Variable frequency drive · Modbus register map
ABB ACS180 machinery drive (embedded Modbus RTU) Modbus register map
Updated 17 November 2026
ABB's compact ACS180 machinery drive has a built-in EIA-485 terminal on its front that speaks Modbus RTU. The first six holding registers carry the control word, two references, status word and two actual values; every parameter is also a holding register derived from its group and index. This map covers the cyclic block, key 01/04/05 monitoring parameters, the comm-loss settings and the main 32-bit actual values.
This page lists 46 Modbus registers for the ABB ACS180 machinery drive (embedded Modbus RTU) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ABB’s own free documentation (linked below) and checked against it.
- Manufacturer
- ABB
- Model
- ACS180 machinery drive (embedded Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 46 (5 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- CDAB low word first (word-swapped)
- Firmware
- ACS180 machinery control program, manual revision D
- Also known as
- ACS180-04, ACS180 machinery control program
Integration notes: ABB ACS180 machinery drive (embedded Modbus RTU)
Pick the Modbus RTU control macro (or set 58.01 = Modbus RTU and point 20.01 and 22.11/28.11 at the embedded fieldbus), then write the ABB Drives control word and Reference 1 at 400001/400002 and poll the status word and actual values at 400004-400006. Read further monitoring values from their parameter registers (400000 + 100*group + index).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Control word (EFB CW) | BITMAP16 | Control word: start/stop/reset | Read/write |
| HR 1 | Reference 1 (EFB Ref1) | INT16 | Reference 1 (speed/frequency setpoint, 20000 = 46.01/46.02) | Read/write |
| HR 3 | Status word (EFB SW) | BITMAP16 | Status word: ready/running/fault/remote | Read |
| HR 4 | Actual value 1 (EFB Act1) | INT16 | Actual value 1 (speed/frequency feedback) | Read |
| HR 110 | 01.11 DC voltage | UINT16 | 01.11 DC voltage | Read |
| HR 400 | 04.01 Tripping fault | UINT16 | 04.01 Tripping fault code | Read |
| HR 20211 | 01.06 Output frequency (32-bit) | INT32 CDAB | 01.06 Output frequency, 0.01 Hz (32-bit) | Read |
| HR 20213 | 01.07 Motor current (32-bit) | UINT32 CDAB | 01.07 Motor current, 0.01 A (32-bit) | Read |
Enable Modbus control & writes
Selecting the Modbus RTU control macro sets 20.01 Ext1 commands = Embedded fieldbus, 22.11 and 28.11 = EFB ref1 and 58.01 = Modbus RTU (and puts fault reset on DI1). Otherwise set them by hand, plus 58.03 node address, 58.04 baud and 58.05 parity, and apply with 58.06 Communication control = Refresh settings.
Communication loss & watchdog
58.14 Communication loss action (default Fault; also No action / Last speed / Speed ref safe / Fault always / Warning) with 58.16 Communication loss time (default 3.0 s) and 58.15 Communication loss mode (default: only control word/reference writes reset the timer). A loss trips 6681 EFB comm loss or warns A7CE.
Byte order & addressing
- Addresses are 6-digit Modicon references: 400001 = wire 0. 32-bit parameter registers start at 420000 and cannot be reached with 5-digit (4xxxx) addressing.
- 32-bit values in this map are listed CDAB, which assumes 58.34 Word order = LO-HI (default). If 58.34 is set to HI-LO, read them as ABCD.
- References and actual values are signed 16-bit with 20000 = the 46.01/46.02 scaling value, not engineering units.
- Start (manual's sequence): write 0x476; when status bit 0 is 1 write 0x477 (ready/stopped), then 0x47F to run. Stop: 0x477 stops per 21.03 Stop mode; 0x47E is an OFF1 ramp stop. Fault reset: rising edge of control-word bit 7.
Network setup
- Defaults: node 1, 19.2 kbit/s, 8 data bits, even parity, 1 stop bit (58.03-58.05).
- Changes to group 58 take effect only after 58.06 = Refresh settings or a control-unit reboot.
- Termination (jumper J1) must be ON at the drives at both ends of the bus.
Watch out for
- The default comm-loss action is Fault with a 3 s timeout, so a stopped poll trips the drive.
- Exception 04h means the drive rejected the request (for example a limit was exceeded).
