- TOSVERT VF-AS3 inverter (RS485 Modbus RTU)
Variable frequency drive · Modbus register map
Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU) Modbus register map
Updated 19 November 2026
The VF-AS3 inverter's RS485 ports speak either the Toshiba protocol or Modbus RTU. In Modbus every parameter and monitor is addressed by its hexadecimal communication number: FA codes are commands (run word, frequency), FD/FE codes are monitors and trip-held values, and 08xx codes are the RS485 settings. This map covers control, the main monitors, trip history and the port 1 settings.
This page lists 57 Modbus registers for the Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU) — 18 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Toshiba’s own free documentation (linked below) and checked against it.
- Manufacturer
- Toshiba
- Model
- TOSVERT VF-AS3 inverter (RS485 Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 57 (18 writable)
- Transport
- Modbus RTU
- Default unit ID
- 0
- Default serial
- 19200 baud, 8E1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- VF-AS3, TOSVERT VF-AS3
Integration notes: Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU)
Set F807 = 1 (MODBUS), F802 to a non-zero address and F800/F801 for the line, then power-cycle. Write FA01 with the frequency and FA00 = 8400h (bit 15 run priority + bit 10 run) to run forward, adding bit 14 (C400h) when the frequency also comes from comms; read FD00, FD01, FD03 and FC90 for status.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 64000 | RS485 (1) command 1 | BITMAP16 | Command word FA00 | Read/write |
| HR 64001 | RS485 (1) frequency command | UINT16 | Frequency command FA01 | Read/write |
| HR 64768 | Output frequency | UINT16 | Output frequency FD00 | Read |
| HR 64769 | Status information 1 | BITMAP16 | Status word FD01 | Read |
| HR 64771 | Output current | UINT16 | Output current FD03 | Read |
| HR 64656 | Current trip | UINT16 | Current trip FC90 | Read |
Enable Modbus control & writes
Set F807 (port 1) or F827 (port 2) to 1: MODBUS and reset the drive. Commands from FA00/FA01 are accepted regardless of CMOd/FMOd once FA00 bit 15 (run priority) and/or bit 14 (frequency priority) are set; that priority stays until cleared, power-off or reset.
Communication loss & watchdog
F803 sets the RS485 time-out (0.0 = off, 0.1-100.0 s); F804 picks continue, trip, or trip after deceleration stop; F808 sets when the time-out is checked. The manual says the time-out should be set so the drive stops on comm loss.
Byte order & addressing
- Addresses are the hexadecimal communication numbers (FA00, FD00 ...), not 4xxxx numbers.
- A plain 03 read returns one word; multi-word direct reads are limited to 8 words and skip numbers that do not exist unless F830 = 1. Missing numbers read as 8000H.
- Manual examples: 8400H = run forward with run priority; 8600H / C600H = run reverse (C600H also takes frequency priority).
Network setup
- F800 baud: 0 = 9600, 1 = 19200 (default), 2 = 38400; F801 parity default even; both take effect after reset. With F809 (operation panel connection) at its default 1 = connector 1, port 1 is fixed at 19200 bps / even parity whatever F800/F801 say (likewise F820/F821 for port 2 when F809 = 2).
- F802 inverter number defaults to 0 (broadcast): set 1-247 for Modbus.
- Inverter-to-inverter communication (F806/F826) does not work in Modbus mode.
Watch out for
- Emergency off (bit 12) and PID-off bits in FA00 act even without the priority bits set.
- Changing F809 (operation panel connection priority) can lock out the LCD panel until it is rewritten over comms.
- F806/F826 inverter-to-inverter settings are disabled on the connector chosen in F809.
Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 2048doc 0800 | RS485 (1) baud rate [F800] | Takes effect after reset. | UINT16 | Read/write | 0 = 9600 bps; 1 = 19200 bps; 2 = 38400 bps | |||
| HR | 2049doc 0801 | RS485 (1) parity [F801] | Takes effect after reset. | UINT16 | Read/write | 0 = Disabled (none); 1 = Even parity; 2 = Odd parity | |||
| HR | 2050doc 0802 | Inverter number [F802] | 0-247; use 1-247 for Modbus (0 = broadcast). | UINT16 | Read/write | ||||
| HR | 2051doc 0803 | RS485 (1) time-out time [F803] | 0.0 = disabled, 0.1-100.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 2052doc 0804 | RS485 (1) time-out operation [F804] | UINT16 | Read/write | 1 = Continue running; 4 = Trip; 6 = Trip after deceleration stop | ||||
| HR | 2053doc 0805 | RS485 (1) transmission wait time [F805] | 0.00-2.00 s. | UINT16 | × 0.01 | s | Read/write | ||
| HR | 2055doc 0807 | RS485 (1) protocol [F807] | Takes effect after reset. | UINT16 | Read/write | 0 = TOSHIBA; 1 = MODBUS | |||
| HR | 2056doc 0808 | RS485 (1) time-out detection [F808] | UINT16 | Read/write | 0 = Always; 1 = When run and frequency commands come from comms; 2 = During run by communication | ||||
| HR | 2096doc 0830 | MODBUS continuous address [F830] | How block reads step through missing numbers. | UINT16 | Read/write | 0 = Disabled (skip non-existent numbers); 1 = Enabled (all addresses) | |||
| HR | 64000doc FA00 | RS485 (1) command 1 | Run/stop and control bits; set bit 15 for run priority, bit 14 for frequency priority. | BITMAP16 | Read/write | bit 0 = Preset speed bit 1; bit 1 = Preset speed bit 2; bit 2 = Preset speed bit 3; bit 3 = Preset speed bit 4; bit 4 = V/f switching (1 = V/f2); bit 5 = PID control off; bit 6 = Acc/Dec switching (1 = Acc/Dec 2); bit 7 = Forced DC braking; bit 8 = Jog run; bit 9 = Direction (0 = forward, 1 = reverse); bit 10 = Run (0 = stop, 1 = run); bit 11 = Coast stop; bit 12 = Emergency off (E trip); bit 13 = Reset; bit 14 = Frequency command priority (comms); bit 15 = Run command priority (comms) | |||
| HR | 64001doc FA01 | RS485 (1) frequency command | 0 to maximum frequency (FH). | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 64004doc FA04 | RS485 (2) command 1 | Same bit layout as FA00, for RS485 port 2. | BITMAP16 | Read/write | bit 0 = Preset speed bit 1; bit 1 = Preset speed bit 2; bit 2 = Preset speed bit 3; bit 3 = Preset speed bit 4; bit 4 = V/f switching (1 = V/f2); bit 5 = PID control off; bit 6 = Acc/Dec switching (1 = Acc/Dec 2); bit 7 = Forced DC braking; bit 8 = Jog run; bit 9 = Direction (0 = forward, 1 = reverse); bit 10 = Run (0 = stop, 1 = run); bit 11 = Coast stop; bit 12 = Emergency off (E trip); bit 13 = Reset; bit 14 = Frequency command priority (comms); bit 15 = Run command priority (comms) | |||
| HR | 64005doc FA05 | RS485 (2) frequency command | UINT16 | × 0.01 | Hz | Read/write | |||
| HR | 64019doc FA13 | RS485 (1) motor speed command | 0-32700 rpm. | UINT16 | rpm | Read/write | |||
| HR | 64048doc FA30 | RS485 (1) torque command | -250.00 to 250.00 %. | INT16 | × 0.01 | % | Read/write | ||
| HR | 64080doc FA50 | Terminal output data | Drives outputs assigned to 'designated data' functions. | BITMAP16 | Read/write | ||||
| HR | 64081doc FA51 | Terminal FM output data | UINT16 | × 0.1 | % | Read/write | |||
| HR | 64082doc FA52 | Terminal AM output data | UINT16 | × 0.1 | % | Read/write | |||
| HR | 64263doc FB07 | Inverter series type | Reads 178 on a VF-AS3. | UINT16 | Read | ||||
| HR | 64656doc FC90 | Current trip | Trip code of the present trip. | UINT16 | Read | ||||
| HR | 64657doc FC91 | Alarm | Alarm information word. | BITMAP16 | Read | ||||
| HR | 64768doc FD00 | Output frequency | Current value. | UINT16 | × 0.01 | Hz | Read | ||
