- ACS550-01/U1 general purpose drive (embedded Modbus RTU)
Variable frequency drive · Modbus register map
ABB ACS550-01/U1 general purpose drive (embedded Modbus RTU) Modbus register map
Updated 17 November 2026
ABB's ACS550 general purpose drive has a built-in RS-485 port that runs Modbus RTU. Control bits and relay outputs are coils, status bits and digital inputs are discrete inputs, and all parameters plus the control/status words and references are 16-bit holding registers, with parameter NNNN at register 4NNNN. This map covers the control block, main operating data, fault and alarm words, fault history and the EFB set-up parameters.
This page lists 82 Modbus registers for the ABB ACS550-01/U1 general purpose drive (embedded Modbus RTU) — 19 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ABB’s own free documentation (linked below) and checked against it.
- Manufacturer
- ABB
- Model
- ACS550-01/U1 general purpose drive (embedded Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 82 (19 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- ACS550-01, ACS550-U1
Integration notes: ABB ACS550-01/U1 general purpose drive (embedded Modbus RTU)
Set 9802 = 1 (STD MODBUS), set 5302 and the line settings, then 5305 = 2 (ABB DRV FULL) and point 1001/1102/1103 at COMM. Write the control word and REF1 at 40001/40002, poll the status word 40004 and output frequency/current at 40103/40104.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Control word (ABB Drives) | BITMAP16 | Control word: start/stop/reset | Read/write |
| HR 1 | Reference 1 | INT16 | Reference 1 (20000 = 1105 REF1 MAX) | Read/write |
| HR 3 | Status word (ABB Drives) | BITMAP16 | Status word | Read |
| HR 102 | 0103 Output freq | UINT16 | 0103 Output frequency, 0.1 Hz | Read |
| HR 103 | 0104 Current | UINT16 | 0104 Current, 0.1 A | Read |
| HR 105 | 0106 Power | INT16 | 0106 Power, 0.1 kW | Read |
| HR 400 | 0401 Last fault | UINT16 | 0401 Last fault | Read |
| HR 304 | 0305 Fault word 1 | BITMAP16 | 0305 Fault word 1 | Read |
Enable Modbus control & writes
Set 9802 COMM PROT SEL = 1 (STD MODBUS); this loads Modbus defaults into group 53. Set 5302 station ID (a new address applies after a power cycle, or after setting 5302 to 0 and then the new value), 5303 baud and 5304 parity. For control set 1001 EXT1 COMMANDS = COMM, 1102 EXT1/EXT2 SEL and 1103 REF1 SELECT = COMM, and optionally 1601 RUN ENABLE and 1604 FAULT RESET SEL = COMM. Parameter writes are volatile until 1607 PARAM. SAVE = 1.
Communication loss & watchdog
3018 COMM FAULT FUNC (NOT SEL default / FAULT 28 SERIAL 1 ERR / CONST SP 7 / LAST SPEED with alarm 2005 I/O COMM) after 3019 COMM FAULT TIME (default 3.0 s).
Byte order & addressing
- Zero-based addressing: 4xxxx is sent as xxxx - 1.
- Everything is 16-bit.
- With ABB DRV LIM (default) control word bits 4 and 10 are ignored; choose ABB DRV FULL for the full ABB Drives state machine.
- Alarm words 0308/0309 stay set until the whole word is written to zero.
Network setup
- RS-485 on X1:28-32 with terminal 31 as logical ground; DIP switch J2 sets RS-485 termination.
- Fit termination at both ends of the RS-485 line.
Watch out for
- 5302 = 0 holds the RS-485 channel in reset and stops communication.
- Parameter writes over Modbus are lost at power-down unless saved with 1607.