ABB ACS180 machinery drive (embedded Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 400001 | Control word (EFB CW) | ABB Drives profile bits shown; DCU profile layout differs (58.25). | BITMAP16 | Read/write | bit 0 = OFF1_CONTROL: 1 = ready to operate, 0 = ramp stop (OFF1); bit 1 = OFF2_CONTROL: 0 = emergency OFF, coast to stop; bit 2 = OFF3_CONTROL: 0 = emergency stop (OFF3 ramp); bit 3 = INHIBIT_OPERATION: 1 = operation enabled (run), 0 = inhibit; bit 4 = RAMP_OUT_ZERO: 0 = force ramp output to zero; bit 5 = RAMP_HOLD: 0 = hold ramp; bit 6 = RAMP_IN_ZERO: 0 = force ramp input to zero; bit 7 = RESET: 0->1 = fault reset; bit 8 = JOGGING_1: 1 = run at jogging speed 1; bit 9 = JOGGING_2: 1 = run at jogging speed 2; bit 10 = REMOTE_CMD: 1 = fieldbus control; 0 = last CW/reference kept unless both are 0; bit 11 = EXT_CTRL_LOC: 1 = select EXT2, 0 = select EXT1; bit 12 = USER_0; bit 13 = USER_1; bit 14 = USER_2; bit 15 = USER_3 | |||
| HR | 1doc 400002 | Reference 1 (EFB Ref1) | Signed; 20000 = value of 46.01/46.02 scaling, type per 58.26. | INT16 | Read/write | ||||
| HR | 2doc 400003 | Reference 2 (EFB Ref2) | Signed second reference; type and scaling per 58.27. | INT16 | Read/write | ||||
| HR | 3doc 400004 | Status word (EFB SW) | ABB Drives profile bits shown; DCU profile layout differs (58.25). | BITMAP16 | Read | bit 0 = RDY_ON: ready to switch on; bit 1 = RDY_RUN: ready to operate (0 = OFF1 active); bit 2 = RDY_REF: operation enabled; bit 3 = TRIPPED: fault; bit 4 = OFF_2_STATUS: 1 = OFF2 inactive; bit 5 = OFF_3_STATUS: 1 = OFF3 inactive; bit 6 = SWC_ON_INHIB: switch-on inhibited; bit 7 = ALARM: warning active; bit 8 = AT_SETPOINT: actual value at reference; bit 9 = REMOTE: 1 = remote (EXT1/EXT2), 0 = local; bit 10 = ABOVE_LIMIT: speed/frequency at or above supervision limit; bit 11 = USER_0; bit 12 = USER_1; bit 13 = USER_2; bit 14 = USER_3; bit 15 = Reserved | |||
| HR | 4doc 400005 | Actual value 1 (EFB Act1) | Signed; 20000 = value of 46.01/46.02, type per 58.28. | INT16 | Read | ||||
| HR | 5doc 400006 | Actual value 2 (EFB Act2) | Signed second actual value; type per 58.29. | INT16 | Read | ||||
| HR | 107doc 400108 | 01.08 Motor current % of motor nom | UINT16 | % | Read | ||||
| HR | 108doc 400109 | 01.09 Motor current % of drive nom | UINT16 | % | Read | ||||
| HR | 110doc 400111 | 01.11 DC voltage | Measured DC link voltage. | UINT16 | × 0.1 | V | Read | ||
| HR | 112doc 400113 | 01.13 Output voltage | Calculated motor voltage (AC). | UINT16 | V | Read | |||
| HR | 114doc 400115 | 01.15 Output power % of motor nom | INT16 | × 0.1 | % | Read | |||
| HR | 117doc 400118 | 01.18 Inverter GWh counter | Whole GWh through the drive; combine with 01.19 and 01.20. | UINT16 | GWh | Read | |||
| HR | 118doc 400119 | 01.19 Inverter MWh counter | Whole MWh, rolls over into 01.18. | UINT16 | MWh | Read | |||
| HR | 119doc 400120 | 01.20 Inverter kWh counter | kWh part (0-1000), rolls over into 01.19. | UINT16 | × 0.1 | kWh | Read | ||
| HR | 123doc 400124 | 01.24 Flux actual % | UINT16 | % | Read | ||||
| HR | 161doc 400162 | 01.62 Abs motor speed % | UINT16 | × 0.1 | % | Read | |||
| HR | 164doc 400165 | 01.65 Abs output power | UINT16 | kW | Read | ||||
