- DURApulse GS20 / GS20X AC drive
Variable frequency drive · Modbus register map
AutomationDirect DURApulse GS20 / GS20X AC drive Modbus register map
Updated 17 November 2026
The DURApulse GS20 and GS20X are AutomationDirect's compact and NEMA 4X general-purpose drives with a built-in RS-485 Modbus RTU/ASCII port. Control goes through command words at 2000h-2002h and status is read from 2100h upward; every parameter Pxx.yy is also a register. This map covers the command and status words, frequency, voltages, the main serial setup parameters and the block-transfer registers.
This page lists 34 Modbus registers for the AutomationDirect DURApulse GS20 / GS20X AC drive — 23 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from AutomationDirect’s own free documentation (linked below) and checked against it.
- Manufacturer
- AutomationDirect
- Model
- DURApulse GS20 / GS20X AC drive
- Equipment type
- Variable frequency drive
- Registers
- 34 (23 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- 1
- Default serial
- 9600 baud
- Documented addressing
- hexadecimal, 0-based
- Also known as
- GS20X, DURApulse GS20, GS21-11P0
Integration notes: AutomationDirect DURApulse GS20 / GS20X AC drive
Set the drive's run source and frequency source to RS-485, then write 2000h (run/stop/direction) and 2001h (frequency in 0.01 Hz) in one function-16 write. Poll 2100h-2106h for fault, state and frequency.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 8192 | Control word 1 | BITMAP16 | Run/stop/direction command | Write |
| HR 8193 | Frequency command | UINT16 | Frequency command 0.01 Hz | Write |
| HR 8448 | Status monitor 1 | UINT16 | Warning/error code | Read |
| HR 8449 | Status monitor 2 | BITMAP16 | Drive state | Read |
| HR 8451 | Output frequency | UINT16 | Output frequency | Read |
| HR 8453 | DC bus voltage | UINT16 | DC bus voltage | Read |
Enable Modbus control & writes
Set P09.00 address and P09.04 protocol (codes 12-17 are RTU), then select RS-485 as the frequency reference (P00.20 = 1 in Remote/Auto or P00.30 = 1 in Local/Hand, per the manual's note) and as the run-command source (see chapter 4).
Communication loss & watchdog
P09.03 COM1 time-out detection (0.0-100.0 s, factory 0.0) sets the loss timeout; P09.02 selects warn, ramp-stop, coast-stop or no action on loss.
Byte order & addressing
- Hex addresses are the wire addresses.
- 2000h-2002h are write-only command words.
- If the RS-485 frequency reference exceeds P01.00, the drive runs at maximum output frequency.
Network setup
- Use P09.04 to pick RTU framing (e.g. 13 = 8N2 RTU); all nodes must match.
Watch out for
- Block transfer registers P09.11-P09.26 let one read/write reach scattered parameters: write the target address (e.g. 8448 for 2100h) into a block-transfer slot.
- Run command bits are a 2-bit code, not independent flags.
AutomationDirect DURApulse GS20 / GS20X AC drive Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1553doc 0611h (41554) | P06.17 Fault record 1 | Most recent fault code (same coding as status monitor 1). | UINT16 | Read | ||||
| HR | 2304doc 0900h (42305) | P09.00 Communication address | RS-485 station address, 1-254. | UINT16 | Read/write | ||||
| HR | 2306doc 0902h (42307) | P09.02 COM1 transmission fault treatment | UINT16 | Read/write | 0 = Warn and continue; 1 = Fault and ramp to stop; 2 = Fault and coast to stop; 3 = No warning, no fault, continue | ||||
| HR | 2308doc 0904h (42309) | P09.04 COM1 communication protocol | UINT16 | Read/write | 1 = 7N2 ASCII; 2 = 7E1 ASCII; 3 = 7O1 ASCII; 4 = 7E2 ASCII; 5 = 7O2 ASCII; 6 = 8N1 ASCII; 7 = 8N2 ASCII; 8 = 8E1 ASCII; 9 = 8O1 ASCII; 10 = 8E2 ASCII; 11 = 8O2 ASCII; 12 = 8N1 RTU; 13 = 8N2 RTU; 14 = 8E1 RTU; 15 = 8O1 RTU; 16 = 8E2 RTU; 17 = 8O2 RTU | ||||
| HR | 2315doc 090Bh (42316) | P09.11 Block transfer 1 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2316doc 090Ch (42317) | P09.12 Block transfer 2 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2317doc 090Dh (42318) | P09.13 Block transfer 3 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2318doc 090Eh (42319) | P09.14 Block transfer 4 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2319doc 090Fh (42320) | P09.15 Block transfer 5 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2320doc 0910h (42321) | P09.16 Block transfer 6 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2321doc 0911h (42322) | P09.17 Block transfer 7 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2322doc 0912h (42323) | P09.18 Block transfer 8 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2323doc 0913h (42324) | P09.19 Block transfer 9 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2324doc 