ABB ACS550-01/U1 general purpose drive (embedded Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 32doc 00033 | Relay output 1 | Always readable; forcing needs the drive configured for fieldbus control. RO4-6 need OREL-01. | BIT | Read/write | ||||
| CO | 33doc 00034 | Relay output 2 | Always readable; forcing needs the drive configured for fieldbus control. RO4-6 need OREL-01. | BIT | Read/write | ||||
| CO | 34doc 00035 | Relay output 3 | Always readable; forcing needs the drive configured for fieldbus control. RO4-6 need OREL-01. | BIT | Read/write | ||||
| CO | 35doc 00036 | Relay output 4 | Always readable; forcing needs the drive configured for fieldbus control. RO4-6 need OREL-01. | BIT | Read/write | ||||
| CO | 36doc 00037 | Relay output 5 | Always readable; forcing needs the drive configured for fieldbus control. RO4-6 need OREL-01. | BIT | Read/write | ||||
| CO | 37doc 00038 | Relay output 6 | Always readable; forcing needs the drive configured for fieldbus control. RO4-6 need OREL-01. | BIT | Read/write | ||||
| DI | 0doc 10001 | Status bit 0: RDY_ON | ABB Drives profile (5305 = 0 or 2) meaning. | BIT | Read | ||||
| DI | 1doc 10002 | Status bit 1: RDY_RUN | ABB Drives profile (5305 = 0 or 2) meaning. | BIT | Read | ||||
| DI | 2doc 10003 | Status bit 2: RDY_REF | ABB Drives profile (5305 = 0 or 2) meaning. | BIT | Read | ||||
| DI | 3doc 10004 | Status bit 3: TRIPPED | ABB Drives profile (5305 = 0 or 2) meaning. | BIT | Read | ||||
| DI | 4doc 10005 | Status bit 4: OFF_2_STA (active low) | ABB Drives profile (5305 = 0 or 2) meaning. | BIT | Read | ||||
| DI | 5doc 10006 | Status bit 5: OFF_3_STA (active low) | ABB Drives profile (5305 = 0 or 2) meaning. | BIT | Read | ||||
| DI | 6doc 10007 | Status bit 6: SWC_ON_INHIB | ABB Drives profile (5305 = 0 or 2) meaning. | BIT | Read | ||||
| DI | 7doc 10008 | Status bit 7: ALARM | ABB Drives profile (5305 = 0 or 2) meaning. | BIT | Read | ||||
| DI | 8doc 10009 | Status bit 8: AT_SETPOINT | ABB Drives profile (5305 = 0 or 2) meaning. | BIT | Read | ||||
| DI | 9doc 10010 | Status bit 9: REMOTE | ABB Drives profile (5305 = 0 or 2) meaning. | BIT | Read | ||||
| DI | 10doc 10011 | Status bit 10: ABOVE_LIMIT | ABB Drives profile (5305 = 0 or 2) meaning. | BIT | Read | ||||
| DI | 11doc 10012 | Status bit 11: EXT2 | ABB Drives profile (5305 = 0 or 2) meaning. | BIT | Read | ||||
| DI | 12doc 10013 | Status bit 12: RUN_ENABLE | ABB Drives profile (5305 = 0 or 2) meaning. | BIT | Read | ||||
| DI | 32doc 10033 | DI1 | Digital input state. | BIT | Read | ||||
| DI | 33doc 10034 | DI2 | Digital input state. | BIT | Read | ||||
| DI | 34doc 10035 | DI3 | Digital input state. | BIT | Read | ||||
| DI | 35doc 10036 | DI4 | Digital input state. | BIT | Read | ||||
| DI | 36doc 10037 | DI5 | Digital input state. | BIT | Read | ||||
| DI | 37doc 10038 | DI6 | Digital input state. | BIT | Read | ||||
