Variable frequency drive · Modbus register map

AutomationDirect DURApulse GS10 AC drive Modbus register map

Updated 17 November 2026

Short answer

The DURApulse GS10 is AutomationDirect's micro general-purpose drive with a built-in RS-485 Modbus RTU/ASCII port. Control goes through command words at 2000h-2002h and status is read from 2100h upward; every parameter Pxx.yy is also a register. This map covers the command and status words, frequency, voltages, the main serial setup parameters and the block-transfer registers.

This page lists 33 Modbus registers for the AutomationDirect DURApulse GS10 AC drive — 22 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from AutomationDirect’s own free documentation (linked below) and checked against it.

Manufacturer
AutomationDirect
Model
DURApulse GS10 AC drive
Equipment type
Variable frequency drive
Registers
33 (22 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
1
Default serial
38400 baud, 8N2
Documented addressing
hexadecimal, 0-based
Also known as
DURApulse GS10, GS10 micro drive
Source document
DURApulse GS10 Drive User Manual - Chapter 5: Serial Communications · GS10-M 1st Edition, Rev. C (chapter 5)
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: AutomationDirect DURApulse GS10 AC drive

Integration in brief

Set the drive's run source and frequency source to RS-485, then write 2000h (run/stop/direction) and 2001h (frequency in 0.01 Hz) in one function-16 write. Poll 2100h-2106h for fault, state and frequency.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 8192Control word 1BITMAP16Run/stop/direction commandWrite
HR 8193Frequency commandUINT16Frequency command 0.01 HzWrite
HR 8448Status monitor 1UINT16Warning/error codeRead
HR 8449Status monitor 2BITMAP16Drive stateRead
HR 8451Output frequencyUINT16Output frequencyRead
HR 8453DC bus voltageUINT16DC bus voltageRead

Enable Modbus control & writes

Set P09.00 address and P09.04 protocol (codes 12-17 are RTU), then select RS-485 as the frequency reference (P00.20 = 1 in Remote/Auto or P00.30 = 1 in Local/Hand, per the manual's note) and as the run-command source (see chapter 4).

Communication loss & watchdog

P09.03 COM1 time-out detection (0.0-100.0 s, factory 0.0) sets the loss timeout; P09.02 selects warn, ramp-stop, coast-stop or no action on loss.

Byte order & addressing

Network setup

Watch out for

AutomationDirect DURApulse GS10 AC drive Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

