Variable frequency drive · Modbus register map
AutomationDirect DURApulse GS3 AC drive Modbus register map
Updated 17 November 2026
The GS3 is an AutomationDirect AC drive with a built-in RS-485 port running Modbus ASCII or RTU. Drive parameters P0.00-P9.xx map to holding registers (parameter group x 256 + number), and read-only status registers at 2100h report fault code, run state, frequencies, voltages and load. This map covers the status block and the P9 serial control parameters used to run the drive over Modbus.
This page lists 21 Modbus registers for the AutomationDirect DURApulse GS3 AC drive — 11 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from AutomationDirect’s own free documentation (linked below) and checked against it.
- Manufacturer
- AutomationDirect
- Model
- DURApulse GS3 AC drive
- Equipment type
- Variable frequency drive
- Registers
- 21 (11 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- Not stated
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- DURApulse GS3, GS3-21P0, GS3-22P0, GS3-23P0, GS3-25P0, GS3-27P5, GS3-2010, GS3-2015, GS3-2020, GS3-2025
Integration notes: AutomationDirect DURApulse GS3 AC drive
Set P9.02 to an RTU mode, P3.00 to serial operation and P4.00 = 5 for serial frequency source, then write speed (P9.26, x10) and run (P9.27). Monitor Status Monitor 1/2 and output frequency at 2100h-2103h.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2330 | P9.26 Serial Comm Speed Reference | UINT16 | Speed reference | Read/write |
| HR 2331 | P9.27 Serial Comm RUN Command | UINT16 | Run/stop | Read/write |
| HR 2332 | P9.28 Serial Comm Direction Command | UINT16 | Direction | Read/write |
| HR 8448 | Status Monitor 1 | UINT16 | Fault code | Read |
| HR 8449 | Status Monitor 2 | BITMAP16 | Run state bits | Read |
| HR 8451 | Output Frequency H | UINT16 | Output frequency | Read |
Enable Modbus control & writes
Set P3.00 (source of operation) to 3 or 4 and P4.00 (source of frequency) to 5 for serial control, as referenced in Status Monitor 2; set P9.00-P9.02 for address, baud and protocol from the keypad.
Communication loss & watchdog
P9.04 enables communication time-out detection, P9.05 sets the time (0.1-60.0 s) and P9.03 selects the reaction (keep running, ramp stop, coast stop).
Byte order & addressing
- Factory protocol is Modbus ASCII, not RTU.
- Speed reference has an implied decimal: write 600 for 60.0 Hz.
- Hex addresses are wire addresses: 091Ah = 2330 decimal = 42331 Modicon.
Network setup
- P9.00 address 1-254, P9.01 baud code (the setup example uses 01 = 9600 baud), P9.02 protocol/format.
- Writes to P0-P8 parameters can be grouped through the block transfer parameters P9.11 onward.
Watch out for
- Some faults only show in Status Monitor 1 after a hard trip; warnings may not appear there.
AutomationDirect DURApulse GS3 AC drive Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 2304doc 0900h (42305) | P9.00 Communication Address | Drive address 1-254. | UINT16 | Read/write | ||||
| HR | 2305doc 0901h (42306) | P9.01 Transmission Speed | Baud rate code; the setup example uses 01 = 9600 baud. | UINT16 | Read/write | ||||
| HR | 2306doc 0902h (42307) | P9.02 Communication Protocol | Factory default 0 is Modbus ASCII. | UINT16 | Read/write | 0 = ASCII 7N2; 1 = ASCII 7E1; 2 = ASCII 7O1; 3 = RTU 8N2; 4 = RTU 8E1; 5 = RTU 8O1 | |||
| HR | 2307doc 0903h (42308) | P9.03 Transmission Fault Treatment | UINT16 | Read/write | 0 = Display fault, keep running; 1 = Display fault, ramp to stop; 2 = Display fault, coast to stop; 3 = No fault, keep running | ||||
| HR | 2308doc 0904h (42309) | P9.04 Time Out Detection | UINT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 2330doc 091Ah (42331) | P9.26 Serial Comm Speed Reference | 0.0-400.0 Hz with implied decimal (600 = 60.0 Hz). | UINT16 | × 0.1 | Hz | Read/write | ||
| HR | 2331doc 091Bh (42332) | P9.27 Serial Comm RUN Command | UINT16 | Read/write | 0 = Stop; 1 = Run | ||||
| HR | 2332doc 091Ch (42333) | P9.28 Serial Comm Direction Command | UINT16 | Read/write | 0 = Forward; 1 = Reverse | ||||
| HR | 2333doc 091Dh (42334) | P9.29 Serial Comm External Fault | UINT16 | Read/write | 0 = No fault; 1 = External fault | ||||
