Variable frequency drive · Modbus register map
AutomationDirect DURApulse GS10 AC drive Modbus register map
Updated 17 November 2026
The DURApulse GS10 is AutomationDirect's micro general-purpose drive with a built-in RS-485 Modbus RTU/ASCII port. Control goes through command words at 2000h-2002h and status is read from 2100h upward; every parameter Pxx.yy is also a register. This map covers the command and status words, frequency, voltages, the main serial setup parameters and the block-transfer registers.
This page lists 33 Modbus registers for the AutomationDirect DURApulse GS10 AC drive — 22 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from AutomationDirect’s own free documentation (linked below) and checked against it.
- Manufacturer
- AutomationDirect
- Model
- DURApulse GS10 AC drive
- Equipment type
- Variable frequency drive
- Registers
- 33 (22 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- 1
- Default serial
- 38400 baud, 8N2
- Documented addressing
- hexadecimal, 0-based
- Also known as
- DURApulse GS10, GS10 micro drive
Integration notes: AutomationDirect DURApulse GS10 AC drive
Set the drive's run source and frequency source to RS-485, then write 2000h (run/stop/direction) and 2001h (frequency in 0.01 Hz) in one function-16 write. Poll 2100h-2106h for fault, state and frequency.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 8192 | Control word 1 | BITMAP16 | Run/stop/direction command | Write |
| HR 8193 | Frequency command | UINT16 | Frequency command 0.01 Hz | Write |
| HR 8448 | Status monitor 1 | UINT16 | Warning/error code | Read |
| HR 8449 | Status monitor 2 | BITMAP16 | Drive state | Read |
| HR 8451 | Output frequency | UINT16 | Output frequency | Read |
| HR 8453 | DC bus voltage | UINT16 | DC bus voltage | Read |
Enable Modbus control & writes
Set P09.00 address and P09.04 protocol (codes 12-17 are RTU), then select RS-485 as the frequency reference (P00.20 = 1 in Remote/Auto or P00.30 = 1 in Local/Hand, per the manual's note) and as the run-command source (see chapter 4).
Communication loss & watchdog
P09.03 COM1 time-out detection (0.0-100.0 s, factory 0.0) sets the loss timeout; P09.02 selects warn, ramp-stop, coast-stop or no action on loss.
Byte order & addressing
- Hex addresses are the wire addresses.
- 2000h-2002h are write-only command words.
- If the RS-485 frequency reference exceeds P01.00, the drive runs at maximum output frequency.
Network setup
- Use P09.04 to pick RTU framing (e.g. 13 = 8N2 RTU); all nodes must match.
Watch out for
- Block transfer registers P09.11-P09.26 let one read/write reach scattered parameters: write the target address (e.g. 8448 for 2100h) into a block-transfer slot.
- Run command bits are a 2-bit code, not independent flags.
AutomationDirect DURApulse GS10 AC drive Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1553doc 0611h (41554) | P06.17 Fault record 1 | Most recent fault code (same coding as status monitor 1). | UINT16 | Read | ||||
| HR | 2304doc 0900h (42305) | P09.00 Communication address | RS-485 station address, 1-254. | UINT16 | Read/write | ||||
| HR | 2306doc 0902h (42307) | P09.02 COM1 transmission fault treatment | UINT16 | Read/write | 0 = Warn and continue; 1 = Fault and ramp to stop; 2 = Fault and coast to stop; 3 = No warning, no fault, continue | ||||
| HR | 2308doc 0904h (42309) | P09.04 COM1 communication protocol | UINT16 | Read/write | 1 = 7N2 ASCII; 2 = 7E1 ASCII; 3 = 7O1 ASCII; 4 = 7E2 ASCII; 5 = 7O2 ASCII; 6 = 8N1 ASCII; 7 = 8N2 ASCII; 8 = 8E1 ASCII; 9 = 8O1 ASCII; 10 = 8E2 ASCII; 11 = 8O2 ASCII; 12 = 8N1 RTU; 13 = 8N2 RTU; 14 = 8E1 RTU; 15 = 8O1 RTU; 16 = 8E2 RTU; 17 = 8O2 RTU | ||||
| HR | 2315doc 090Bh (42316) | P09.11 Block transfer 1 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2316doc 090Ch (42317) | P09.12 Block transfer 2 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2317doc 090Dh (42318) | P09.13 Block transfer 3 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2318doc 090Eh (42319) | P09.14 Block transfer 4 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2319doc 090Fh (42320) | P09.15 Block transfer 5 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2320doc 0910h (42321) | P09.16 Block transfer 6 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2321doc 0911h (42322) | P09.17 Block transfer 7 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2322doc 0912h (42323) | P09.18 Block transfer 8 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2323doc 0913h (42324) | P09.19 Block transfer 9 