33 of 33 shown
AutomationDirect DURApulse GS10 AC drive Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1553doc 0611h (41554)P06.17 Fault record 1Most recent fault code (same coding as status monitor 1).UINT16Read
HR2304doc 0900h (42305)P09.00 Communication addressRS-485 station address, 1-254.UINT16Read/write
HR2306doc 0902h (42307)P09.02 COM1 transmission fault treatmentUINT16Read/write0 = Warn and continue; 1 = Fault and ramp to stop; 2 = Fault and coast to stop; 3 = No warning, no fault, continue
HR2308doc 0904h (42309)P09.04 COM1 communication protocolUINT16Read/write1 = 7N2 ASCII; 2 = 7E1 ASCII; 3 = 7O1 ASCII; 4 = 7E2 ASCII; 5 = 7O2 ASCII; 6 = 8N1 ASCII; 7 = 8N2 ASCII; 8 = 8E1 ASCII; 9 = 8O1 ASCII; 10 = 8E2 ASCII; 11 = 8O2 ASCII; 12 = 8N1 RTU; 13 = 8N2 RTU; 14 = 8E1 RTU; 15 = 8O1 RTU; 16 = 8E2 RTU; 17 = 8O2 RTU
HR2315doc 090Bh (42316)P09.11 Block transfer 1Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2316doc 090Ch (42317)P09.12 Block transfer 2Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2317doc 090Dh (42318)P09.13 Block transfer 3Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2318doc 090Eh (42319)P09.14 Block transfer 4Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2319doc 090Fh (42320)P09.15 Block transfer 5Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2320doc 0910h (42321)P09.16 Block transfer 6Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2321doc 0911h (42322)P09.17 Block transfer 7Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2322doc 0912h (42323)P09.18 Block transfer 8Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2323doc 0913h (42324)P09.19 Block transfer 9Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2324doc 0914h (42325)P09.20 Block transfer 10Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2325doc 0915h (42326)P09.21 Block transfer 11Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2326doc 0916h (42327)P09.22 Block transfer 12Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2327doc 0917h (42328)P09.23 Block transfer 13Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2328doc 0918h (42329)P09.24 Block transfer 14Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2329doc 0919h (42330)P09.25 Block transfer 15Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR2330doc 091Ah (42331)P09.26 Block transfer 16Holds the address of another register; reads/writes go through to it.UINT16Read/write
HR8192doc 2000h (48193)Control word 1Run/stop and direction codes; see notes.BITMAP16Writebit 0 = Run/stop code bit 0 (with bit 1); bit 1 = Run/stop code bit 1; bit 4 = Direction code bit 0 (with bit 5); bit 5 = Direction code bit 1; bit 12 = Enable bits 6-11 (accel set, step speed)
HR8193doc 2001h (48194)Frequency commandSpeed reference in 0.01 Hz.UINT16× 0.01HzWrite
HR8194doc 2002h (48195)Control word 2BITMAP16Writebit 0 = External fault (EF) on; bit 1 = Fault reset; bit 2 = Base block (BB) on; bit 5 = Enable fire mode
HR8448doc 2100h (48449)Status monitor 1High byte warning code, low byte error code.UINT16Read
HR8449doc 2101h (48450)Status monitor 2Bits 1-0 run state (00 stop, 01 decel, 10 standby, 11 running); bits 4-3 direction.BITMAP16Readbit 0 = Run state bit 0; bit 1 = Run state bit 1; bit 2 = JOG command; bit 3 = Direction bit 0; bit 4 = Direction bit 1; bit 8 = Frequency from communication; bit 9 = Frequency from analog/terminal; bit 10 = Run command from communication; bit 11 = Parameters locked; bit 12 = Copy parameters from keypad enabled
HR8450doc 2102h (48451)Frequency command (status)Active frequency command.UINT16× 0.01HzRead
HR8451doc 2103h (48452)Output frequencyUINT16× 0.01HzRead
HR8453doc 2105h (48454)DC bus voltageUINT16× 0.1VRead
HR8454doc 2106h (48455)Output voltageUINT16× 0.1VRead
HR8455doc 2107h (48456)Multi-step speed stepCurrent multi-step speed step number.UINT16Read
HR8457doc 2109h (48458)Counter valueUINT16Read
HR8458doc 210Ah (48459)Output power factor angleUINT16× 0.1Read
HR8460doc 210Ch (48461)Actual motor speedUINT16rpmRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the AutomationDirect DURApulse GS10 AC drive

What Modbus registers does the AutomationDirect DURApulse GS10 AC drive have?

This map lists 33 registers: 33 holding registers. 22 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the AutomationDirect DURApulse GS10 AC drive Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed in hex with the matching Modicon number (2000h = 48193, 2100h = 48449, 0900h = 42305). The hex value is the wire address; the manual's RTU examples send 21 02 to read 2102h and 20 00 to write 2000h.

What are the minimum Modbus registers to integrate the AutomationDirect DURApulse GS10 AC drive?

Start with HR 8192 Control word 1 (Run/stop/direction command); HR 8193 Frequency command (Frequency command 0.01 Hz); HR 8448 Status monitor 1 (Warning/error code); HR 8449 Status monitor 2 (Drive state); HR 8451 Output frequency (Output frequency); HR 8453 DC bus voltage (DC bus voltage).

How do I enable Modbus control of the AutomationDirect DURApulse GS10 AC drive?

Set P09.00 address and P09.04 protocol (codes 12-17 are RTU), then select RS-485 as the frequency reference (P00.20 = 1 in Remote/Auto or P00.30 = 1 in Local/Hand, per the manual's note) and as the run-command source (see chapter 4).

What happens when the AutomationDirect DURApulse GS10 AC drive loses Modbus communication?

P09.03 COM1 time-out detection (0.0-100.0 s, factory 0.0) sets the loss timeout; P09.02 selects warn, ramp-stop, coast-stop or no action on loss.

Where is the official AutomationDirect DURApulse GS10 AC drive Modbus documentation?

The source is DURApulse GS10 Drive User Manual - Chapter 5: Serial Communications (GS10-M 1st Edition, Rev. C (chapter 5)), published free by AutomationDirect at https://cdn.automationdirect.com/static/manuals/gs10m/ch5.pdf.