Easy Modbus
  1. Home
  2. Modbus register maps
  3. Invertek Drives
  4. Optidrive Coolvert compressor drive (built-in Modbus RTU)

Variable frequency drive · Modbus register map

Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The Optidrive Coolvert is Invertek's variable speed drive for refrigeration and HVAC compressors (BLDC, PM, induction and synchronous reluctance). Modbus RTU is built in on control terminals 1-3 and the RJ45 port. Registers 1-5 take the control word, speed set point in rps and ramp time; registers 7-45 report speed, current, power, trip codes, energy and run time. Every parameter also has its own register (P1-11 = 111).

This page lists 46 Modbus registers for the Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU) — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Invertek Drives’s own free documentation (linked below) and checked against it.

Manufacturer
Invertek Drives
Model
Optidrive Coolvert compressor drive (built-in Modbus RTU)
Equipment type
Variable frequency drive
Registers
46 (14 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
115200 baud, 8N1
Documented addressing
1-based (subtract 1 for the wire address)
Also known as
Optidrive CoolVert, Coolvert
Source document
Optidrive Coolvert User Guide · Version 2.01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU)

Integration in brief

Set P1-11 = 0, close the STO circuit, then write register 1 = 1 to run and register 2 with the speed in 0.1 rps. Poll registers 7, 8, 10 and 9 for speed, current, power and the trip code.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Drive control wordBITMAP16Control word: run, coast stop, resetRead/write
HR 1Speed set pointINT16Speed set point, 0.1 rpsRead/write
HR 6Output frequency (compressor speed)UINT16Compressor speed, 0.1 rpsRead
HR 7Output currentUINT16Output current, 0.1 ARead
HR 8Trip codeUINT16Trip codeRead
HR 9Output powerUINT16Output power, 0.01 kWRead
HR 110P1-11 Primary command sourceUINT16P1-11 command sourceRead/write

Enable Modbus control & writes

Set P1-11 = 0 (Modbus mode). The STO inputs (terminals 8 and 9) must be energised for the drive to run. Set the drive address in P6-01 (or a separate Modbus address in P6-08), the baud rate in P6-02 and parity in P6-03. Set P6-06 = 1 to take ramp times from register 4.

Communication loss & watchdog

P6-04 sets the communication-loss time (0-60 s, default 5 s). P6-05 picks the reaction: 0 trip (default), 1 ramp to stop then trip, 2 ramp to stop without a trip, 3 run at the signal-loss speed P3-11. A comms loss trip shows as code 50 (SC-F01).

