- F510 HVAC fan/pump inverter (Modbus RTU/ASCII)
Variable frequency drive (HVAC fan / pump) · Modbus register map
TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII) Modbus register map
Updated 17 November 2026
The F510 is TECO-Westinghouse's HVAC fan and pump inverter; its RS-485 port supports Modbus RTU/ASCII as well as BACnet MS/TP and Metasys N2. Run/stop and frequency (0.01 Hz) are written to 2501H/2502H, and status, fault and warning codes and monitors are read from 2520H-252FH. Each parameter nn-mm has its own register, with the group in the high byte and the number in the low byte.
This page lists 15 Modbus registers for the TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII) — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from TECO-Westinghouse’s own free documentation (linked below) and checked against it.
- Manufacturer
- TECO-Westinghouse
- Model
- F510 HVAC fan/pump inverter (Modbus RTU/ASCII)
- Equipment type
- Variable frequency drive (HVAC fan / pump)
- Registers
- 15 (4 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- Not stated
- Documented addressing
- hexadecimal, 0-based
- Also known as
- TECO F510, F510 HVAC drive
Integration notes: TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII)
Set the RS-485 protocol to Modbus, the node address and serial parameters, and select communication as run/frequency source, then write 2501H and 2502H (0.01 Hz) and poll 2520H-2528H.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 9473 | Operation signal | BITMAP16 | Run/stop, direction, reset | Read/write |
| HR 9474 | Frequency command | UINT16 | Frequency command 0.01 Hz | Read/write |
| HR 9504 | State signal | BITMAP16 | Status bits | Read |
| HR 9505 | Error description | UINT16 | Fault code | Read |
| HR 9508 | Output frequency | UINT16 | Output frequency | Read |
| HR 9512 | Warning description | UINT16 | Warning code | Read |
Enable Modbus control & writes
Select Modbus as the communication protocol (the port also does BACnet and Metasys N2), then set node address, serial settings and run/frequency source at the keypad per the F510 manual.
Byte order & addressing
- Registers are hex.
- Functions 03H, 06H, 08H and 10H; maximum frame 80 bytes.
- Node addresses 01H-FEH; 00H is broadcast.
- Write 0 to unused bits and never write reserved registers.
Network setup
- RS-485 on CN6: S+ / S- per the CN6 pin-out.
- The addendum shows 120 ohm terminators on p. 1-1 but says 220 ohm in Appendix A; up to 31 inverters.
Watch out for
- Exception codes: 01 function, 02 register number, 03 number, 04 data setting error.
- Inverter response time is about 10 ms.
TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 9473doc 2501H | Operation signal | Run, direction, fault, reset, comm inputs S1-S6, inverter mode. | BITMAP16 | Read/write | bit 0 = Run (0 stop); bit 1 = Reverse (0 forward); bit 2 = External fault; bit 3 = Fault reset; bit 6 = Comm input S1; bit 7 = Comm input S2; bit 8 = Comm input S3; bit 9 = Comm input S4; bit 10 = Comm input S5; bit 11 = Comm input S6; bit 14 = Inverter mode | |||
| HR | 9474doc 2502H | Frequency command | UINT16 | × 0.01 | Hz | Read/write | |||
| HR | 9477doc 2505H | AO1 command | 0-1000 = 0.00-10.00 V or 4-20 mA. | UINT16 | Read/write | ||||
| HR | 9478doc 2506H | AO2 command | 0-1000 = 0.00-10.00 V or 4-20 mA. | UINT16 | Read/write | ||||
| HR | 9504doc 2520H | State signal | BITMAP16 | Read | bit 0 = Running; bit 1 = Reverse; bit 2 = Inverter ready; bit 3 = Fault; bit 4 = Warning; bit 5 = Zero speed; bit 6 = Is 440 V; bit 7 = Frequency agree; bit 8 = Set frequency agree; bit 9 = Frequency detection 1; bit 10 = Frequency detection 2; bit 11 = Under voltage; bit 12 = Baseblock; bit 13 = Frequency reference not from comm; bit 14 = Sequence not from comm; bit 15 = Over torque | ||||