| HR | 0doc 40001 | Control word (ABB Drives) | Only with 5305 = 0 or 2; copy in 5319. | BITMAP16 | Read/write | bit 0 = OFF1 CONTROL: 1 = ready to operate, 0 = ramp stop; bit 1 = OFF2 CONTROL: 0 = emergency off, coast to stop; bit 2 = OFF3 CONTROL: 0 = emergency stop (2208); bit 3 = INHIBIT OPERATION: 1 = operation enabled (needs run enable, 1601); bit 4 = RAMP_OUT_ZERO (ABB DRV FULL only): 0 = force ramp output to zero; bit 5 = RAMP_HOLD: 0 = halt ramping; bit 6 = RAMP_IN_ZERO: 0 = force ramp input to zero; bit 7 = RESET: 0->1 = fault reset (1604 = COMM); bit 8 = Unused; bit 9 = Unused; bit 10 = REMOTE_CMD (ABB DRV FULL only): 1 = fieldbus control enabled; bit 11 = EXT CTRL LOC: 1 = EXT2, 0 = EXT1 (1102 = COMM); bit 12 = Unused; bit 13 = Unused; bit 14 = Unused; bit 15 = Unused | |||
| HR | 1doc 40002 | Reference 1 | 0...+/-20000 = 0...1105 REF1 MAX. | INT16 | Read/write | ||||
| HR | 2doc 40003 | Reference 2 | 0...+/-10000 = 0...1108 REF2 MAX. | INT16 | Read/write | ||||
| HR | 3doc 40004 | Status word (ABB Drives) | Only with 5305 = 0 or 2; copy in 5320. | BITMAP16 | Read | bit 0 = RDY_ON: ready to switch on; bit 1 = RDY_RUN: ready to operate; bit 2 = RDY_REF: operation enabled; bit 3 = TRIPPED: fault; bit 4 = OFF_2_STA: 1 = OFF2 inactive; bit 5 = OFF_3_STA: 1 = OFF3 inactive; bit 6 = SWC_ON_INHIB: switch-on inhibit active; bit 7 = ALARM; bit 8 = AT_SETPOINT: actual equals reference; bit 9 = REMOTE: 1 = EXT1/EXT2, 0 = local; bit 10 = ABOVE_LIMIT: supervised value above limit (group 32); bit 11 = EXT CTRL LOC: 1 = EXT2 selected; bit 12 = EXT RUN ENABLE received; bit 13 = Unused; bit 14 = Unused; bit 15 = Unused | |||
| HR | 4doc 40005 | Actual 1 | Default copy of 0103 output frequency (5310); 0.1 Hz with the default. | INT16 | Read | ||||
| HR | 5doc 40006 | Actual 2 | Default copy of 0104 current (5311); 0.1 A with the default. | INT16 | Read | ||||
| HR | 30doc 40031 | DCU control word LSW | Only with 5305 = 1 (see 0301). | BITMAP16 | Read/write | ||||
| HR | 31doc 40032 | DCU control word MSW | Only with 5305 = 1 (see 0302). | BITMAP16 | Read | ||||
| HR | 32doc 40033 | DCU status word LSW | Only with 5305 = 1 (see 0303). | BITMAP16 | Read | ||||
| HR | 33doc 40034 | DCU status word MSW | Only with 5305 = 1 (see 0304). | BITMAP16 | Read | ||||
| HR | 100doc 40101 | 0101 Speed & dir | Signed motor speed; negative = reverse. | INT16 | rpm | Read | |||
| HR | 101doc 40102 | 0102 Speed | UINT16 | rpm | Read | ||||
| HR | 102doc 40103 | 0103 Output freq | UINT16 | × 0.1 | Hz | Read | |||
| HR | 103doc 40104 | 0104 Current | Measured motor current. | UINT16 | × 0.1 | A | Read | ||
| HR | 104doc 40105 | 0105 Torque | Percent of nominal motor torque. | INT16 | × 0.1 | % | Read | ||
| HR | 105doc 40106 | 0106 Power | Measured motor power. | INT16 | × 0.1 | kW | Read | ||
| HR | 106doc 40107 | 0107 DC bus voltage | UINT16 | V | Read | ||||
| HR | 108doc 40109 | 0109 Output voltage | UINT16 | V | Read | ||||
| HR | 109doc 40110 | 0110 Drive temp | Power transistor temperature. | INT16 | × 0.1 | °C | Read | ||
| HR | 111doc 40112 | 0112 External ref 2 | INT16 | × 0.1 | % | Read | |||
| HR | 112doc 40113 | 0113 Ctrl location | UINT16 | Read | 0 = LOCAL; 1 = EXT1; 2 = EXT2 | ||||
| HR | 113doc 40114 | 0114 Run time (R) | Resettable run hours. | UINT16 | h | Read | |||
| HR | 114doc 40115 | 0115 kWh counter (R) | Rolls over at 65535; resettable. | UINT16 | kWh | Read | |||
| HR | 119doc 40120 | 0120 AI 1 | UINT16 | × 0.1 | % | Read | |||
| HR | 120doc 40121 | 0121 AI 2 | UINT16 | × 0.1 | % | Read | |||
