Variable frequency drive · Modbus register map
Invertek Drives Optidrive Elevator Core (built-in Modbus RTU) Modbus register map
Updated 19 November 2026
The Elevator Core is Invertek's drive for lift (elevator) motors, geared or gearless, open or closed loop. Modbus RTU is built in on the RJ45 port. Register 1 runs the drive forward or reverse and resets faults, register 2 sets the speed in the drive's active unit, and registers 5-48 report status, speed, current, torque, power, faults and run time. Parameters sit at their group-and-number register, and group 0 monitor values at 10000 + number.
This page lists 46 Modbus registers for the Invertek Drives Optidrive Elevator Core (built-in Modbus RTU) — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Invertek Drives’s own free documentation (linked below) and checked against it.
- Manufacturer
- Invertek Drives
- Model
- Optidrive Elevator Core (built-in Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 46 (9 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 115200 baud, 8N1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- Elevator Core, Optidrive Elevator Core
Integration notes: Invertek Drives Optidrive Elevator Core (built-in Modbus RTU)
Set P1-01 = 1, close both STO inputs, write the speed to register 2 and then write register 1 = 1 (up/forward) or 2 (reverse). Poll register 6 for status, 7-10 for speed, current, torque and power, and 18 for the fault code.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Command control word | BITMAP16 | Control word: run forward/reverse, reset | Read/write |
| HR 1 | Commanded speed reference | INT16 | Speed reference | Read/write |
| HR 5 | Status word | BITMAP16 | Status word | Read |
| HR 6 | Output speed | INT16 | Output speed | Read |
| HR 7 | Output current | INT16 | Output current, 0.1 A | Read |
| HR 17 | Active fault code | UINT16 | Active fault code | Read |
| HR 100 | P1-01 Primary command source | UINT16 | P1-01 command source | Read/write |
Enable Modbus control & writes
Set P1-01 = 1 (Modbus RTU). Set the address in P2-01, baud in P2-02 and data format in P2-03. STO1 and STO2 must both be closed (24 V present); no digital input is needed to run.
Communication loss & watchdog
P2-04 sets the Modbus loss timeout (0.0-5.0 s, default 1.0 s) and P2-05 the reaction: 0 trip (default), 1 ramp to stop then trip, 2 ramp to stop only, 3 run at inspection speed P8-08.
Byte order & addressing
- Register numbers are 1-based; subtract 1 for the wire address.
- Setting both run bits (value 3) stops the drive or keeps it from starting.
- Group 0 monitor parameters are read at 10000 + number, and their sub-indexes at 11000 + number x 10 + index.
Network setup
- RS-485 on the RJ45 port; always connect the 0 V pin.
- Factory settings: address 1, 115200 bps, no parity, 1 stop bit. Up to 247 drives per network.
- A 120 ohm terminating resistor at the end of the line helps with dropped telegrams.
Watch out for
- The drive rejects a speed reference outside the range of P8-01, and ramps still follow the group 8 and 9 S-ramp parameters under Modbus control.
- Leaving out the 0 V connection can damage the port.
