Variable frequency drive · Modbus register map

AutomationDirect DURApulse GS20 / GS20X AC drive Modbus register map

Updated 17 November 2026

Short answer

The DURApulse GS20 and GS20X are AutomationDirect's compact and NEMA 4X general-purpose drives with a built-in RS-485 Modbus RTU/ASCII port. Control goes through command words at 2000h-2002h and status is read from 2100h upward; every parameter Pxx.yy is also a register. This map covers the command and status words, frequency, voltages, the main serial setup parameters and the block-transfer registers.

This page lists 34 Modbus registers for the AutomationDirect DURApulse GS20 / GS20X AC drive — 23 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from AutomationDirect’s own free documentation (linked below) and checked against it.

Manufacturer
AutomationDirect
Model
DURApulse GS20 / GS20X AC drive
Equipment type
Variable frequency drive
Registers
34 (23 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
1
Default serial
9600 baud
Documented addressing
hexadecimal, 0-based
Also known as
GS20X, DURApulse GS20, GS21-11P0
Source document
DURApulse GS20 & GS20X Drive User Manual - Chapter 5: Serial Communications · GS20-M 1st Edition, Rev. F (chapter 5)
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: AutomationDirect DURApulse GS20 / GS20X AC drive

Integration in brief

Set the drive's run source and frequency source to RS-485, then write 2000h (run/stop/direction) and 2001h (frequency in 0.01 Hz) in one function-16 write. Poll 2100h-2106h for fault, state and frequency.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 8192Control word 1BITMAP16Run/stop/direction commandWrite
HR 8193Frequency commandUINT16Frequency command 0.01 HzWrite
HR 8448Status monitor 1UINT16Warning/error codeRead
HR 8449Status monitor 2BITMAP16Drive stateRead
HR 8451Output frequencyUINT16Output frequencyRead
HR 8453DC bus voltageUINT16DC bus voltageRead

Enable Modbus control & writes

Set P09.00 address and P09.04 protocol (codes 12-17 are RTU), then select RS-485 as the frequency reference (P00.20 = 1 in Remote/Auto or P00.30 = 1 in Local/Hand, per the manual's note) and as the run-command source (see chapter 4).

Communication loss & watchdog

P09.03 COM1 time-out detection (0.0-100.0 s, factory 0.0) sets the loss timeout; P09.02 selects warn, ramp-stop, coast-stop or no action on loss.

Byte order & addressing

Network setup

Watch out for

AutomationDirect DURApulse GS20 / GS20X AC drive Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