| HR | 123doc 40124 | 0124 AO 1 | UINT16 | × 0.1 | mA | Read | |||
| HR | 139doc 40140 | 0140 Run time | Thousands of hours. | UINT16 | × 0.01 | kh | Read | ||
| HR | 140doc 40141 | 0141 MWh counter | UINT16 | MWh | Read | ||||
| HR | 142doc 40143 | 0143 Drive on time hi | Power-on days. | UINT16 | days | Read | |||
| HR | 143doc 40144 | 0144 Drive on time lo | 2 s ticks within the day. | UINT16 | × 2 | s | Read | ||
| HR | 152doc 40153 | 0153 Mot therm stress | Motor thermal load. | UINT16 | × 0.1 | % | Read | ||
| HR | 304doc 40305 | 0305 Fault word 1 | BITMAP16 | Read | bit 0 = OVERCURRENT; bit 1 = DC OVERVOLT; bit 2 = DEV OVERTEMP; bit 3 = SHORT CIRC; bit 4 = Reserved; bit 5 = DC UNDERVOLT; bit 6 = AI1 LOSS; bit 7 = AI2 LOSS; bit 8 = MOT OVERTEMP; bit 9 = PANEL LOSS; bit 10 = ID RUN FAIL; bit 11 = MOTOR STALL; bit 12 = CB OVERTEMP; bit 13 = EXT FAULT 1; bit 14 = EXT FAULT 2; bit 15 = EARTH FAULT | ||||
| HR | 305doc 40306 | 0306 Fault word 2 | BITMAP16 | Read | bit 0 = Obsolete; bit 1 = THERM FAIL; bit 2 = OPEX LINK; bit 3 = OPEX PWR; bit 4 = CURR MEAS; bit 5 = SUPPLY PHASE; bit 6 = ENCODER ERR; bit 7 = OVERSPEED; bit 8 = Reserved; bit 9 = DRIVE ID; bit 10 = CONFIG FILE; bit 11 = SERIAL 1 ERR; bit 12 = EFB CON FILE; bit 13 = FORCE TRIP; bit 14 = MOTOR PHASE; bit 15 = OUTP WIRING | ||||
| HR | 306doc 40307 | 0307 Fault word 3 | BITMAP16 | Read | bit 0 = EFB 1; bit 1 = EFB 2; bit 2 = EFB 3; bit 3 = INCOMPATIBLE SW; bit 4 = USER LOAD CURVE; bit 5 = Reserved; bit 6 = Reserved; bit 7 = Reserved; bit 8 = Reserved; bit 9 = Reserved; bit 10 = System error; bit 11 = System error; bit 12 = System error; bit 13 = System error; bit 14 = System error; bit 15 = Param. setting fault | ||||
| HR | 307doc 40308 | 0308 Alarm word 1 | Write 0 to clear. | BITMAP16 | Read | bit 0 = OVERCURRENT; bit 1 = OVERVOLTAGE; bit 2 = UNDERVOLTAGE; bit 3 = DIR LOCK; bit 4 = IO COMM; bit 5 = AI1 LOSS; bit 6 = AI2 LOSS; bit 7 = PANEL LOSS; bit 8 = DEVICE OVERTEMP; bit 9 = MOTOR TEMP; bit 10 = Reserved; bit 11 = MOTOR STALL; bit 12 = AUTORESET; bit 13 = AUTOCHANGE; bit 14 = PFC I LOCK; bit 15 = Reserved | |||
| HR | 308doc 40309 | 0309 Alarm word 2 | Write 0 to clear. | BITMAP16 | Read | bit 0 = Reserved; bit 1 = PID SLEEP; bit 2 = ID RUN; bit 3 = Reserved; bit 4 = START ENABLE 1 MISSING; bit 5 = START ENABLE 2 MISSING; bit 6 = EMERGENCY STOP; bit 7 = ENCODER ERROR; bit 8 = FIRST START; bit 9 = Reserved; bit 10 = USER LOAD CURVE; bit 11 = START DELAY; bit 12 = Reserved; bit 13 = Reserved; bit 14 = Reserved; bit 15 = Reserved | |||
| HR | 400doc 40401 | 0401 Last fault | Latest fault code; 0 = history clear. | UINT16 | Read | ||||
| HR | 403doc 40404 | 0404 Speed at flt | INT16 | rpm | Read | ||||
| HR | 404doc 40405 | 0405 Freq at flt | INT16 | × 0.1 | Hz | Read | |||
| HR | 405doc 40406 | 0406 Voltage at flt | DC bus voltage at the fault. | UINT16 | × 0.1 | V | Read | ||
| HR | 406doc 40407 | 0407 Current at flt | UINT16 | × 0.1 | A | Read | |||
| HR | 407doc 40408 | 0408 Torque at flt | INT16 | × 0.1 | % | Read | |||
| HR | 411doc 40412 | 0412 Previous fault 1 | UINT16 | Read | |||||
| HR | 412doc 40413 | 0413 Previous fault 2 | UINT16 | Read | |||||