Invertek Drives Optidrive Elevator Core (built-in Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | Command control word | Run forward, run reverse and fault reset; needs P1-01 = 1. | BITMAP16 | Read/write | bit 0 = Run forward (0 = stop); bit 1 = Run reverse (0 = stop); bit 2 = Fault reset request | |||
| HR | 1doc 2 | Commanded speed reference | Units follow the drive setting: 0.1 Hz, 1 rpm, 0.01 ft/s or 0.01 m/s. | INT16 | Read/write | ||||
| HR | 4doc 5 | Internal speed reference | Pre-ramp speed reference (as P0-13), 0.01 resolution in the active unit. | INT16 | Read | ||||
| HR | 5doc 6 | Status word | BITMAP16 | Read | bit 0 = Ready (no fault, mains present, safety chain closed); bit 1 = Running; bit 2 = Tripped; bit 6 = At speed set-point; bit 7 = Below minimum speed (P8-02) while enabled; bit 8 = Overload (current above P4-03); bit 9 = Mains loss; bit 10 = Heatsink above 85 °C; bit 11 = Control board above 80 °C; bit 12 = Switching frequency reduction active; bit 13 = Reverse rotation; bit 14 = Auto-tune active; bit 15 = Live toggle bit | ||||
| HR | 6doc 7 | Output speed | In the active speed unit, two decimal places. | INT16 | Read | ||||
| HR | 7doc 8 | Output current | 105 = 10.5 A. | INT16 | × 0.1 | A | Read | ||
| HR | 8doc 9 | Output torque | 474 = 47.4 %. | INT16 | × 0.1 | % | Read | ||
| HR | 9doc 10 | Output power | 1100 = 11.00 kW. | INT16 | × 0.01 | kW | Read | ||
| HR | 10doc 11 | Digital input status | One bit per drive input. | UINT16 | Read | ||||
| HR | 12doc 13 | Drive power rating | Power rating in kW; resolution not stated. | UINT16 | Read | ||||
| HR | 13doc 14 | Drive voltage rating | Voltage rating; resolution not stated. | UINT16 | Read | ||||
| HR | 14doc 15 | I/O firmware | Major x 100 + minor. | UINT16 | × 0.01 | Read | |||
| HR | 15doc 16 | Power firmware | Major x 100 + minor. | UINT16 | × 0.01 | Read | |||
| HR | 16doc 17 | Drive type code | Always 0x0330. | UINT16 | Read | ||||
| HR | 17doc 18 | Active fault code | Low byte = active fault code, high byte = fault sub-index (0 if none). | UINT16 | Read | ||||
| HR | 18doc 19 | Alarm code | One bit per active alarm (see the Alarm Codes topic). | UINT16 | Read | ||||
| HR | 19doc 20 | Analog 1 level | 1000 = 100.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 20doc 21 | Analog 2 level | 1000 = 100.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 21doc 22 | Pre-ramp speed reference | Internal speed set-point. | INT16 | Read | ||||
| HR | 22doc 23 | DC bus voltage | Measured, in volts. | UINT16 | V | Read | |||
| HR | 23doc 24 | Drive temperature | Heatsink temperature. | INT16 | °C | Read | |||
| HR | 24doc 25 | Serial number part 1 | Registers 25-28 together form the serial number. | UINT16 | Read | ||||
| HR | 25doc 26 | Serial number part 2 | UINT16 | Read | |||||
| HR | 26doc 27 | Serial number part 3 | UINT16 | Read | |||||
| HR | 27doc 28 | Serial number part 4 | UINT16 | Read | |||||
| HR | 28doc 29 | Digital output status | Bit = 1 when that output is closed. | UINT16 | Read | ||||
| HR | 29doc 30 | Energy consumption kWh | kWh part of the energy total. | UINT16 | kWh | Read | |||
| HR | 30doc 31 | Energy consumption MWh | MWh part of the energy total. | UINT16 | MWh | Read | |||
| HR | 33doc 34 | Drive total run time (h) | UINT16 | h | Read | ||||
| HR | 34doc 35 | Drive total run time (m) | UINT16 | min | Read | ||||
| HR | 35doc 36 | Run time since last enable (h) | UINT16 | h | Read | ||||
| HR | 36doc 37 | Run time since last enable (m) | UINT16 | min | Read | ||||
| HR | 37doc 38 | Service time remaining | Time until the next service is due; unit not stated. | UINT16 | Read | ||||
| HR | 38doc 39 | Control board temperature | INT16 | °C | Read | ||||
| HR | 47doc 48 | STO status | 1 when both STO1 and STO2 are closed. | UINT16 | Read | ||||
| HR | 100doc 101 | P1-01 Primary command source | Set 1 for Modbus RTU control. | UINT16 | Read/write | 0 = Terminal; 1 = Modbus RTU; 2 = CANopen | |||
| HR | 200doc 201 | P2-01 Modbus slave address | 0-247, default 1. | UINT16 | Read/write | ||||