| HR | 2334doc 091Eh (42335) | P9.30 Serial Comm Fault Reset | UINT16 | Read/write | 0 = No action; 1 = Fault reset | ||||
| HR | 2335doc 091Fh (42336) | P9.31 Serial Comm JOG Command | UINT16 | Read/write | 0 = Stop; 1 = Jog | ||||
| HR | 8448doc 2100h (48449) | Status Monitor 1 | Present fault code. | UINT16 | Read | 0 = No fault; 1 = Over-current (oc); 2 = Over-voltage (ov); 3 = Overheat (oH); 4 = Overload (oL); 5 = Thermal overload 1 (oL1); 6 = Over-torque (oL2); 7 = External fault (EF); 8 = CPU failure 1 (cF1); 9 = CPU failure 2 (cF2); 10 = CPU failure 3 (cF3); 11 = Hardware protection failure (HPF); 12 = Over-current during accel (ocA); 13 = Over-current during decel (ocd); 14 = Over-current at steady state (ocn); 15 = Ground fault or fuse failure (GFF); 16 = Low voltage (Lv); 17 = Input power 3-phase loss (PHL); 18 = External base-block (bb); 19 = Auto adjust accel/decel failure (cFA); 20 = Software protection code (codE); 21 = PID feedback loss (FbE); 22 = Encoder feedback loss; 23 = Output shorted (occ); 24 = Momentary power loss | |||
| HR | 8449doc 2101h (48450) | Status Monitor 2 | Bits 0-1 run state (0 stop..3 run); bits 3-4 direction (0 FWD..3 REV). | BITMAP16 | Read | bit 2 = JOG active; bit 8 = Frequency source = serial comm (P4.00 = 5); bit 9 = Frequency source = AI terminal; bit 10 = Operation source = serial comm (P3.00 = 3 or 4); bit 11 = Parameters locked (P9.07 = 1) | |||
| HR | 8450doc 2102h (48451) | Frequency Command F | Frequency setpoint (XXX.X). | UINT16 | × 0.1 | Hz | Read | ||
| HR | 8451doc 2103h (48452) | Output Frequency H | Output frequency (XXX.X). | UINT16 | × 0.1 | Hz | Read | ||
| HR | 8453doc 2105h (48454) | DC Bus Voltage d | (XXX.X) | UINT16 | × 0.1 | V | Read | ||
| HR | 8454doc 2106h (48455) | Output Voltage U | RMS line-to-line output voltage (XXX.X). | UINT16 | × 0.1 | V | Read | ||
| HR | 8455doc 2107h (48456) | Motor RPM | Estimated motor speed. | UINT16 | rpm | Read | |||
| HR | 8456doc 2108h (48457) | Scale Frequency | Output frequency x P8.01; low word at 2108h, high word at 2109h. | UINT32 | CDAB | Read | |||
| HR | 8459doc 210Bh (48460) | % Load | Output current / drive rated current x 100. | UINT16 | % | Read | |||
| HR | 8464doc 2110h (48465) | Firmware Version | UINT16 | Read |
Notes on this map
- AutomationDirect's own manual chapter (cdn.automationdirect.com).
- Parameter-to-register rule: Px.yy is at hex x*256 + yy (e.g. P9.26 = 091Ah = 42331); the full list is in the chapter's parameter address tables. Only the P9 communication/control parameters are included here.
- Status values marked XXX.X in the manual carry one implied decimal (scale 0.1).
- Scale Frequency is split into low word (2108h) and high word (2109h), so it is listed as a 32-bit value with the low word first (CDAB); its unit depends on P8.01.
- P9.05 (communication time-out, 0.1-60.0 s) is left out because its raw encoding is not stated in this chapter.
- The factory protocol (P9.02 = 0) is Modbus ASCII 7N2; set 3, 4 or 5 for RTU.
- Speed reference scaling: the manual's example frame 01 10 09 1B 00 02 04 02 58 00 01 writes 0258h (600) for 60 Hz; it starts at 091Bh although the table puts P9.26 at 091Ah (42331). The table address is used here.
- Left out: Output Current (2104h), Power Factor Angle (210Ah) and PID setpoint/feedback (210Ch/210Dh) because no decimal format is given for them.
- P9.01 baud codes are not readable in the chapter's summary table; the setup example uses 01 = 9600 baud.
- The P9.00/P9.01 rows of the chapter's summary table are not readable, so their factory defaults are not given here.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the AutomationDirect DURApulse GS3 AC drive
What Modbus registers does the AutomationDirect DURApulse GS3 AC drive have?
This map lists 21 registers: 21 holding registers. 11 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the AutomationDirect DURApulse GS3 AC drive Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists each register in hex and as a Modicon number: hex 0000h = 40001, 2100h = 48449. The hex value is the wire address. CLICK PLCs need a six-digit form (402331 instead of 42331).
What byte order does the AutomationDirect DURApulse GS3 AC drive use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the AutomationDirect DURApulse GS3 AC drive?