| HR | 64769doc FD01 | Status information 1 | Current status. | BITMAP16 | Read | bit 0 = Failure FL output; bit 1 = Tripped; bit 2 = Alarm occurring; bit 3 = Main circuit undervoltage (MOFF); bit 4 = V/f2 active; bit 5 = PID control off; bit 6 = Acc/Dec 2 active; bit 7 = DC braking; bit 8 = Jog run; bit 9 = Reverse run; bit 10 = Running; bit 11 = Coast stop (ST off); bit 12 = Emergency off; bit 13 = Ready for run 1 (ST on); bit 14 = Ready for run 2; bit 15 = HAND / LOC (0 = AUTO / REM) | |||
| HR | 64770doc FD02 | Frequency command value | UINT16 | × 0.01 | Hz | Read | |||
| HR | 64771doc FD03 | Output current | % of inverter rated current. | UINT16 | × 0.01 | % | Read | ||
| HR | 64772doc FD04 | Input voltage (DC detection) | % of rated voltage. | UINT16 | × 0.01 | % | Read | ||
| HR | 64773doc FD05 | Output voltage | % of rated voltage. | UINT16 | × 0.01 | % | Read | ||
| HR | 64774doc FD06 | Input terminal status | BITMAP16 | Read | |||||
| HR | 64775doc FD07 | Output terminal status | BITMAP16 | Read | |||||
| HR | 64789doc FD15 | Motor primary frequency | UINT16 | × 0.01 | Hz | Read | |||
| HR | 64792doc FD18 | Torque | INT16 | × 0.01 | % | Read | |||
| HR | 64802doc FD22 | PID feedback value | UINT16 | × 0.01 | Hz | Read | |||
| HR | 64803doc FD23 | Motor overload factor (OL2) | UINT16 | × 0.01 | % | Read | |||
| HR | 64804doc FD24 | Inverter overload factor (OL1) | UINT16 | × 0.01 | % | Read | |||
| HR | 64806doc FD26 | Motor load factor | UINT16 | % | Read | ||||
| HR | 64807doc FD27 | Inverter load factor | UINT16 | % | Read | ||||
| HR | 64809doc FD29 | Input power | UINT16 | × 0.01 | kW | Read | |||
| HR | 64816doc FD30 | Output power | UINT16 | × 0.01 | kW | Read | |||
| HR | 64833doc FD41 | Cumulative cooling fan run time | UINT16 | × 10 | h | Read | |||
| HR | 64834doc FD42 | Inverter status 2 | BITMAP16 | Read | |||||
| HR | 64856doc FD58 | PID set value | UINT16 | × 0.01 | Hz | Read | |||
| HR | 64888doc FD78 | Power circuit board temperature | INT16 | °C | Read | ||||
| HR | 64899doc FD83 | Internal temperature 1 | INT16 | °C | Read | ||||
| HR | 64912doc FD90 | Motor speed (estimated) | INT16 | rpm | Read | ||||
| HR | 65032doc FE08 | Inverter CPU version | UINT16 | Read | |||||
| HR | 65040doc FE10 | Past trip 1 (latest) | UINT16 | Read | |||||
| HR | 65041doc FE11 | Past trip 2 | UINT16 | Read | |||||
| HR | 65042doc FE12 | Past trip 3 | UINT16 | Read | |||||
| HR | 65043doc FE13 | Past trip 4 | UINT16 | Read | |||||
| HR | 65044doc FE14 | Cumulative run time | UINT16 | h | Read | ||||
| HR | 65077doc FE35 | Terminal RR input value | 0-100.00 %. | UINT16 | × 0.01 | % | Read | ||
| HR | 65078doc FE36 | Terminal RX input value | -100.00 to 100.00 %. | INT16 | × 0.01 | % | Read | ||
| HR | 65079doc FE37 | Terminal II input value | 0-100.00 %. | UINT16 | × 0.01 | % | Read | ||
| HR | 65136doc FE70 | Inverter rated current | UINT16 | × 0.1 | A | Read | |||
| HR | 65137doc FE71 | Inverter rated voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 65145doc FE79 | Parts replacement alarm status | BITMAP16 | Read | |||||
| HR | 65152doc FE80 | Cumulative power-on time | UINT16 | × 10 | h | Read |
Notes on this map
- Toshiba's own download host refused automated access (HTTP 403), so the link is the copy on AutomationDirect, a Toshiba drive distributor; it appears to be the unaltered Toshiba manual.
- Every value is a single 16-bit word; negative values are two's complement.
- FE versions of the FD monitors (FE00-FE07, FE15 ...) hold the value captured just before the last trip; only a few are listed.
- Output current and voltages are in % of the drive rating (0.01 % steps); convert with FE70/FE71.