| HR | 201doc 202 | P2-02 Modbus RTU baud rate | UINT16 | Read/write | 0 = 9600 bps; 1 = 19200 bps; 2 = 38400 bps; 3 = 57600 bps; 4 = 115200 bps (default) | ||||
| HR | 202doc 203 | P2-03 Modbus RTU data format | UINT16 | Read/write | 0 = No parity, 1 stop bit (default); 1 = No parity, 2 stop bits; 2 = Odd parity, 1 stop bit; 3 = Even parity, 1 stop bit | ||||
| HR | 203doc 204 | P2-04 Modbus communications loss timeout | 0.0-5.0 s, default 1.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 204doc 205 | P2-05 Communications loss action | UINT16 | Read/write | 0 = Trip (default); 1 = Ramp to stop then trip; 2 = Ramp to stop only (no trip); 3 = Run at inspection speed (P8-08) | ||||
| HR | 205doc 206 | P2-06 Modbus RTU response delay | Extra characters of delay, 0-16. | UINT16 | Read/write | ||||
| HR | 255doc 256 | P2-56 Modbus status word (byte pair) | High byte = active error code; low byte = extra status bits. | UINT16 | Read | ||||
| HR | 257doc 258 | P2-58 Modbus motor current | Only active while P1-01 = 1. | INT16 | × 0.1 | A | Read | ||
| HR | 258doc 259 | P2-59 Modbus output torque | Only active while P1-01 = 1. | INT16 | × 0.1 | % | Read | ||
| HR | 10002doc 10003 | P0-03 STO status (group 0 read) | Group 0 parameters read at 10000 + parameter number. | UINT16 | Read |
Notes on this map
- Source is Invertek's official online user guide (HTML), spread over the topics named in the source pages field.
- Fault reset: the bit tables put reset on control-word bit 2, while one troubleshooting line says bit 3; this map follows the bit tables (bit 2, also shown in P2-50). The reset only acts on a 0 to 1 change.
- A troubleshooting line says the fault code is in the upper byte of register 6, but the status-word topic defines all 16 bits of register 6 and puts the fault code in P2-56 (register 256) and register 18. This map follows the status-word topic.
- P2-56 low-byte status bits are left as a plain value: the register-details topic and the group 2 topic give different bit layouts.
- Speed registers (2, 5, 7, 22) use the drive's active unit, set by P4-06 and P3-08: Hz (0.1), rpm (1), ft/s (0.01) or m/s (0.01). They are kept raw. Signedness is not printed; speeds are typed INT16 because the drive runs in both directions.
- Registers 3, 4, 12, 32, 33 and 40-47 are reserved. The CANopen interface and the full parameter list are not covered here.
- Supported functions: 03, 06 and 16.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Invertek Drives Optidrive Elevator Core (built-in Modbus RTU)
What Modbus registers does the Invertek Drives Optidrive Elevator Core (built-in Modbus RTU) have?
This map lists 46 registers: 46 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Invertek Drives Optidrive Elevator Core (built-in Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are numbered from 1. The guide's worked telegrams settle it: the control-word write is broken down as physical address 0x0000 = logical register 1, and the status-word read uses physical 0x0005 for register 6. Parameters use group and number (P1-01 = register 101 = wire address 100); group 0 is read at 10000 + parameter number.
What are the minimum Modbus registers to integrate the Invertek Drives Optidrive Elevator Core (built-in Modbus RTU)?
Start with HR 0 Command control word (Control word: run forward/reverse, reset); HR 1 Commanded speed reference (Speed reference); HR 5 Status word (Status word); HR 6 Output speed (Output speed); HR 7 Output current (Output current, 0.1 A); HR 17 Active fault code (Active fault code); HR 100 P1-01 Primary command source (P1-01 command source).
How do I enable Modbus control of the Invertek Drives Optidrive Elevator Core (built-in Modbus RTU)?
Set P1-01 = 1 (Modbus RTU). Set the address in P2-01, baud in P2-02 and data format in P2-03. STO1 and STO2 must both be closed (24 V present); no digital input is needed to run.
What happens when the Invertek Drives Optidrive Elevator Core (built-in Modbus RTU) loses Modbus communication?