| HR | 9505doc 2521H | Error description | Active fault code. | UINT16 | Read | 1 = UV; 2 = OC; 3 = OV; 4 = OH1; 5 = OL1; 6 = OL2; 7 = OT; 8 = UT; 9 = SC; 10 = Ground OC; 11 = Fuse blown; 12 = Input phase loss; 13 = Output phase loss; 17 = External fault 01; 18 = External fault 02; 19 = External fault 03; 20 = External fault 04; 21 = External fault 05; 22 = External fault 06; 25 = Feedback fault; 26 = Keypad removed; 27 = Modbus external fault; 28 = CE; 29 = STO; 36 = Low suction fault; 37 = Low suction fault (with retry); 38 = CF07; 39 = Low flow fault; 40 = High flow fault; 42 = Low pressure fault; 43 = High pressure fault; 44 = Feedback loss; 46 = Motor overheat (OH4) | |||
| HR | 9506doc 2522H | DI state | BITMAP16 | Read | bit 0 = Comm S1; bit 1 = Comm S2; bit 2 = Comm S3; bit 3 = Comm S4; bit 4 = Comm S5; bit 5 = Comm S6 | ||||
| HR | 9507doc 2523H | Frequency command | Raw; unit not printed in the monitor table. | UINT16 | Read | ||||
| HR | 9508doc 2524H | Output frequency | Raw; unit not printed in the monitor table. | UINT16 | Read | ||||
| HR | 9510doc 2526H | DC voltage command | Raw; unit not printed in the monitor table. | UINT16 | Read | ||||
| HR | 9511doc 2527H | Output current | Raw; unit not printed in the monitor table. | UINT16 | Read | ||||
| HR | 9512doc 2528H | Warning description | Active warning code. | UINT16 | Read | 0 = No alarm; 1 = OV; 2 = UV; 3 = OL2; 4 = OH2; 6 = OT; 9 = UT; 13 = CE; 16 = EF0; 17 = EF1; 18 = EF2; 19 = EF3; 20 = EF4; 21 = EF5; 22 = EF6; 25 = CLA; 26 = CLB; 29 = USP; 30 = RDE; 31 = WRE; 32 = FB; 33 = VRYE; 34 = SE01; 35 = SE02; 36 = SE03; 37 = SE04; 38 = SE05; 39 = HPERR; 40 = EF; 41 = CTRLE; 42 = SUME; 43 = RDP; 45 = OL1; 47 = SE10; 49 = BB1; 50 = BB2; 51 = BB3; 52 = BB4; 53 = BB5; 54 = BB6; 57 = LOPb; 58 = HIPb; 59 = LSCFT; 60 = LOPb; 61 = RETRY; 62 = SE07; 63 = SE08; 64 = HIPb; 65 = OH1; 66 = FIRE | |||
| HR | 9514doc 252AH | AO1 value | 0-1000 = 0.00-10.00 V or 4-20 mA. | UINT16 | Read | ||||
| HR | 9515doc 252BH | AO2 value | 0-1000 = 0.00-10.00 V or 4-20 mA. | UINT16 | Read | ||||
| HR | 9519doc 252FH | F510 check | F510 identification value. | UINT16 | Read |
Notes on this map
- Unlike the A510/E510 Compact addenda, the F510 monitor table prints no units for 2523H, 2524H, 2526H and 2527H, so they are listed raw.
- The addendum does not name the drive parameters for node address, baud rate, parity or run/frequency source; set those per the F510 manual.
- 2521H (faults) and 2528H (warnings) are code tables, mapped as enums.
- Left out: 2507H DO, 2529H digital output state (no bit list), 252CH/252DH analog inputs (no unit).
- Parameter 12-00 is 32-bit (2510H high word, 2511H low word) and is not listed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII)
What Modbus registers does the TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII) have?
This map lists 15 registers: 15 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and sent unchanged (2520H is sent as 25 20). Parameters map group to the high byte and number to the low byte, except 12-00 which is 32-bit at 2510H (high word) / 2511H (low word).
What are the minimum Modbus registers to integrate the TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII)?
Start with HR 9473 Operation signal (Run/stop, direction, reset); HR 9474 Frequency command (Frequency command 0.01 Hz); HR 9504 State signal (Status bits); HR 9505 Error description (Fault code); HR 9508 Output frequency (Output frequency); HR 9512 Warning description (Warning code).