- Input and output cumulative power (FE76/FE77) are left out because their unit depends on parameter F749.
- The Modbus implementation is partial: function 03 reads one word, an indirect block (F875-F879) or up to 8 consecutive numbers; 06 and 10 write one word; 10 also writes the F870/F871 block and 17 combines block write and read.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU)
What Modbus registers does the Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU) have?
This map lists 57 registers: 57 holding registers. 18 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register address is the parameter's hexadecimal communication number sent unchanged: the manual's example reads output frequency FD00 with the frame 01 03 FD 00 00 01. Parameter F800 has communication number 0800 (wire 0x0800).
What are the minimum Modbus registers to integrate the Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU)?
Start with HR 64000 RS485 (1) command 1 (Command word FA00); HR 64001 RS485 (1) frequency command (Frequency command FA01); HR 64768 Output frequency (Output frequency FD00); HR 64769 Status information 1 (Status word FD01); HR 64771 Output current (Output current FD03); HR 64656 Current trip (Current trip FC90).
How do I enable Modbus control of the Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU)?
Set F807 (port 1) or F827 (port 2) to 1: MODBUS and reset the drive. Commands from FA00/FA01 are accepted regardless of CMOd/FMOd once FA00 bit 15 (run priority) and/or bit 14 (frequency priority) are set; that priority stays until cleared, power-off or reset.
What happens when the Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU) loses Modbus communication?
F803 sets the RS485 time-out (0.0 = off, 0.1-100.0 s); F804 picks continue, trip, or trip after deceleration stop; F808 sets when the time-out is checked. The manual says the time-out should be set so the drive stops on comm loss.
Where is the official Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU) Modbus documentation?
The source is TOSVERT VF-AS3 RS485 Communication Function Instruction Manual (E6582143). Toshiba doesn't publish it on its own website, so this map was re-typed from a free copy at https://cdn.automationdirect.com/static/manuals/toshibamotors/as3rs485manual.pdf. It may be an older revision, so check it against the live unit.
More Toshiba Modbus register maps
- Heat pump (air-to-water) Modbus interface
Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps
Toshiba BMS-IFMB0UEW-E MB interface on ESTIA R410A 4 Series and 5 Series (WM type) and R32 1 Series (WM and AIO type) hydro units, user manual EEU-006 issued 31/05/2021.
Also known as: BMS-IFMB0UEW-E, ESTIA Modbus interface, Toshiba MB interface, EEU-006 - Variable frequency drive
Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU)
Toshiba TOSVERT VF-nC3 series inverters using the built-in RS-485 port with f829 = 1 (Modbus RTU), per manual E6581657.
Also known as: VF-nC3, VF-nC3M, TOSVERT VF-nC3, VFNC3
Other variable frequency drives register maps
- Variable frequency drive
Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU
Yaskawa F7 (CIMR-F7U) general-purpose drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.F7.01 Appendix D, with parameter and monitor addresses from TM.F7.11.
Also known as: CIMR-F7U, F7U, F7 Drive - Variable frequency drive
Yaskawa HV600 HVAC fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa HV600 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPC71061732 revision F.
Also known as: CIPR-HV60, HV600 HVAC drive - Variable frequency drive (HVAC bypass package)
Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU)
P1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIP1B 01D, appendix D.
Also known as: P1000 Bypass, P1B - Variable frequency drive (HVAC bypass package)
Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU)
Z1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIZ1B 01F, appendix D.
Also known as: Z1000 Bypass, Z1B1 - Variable frequency drive
ABB ACS180 machinery drive (embedded Modbus RTU)
ACS180 drives running the machinery control program, built-in EIA-485 Modbus RTU terminal (embedded fieldbus, EFB), addressing mode 0 (default); firmware manual 3AXD50000467860 Rev D.
Also known as: ACS180-04, ACS180 machinery control program - Variable frequency drive
ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link)
ACS800 drives running Standard Control Program 7.x with an RMBA-01 Modbus Adapter in option slot 1 or 2 (Standard Modbus Link, RTU only), ABB Drives communication profile.
Also known as: ACS800-01, ACS800-02, ACS800-04, ACS800-07, ACS800-11, ACS800-17, ACS800-31, ACS800-37, RMBA-01, ACS800 Standard Control Program
All variable frequency drives Modbus register maps →
Source: TOSVERT VF-AS3 RS485 Communication Function Instruction Manual · E6582143 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.