P2-04 sets the Modbus loss timeout (0.0-5.0 s, default 1.0 s) and P2-05 the reaction: 0 trip (default), 1 ramp to stop then trip, 2 ramp to stop only, 3 run at inspection speed P8-08.
Where is the official Invertek Drives Optidrive Elevator Core (built-in Modbus RTU) Modbus documentation?
The source is Elevator Core User Guide (online) - Modbus RTU Individual Register Details, published free by Invertek Drives at https://support.invertekdrives.com/elevator-core/en/modbus-rtu-individual-register-details.html.
More Invertek Drives Modbus register maps
- Variable frequency drive
Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU)
Invertek Optidrive Coolvert HVAC compressor drives on the terminal or RJ45 Modbus RTU port, per user guide version 2.01.
Also known as: Optidrive CoolVert, Coolvert - Variable frequency drive
Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU)
Invertek Optidrive E3 (ODE-3) IP20 drives on the RJ45 Modbus RTU port, per user guide 82-E3I20-IN V1.05.
Also known as: ODE-3, Optidrive E3, ODE-3 IP20, Optidrive ODE-3 - Variable frequency drive
Invertek Drives Optidrive Eco (built-in Modbus RTU)
Invertek Optidrive Eco drives using the built-in RJ45 RS-485 Modbus RTU port, per user guide 82-HEMAN-IN V3.13.
Also known as: ODV-3, Optidrive Eco HVAC, Optidrive Eco IP20, Optidrive Eco IP55, Optidrive Eco IP66 - Variable frequency drive
Invertek Drives Optidrive P2 (built-in Modbus RTU)
Invertek Optidrive P2 drives (0.75-250 kW) using the built-in RJ45 RS-485 Modbus RTU port, per user guide 82-P2MAN-IN V3.10.
Also known as: ODP-2, Optidrive P2 IP20, Optidrive P2 IP55, Optidrive P2 IP66
Other variable frequency drives register maps
- Variable frequency drive
INVT Goodrive35 (GD35) closed-loop vector VFD
INVT Goodrive35 closed-loop vector drives using the built-in RS-485 Modbus RTU port, per the GD35 VFD manual V4.0 (communication protocol chapter).
Also known as: GD35, Goodrive35, GD35 vector VFD - Variable frequency drive
Lenze SCF Series drive with Modbus module (basic network control)
Lenze AC Tech SCF Series drives with the optional Modbus RTU communication module; application note AN0028/A1 (January 2008).
Also known as: SCF, Lenze AC Tech SCF, AN0028 - Variable frequency drive
Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU)
FR-E700 series (FR-E720/E740/E720S/E710W, incl. SC safety-stop models) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision G.
Also known as: FR-E720, FR-E740, FR-E720S, FR-E710W, FR-E700-SC - Variable frequency drive
Schneider Electric Altivar Process ATV900 (ATV930/ATV950, embedded Modbus serial / Modbus TCP)
Altivar Process ATV900 drives (ATV930, ATV950) on the built-in Modbus serial port and the embedded Ethernet port (Modbus TCP). Per Communication Parameters file NHA80944 V4.6.
Also known as: ATV900, ATV930, ATV950, Altivar Process 900, Altivar 930, Altivar 950, ATV930U, ATV930D, ATV950U - Air handler (rotary heat exchanger drive controller)
Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU)
The rotary heat exchanger (rotor) drive controller in Swegon SILVER C RX air handling units, per sheet SILVERCModbusHX.201115.
Also known as: SILVER RX heat exchanger controller, SILVER C RX rotor drive, DRHX, SILVERCModbusHX - Variable frequency drive
Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU)
Toshiba TOSVERT VF-AS3 inverters on RS485 port 1 or 2 with the protocol set to MODBUS (F807/F827 = 1); RS485 Communication Function Instruction Manual E6582143.
Also known as: VF-AS3, TOSVERT VF-AS3
All variable frequency drives Modbus register maps →
Source: Elevator Core User Guide (online) - Modbus RTU Individual Register Details. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.