Start with HR 2330 P9.26 Serial Comm Speed Reference (Speed reference); HR 2331 P9.27 Serial Comm RUN Command (Run/stop); HR 2332 P9.28 Serial Comm Direction Command (Direction); HR 8448 Status Monitor 1 (Fault code); HR 8449 Status Monitor 2 (Run state bits); HR 8451 Output Frequency H (Output frequency).
How do I enable Modbus control of the AutomationDirect DURApulse GS3 AC drive?
Set P3.00 (source of operation) to 3 or 4 and P4.00 (source of frequency) to 5 for serial control, as referenced in Status Monitor 2; set P9.00-P9.02 for address, baud and protocol from the keypad.
What happens when the AutomationDirect DURApulse GS3 AC drive loses Modbus communication?
P9.04 enables communication time-out detection, P9.05 sets the time (0.1-60.0 s) and P9.03 selects the reaction (keep running, ramp stop, coast stop).
Where is the official AutomationDirect DURApulse GS3 AC drive Modbus documentation?
The source is DURApulse GS3 AC Drives User Manual - Chapter 5: GS3 Modbus Communications (GS3-M 2nd Edition (chapter 5)), published free by AutomationDirect at https://cdn.automationdirect.com/static/manuals/gs3m/ch5.pdf.
More AutomationDirect Modbus register maps
- Variable frequency drive
AutomationDirect DURApulse GS10 AC drive
GS10 drives (built-in RS-485 port) per the GS10 user manual, 1st edition rev. C, chapter 5.
Also known as: DURApulse GS10, GS10 micro drive - Variable frequency drive
AutomationDirect DURApulse GS20 / GS20X AC drive
GS20 and GS20X drives (built-in RS-485 port) per the GS20 & GS20X user manual, 1st edition rev. F, chapter 5.
Also known as: GS20X, DURApulse GS20, GS21-11P0 - Variable frequency drive
AutomationDirect GS1 series AC drive
All GS1 drives; status addresses and P9.xx serial-communication parameters from chapter 5 of the user manual.
Also known as: GS1-10P2, GS1-10P5, GS1-20P2, GS1-20P5, GS1-21P0, GS1-22P0 - Variable frequency drive
AutomationDirect GS2 series AC drive
All GS2 drives; status addresses and P9.xx serial-communication parameters from chapter 5 of the user manual.
Also known as: GS2-10P2, GS2-10P5, GS2-11P0, GS2-20P5, GS2-21P0, GS2-22P0, GS2-23P0, GS2-25P0, GS2-27P5, GS2-41P0, GS2-42P0, GS2-43P0, GS2-45P0, GS2-47P5
Other variable frequency drives register maps
- Variable frequency drive
Danfoss VLT AutomationDrive FC 301/302 (Modbus RTU)
VLT AutomationDrive FC 301 and FC 302 (0.25-75 kW design guide; same scheme across sizes) using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter data checked against the software 9.5x / 48.96 programming guide.
Also known as: VLT AutomationDrive, FC 301, FC301, FC302, FC-302, FC-301, FC 300 - Variable frequency drive
Danfoss VACON VACON 100 family (built-in Modbus RTU / Modbus TCP)
VACON 100 INDUSTRIAL, FLOW, HVAC and 100 X drives using the built-in RS-485 Modbus RTU or Ethernet Modbus TCP/UDP (manual DPD00156D); application IDs per the VACON 100 INDUSTRIAL application guide DPD00927L (FW0072V037).
Also known as: VACON 100 INDUSTRIAL, VACON 100 FLOW, VACON 100 HVAC, VACON 100 X, VACON0100 - Variable frequency drive (HVAC / pump)
Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU)
Fuji Electric FRENIC-HVAC (AR) and FRENIC-AQUA (AQ) inverters on the RS-485 port in Modbus RTU mode (y10 = 0); RS-485 Communication User's Manual 24A7-E-0021b.
Also known as: FRENIC-HVAC, FRENIC-AQUA, FRN-AR, FRN-AQ - Variable frequency drive
Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU)
Invertek Optidrive Coolvert HVAC compressor drives on the terminal or RJ45 Modbus RTU port, per user guide version 2.01.
Also known as: Optidrive CoolVert, Coolvert - Variable frequency drive
INVT Goodrive200A (GD200A) general-purpose VFD
INVT Goodrive200A drives using the built-in RS-485 Modbus port, per the GD200A manual V3.1 (chapter 9).
Also known as: GD200A, Goodrive200A, GD200A general VFD - Variable frequency drive
Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU)
Lenze i510 cabinet inverters 0.25-2.2 kW with the Modbus/CANopen control unit, selector set to Modbus, firmware 01.01.01.00 as documented in the commissioning manual.
Also known as: i500 series, i510 Cabinet, I51AE
All variable frequency drives Modbus register maps →
Source: DURApulse GS3 AC Drives User Manual - Chapter 5: GS3 Modbus Communications · GS3-M 2nd Edition (chapter 5). Register numbers, types, scaling and units are reproduced as published; descriptions are our own.