0914h (42325) | P09.20 Block transfer 10 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2325doc 0915h (42326) | P09.21 Block transfer 11 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2326doc 0916h (42327) | P09.22 Block transfer 12 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2327doc 0917h (42328) | P09.23 Block transfer 13 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2328doc 0918h (42329) | P09.24 Block transfer 14 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2329doc 0919h (42330) | P09.25 Block transfer 15 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2330doc 091Ah (42331) | P09.26 Block transfer 16 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2337doc 0921h (42338) | P09.33 PLC command force to 0 | UINT16 | Read/write | |||||
| HR | 8192doc 2000h (48193) | Control word 1 | Run/stop and direction codes; see notes. | BITMAP16 | Write | bit 0 = Run/stop code bit 0 (with bit 1); bit 1 = Run/stop code bit 1; bit 4 = Direction code bit 0 (with bit 5); bit 5 = Direction code bit 1; bit 12 = Enable bits 6-11 (accel set, step speed) | |||
| HR | 8193doc 2001h (48194) | Frequency command | Speed reference in 0.01 Hz. | UINT16 | × 0.01 | Hz | Write | ||
| HR | 8194doc 2002h (48195) | Control word 2 | BITMAP16 | Write | bit 0 = External fault (EF) on; bit 1 = Fault reset; bit 2 = Base block (BB) on; bit 5 = Enable fire mode | ||||
| HR | 8448doc 2100h (48449) | Status monitor 1 | High byte warning code, low byte error code. | UINT16 | Read | ||||
| HR | 8449doc 2101h (48450) | Status monitor 2 | Bits 1-0 run state (00 stop, 01 decel, 10 standby, 11 running); bits 4-3 direction. | BITMAP16 | Read | bit 0 = Run state bit 0; bit 1 = Run state bit 1; bit 2 = JOG command; bit 3 = Direction bit 0; bit 4 = Direction bit 1; bit 8 = Frequency from communication; bit 9 = Frequency from analog/terminal; bit 10 = Run command from communication; bit 11 = Parameters locked; bit 12 = Copy parameters from keypad enabled | |||
| HR | 8450doc 2102h (48451) | Frequency command (status) | Active frequency command. | UINT16 | × 0.01 | Hz | Read | ||
| HR | 8451doc 2103h (48452) | Output frequency | UINT16 | × 0.01 | Hz | Read | |||
| HR | 8453doc 2105h (48454) | DC bus voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 8454doc 2106h (48455) | Output voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 8455doc 2107h (48456) | Multi-step speed step | Current multi-step speed step number. | UINT16 | Read | ||||
| HR | 8457doc 2109h (48458) | Counter value | UINT16 | Read | |||||
| HR | 8458doc 210Ah (48459) | Output power factor angle | UINT16 | × 0.1 | Read | ||||
| HR | 8460doc 210Ch (48461) | Actual motor speed | UINT16 | rpm | Read |
Notes on this map
- AutomationDirect's own manual chapter (cdn.automationdirect.com).
- Parameter-to-register rule: Pxx.yy is at hex xx*256 + yy (P09.00 = 0900h = 42305; the block-transfer example P02.22 = 0216h). Only selected P09 communication parameters are listed; the rest are in chapter 4.
- Values printed as XXX.XX carry two implied decimals (scale 0.01) and XXX.X one (scale 0.1).
- Left out: output current (2104h), whose decimal places shift with the current and depend on 211Fh; output torque (210Bh), because its sign handling is not stated; P09.01 baud rate, P09.03 time-out and P09.09 response delay, whose raw encodings of decimal values are not given in this chapter.
- The P09.02-P09.04 rows of the summary table print the defaults out of line, so their factory defaults are not given here; the manual says P09.04 selects mode, data bits, parity and stop bits.
- Up to 12 words can be read in one request (function 03).
- Control word 1 (2000h): bits 1-0 = 01 stop, 10 run, 11 jog + run; bits 5-4 = 01 forward, 10 reverse, 11 change direction; bits 7-6 accel/decel set; bits 11-8 multi-step speed; bit 12 enables bits 6-11; bits 14-13 = 01 keypad, 10 per P00.21, 11 change operation source.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the AutomationDirect DURApulse GS20 / GS20X AC drive
What Modbus registers does the AutomationDirect DURApulse GS20 / GS20X AC drive have?
This map lists 34 registers: 34 holding registers. 23 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the AutomationDirect DURApulse GS20 / GS20X AC drive Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed in hex with the matching Modicon number (2000h = 48193, 2100h = 48449, 0900h = 42305). The hex value is the wire address; the manual's RTU examples send 21 02 to read 2102h and 20 00 to write 2000h.
What are the minimum Modbus registers to integrate the AutomationDirect DURApulse GS20 / GS20X AC drive?
