Variable frequency drive · Modbus register map
Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU) Modbus register map
Updated 19 November 2026
The Optidrive Coolvert is Invertek's variable speed drive for refrigeration and HVAC compressors (BLDC, PM, induction and synchronous reluctance). Modbus RTU is built in on control terminals 1-3 and the RJ45 port. Registers 1-5 take the control word, speed set point in rps and ramp time; registers 7-45 report speed, current, power, trip codes, energy and run time. Every parameter also has its own register (P1-11 = 111).
This page lists 46 Modbus registers for the Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU) — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Invertek Drives’s own free documentation (linked below) and checked against it.
- Manufacturer
- Invertek Drives
- Model
- Optidrive Coolvert compressor drive (built-in Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 46 (14 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 115200 baud, 8N1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- Optidrive CoolVert, Coolvert
- Source document
- Optidrive Coolvert User Guide · Version 2.01
Integration notes: Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU)
Set P1-11 = 0, close the STO circuit, then write register 1 = 1 to run and register 2 with the speed in 0.1 rps. Poll registers 7, 8, 10 and 9 for speed, current, power and the trip code.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Drive control word | BITMAP16 | Control word: run, coast stop, reset | Read/write |
| HR 1 | Speed set point | INT16 | Speed set point, 0.1 rps | Read/write |
| HR 6 | Output frequency (compressor speed) | UINT16 | Compressor speed, 0.1 rps | Read |
| HR 7 | Output current | UINT16 | Output current, 0.1 A | Read |
| HR 8 | Trip code | UINT16 | Trip code | Read |
| HR 9 | Output power | UINT16 | Output power, 0.01 kW | Read |
| HR 110 | P1-11 Primary command source | UINT16 | P1-11 command source | Read/write |
Enable Modbus control & writes
Set P1-11 = 0 (Modbus mode). The STO inputs (terminals 8 and 9) must be energised for the drive to run. Set the drive address in P6-01 (or a separate Modbus address in P6-08), the baud rate in P6-02 and parity in P6-03. Set P6-06 = 1 to take ramp times from register 4.
Communication loss & watchdog
P6-04 sets the communication-loss time (0-60 s, default 5 s). P6-05 picks the reaction: 0 trip (default), 1 ramp to stop then trip, 2 ramp to stop without a trip, 3 run at the signal-loss speed P3-11. A comms loss trip shows as code 50 (SC-F01).
Byte order & addressing
- Register numbers are 1-based: subtract 1 for the wire address.
- Speeds are in revolutions per second (rps), not Hz or rpm; the IDL-format registers are the exception.
- The fault-reset bit in the control word must be returned to 0 after the reset or the drive will reset again unexpectedly.
Network setup
- RS-485 on control terminals 1 (0 V), 2 (+) and 3 (-), or RJ45 pins 3 (0 V), 8 (+) and 7 (-).
- Factory settings: address 1, 115.2 kbps, no parity, 1 stop bit.
- Connect 0 V common to every device; terminate the shield at the controller only, not at the drive.
Watch out for
- The RJ45 port is not Ethernet; do not plug it into a network switch.
- Class B trips on frame 3-5 drives cannot be reset for two minutes, and ten trips of one kind before a power cycle cause a lockout that only a power cycle clears.
Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | Drive control word | Run, coast stop, fault reset, relay and crankcase heating commands. | BITMAP16 | Read/write | bit 0 = Run (1) / stop (0); bit 2 = Coast stop request; bit 3 = Fault reset request (return to 0 after reset); bit 4 = User relay control (P3-05 = 6); bit 5 = Activate crankcase heating | |||
| HR | 1doc 2 | Speed set point | 600 = 60.0 rps. Negative values only if enabled by parameter. | INT16 | × 0.1 | rps | Read/write | ||
| HR | 3doc 4 | Modbus user ramp time | 3000 = 300.0 s; used only when P6-06 = 1. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 4doc 5 | Speed reference (IDL format) | Printed scaling: 3000 = 50.0 Hz. | UINT16 | Read/write | ||||
| HR | 6doc 7 | Output frequency (compressor speed) | 600 = 60.0 rps (P0-60). | UINT16 | × 0.1 | rps | Read | ||
| HR | 7doc 8 | Output current | 100 = 10.0 A. | UINT16 | × 0.1 | A | Read | ||
| HR | 8doc 9 | Trip code | Active trip code; 0 when healthy. | UINT16 | Read | 0 = No trip; 3 = O-I over current; 5 = PS-trp power stage trip; 6 = O-Volt over voltage; 7 = U-Volt under voltage; 10 = P-DEF load default parameters; 11 = E-Trip external trip (STO opened while running); 12 = SC-OBS Optibus serial comms fault; 13 = Flt-DC excessive DC bus ripple; 14 = P-Loss input phase loss; 15 = h O-I hardware over current; 17 = DATA-F I/O processor data error; 18 = 4-20F 4-20 mA signal out of range; 19 = DATA-E motor control processor data error; 20 = U-DEF user parameters default; 21 = F-PTC motor PTC overheat; 22 = FAN-F drive cooling fan fault; 23 = O-hEAt ambient temperature too high; 26 = Out-F drive output fault; 29 = STO-F fault in STO circuit; 40 = AtF-01 stator resistance unbalance; 41 = AtF-02 stator resistance too large; 42 = AtF-03 motor inductance too low; 43 = AtF-04 motor inductance too large; 44 = AtF-05 parameters not convergent; 49 = Out-Ph motor output phase loss; 50 = SC-F01 Modbus comms fault; 81 = OI-U phase U over current; 82 = OI-V phase V over current; 83 = OI-W phase W over current; 88 = Out-U phase U output fault; 89 = Out-V phase V output fault; 90 = Out-W phase W output fault; 97 = SC-Los IO-PS comms loss; 98 = DATA-03 wrong VDo3 checksum; 101 = STO-R STO opened at drive running; 102 = ML-Run mains loss at running; 103 = FW-Err PS firmware is changed; 107 = Stall compressor is stalled; 253 = HW-ID hardware ID not supported; 254 = Type-E drive ID not supported | |||
| HR | 9doc 10 | Output power | 1000 = 10.00 kW. | UINT16 | × 0.01 | kW | Read | ||
| HR | 10doc 11 | Digital input status | Bit 0 = digital input 1 (P0-03). | BITMAP16 | Read | bit 0 = Digital input 1 | |||
| HR | 11doc 12 | Rating ID | Frame size and input voltage code (P0-29). | UINT16 | Read | ||||
| HR | 12doc 13 | Power rating | P0-29 entry 2. | UINT16 | Read | ||||
| HR | 13doc 14 | Voltage rating | P0-29 entry 3. | UINT16 | Read | ||||
| HR | 14doc 15 | IO processor software version | 100 = 1.00. | UINT16 | × 0.01 | Read | |||
| HR | 15doc 16 | Compressor control processor software version | 100 = 1.00. | UINT16 | × 0.01 | Read | |||
| HR | 16doc 17 | Drive type | P0-29 entry 4 (drive ID). | UINT16 | Read | ||||
| HR | 19doc 20 | Analogue input signal level | 1000 = 100.0 % (P0-01, range -100.0 to 100.0 %). | INT16 | × 0.1 | % | Read | ||
| HR | 21doc 22 | Pre-ramp speed reference | 600 = 60.0 rps. | INT16 | × 0.1 | rps | Read | ||
| HR | 22doc 23 | DC bus voltage | 600 = 600 V (P0-20). | UINT16 | V | Read | |||
| HR | 23doc 24 | Drive temperature | Heatsink temperature, 40 = 40 °C (P0-21). | INT16 | °C | Read | |||
| HR | 24doc 25 | Drive serial number 4 | Serial number part (P0-30). | UINT16 | Read | ||||
| HR | 25doc 26 | Drive serial number 3 | Serial number part (P0-30). | UINT16 | Read | ||||
| HR | 26doc 27 | Drive serial number 2 | Serial number part (P0-30). | UINT16 | Read | ||||
| HR | 27doc 28 | Drive serial number 1 | Serial number part (P0-30). | UINT16 | Read | ||||
| HR | 28doc 29 | Relay output status | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| HR | 29doc 30 | Last two faults | Two trip codes, one per byte (P0-13). | UINT16 | Read | ||||
| HR | 30doc 31 | Previous two faults | Two older trip codes, one per byte (P0-13). | UINT16 | Read | ||||
| HR | 31doc 32 | kWh meter | 100 = 10.0 kWh; rolls into the MWh meter at 999.9 (P0-26). | UINT16 | × 0.1 | kWh | Read | ||