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2324doc 0914h (42325) | P09.20 Block transfer 10 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2325doc 0915h (42326) | P09.21 Block transfer 11 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2326doc 0916h (42327) | P09.22 Block transfer 12 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2327doc 0917h (42328) | P09.23 Block transfer 13 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2328doc 0918h (42329) | P09.24 Block transfer 14 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2329doc 0919h (42330) | P09.25 Block transfer 15 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 2330doc 091Ah (42331) | P09.26 Block transfer 16 | Holds the address of another register; reads/writes go through to it. | UINT16 | Read/write | ||||
| HR | 8192doc 2000h (48193) | Control word 1 | Run/stop and direction codes; see notes. | BITMAP16 | Write | bit 0 = Run/stop code bit 0 (with bit 1); bit 1 = Run/stop code bit 1; bit 4 = Direction code bit 0 (with bit 5); bit 5 = Direction code bit 1; bit 12 = Enable bits 6-11 (accel set, step speed) | |||
| HR | 8193doc 2001h (48194) | Frequency command | Speed reference in 0.01 Hz. | UINT16 | × 0.01 | Hz | Write | ||
| HR | 8194doc 2002h (48195) | Control word 2 | BITMAP16 | Write | bit 0 = External fault (EF) on; bit 1 = Fault reset; bit 2 = Base block (BB) on; bit 5 = Enable fire mode | ||||
| HR | 8448doc 2100h (48449) | Status monitor 1 | High byte warning code, low byte error code. | UINT16 | Read | ||||
| HR | 8449doc 2101h (48450) | Status monitor 2 | Bits 1-0 run state (00 stop, 01 decel, 10 standby, 11 running); bits 4-3 direction. | BITMAP16 | Read | bit 0 = Run state bit 0; bit 1 = Run state bit 1; bit 2 = JOG command; bit 3 = Direction bit 0; bit 4 = Direction bit 1; bit 8 = Frequency from communication; bit 9 = Frequency from analog/terminal; bit 10 = Run command from communication; bit 11 = Parameters locked; bit 12 = Copy parameters from keypad enabled | |||
| HR | 8450doc 2102h (48451) | Frequency command (status) | Active frequency command. | UINT16 | × 0.01 | Hz | Read | ||
| HR | 8451doc 2103h (48452) | Output frequency | UINT16 | × 0.01 | Hz | Read | |||
| HR | 8453doc 2105h (48454) | DC bus voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 8454doc 2106h (48455) | Output voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 8455doc 2107h (48456) | Multi-step speed step | Current multi-step speed step number. | UINT16 | Read | ||||
| HR | 8457doc 2109h (48458) | Counter value | UINT16 | Read | |||||
| HR | 8458doc 210Ah (48459) | Output power factor angle | UINT16 | × 0.1 | Read | ||||
| HR | 8460doc 210Ch (48461) | Actual motor speed | UINT16 | rpm | Read |
Notes on this map
- AutomationDirect's own manual chapter (cdn.automationdirect.com).
- Parameter-to-register rule: Pxx.yy is at hex xx*256 + yy (P09.00 = 0900h = 42305; the block-transfer example P02.22 = 0216h). Only selected P09 communication parameters are listed; the rest are in chapter 4.
- Values printed as XXX.XX carry two implied decimals (scale 0.01) and XXX.X one (scale 0.1).
- Left out: output current (2104h), whose decimal places shift with the current and depend on 211Fh; output torque (210Bh), because its sign handling is not stated; P09.01 baud rate, P09.03 time-out and P09.09 response delay, whose raw encodings of decimal values are not given in this chapter.
- Factory serial settings from the P09 summary: address 1, 38.4 kbps, protocol 13 (8 data bits, no parity, 2 stop bits, RTU).
- Up to 12 words can be read in one request (function 03).
- Control word 1 (2000h): bits 1-0 = 01 stop, 10 run, 11 jog + run; bits 5-4 = 01 forward, 10 reverse, 11 change direction; bits 7-6 accel/decel set; bits 11-8 multi-step speed; bit 12 enables bits 6-11; bits 14-13 = 01 keypad, 10 per P00.21, 11 change operation source.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the AutomationDirect DURApulse GS10 AC drive
What Modbus registers does the AutomationDirect DURApulse GS10 AC drive have?
This map lists 33 registers: 33 holding registers. 22 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the AutomationDirect DURApulse GS10 AC drive Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed in hex with the matching Modicon number (2000h = 48193, 2100h = 48449, 0900h = 42305). The hex value is the wire address; the manual's RTU examples send 21 02 to read 2102h and 20 00 to write 2000h.
What are the minimum Modbus registers to integrate the AutomationDirect DURApulse GS10 AC drive?