Start with HR 8192 Control word 1 (Run/stop/direction command); HR 8193 Frequency command (Frequency command 0.01 Hz); HR 8448 Status monitor 1 (Warning/error code); HR 8449 Status monitor 2 (Drive state); HR 8451 Output frequency (Output frequency); HR 8453 DC bus voltage (DC bus voltage).
How do I enable Modbus control of the AutomationDirect DURApulse GS20 / GS20X AC drive?
Set P09.00 address and P09.04 protocol (codes 12-17 are RTU), then select RS-485 as the frequency reference (P00.20 = 1 in Remote/Auto or P00.30 = 1 in Local/Hand, per the manual's note) and as the run-command source (see chapter 4).
What happens when the AutomationDirect DURApulse GS20 / GS20X AC drive loses Modbus communication?
P09.03 COM1 time-out detection (0.0-100.0 s, factory 0.0) sets the loss timeout; P09.02 selects warn, ramp-stop, coast-stop or no action on loss.
Where is the official AutomationDirect DURApulse GS20 / GS20X AC drive Modbus documentation?
The source is DURApulse GS20 & GS20X Drive User Manual - Chapter 5: Serial Communications (GS20-M 1st Edition, Rev. F (chapter 5)), published free by AutomationDirect at https://cdn.automationdirect.com/static/manuals/gs20m/ch5.pdf.
More AutomationDirect Modbus register maps
- Variable frequency drive
AutomationDirect DURApulse GS10 AC drive
GS10 drives (built-in RS-485 port) per the GS10 user manual, 1st edition rev. C, chapter 5.
Also known as: DURApulse GS10, GS10 micro drive - Variable frequency drive
AutomationDirect DURApulse GS3 AC drive
All GS3 drives; status addresses and P9.xx serial-communication parameters from chapter 5 of the user manual.
Also known as: DURApulse GS3, GS3-21P0, GS3-22P0, GS3-23P0, GS3-25P0, GS3-27P5, GS3-2010, GS3-2015, GS3-2020, GS3-2025 - Variable frequency drive
AutomationDirect GS1 series AC drive
All GS1 drives; status addresses and P9.xx serial-communication parameters from chapter 5 of the user manual.
Also known as: GS1-10P2, GS1-10P5, GS1-20P2, GS1-20P5, GS1-21P0, GS1-22P0 - Variable frequency drive
AutomationDirect GS2 series AC drive
All GS2 drives; status addresses and P9.xx serial-communication parameters from chapter 5 of the user manual.
Also known as: GS2-10P2, GS2-10P5, GS2-11P0, GS2-20P5, GS2-21P0, GS2-22P0, GS2-23P0, GS2-25P0, GS2-27P5, GS2-41P0, GS2-42P0, GS2-43P0, GS2-45P0, GS2-47P5
Other variable frequency drives register maps
- Variable frequency drive
Danfoss VLT AQUA Drive FC 202 (Modbus RTU)
VLT AQUA Drive FC 202 using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter data checked against the software 5.4X programming guide.
Also known as: VLT AQUA Drive, FC202, FC-202, AQUA Drive FC 202 - Variable frequency drive
Danfoss VLT Midi Drive FC 280 (Modbus RTU)
VLT Midi Drive FC 280 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC280, FC-280, VLT Midi Drive FC 280, VLT Midi Drive - Variable frequency drive
Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP)
PowerXL DG1 general-purpose and DH1 HVAC drives per PowerXL Series VFD Communication Manual MN040010EN (June 2018).
Also known as: DG1, DH1, PowerXL DG1, PowerXL DH1, DG1 general purpose drive, DH1 HVAC drive - Variable frequency drive
Inovance MD500-PLUS series AC drive
Inovance MD500-PLUS drives with the MD38TX1 RS-485 extension card, Modbus RTU slave, per software guide 19011580 rev. A04.
Also known as: MD500-PLUS, MD500 PLUS, MD500T-PLUS, Inovance MD500-PLUS - Variable frequency drive
INVT Goodrive20 (GD20) general-purpose VFD
INVT Goodrive20 drives using the built-in RS-485 Modbus port, per the GD20 VFD manual V2.1 (chapter 7, communication protocol).
Also known as: GD20, Goodrive20, GD20-EU, GD20-UL, GD20 vector VFD - Variable frequency drive
Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU)
Johnson Controls / PENN VFD68Bxx (200-240 V) and VFD68Cxx (380-480 V) drives on their RJ45 PU port with Modbus RTU selected (P.549 = 1), per the VFD68 Variable Frequency Drives Technical Bulletin, Appendix 4.
Also known as: VFD68Bxx, VFD68Cxx, VFD68BDC-2C, VFD68CDF-2C, PENN VFD68
All variable frequency drives Modbus register maps →
Source: DURApulse GS20 & GS20X Drive User Manual - Chapter 5: Serial Communications · GS20-M 1st Edition, Rev. F (chapter 5). Register numbers, types, scaling and units are reproduced as published; descriptions are our own.