Variable frequency drive · Modbus register map

Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The VF-AS3 inverter's RS485 ports speak either the Toshiba protocol or Modbus RTU. In Modbus every parameter and monitor is addressed by its hexadecimal communication number: FA codes are commands (run word, frequency), FD/FE codes are monitors and trip-held values, and 08xx codes are the RS485 settings. This map covers control, the main monitors, trip history and the port 1 settings.

This page lists 57 Modbus registers for the Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU) — 18 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Toshiba’s own free documentation (linked below) and checked against it.

Manufacturer
Toshiba
Model
TOSVERT VF-AS3 inverter (RS485 Modbus RTU)
Equipment type
Variable frequency drive
Registers
57 (18 writable)
Transport
Modbus RTU
Default unit ID
0
Default serial
19200 baud, 8E1
Documented addressing
hexadecimal, 0-based
Also known as
VF-AS3, TOSVERT VF-AS3
Source document
TOSVERT VF-AS3 RS485 Communication Function Instruction Manual · E6582143 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU)

Integration in brief

Set F807 = 1 (MODBUS), F802 to a non-zero address and F800/F801 for the line, then power-cycle. Write FA01 with the frequency and FA00 = 8400h (bit 15 run priority + bit 10 run) to run forward, adding bit 14 (C400h) when the frequency also comes from comms; read FD00, FD01, FD03 and FC90 for status.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 64000RS485 (1) command 1BITMAP16Command word FA00Read/write
HR 64001RS485 (1) frequency commandUINT16Frequency command FA01Read/write
HR 64768Output frequencyUINT16Output frequency FD00Read
HR 64769Status information 1BITMAP16Status word FD01Read
HR 64771Output currentUINT16Output current FD03Read
HR 64656Current tripUINT16Current trip FC90Read

Enable Modbus control & writes

Set F807 (port 1) or F827 (port 2) to 1: MODBUS and reset the drive. Commands from FA00/FA01 are accepted regardless of CMOd/FMOd once FA00 bit 15 (run priority) and/or bit 14 (frequency priority) are set; that priority stays until cleared, power-off or reset.

Communication loss & watchdog

F803 sets the RS485 time-out (0.0 = off, 0.1-100.0 s); F804 picks continue, trip, or trip after deceleration stop; F808 sets when the time-out is checked. The manual says the time-out should be set so the drive stops on comm loss.