Byte order & addressing

Network setup

Watch out for

Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

46 of 46 shown
Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1Drive control wordRun, coast stop, fault reset, relay and crankcase heating commands.BITMAP16Read/writebit 0 = Run (1) / stop (0); bit 2 = Coast stop request; bit 3 = Fault reset request (return to 0 after reset); bit 4 = User relay control (P3-05 = 6); bit 5 = Activate crankcase heating
HR1doc 2Speed set point600 = 60.0 rps. Negative values only if enabled by parameter.INT16× 0.1rpsRead/write
HR3doc 4Modbus user ramp time3000 = 300.0 s; used only when P6-06 = 1.UINT16× 0.1sRead/write
HR4doc 5Speed reference (IDL format)Printed scaling: 3000 = 50.0 Hz.UINT16Read/write
HR6doc 7Output frequency (compressor speed)600 = 60.0 rps (P0-60).UINT16× 0.1rpsRead
HR7doc 8Output current100 = 10.0 A.UINT16× 0.1ARead
HR8doc 9Trip codeActive trip code; 0 when healthy.UINT16Read0 = No trip; 3 = O-I over current; 5 = PS-trp power stage trip; 6 = O-Volt over voltage; 7 = U-Volt under voltage; 10 = P-DEF load default parameters; 11 = E-Trip external trip (STO opened while running); 12 = SC-OBS Optibus serial comms fault; 13 = Flt-DC excessive DC bus ripple; 14 = P-Loss input phase loss; 15 = h O-I hardware over current; 17 = DATA-F I/O processor data error; 18 = 4-20F 4-20 mA signal out of range; 19 = DATA-E motor control processor data error; 20 = U-DEF user parameters default; 21 = F-PTC motor PTC overheat; 22 = FAN-F drive cooling fan fault; 23 = O-hEAt ambient temperature too high; 26 = Out-F drive output fault; 29 = STO-F fault in STO circuit; 40 = AtF-01 stator resistance unbalance; 41 = AtF-02 stator resistance too large; 42 = AtF-03 motor inductance too low; 43 = AtF-04 motor inductance too large; 44 = AtF-05 parameters not convergent; 49 = Out-Ph motor output phase loss; 50 = SC-F01 Modbus comms fault; 81 = OI-U phase U over current; 82 = OI-V phase V over current; 83 = OI-W phase W over current; 88 = Out-U phase U output fault; 89 = Out-V phase V output fault; 90 = Out-W phase W output fault; 97 = SC-Los IO-PS comms loss; 98 = DATA-03 wrong VDo3 checksum; 101 = STO-R STO opened at drive running; 102 = ML-Run mains loss at running; 103 = FW-Err PS firmware is changed; 107 = Stall compressor is stalled; 253 = HW-ID hardware ID not supported; 254 = Type-E drive ID not supported
HR9doc 10Output power1000 = 10.00 kW.UINT16× 0.01kWRead
HR10doc 11Digital input statusBit 0 = digital input 1 (P0-03).BITMAP16Readbit 0 = Digital input 1
HR11doc 12Rating IDFrame size and input voltage code (P0-29).UINT16Read
HR12doc 13Power ratingP0-29 entry 2.UINT16Read
HR13doc 14Voltage ratingP0-29 entry 3.UINT16Read
HR14doc 15IO processor software version100 = 1.00.UINT16× 0.01Read
HR15doc 16Compressor control processor software version100 = 1.00.UINT16× 0.01Read
HR16doc 17Drive typeP0-29 entry 4 (drive ID).UINT16Read
HR19doc 20Analogue input signal level1000 = 100.0 % (P0-01, range -100.0 to 100.0 %).INT16× 0.1%Read
HR21doc 22Pre-ramp speed reference600 = 60.0 rps.INT16× 0.1rpsRead
HR22doc 23DC bus voltage600 = 600 V (P0-20).UINT16VRead
HR23doc 24Drive temperatureHeatsink temperature, 40 = 40 °C (P0-21).INT16°CRead
HR24doc 25Drive serial number 4Serial number part (P0-30).UINT16Read
HR25doc 26Drive serial number 3Serial number part (P0-30).UINT16Read
HR26doc 27Drive serial number 2Serial number part (P0-30).UINT16Read
HR27doc 28Drive serial number 1Serial number part (P0-30).UINT16Read
HR28doc 29Relay output statusUINT16Read0 = Open; 1 = Closed
HR29doc 30Last two faultsTwo trip codes, one per byte (P0-13).UINT16Read
HR30doc 31Previous two faultsTwo older trip codes, one per byte (P0-13).UINT16Read
HR31doc 32kWh meter100 = 10.0 kWh; rolls into the MWh meter at 999.9 (P0-26).UINT16× 0.1kWhRead
HR32doc 33MWh meter100 = 100 MWh (P0-27).UINT16MWhRead
HR33doc 34Running time - hoursHours run since manufacture (P0-31).UINT16hRead
HR34doc 35Running time - min/secMinutes and seconds part of P0-31; packing not stated.UINT16Read
HR35doc 36Run time since enable - hoursP0-34.UINT16hRead
HR36doc 37Run time since enable - min/secMinutes and seconds part of P0-34; packing not stated.UINT16Read
HR38doc 39Room (control PCB) temperature40 = 40 °C (P0-05).INT16°CRead
HR39doc 40Speed reference valuePrinted scaling: 3000 = 50 Hz.INT16Read
HR41doc 42Compressor speed (IDL format)Printed scaling: 3000 = 50 Hz.INT16Read
HR42doc 43Compressor output voltage100 = 100 V AC (P0-11).UINT16VRead
HR43doc 44Indirect parameter access indexParameter to access through register 45.UINT16Read/write
HR44doc 45Indirect parameter access valueValue of the parameter chosen in register 44.UINT16Read/write
HR110doc 111P1-11 Primary command sourceSet 0 for Modbus control.UINT16Read/write0 = Modbus control; 1 = Terminal mode; 2 = Terminal mode, start when AI1 > 10 %; 3 = User PI mode; 4 = Slave mode
HR600doc 601P6-01 Fieldbus drive address1-63, default 1; Modbus address unless P6-08 is set.UINT16Read/write
HR602doc 603P6-03 Modbus data formatUINT16Read/write0 = No parity, 1 stop bit (default); 1 = No parity, 2 stop bits; 2 = Odd parity, 1 stop bit; 3 = Even parity, 1 stop bit
HR603doc 604P6-04 Communications loss timeout0-60 s, default 5.UINT16sRead/write
HR604doc 605P6-05 Communications loss actionUINT16Read/write0 = Trip; 1 = Ramp to stop then trip; 2 = Ramp to stop (no trip); 3 = Run at signal loss speed P3-11
HR605doc 606P6-06 Fieldbus ramp control enable1 = ramps come from register 4.UINT16Read/write0 = Disabled (internal ramps); 1 = Enabled (ramps from fieldbus)
HR606doc 607P6-07 Modbus response delayExtra characters of delay, 0-16.UINT16Read/write
HR607doc 608P6-08 Modbus address0-200; 0 = use P6-01 for Modbus too.UINT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU)

What Modbus registers does the Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU) have?

This map lists 46 registers: 46 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers from 1 and tells masters that start at register 0 to subtract 1, so control word register 1 is wire address 0. Parameters use their group and number as the register (P6-04 = register 604 = wire address 603).

What are the minimum Modbus registers to integrate the Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU)?

Start with HR 0 Drive control word (Control word: run, coast stop, reset); HR 1 Speed set point (Speed set point, 0.1 rps); HR 6 Output frequency (compressor speed) (Compressor speed, 0.1 rps); HR 7 Output current (Output current, 0.1 A); HR 8 Trip code (Trip code); HR 9 Output power (Output power, 0.01 kW); HR 110 P1-11 Primary command source (P1-11 command source).

How do I enable Modbus control of the Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU)?

Set P1-11 = 0 (Modbus mode). The STO inputs (terminals 8 and 9) must be energised for the drive to run. Set the drive address in P6-01 (or a separate Modbus address in P6-08), the baud rate in P6-02 and parity in P6-03. Set P6-06 = 1 to take ramp times from register 4.

What happens when the Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU) loses Modbus communication?

P6-04 sets the communication-loss time (0-60 s, default 5 s). P6-05 picks the reaction: 0 trip (default), 1 ramp to stop then trip, 2 ramp to stop without a trip, 3 run at the signal-loss speed P3-11. A comms loss trip shows as code 50 (SC-F01).

Where is the official Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU) Modbus documentation?

The source is Optidrive Coolvert User Guide (Version 2.01), published free by Invertek Drives at https://www.invertekdrives.com/downloads/Optidrive%20Coolvert%20User%20Guide%20V2.01.pdf.

More Invertek Drives Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: Optidrive Coolvert User Guide · Version 2.01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.