34 of 34 shown
AutomationDirect DURApulse GS20 / GS20X AC drive Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1553doc 0611h (41554)P06.17 Fault record 1Most recent fault code (same coding as status monitor 1).UINT16Read
HR2304doc 0900h (42305)P09.00 Communication addressRS-485 station address, 1-254.UINT16Read/write
HR2306doc 0902h (42307)P09.02 COM1 transmission fault treatmentUINT16Read/write0 = Warn and continue; 1 = Fault and ramp to stop; 2 = Fault and coast to stop; 3 = No warning, no fault, continue
HR2308doc 0904h (42309)P09.04 COM1 communication protocolUINT16Read/write1 = 7N2 ASCII; 2 = 7E1 ASCII; 3 = 7O1 ASCII; 4 = 7E2 ASCII; 5 = 7O2 ASCII; 6 = 8N1 ASCII; 7 = 8N2 ASCII; 8 = 8E1 ASCII; 9 = 8O1 ASCII; 10 = 8E2 ASCII; 11 = 8O2 ASCII; 12 = 8N1 RTU; 13 = 8N2 RTU; 14 = 8E1 RTU; 15 = 8O1 RTU; 16 = 8E2 RTU; 17 = 8O2 RTU
HR2315doc 090Bh (42316)P09.11 Block transfer 1Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2316doc 090Ch (42317)P09.12 Block transfer 2Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2317doc 090Dh (42318)P09.13 Block transfer 3Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2318doc 090Eh (42319)P09.14 Block transfer 4Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2319doc 090Fh (42320)P09.15 Block transfer 5Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2320doc 0910h (42321)P09.16 Block transfer 6Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2321doc 0911h (42322)P09.17 Block transfer 7Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2322doc 0912h (42323)P09.18 Block transfer 8Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2323doc 0913h (42324)P09.19 Block transfer 9Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2324doc 0914h (42325)P09.20 Block transfer 10Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2325doc 0915h (42326)P09.21 Block transfer 11Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2326doc 0916h (42327)P09.22 Block transfer 12Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2327doc 0917h (42328)P09.23 Block transfer 13Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2328doc 0918h (42329)P09.24 Block transfer 14Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2329doc 0919h (42330)P09.25 Block transfer 15Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2330doc 091Ah (42331)P09.26 Block transfer 16Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2337doc 0921h (42338)P09.33 PLC command force to 0UINT16Read/write
HR8192doc 2000h (48193)Control word 1Run/stop and direction codes; see notes.BITMAP16Writebit 0 = Run/stop code bit 0 (with bit 1); bit 1 = Run/stop code bit 1; bit 4 = Direction code bit 0 (with bit 5); bit 5 = Direction code bit 1; bit 12 = Enable bits 6-11 (accel set, step speed)
HR8193doc 2001h (48194)Frequency commandSpeed reference in 0.01 Hz.UINT16× 0.01HzWrite
HR8194doc 2002h (48195)Control word 2BITMAP16Writebit 0 = External fault (EF) on; bit 1 = Fault reset; bit 2 = Base block (BB) on; bit 5 = Enable fire mode
HR8448doc 2100h (48449)Status monitor 1High byte warning code, low byte error code.UINT16Read
HR8449doc 2101h (48450)Status monitor 2Bits 1-0 run state (00 stop, 01 decel, 10 standby, 11 running); bits 4-3 direction.BITMAP16Readbit 0 = Run state bit 0; bit 1 = Run state bit 1; bit 2 = JOG command; bit 3 = Direction bit 0; bit 4 = Direction bit 1; bit 8 = Frequency from communication; bit 9 = Frequency from analog/terminal; bit 10 = Run command from communication; bit 11 = Parameters locked; bit 12 = Copy parameters from keypad enabled
HR8450doc 2102h (48451)Frequency command (status)Active frequency command.UINT16× 0.01HzRead
HR8451doc 2103h (48452)Output frequencyUINT16× 0.01HzRead
HR8453doc 2105h (48454)DC bus voltageUINT16× 0.1VRead
HR8454doc 2106h (48455)Output voltageUINT16× 0.1VRead
HR8455doc 2107h (48456)Multi-step speed stepCurrent multi-step speed step number.UINT16Read
HR8457doc 2109h (48458)Counter valueUINT16Read
HR8458doc 210Ah (48459)Output power factor angleUINT16× 0.1Read
HR8460doc 210Ch (48461)Actual motor speedUINT16rpmRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the AutomationDirect DURApulse GS20 / GS20X AC drive

What Modbus registers does the AutomationDirect DURApulse GS20 / GS20X AC drive have?

This map lists 34 registers: 34 holding registers. 23 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the AutomationDirect DURApulse GS20 / GS20X AC drive Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed in hex with the matching Modicon number (2000h = 48193, 2100h = 48449, 0900h = 42305). The hex value is the wire address; the manual's RTU examples send 21 02 to read 2102h and 20 00 to write 2000h.

What are the minimum Modbus registers to integrate the AutomationDirect DURApulse GS20 / GS20X AC drive?

Start with HR 8192 Control word 1 (Run/stop/direction command); HR 8193 Frequency command (Frequency command 0.01 Hz); HR 8448 Status monitor 1 (Warning/error code); HR 8449 Status monitor 2 (Drive state); HR 8451 Output frequency (Output frequency); HR 8453 DC bus voltage (DC bus voltage).

How do I enable Modbus control of the AutomationDirect DURApulse GS20 / GS20X AC drive?

Set P09.00 address and P09.04 protocol (codes 12-17 are RTU), then select RS-485 as the frequency reference (P00.20 = 1 in Remote/Auto or P00.30 = 1 in Local/Hand, per the manual's note) and as the run-command source (see chapter 4).

What happens when the AutomationDirect DURApulse GS20 / GS20X AC drive loses Modbus communication?

P09.03 COM1 time-out detection (0.0-100.0 s, factory 0.0) sets the loss timeout; P09.02 selects warn, ramp-stop, coast-stop or no action on loss.

Where is the official AutomationDirect DURApulse GS20 / GS20X AC drive Modbus documentation?

The source is DURApulse GS20 & GS20X Drive User Manual - Chapter 5: Serial Communications (GS20-M 1st Edition, Rev. F (chapter 5)), published free by AutomationDirect at https://cdn.automationdirect.com/static/manuals/gs20m/ch5.pdf.

More AutomationDirect Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: DURApulse GS20 & GS20X Drive User Manual - Chapter 5: Serial Communications · GS20-M 1st Edition, Rev. F (chapter 5). Register numbers, types, scaling and units are reproduced as published; descriptions are our own.