Start with HR 8192 Control word 1 (Run/stop/direction command); HR 8193 Frequency command (Frequency command 0.01 Hz); HR 8448 Status monitor 1 (Warning/error code); HR 8449 Status monitor 2 (Drive state); HR 8451 Output frequency (Output frequency); HR 8453 DC bus voltage (DC bus voltage).
How do I enable Modbus control of the AutomationDirect DURApulse GS10 AC drive?
Set P09.00 address and P09.04 protocol (codes 12-17 are RTU), then select RS-485 as the frequency reference (P00.20 = 1 in Remote/Auto or P00.30 = 1 in Local/Hand, per the manual's note) and as the run-command source (see chapter 4).
What happens when the AutomationDirect DURApulse GS10 AC drive loses Modbus communication?
P09.03 COM1 time-out detection (0.0-100.0 s, factory 0.0) sets the loss timeout; P09.02 selects warn, ramp-stop, coast-stop or no action on loss.
Where is the official AutomationDirect DURApulse GS10 AC drive Modbus documentation?
The source is DURApulse GS10 Drive User Manual - Chapter 5: Serial Communications (GS10-M 1st Edition, Rev. C (chapter 5)), published free by AutomationDirect at https://cdn.automationdirect.com/static/manuals/gs10m/ch5.pdf.
More AutomationDirect Modbus register maps
- Variable frequency drive
AutomationDirect DURApulse GS20 / GS20X AC drive
GS20 and GS20X drives (built-in RS-485 port) per the GS20 & GS20X user manual, 1st edition rev. F, chapter 5.
Also known as: GS20X, DURApulse GS20, GS21-11P0 - Variable frequency drive
AutomationDirect DURApulse GS3 AC drive
All GS3 drives; status addresses and P9.xx serial-communication parameters from chapter 5 of the user manual.
Also known as: DURApulse GS3, GS3-21P0, GS3-22P0, GS3-23P0, GS3-25P0, GS3-27P5, GS3-2010, GS3-2015, GS3-2020, GS3-2025 - Variable frequency drive
AutomationDirect GS1 series AC drive
All GS1 drives; status addresses and P9.xx serial-communication parameters from chapter 5 of the user manual.
Also known as: GS1-10P2, GS1-10P5, GS1-20P2, GS1-20P5, GS1-21P0, GS1-22P0 - Variable frequency drive
AutomationDirect GS2 series AC drive
All GS2 drives; status addresses and P9.xx serial-communication parameters from chapter 5 of the user manual.
Also known as: GS2-10P2, GS2-10P5, GS2-11P0, GS2-20P5, GS2-21P0, GS2-22P0, GS2-23P0, GS2-25P0, GS2-27P5, GS2-41P0, GS2-42P0, GS2-43P0, GS2-45P0, GS2-47P5
Other variable frequency drives register maps
- Variable frequency drive
Danfoss iC2-Micro frequency converter (Modbus RTU)
Danfoss iC2-Micro frequency converters using the built-in RS-485 port with P 10.1.1 Protocol = [2] Modbus RTU and the FC control profile; Application Guide AB413939445838en-000401.
Also known as: iC2-Micro, iC2 Micro, Danfoss iC2 - Variable frequency drive
Danfoss VLT Micro Drive FC 51 (Modbus RTU)
VLT Micro Drive FC 51 on the built-in RS-485 port with 8-30 = Modbus, software 3.1x; registers per design guide MG02K402 and parameter data per programming guide MG02C702.
Also known as: FC 51, FC51, VLT Micro Drive, VLT Micro Drive FC 51 - Variable frequency drive (variable speed starter)
Eaton PowerXL DE1 variable speed starter (Modbus RTU)
Eaton PowerXL DE1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DE1, DE11, PowerXL DE1, PowerXL DE11, DE1-12, DE1-34, DE11-12, DE11-34 - Variable frequency drive
Inovance MD200 series compact AC drive
Inovance MD200 single- and three-phase compact drives using the RS-485 Modbus RTU port, per user guide 19012113 rev. C02.
Also known as: MD200, MD200T, MD200S, MD200-NC, Inovance MD200 - Variable frequency drive
INVT Goodrive10 (GD10) mini VFD
INVT Goodrive10 mini drives using the built-in RS-485 Modbus RTU port, per the GD10 VFD manual V2.9 (chapter 7).
Also known as: GD10, Goodrive10, GD10 mini VFD - Variable frequency drive
INVT Goodrive350A (GD350A) high-performance multifunction VFD
INVT Goodrive350A drives using the built-in RS-485 Modbus RTU port, per the GD350A manual V1.3 (chapter 9).
Also known as: GD350A, Goodrive350A, GD350A series
All variable frequency drives Modbus register maps →
Source: DURApulse GS10 Drive User Manual - Chapter 5: Serial Communications · GS10-M 1st Edition, Rev. C (chapter 5). Register numbers, types, scaling and units are reproduced as published; descriptions are our own.