How do I enable Modbus control of the TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII)?
Select Modbus as the communication protocol (the port also does BACnet and Metasys N2), then set node address, serial settings and run/frequency source at the keypad per the F510 manual.
Where is the official TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII) Modbus documentation?
The source is F510 Communication Addendum Modbus RTU/ASCII, BACnet, Metasys N2 (DOCUMENT-TECO-F510-AC001 Ver01), revision 2015-03, published free by TECO-Westinghouse at https://tecowestinghouse.com/PDF/F510_comm_addendum.pdf.
More TECO-Westinghouse Modbus register maps
- Variable frequency drive
TECO-Westinghouse A510 inverter (Modbus RTU/ASCII)
TECO-Westinghouse A510 inverters using the built-in RS-485 port (CN6), per communication addendum DOCUMENT-TECO-A510-AC001 Ver01 (2015-04).
Also known as: TECO A510, A510s - Variable frequency drive
TECO-Westinghouse E510 Compact (E510N1) inverter (Modbus RTU/ASCII)
TECO-Westinghouse E510 Compact (E510N1) inverters with the built-in RS-485 port (CON2), per communication addendum DOCUMENT-TECO-E510N1-AC002 Ver01 (2017-08).
Also known as: E510N1, E510s, TECO E510 Compact - Variable frequency drive
TECO-Westinghouse E510 inverter (Modbus RTU/ASCII)
TECO-Westinghouse E510 inverters using the built-in RS-485 port (CON2), per communication addendum DOCUMENT-TECO-E510-AC001 Ver01 (2015-03).
Also known as: TECO E510, E510 Communication Addendum - Variable frequency drive
TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII)
TECO-Westinghouse EV series micro inverters with the RS-485 option card, per the EV Inverter Series Modbus Communication Manual.
Also known as: TECO EV, EV Inverter Series - Variable frequency drive
TECO-Westinghouse L510 inverter (Modbus RTU/ASCII)
TECO-Westinghouse L510 micro inverters with the RS-485 option card, per communication addendum DOCUMENT-TECO-L510-AC001 Ver01 (2015-06).
Also known as: TECO L510, L510 Communication Addendum
Other variable frequency drives register maps
- Variable frequency drive
Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa A1000 drives (CIMR-AU; 200 V, 400 V and 600 V classes) using the built-in RS-422/485 MEMOBUS/Modbus terminals (TB5), per Technical Manual SIEP C710616 41H.
Also known as: CIMR-AU, CIMR-AUA, A1000 High Performance Vector Control Drive - Variable frequency drive
Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA800 drives using the built-in RS-485 MEMOBUS/Modbus port, per technical reference SIEPC71061737 revision G.
Also known as: CIPR-GA80, GA800 Industrial AC Microdrive - Variable frequency drive
Yaskawa iQpump605 intelligent pump controller (MEMOBUS/Modbus RTU)
Yaskawa iQpump605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per user manual SIEPYAIWM6502D.
Also known as: WM65W, iQpump605 drive, iQpump605 Intelligent Pump Controller - Variable frequency drive
Yaskawa V1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa V1000 drives (CIMR-VU; 200 V single/three-phase and 400 V three-phase, 0.1-18.5 kW) using the built-in RS-422/485 MEMOBUS/Modbus terminals, per Technical Manual SIEP C710606 18F.
Also known as: CIMR-VU, V1000 Compact Vector Control Drive - Variable frequency drive
ABB ACH580 HVAC drive (embedded Modbus RTU)
ACH580 drives running the ACH580 HVAC control program, embedded fieldbus (EFB) set to Modbus RTU, addressing mode 0 (default).
Also known as: ACH580-01, ACH580-07, ACH580-31, ACH580-34, ACH580 HVAC control program - Variable frequency drive
ABB ACS550-01/U1 general purpose drive (embedded Modbus RTU)
ACS550-01 and ACS550-U1 drives (0.75-160 kW / 1-200 hp) using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AFE64804588 Rev H.
Also known as: ACS550-01, ACS550-U1
All variable frequency drives Modbus register maps →
Source: F510 Communication Addendum Modbus RTU/ASCII, BACnet, Metasys N2 · DOCUMENT-TECO-F510-AC001 Ver01 · rev. 2015-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.