| HR | 32doc 33 | MWh meter | 100 = 100 MWh (P0-27). | UINT16 | MWh | Read | |||
| HR | 33doc 34 | Running time - hours | Hours run since manufacture (P0-31). | UINT16 | h | Read | |||
| HR | 34doc 35 | Running time - min/sec | Minutes and seconds part of P0-31; packing not stated. | UINT16 | Read | ||||
| HR | 35doc 36 | Run time since enable - hours | P0-34. | UINT16 | h | Read | |||
| HR | 36doc 37 | Run time since enable - min/sec | Minutes and seconds part of P0-34; packing not stated. | UINT16 | Read | ||||
| HR | 38doc 39 | Room (control PCB) temperature | 40 = 40 °C (P0-05). | INT16 | °C | Read | |||
| HR | 39doc 40 | Speed reference value | Printed scaling: 3000 = 50 Hz. | INT16 | Read | ||||
| HR | 41doc 42 | Compressor speed (IDL format) | Printed scaling: 3000 = 50 Hz. | INT16 | Read | ||||
| HR | 42doc 43 | Compressor output voltage | 100 = 100 V AC (P0-11). | UINT16 | V | Read | |||
| HR | 43doc 44 | Indirect parameter access index | Parameter to access through register 45. | UINT16 | Read/write | ||||
| HR | 44doc 45 | Indirect parameter access value | Value of the parameter chosen in register 44. | UINT16 | Read/write | ||||
| HR | 110doc 111 | P1-11 Primary command source | Set 0 for Modbus control. | UINT16 | Read/write | 0 = Modbus control; 1 = Terminal mode; 2 = Terminal mode, start when AI1 > 10 %; 3 = User PI mode; 4 = Slave mode | |||
| HR | 600doc 601 | P6-01 Fieldbus drive address | 1-63, default 1; Modbus address unless P6-08 is set. | UINT16 | Read/write | ||||
| HR | 602doc 603 | P6-03 Modbus data format | UINT16 | Read/write | 0 = No parity, 1 stop bit (default); 1 = No parity, 2 stop bits; 2 = Odd parity, 1 stop bit; 3 = Even parity, 1 stop bit | ||||
| HR | 603doc 604 | P6-04 Communications loss timeout | 0-60 s, default 5. | UINT16 | s | Read/write | |||
| HR | 604doc 605 | P6-05 Communications loss action | UINT16 | Read/write | 0 = Trip; 1 = Ramp to stop then trip; 2 = Ramp to stop (no trip); 3 = Run at signal loss speed P3-11 | ||||
| HR | 605doc 606 | P6-06 Fieldbus ramp control enable | 1 = ramps come from register 4. | UINT16 | Read/write | 0 = Disabled (internal ramps); 1 = Enabled (ramps from fieldbus) | |||
| HR | 606doc 607 | P6-07 Modbus response delay | Extra characters of delay, 0-16. | UINT16 | Read/write | ||||
| HR | 607doc 608 | P6-08 Modbus address | 0-200; 0 = use P6-01 for Modbus too. | UINT16 | Read/write |
Notes on this map
- Left out: register 6 (drive status). The guide describes it both as a 16-bit status word with bits 0-15 defined and as a single byte holding the last fault code, so its layout cannot be settled. Use register 9 for the trip code.
- Register 3 is not listed. Function 16 (write multiple) is accepted for registers 1-4 only; 03 and 06 work on the others.
- The guide states no signedness for most registers. Speed and analogue values that can go negative are typed INT16, counters and ratings UINT16.
- Registers 5, 40 and 42 use an 'IDL format' where 3000 = 50 Hz; they are kept raw.
- P6-02 (baud rate) is left out because the guide shows it in kbps (default 115) next to a 0-5 option list, so the stored value is unclear.
- Only the parameters an integrator needs for Modbus control are listed; every other parameter is reachable at its group-and-number register (for example 107 for P1-07).
- Trip codes listed are the A-class table; frame 3-5 drives with EN/UL 60730 certification also have class B trips.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU)
What Modbus registers does the Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU) have?
This map lists 46 registers: 46 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers from 1 and tells masters that start at register 0 to subtract 1, so control word register 1 is wire address 0. Parameters use their group and number as the register (P6-04 = register 604 = wire address 603).
What are the minimum Modbus registers to integrate the Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU)?
Start with HR 0 Drive control word (Control word: run, coast stop, reset); HR 1 Speed set point (Speed set point, 0.1 rps); HR 6 Output frequency (compressor speed) (Compressor speed, 0.1 rps); HR 7 Output current (Output current, 0.1 A); HR 8 Trip code (Trip code); HR 9 Output power (Output power, 0.01 kW); HR 110 P1-11 Primary command source (P1-11 command source).