| HR | 1606doc 41607 | 1607 Param. save | Write 1 to save parameters permanently. | UINT16 | Read/write | 0 = DONE; 1 = SAVE | |||
| HR | 3017doc 43018 | 3018 Comm fault func | Reaction to fieldbus loss. | UINT16 | Read/write | 0 = NOT SEL; 1 = FAULT; 2 = CONST SP 7; 3 = LAST SPEED | |||
| HR | 3018doc 43019 | 3019 Comm fault time | 0.0-600.0 s, default 3.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 5301doc 45302 | 5302 EFB station ID | Default 1 for Modbus. | UINT16 | Read/write | ||||
| HR | 5303doc 45304 | 5304 EFB parity | UINT16 | Read/write | 0 = 8 NONE 1; 1 = 8 NONE 2; 2 = 8 EVEN 1; 3 = 8 ODD 1 | ||||
| HR | 5304doc 45305 | 5305 EFB ctrl profile | UINT16 | Read/write | 0 = ABB DRV LIM; 1 = DCU PROFILE; 2 = ABB DRV FULL | ||||
| HR | 5305doc 45306 | 5306 EFB OK messages | UINT16 | Read | |||||
| HR | 5306doc 45307 | 5307 EFB CRC errors | UINT16 | Read | |||||
| HR | 5307doc 45308 | 5308 EFB UART errors | UINT16 | Read | |||||
| HR | 5308doc 45309 | 5309 EFB status | UINT16 | Read | 0 = IDLE; 1 = EXECUT INIT; 2 = TIME OUT; 3 = CONFIG ERROR; 4 = OFF-LINE; 5 = ON-LINE; 6 = RESET; 7 = LISTEN ONLY | ||||
| HR | 5309doc 45310 | 5310 EFB par 10 | Parameter mapped to 40005. | UINT16 | Read/write | ||||
| HR | 5310doc 45311 | 5311 EFB par 11 | Parameter mapped to 40006. | UINT16 | Read/write | ||||
| HR | 9801doc 49802 | 9802 Comm prot sel | UINT16 | Read/write | 0 = NOT SEL; 1 = STD MODBUS; 4 = EXT FBA (adapter in slot 2) |
Notes on this map
- All registers are 16-bit; there is no word order. Scaling uses each parameter's Resolution column, which the manual says multiplies the fieldbus integer (e.g. 0.1 Hz).
- 40001/40004 work only with 5305 = ABB DRV LIM (default) or ABB DRV FULL; 40031-40034 only with the DCU profile. ABB DRV LIM ignores control word bits 4 and 10. The coil table labels ABB DRV LIM coil 00004 (bit 3) 'START' while the control-word table calls bit 3 INHIBIT OPERATION; it is the same bit.
- Discrete inputs 10001-10013 are listed with their ABB Drives profile meaning; with the DCU profile the same inputs carry DCU status bits (READY, ENABLED, STARTED, RUNNING...). Only 6 DI and 6 RO are listed; RO4-6 need the OREL-01 extension.
- Actual values 40005-40012 follow 5310-5317; 40005/40006 default to 0103 and 0104 according to the Modbus chapter, although the group 53 table lists 0 as the default of 5310-5317.
- Parity default is unclear: the parameter list gives 5304 default 0 (8 NONE 1) while the EFB setup table says selecting Modbus sets it to 1 (8 NONE 2). Read 5304 from the drive. 5303 baud (default 9.6 kbit/s) is left out because its fieldbus encoding is not stated.
- Left out: 0111 External ref 1 (Hz or rpm depending on 9904), PID, process-variable and energy-saving signals, fault time stamps 0402/0403, status/DI at fault, and the DCU REF registers 40045-40048, and input registers 30001/30002 (AI1/AI2 level 0-100 %, integer scaling not stated; use 0120/0121 instead).
- Exception 03 is returned for writes out of range, to read-only parameters, while started, or while a factory macro is selected.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the ABB ACS550-01/U1 general purpose drive (embedded Modbus RTU)
What Modbus registers does the ABB ACS550-01/U1 general purpose drive (embedded Modbus RTU) have?