Byte order & addressing

Network setup

Watch out for

Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

57 of 57 shown
Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR2048doc 0800RS485 (1) baud rate [F800]Takes effect after reset.UINT16Read/write0 = 9600 bps; 1 = 19200 bps; 2 = 38400 bps
HR2049doc 0801RS485 (1) parity [F801]Takes effect after reset.UINT16Read/write0 = Disabled (none); 1 = Even parity; 2 = Odd parity
HR2050doc 0802Inverter number [F802]0-247; use 1-247 for Modbus (0 = broadcast).UINT16Read/write
HR2051doc 0803RS485 (1) time-out time [F803]0.0 = disabled, 0.1-100.0 s.UINT16× 0.1sRead/write
HR2052doc 0804RS485 (1) time-out operation [F804]UINT16Read/write1 = Continue running; 4 = Trip; 6 = Trip after deceleration stop
HR2053doc 0805RS485 (1) transmission wait time [F805]0.00-2.00 s.UINT16× 0.01sRead/write
HR2055doc 0807RS485 (1) protocol [F807]Takes effect after reset.UINT16Read/write0 = TOSHIBA; 1 = MODBUS
HR2056doc 0808RS485 (1) time-out detection [F808]UINT16Read/write0 = Always; 1 = When run and frequency commands come from comms; 2 = During run by communication
HR2096doc 0830MODBUS continuous address [F830]How block reads step through missing numbers.UINT16Read/write0 = Disabled (skip non-existent numbers); 1 = Enabled (all addresses)
HR64000doc FA00RS485 (1) command 1Run/stop and control bits; set bit 15 for run priority, bit 14 for frequency priority.BITMAP16Read/writebit 0 = Preset speed bit 1; bit 1 = Preset speed bit 2; bit 2 = Preset speed bit 3; bit 3 = Preset speed bit 4; bit 4 = V/f switching (1 = V/f2); bit 5 = PID control off; bit 6 = Acc/Dec switching (1 = Acc/Dec 2); bit 7 = Forced DC braking; bit 8 = Jog run; bit 9 = Direction (0 = forward, 1 = reverse); bit 10 = Run (0 = stop, 1 = run); bit 11 = Coast stop; bit 12 = Emergency off (E trip); bit 13 = Reset; bit 14 = Frequency command priority (comms); bit 15 = Run command priority (comms)
HR64001doc FA01RS485 (1) frequency command0 to maximum frequency (FH).UINT16× 0.01HzRead/write
HR64004doc FA04RS485 (2) command 1Same bit layout as FA00, for RS485 port 2.BITMAP16Read/writebit 0 = Preset speed bit 1; bit 1 = Preset speed bit 2; bit 2 = Preset speed bit 3; bit 3 = Preset speed bit 4; bit 4 = V/f switching (1 = V/f2); bit 5 = PID control off; bit 6 = Acc/Dec switching (1 = Acc/Dec 2); bit 7 = Forced DC braking; bit 8 = Jog run; bit 9 = Direction (0 = forward, 1 = reverse); bit 10 = Run (0 = stop, 1 = run); bit 11 = Coast stop; bit 12 = Emergency off (E trip); bit 13 = Reset; bit 14 = Frequency command priority (comms); bit 15 = Run command priority (comms)
HR64005doc FA05RS485 (2) frequency commandUINT16× 0.01HzRead/write
HR64019doc FA13RS485 (1) motor speed command0-32700 rpm.UINT16rpmRead/write
HR64048doc FA30RS485 (1) torque command-250.00 to 250.00 %.INT16× 0.01%Read/write
HR64080doc FA50Terminal output dataDrives outputs assigned to 'designated data' functions.BITMAP16Read/write
HR64081doc FA51Terminal FM output dataUINT16× 0.1%Read/write
HR64082doc FA52Terminal AM output dataUINT16× 0.1%Read/write
HR64263doc FB07Inverter series typeReads 178 on a VF-AS3.UINT16Read
HR64656doc FC90Current tripTrip code of the present trip.UINT16Read
HR64657doc FC91AlarmAlarm information word.BITMAP16Read
HR64768doc FD00Output frequencyCurrent value.UINT16× 0.01HzRead
HR64769doc FD01Status information 1Current status.BITMAP16Readbit 0 = Failure FL output; bit 1 = Tripped; bit 2 = Alarm occurring; bit 3 = Main circuit undervoltage (MOFF); bit 4 = V/f2 active; bit 5 = PID control off; bit 6 = Acc/Dec 2 active; bit 7 = DC braking; bit 8 = Jog run; bit 9 = Reverse run; bit 10 = Running; bit 11 = Coast stop (ST off); bit 12 = Emergency off; bit 13 = Ready for run 1 (ST on); bit 14 = Ready for run 2; bit 15 = HAND / LOC (0 = AUTO / REM)
HR64770doc FD02Frequency command valueUINT16× 0.01HzRead
HR64771doc FD03Output current% of inverter rated current.UINT16× 0.01%Read
HR64772doc FD04Input voltage (DC detection)% of rated voltage.UINT16× 0.01%Read
HR64773doc FD05Output voltage% of rated voltage.UINT16× 0.01%Read
HR64774doc FD06Input terminal statusBITMAP16Read
HR64775doc FD07Output terminal statusBITMAP16Read
HR64789doc FD15Motor primary frequencyUINT16× 0.01HzRead
HR64792doc FD18TorqueINT16× 0.01%Read
HR64802doc FD22PID feedback valueUINT16× 0.01HzRead
HR64803doc FD23Motor overload factor (OL2)UINT16× 0.01%Read
HR64804doc FD24Inverter overload factor (OL1)UINT16× 0.01%Read
HR64806doc FD26Motor load factorUINT16%Read
HR64807doc FD27Inverter load factorUINT16%Read
HR64809doc FD29Input powerUINT16× 0.01kWRead
HR64816doc FD30Output powerUINT16× 0.01kWRead
HR64833doc FD41Cumulative cooling fan run timeUINT16× 10hRead
HR64834doc FD42Inverter status 2BITMAP16Read
HR64856doc FD58PID set valueUINT16× 0.01HzRead
HR64888doc FD78Power circuit board temperatureINT16°CRead
HR64899doc FD83Internal temperature 1INT16°CRead
HR64912doc FD90Motor speed (estimated)INT16rpmRead
HR65032doc FE08Inverter CPU versionUINT16Read
HR65040doc FE10Past trip 1 (latest)UINT16Read
HR65041doc FE11Past trip 2UINT16Read
HR65042doc FE12Past trip 3UINT16Read
HR65043doc FE13Past trip 4UINT16Read
HR65044doc FE14Cumulative run timeUINT16hRead
HR65077doc FE35Terminal RR input value0-100.00 %.UINT16× 0.01%Read
HR65078doc FE36Terminal RX input value-100.00 to 100.00 %.INT16× 0.01%Read
HR65079doc FE37Terminal II input value0-100.00 %.UINT16× 0.01%Read
HR65136doc FE70Inverter rated currentUINT16× 0.1ARead
HR65137doc FE71Inverter rated voltageUINT16× 0.1VRead
HR65145doc FE79Parts replacement alarm statusBITMAP16Read
HR65152doc FE80Cumulative power-on timeUINT16× 10hRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU)

What Modbus registers does the Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU) have?

This map lists 57 registers: 57 holding registers. 18 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register address is the parameter's hexadecimal communication number sent unchanged: the manual's example reads output frequency FD00 with the frame 01 03 FD 00 00 01. Parameter F800 has communication number 0800 (wire 0x0800).

What are the minimum Modbus registers to integrate the Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU)?

Start with HR 64000 RS485 (1) command 1 (Command word FA00); HR 64001 RS485 (1) frequency command (Frequency command FA01); HR 64768 Output frequency (Output frequency FD00); HR 64769 Status information 1 (Status word FD01); HR 64771 Output current (Output current FD03); HR 64656 Current trip (Current trip FC90).

How do I enable Modbus control of the Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU)?

Set F807 (port 1) or F827 (port 2) to 1: MODBUS and reset the drive. Commands from FA00/FA01 are accepted regardless of CMOd/FMOd once FA00 bit 15 (run priority) and/or bit 14 (frequency priority) are set; that priority stays until cleared, power-off or reset.

What happens when the Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU) loses Modbus communication?

F803 sets the RS485 time-out (0.0 = off, 0.1-100.0 s); F804 picks continue, trip, or trip after deceleration stop; F808 sets when the time-out is checked. The manual says the time-out should be set so the drive stops on comm loss.

Where is the official Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU) Modbus documentation?

The source is TOSVERT VF-AS3 RS485 Communication Function Instruction Manual (E6582143). Toshiba doesn't publish it on its own website, so this map was re-typed from a free copy at https://cdn.automationdirect.com/static/manuals/toshibamotors/as3rs485manual.pdf. It may be an older revision, so check it against the live unit.

More Toshiba Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: TOSVERT VF-AS3 RS485 Communication Function Instruction Manual · E6582143 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.