How do I enable Modbus control of the Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU)?
Set P1-11 = 0 (Modbus mode). The STO inputs (terminals 8 and 9) must be energised for the drive to run. Set the drive address in P6-01 (or a separate Modbus address in P6-08), the baud rate in P6-02 and parity in P6-03. Set P6-06 = 1 to take ramp times from register 4.
What happens when the Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU) loses Modbus communication?
P6-04 sets the communication-loss time (0-60 s, default 5 s). P6-05 picks the reaction: 0 trip (default), 1 ramp to stop then trip, 2 ramp to stop without a trip, 3 run at the signal-loss speed P3-11. A comms loss trip shows as code 50 (SC-F01).
Where is the official Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU) Modbus documentation?
The source is Optidrive Coolvert User Guide (Version 2.01), published free by Invertek Drives at https://www.invertekdrives.com/downloads/Optidrive%20Coolvert%20User%20Guide%20V2.01.pdf.
More Invertek Drives Modbus register maps
- Variable frequency drive
Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU)
Invertek Optidrive E3 (ODE-3) IP20 drives on the RJ45 Modbus RTU port, per user guide 82-E3I20-IN V1.05.
Also known as: ODE-3, Optidrive E3, ODE-3 IP20, Optidrive ODE-3 - Variable frequency drive
Invertek Drives Optidrive Eco (built-in Modbus RTU)
Invertek Optidrive Eco drives using the built-in RJ45 RS-485 Modbus RTU port, per user guide 82-HEMAN-IN V3.13.
Also known as: ODV-3, Optidrive Eco HVAC, Optidrive Eco IP20, Optidrive Eco IP55, Optidrive Eco IP66 - Variable frequency drive
Invertek Drives Optidrive Elevator Core (built-in Modbus RTU)
Invertek Elevator Core lift drives on the RJ45 Modbus RTU port, per the online Elevator Core user guide (support.invertekdrives.com).
Also known as: Elevator Core, Optidrive Elevator Core - Variable frequency drive
Invertek Drives Optidrive P2 (built-in Modbus RTU)
Invertek Optidrive P2 drives (0.75-250 kW) using the built-in RJ45 RS-485 Modbus RTU port, per user guide 82-P2MAN-IN V3.10.
Also known as: ODP-2, Optidrive P2 IP20, Optidrive P2 IP55, Optidrive P2 IP66
Other variable frequency drives register maps
- Variable frequency drive
INVT Goodrive200A (GD200A) general-purpose VFD
INVT Goodrive200A drives using the built-in RS-485 Modbus port, per the GD200A manual V3.1 (chapter 9).
Also known as: GD200A, Goodrive200A, GD200A general VFD - Variable frequency drive
Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU)
Lenze i510 cabinet inverters 0.25-2.2 kW with the Modbus/CANopen control unit, selector set to Modbus, firmware 01.01.01.00 as documented in the commissioning manual.
Also known as: i500 series, i510 Cabinet, I51AE - Variable frequency drive
Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU)
FR-A700 series inverters (FR-A720-0.4K to 90K, FR-A740-0.4K to 500K) using the RS-485 terminals with Pr.549 = 1 (Modbus-RTU); Instruction Manual (Applied) revision E.
Also known as: FR-A720, FR-A740, FR-A700 series - Variable frequency drive
Schneider Electric Altivar Machine ATV320 (embedded Modbus RTU)
ATV320 Book (ATV320...B) and Compact (ATV320...C) drives on the built-in RJ45 Modbus serial port; register map per Communication Parameters file NVE41316 V3.5.
Also known as: ATV320, Altivar 320, ATV320U, ATV320D, ATV320 Book, ATV320 Compact - Variable frequency drive
SEW-EURODRIVE MOVITRAC LTP-B standard inverter (built-in Modbus RTU)
SEW-EURODRIVE MOVITRAC LTP-B inverters on the RJ45 Modbus RTU port (no communication or encoder option card fitted), per product manual 31554814/EN edition 10/2023.
Also known as: MOVITRAC LTP-B, LTP-B, MC LTP B - Variable frequency drive
TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII)
TECO-Westinghouse EV series micro inverters with the RS-485 option card, per the EV Inverter Series Modbus Communication Manual.
Also known as: TECO EV, EV Inverter Series
All variable frequency drives Modbus register maps →
Source: Optidrive Coolvert User Guide · Version 2.01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.