This map lists 82 registers: 6 coils, 19 discrete inputs, 57 holding registers. 19 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the ABB ACS550-01/U1 general purpose drive (embedded Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states the drive uses zero-based Modbus addressing: holding register 40002 is sent as 0001 and coil 33 as 0032. So 40001 = wire 0, parameter NNNN = register 4NNNN = wire NNNN - 1 (e.g. 0103 -> 40103 -> 102); coils 00001-00016 are control-word bits, 00033+ relay outputs; discrete inputs 10001-10032 are status-word bits and 10033+ digital inputs; input registers 30001/30002 are AI1/AI2.
What are the minimum Modbus registers to integrate the ABB ACS550-01/U1 general purpose drive (embedded Modbus RTU)?
Start with HR 0 Control word (ABB Drives) (Control word: start/stop/reset); HR 1 Reference 1 (Reference 1 (20000 = 1105 REF1 MAX)); HR 3 Status word (ABB Drives) (Status word); HR 102 0103 Output freq (0103 Output frequency, 0.1 Hz); HR 103 0104 Current (0104 Current, 0.1 A); HR 105 0106 Power (0106 Power, 0.1 kW); HR 400 0401 Last fault (0401 Last fault); HR 304 0305 Fault word 1 (0305 Fault word 1).
How do I enable Modbus control of the ABB ACS550-01/U1 general purpose drive (embedded Modbus RTU)?
Set 9802 COMM PROT SEL = 1 (STD MODBUS); this loads Modbus defaults into group 53. Set 5302 station ID (a new address applies after a power cycle, or after setting 5302 to 0 and then the new value), 5303 baud and 5304 parity. For control set 1001 EXT1 COMMANDS = COMM, 1102 EXT1/EXT2 SEL and 1103 REF1 SELECT = COMM, and optionally 1601 RUN ENABLE and 1604 FAULT RESET SEL = COMM. Parameter writes are volatile until 1607 PARAM. SAVE = 1.
What happens when the ABB ACS550-01/U1 general purpose drive (embedded Modbus RTU) loses Modbus communication?
3018 COMM FAULT FUNC (NOT SEL default / FAULT 28 SERIAL 1 ERR / CONST SP 7 / LAST SPEED with alarm 2005 I/O COMM) after 3019 COMM FAULT TIME (default 3.0 s).
Where is the official ABB ACS550-01/U1 general purpose drive (embedded Modbus RTU) Modbus documentation?
The source is ACS550-01/U1 User's Manual (0.75...160 kW / 1...200 hp) (3AFE64804588 (3AUA0000001418) Rev H), revision 2014-07-04, published free by ABB at https://search.abb.com/library/Download.aspx?DocumentID=3AFE64804588&LanguageCode=en&DocumentPartId=1&Action=Launch.
More ABB Modbus register maps
- Variable frequency drive
ABB ACH480 HVAC drive (embedded Modbus RTU)
ACH480 drives running the ACH480 HVAC control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000247134 Rev E.
Also known as: ACH480-04, ACH480 HVAC control program - Variable frequency drive
ABB ACH550-UH HVAC drive (embedded Modbus RTU)
ACH550-UH HVAC drives using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AUA0000081823 Rev F.
Also known as: ACH550-UH, ACH550 - Variable frequency drive
ABB ACH580 HVAC drive (embedded Modbus RTU)
ACH580 drives running the ACH580 HVAC control program, embedded fieldbus (EFB) set to Modbus RTU, addressing mode 0 (default).
Also known as: ACH580-01, ACH580-07, ACH580-31, ACH580-34, ACH580 HVAC control program - Variable frequency drive
ABB ACQ580 water and wastewater drive (embedded Modbus RTU)
ACQ580 drives running the ACQ580 pump control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000035867 Rev H.
Also known as: ACQ580-01, ACQ580-04, ACQ580-07, ACQ580-31, ACQ580-34, ACQ580 pump control program - Variable frequency drive
ABB ACS180 machinery drive (embedded Modbus RTU)
ACS180 drives running the machinery control program, built-in EIA-485 Modbus RTU terminal (embedded fieldbus, EFB), addressing mode 0 (default); firmware manual 3AXD50000467860 Rev D.
Also known as: ACS180-04, ACS180 machinery control program - Variable frequency drive
ABB ACS310 pump and fan drive (embedded Modbus RTU)
ACS310 drives (01E/01U/03E/03U) using the embedded fieldbus: Modbus RTU on the built-in EIA-485 terminals 23-26 or RS-232 on the panel connector; user's manual 3AUA0000044201 Rev D.
