = BB5; 54 = BB6; 57 = LOPb; 58 = HIPb; 59 = LSCFT; 60 = LOPb; 61 = RETRY; 62 = SE07; 63 = SE08; 64 = HIPb; 65 = OH1; 66 = FIRE
HR9514doc 252AHAO1 value0-1000 = 0.00-10.00 V or 4-20 mA.UINT16Read
HR9515doc 252BHAO2 value0-1000 = 0.00-10.00 V or 4-20 mA.UINT16Read
HR9519doc 252FHF510 checkF510 identification value.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII)

What Modbus registers does the TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII) have?

This map lists 15 registers: 15 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and sent unchanged (2520H is sent as 25 20). Parameters map group to the high byte and number to the low byte, except 12-00 which is 32-bit at 2510H (high word) / 2511H (low word).

What are the minimum Modbus registers to integrate the TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII)?

Start with HR 9473 Operation signal (Run/stop, direction, reset); HR 9474 Frequency command (Frequency command 0.01 Hz); HR 9504 State signal (Status bits); HR 9505 Error description (Fault code); HR 9508 Output frequency (Output frequency); HR 9512 Warning description (Warning code).

How do I enable Modbus control of the TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII)?

Select Modbus as the communication protocol (the port also does BACnet and Metasys N2), then set node address, serial settings and run/frequency source at the keypad per the F510 manual.

Where is the official TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII) Modbus documentation?

The source is F510 Communication Addendum Modbus RTU/ASCII, BACnet, Metasys N2 (DOCUMENT-TECO-F510-AC001 Ver01), revision 2015-03, published free by TECO-Westinghouse at https://tecowestinghouse.com/PDF/F510_comm_addendum.pdf.

More TECO-Westinghouse Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: F510 Communication Addendum Modbus RTU/ASCII, BACnet, Metasys N2 · DOCUMENT-TECO-F510-AC001 Ver01 · rev. 2015-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.