Also known as: ACS310-01E, ACS310-01U, ACS310-03E, ACS310-03U - Variable frequency drive
ABB ACS355 machinery drive (embedded Modbus RTU)
ACS355 drives with firmware 5.110 or later using the embedded fieldbus (Modbus RTU) over an FMBA-01 adapter on terminal X3 (EIA-485) or the panel port (RS-232).
Also known as: ACS355-01E, ACS355-03E, ACS355-01U, ACS355-03U, ACS355 with FMBA-01 - Variable frequency drive
ABB ACS380 machinery drive (embedded Modbus RTU)
ACS380 drives running the machinery control program with the BMIO-01 I/O and Modbus RTU module, embedded fieldbus (EFB), addressing mode 0 (default); firmware manual 3AXD50000029275 Rev J.
Also known as: ACS380-04, ACS380 machinery control program, BMIO-01 - Variable frequency drive
ABB ACS480 general purpose drive (embedded Modbus RTU)
ACS480 drives running the ACS480 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000047399 Rev G.
Also known as: ACS480-04, ACS480 standard control program - Variable frequency drive
ABB ACS580 general purpose drive (embedded Modbus RTU)
ACS580 drives running the ACS580 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default).
Also known as: ACS580-01, ACS580-04, ACS580-07, ACS580 standard control program - Variable frequency drive
ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link)
ACS800 drives running Standard Control Program 7.x with an RMBA-01 Modbus Adapter in option slot 1 or 2 (Standard Modbus Link, RTU only), ABB Drives communication profile.
Also known as: ACS800-01, ACS800-02, ACS800-04, ACS800-07, ACS800-11, ACS800-17, ACS800-31, ACS800-37, RMBA-01, ACS800 Standard Control Program - Variable frequency drive
ABB ACS880 industrial drive, primary control program (embedded Modbus RTU)
ACS880 drives running the primary control program (AINLX) 3.4x or later, embedded fieldbus (EFB) Modbus RTU on terminal XD2D, 58.33 Addressing mode = Mode 0 (default).
Also known as: ACS880-01, ACS880-04, ACS880-07, ACS880-11, ACS880-17, ACS880-31, ACS880-37, AINLX, ACS880 primary control program - Power meter (branch circuit monitoring)
ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)
ABB CMS-700 control unit with up to 96 CMS branch current sensors, per the CMS-700 user manual (Modbus and SNMP mapping chapter).
Also known as: CMS-700, CMS700, ABB CMS-700, CMS-700 control unit - Variable frequency drive (DC drive)
ABB DCS880 DC drive (embedded Modbus RTU)
DCS880 DC drives, firmware manual revision E, embedded fieldbus (EFB) Modbus RTU on control-board terminal XD2D, ABB Drives profile, 58.33 Addressing mode = Mode 0.
Also known as: DCS880-S01, DCS880-S02, DCS880-H, DCS880-R - Energy meter
ABB EQ meter A41 / A42 (Modbus RTU)
ABB EQ A41 (direct connected) and A42 (transformer connected) DIN meters whose RS-485 port is set to Modbus.
Also known as: A41, A42, EQ A41, EQ A42 - Energy meter
ABB EQ meter A43 / A44 (Modbus RTU)
ABB EQ A43 (direct connected) and A44 (transformer connected) three-phase DIN meters whose RS-485 port is set to Modbus.
Also known as: A43, A44, EQ A43, EQ A44 - Energy meter
ABB EQ meter B21 (Modbus RTU)
ABB EQ B21 single-phase 65 A DIN meter with the RS485 interface set to Modbus.
Also known as: B21, EQ B21 - Energy meter
ABB EQ meter B23 / B24 (Modbus RTU)
ABB EQ B23 (direct, 65 A) and B24 (CT-connected) three-phase DIN meters fitted with the RS485 interface set to Modbus.
Also known as: B23, B24, EQ B23, EQ B24 - Power meter (network analyzer)
ABB M4M 20 / M4M 30 network analyzer
ABB M4M 20 and M4M 30 network analyzers, Modbus RTU and Modbus TCP versions, map v1.3O; items marked M4M 30 only are absent on M4M 20.
Also known as: M4M 20, M4M 30, M4M 20 Modbus, M4M 30 Modbus, M4M 20 Ethernet, M4M 30 Ethernet, M4M 20 I/O, M4M 30 I/O, M4M 2X, M4M 30-M, M4M 32 - Process controller (sensor / PID controller)
ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)
ABB Protronic 100/500/550 and Digitric 500 universal process controllers with the RS-485/RS-232 Modbus interface module, interface description 42/62-50040 EN Rev. 04.
Also known as: Protronic 100, Protronic 500, Protronic 550, Digitric 500 - Soft starter (motor control)
ABB PSE softstarter (internal Modbus RTU)
ABB PSE18...PSE370 softstarters using the internal Modbus RTU interface (Modbus RTU adaptor on the front fieldbus connector), document 1SFC132367M0201 Rev B.
Also known as: PSE18, PSE25, PSE30, PSE37, PSE45, PSE60, PSE72, PSE85, PSE105, PSE142, PSE170, PSE210, PSE250, PSE300, PSE370 - Soft starter (motor control)
ABB PSTX softstarter (built-in Modbus RTU)
ABB PSTX30...PSTX1250 softstarters using the built-in Modbus RTU interface on terminals 23/24 (Com3), document 1SFC132089M0201 Rev F.
Also known as: PSTX30, PSTX37, PSTX45, PSTX60, PSTX72, PSTX85, PSTX105, PSTX142, PSTX170, PSTX210, PSTX250, PSTX300, PSTX370, PSTX470, PSTX570, PSTX720, PSTX840, PSTX1050, PSTX1250 - Power meter (DC circuit breaker trip unit)
ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU)
ABB SACE PR122DC and PR123DC DC protection trip units with the PR120/D-M communication module, document rev 02 (04/04/2014, SW 3.01 and later).
Also known as: PR122DC, PR123DC, PR120/D-M, Emax DC, SACE Emax DC - Power meter (circuit breaker trip unit)
ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU)
ABB SACE PR122/P and PR123/P (Emax) and PR332/P and PR333/P (Emax X1, Tmax T7, Tmax T8) protection releases with the Modbus RTU communication module, per 1SDH000556R0001.
Also known as: PR122/P, PR123/P, PR332/P, PR333/P, PR120/D-M, PR330/D-M, Emax PR122, Emax PR123, Tmax T7 PR332, Emax X1 PR333, Tmax T8 PR332 - Power meter (circuit breaker trip unit)
ABB SACE Tmax PR223DS trip unit (Modbus RTU)
ABB SACE PR223DS electronic trip unit (Tmax moulded-case breakers), software version 02.02, per 1SDH000658R0001.
Also known as: PR223DS, Tmax PR223DS, SACE PR223DS
Other variable frequency drives register maps
- Variable frequency drive
AutomationDirect DURApulse GS20 / GS20X AC drive
GS20 and GS20X drives (built-in RS-485 port) per the GS20 & GS20X user manual, 1st edition rev. F, chapter 5.
Also known as: GS20X, DURApulse GS20, GS21-11P0 - Variable frequency drive
Danfoss VLT AQUA Drive FC 202 (Modbus RTU)
VLT AQUA Drive FC 202 using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter data checked against the software 5.4X programming guide.
Also known as: VLT AQUA Drive, FC202, FC-202, AQUA Drive FC 202 - Variable frequency drive
Danfoss VLT Midi Drive FC 280 (Modbus RTU)
VLT Midi Drive FC 280 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC280, FC-280, VLT Midi Drive FC 280, VLT Midi Drive - Variable frequency drive
Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP)
PowerXL DG1 general-purpose and DH1 HVAC drives per PowerXL Series VFD Communication Manual MN040010EN (June 2018).
Also known as: DG1, DH1, PowerXL DG1, PowerXL DH1, DG1 general purpose drive, DH1 HVAC drive - Variable frequency drive
Inovance MD500-PLUS series AC drive
Inovance MD500-PLUS drives with the MD38TX1 RS-485 extension card, Modbus RTU slave, per software guide 19011580 rev. A04.
Also known as: MD500-PLUS, MD500 PLUS, MD500T-PLUS, Inovance MD500-PLUS - Variable frequency drive
INVT Goodrive20 (GD20) general-purpose VFD
INVT Goodrive20 drives using the built-in RS-485 Modbus port, per the GD20 VFD manual V2.1 (chapter 7, communication protocol).
Also known as: GD20, Goodrive20, GD20-EU, GD20-UL, GD20 vector VFD
All variable frequency drives Modbus register maps →
Source: ACS550-01/U1 User's Manual (0.75...160 kW / 1...200 hp) · 3AFE64804588 (3AUA0000001418) Rev H · rev. 2014-07-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.