| HR | 165doc 400166 | 01.66 Abs output power % motor nom | UINT16 | % | Read | ||||
| HR | 400doc 400401 | 04.01 Tripping fault | Hex code of the fault that caused the trip; 0 = none. | UINT16 | Read | ||||
| HR | 401doc 400402 | 04.02 Active fault 2 | UINT16 | Read | |||||
| HR | 402doc 400403 | 04.03 Active fault 3 | UINT16 | Read | |||||
| HR | 405doc 400406 | 04.06 Active warning 1 | Hex code of the first active warning. | UINT16 | Read | ||||
| HR | 406doc 400407 | 04.07 Active warning 2 | UINT16 | Read | |||||
| HR | 407doc 400408 | 04.08 Active warning 3 | UINT16 | Read | |||||
| HR | 410doc 400411 | 04.11 Latest fault | Most recent stored fault code. | UINT16 | Read | ||||
| HR | 411doc 400412 | 04.12 2nd latest fault | UINT16 | Read | |||||
| HR | 412doc 400413 | 04.13 3rd latest fault | UINT16 | Read | |||||
| HR | 415doc 400416 | 04.16 Latest warning | Most recent stored warning code. | UINT16 | Read | ||||
| HR | 500doc 400501 | 05.01 On-time counter | Days the drive has been powered. | UINT16 | days | Read | |||
| HR | 501doc 400502 | 05.02 Run-time counter | Days the motor has been running. | UINT16 | days | Read | |||
| HR | 503doc 400504 | 05.04 Fan on-time counter | Cooling fan running time. | UINT16 | days | Read | |||
| HR | 510doc 400511 | 05.11 Inverter temperature | Drive temperature as percent of fault limit. | INT16 | % | Read | |||
| HR | 5813doc 405814 | 58.14 Communication loss action | Reaction to EFB communication loss (default Fault). | UINT16 | Read/write | 0 = No action; 1 = Fault; 2 = Last speed; 3 = Speed ref safe; 4 = Fault always; 5 = Warning | |||
| HR | 5814doc 405815 | 58.15 Communication loss mode | Which messages reset the comm-loss timer. | UINT16 | Read/write | 1 = Any message; 2 = Cw / Ref1 / Ref2 | |||
| HR | 20201doc 420202 | 01.01 Motor speed used (32-bit) | Measured or estimated motor speed; CDAB assumes 58.34 = LO-HI (default). | INT32 | CDAB | × 0.01 | rpm | Read | |
| HR | 20205doc 420206 | 01.03 Motor speed % (32-bit) | Percent of synchronous speed; CDAB assumes 58.34 = LO-HI (default). | INT32 | CDAB | × 0.01 | % | Read | |
| HR | 20211doc 420212 | 01.06 Output frequency (32-bit) | Estimated output frequency; CDAB assumes 58.34 = LO-HI (default). | INT32 | CDAB | × 0.01 | Hz | Read | |
| HR | 20213doc 420214 | 01.07 Motor current (32-bit) | Measured motor current; CDAB assumes 58.34 = LO-HI (default). | UINT32 | CDAB | × 0.01 | A | Read | |
| HR | 20219doc 420220 | 01.10 Motor torque (32-bit) | Percent of nominal motor torque; CDAB assumes 58.34 = LO-HI (default). | INT32 | CDAB | × 0.1 | % | Read | |
| HR | 20221doc 420222 | 01.11 DC voltage (32-bit) | CDAB assumes 58.34 = LO-HI (default). | UINT32 | CDAB | × 0.01 | V | Read | |
| HR | 20227doc 420228 | 01.14 Output power (32-bit) | Unit kW or hp per 96.16; CDAB assumes 58.34 = LO-HI (default). | INT32 | CDAB | × 0.01 | kW | Read | |
| HR | 20307doc 420308 | 01.54 Cumulative inverter energy (32-bit) | Signed total energy through the drive; CDAB assumes 58.34 = LO-HI (default). | INT32 | CDAB | kWh | Read | ||
| HR | 20343doc 420344 | 01.72 U-phase RMS current (32-bit) | CDAB assumes 58.34 = LO-HI (default). | UINT32 | CDAB | × 0.01 | A | Read | |
| HR | 20345doc 420346 | 01.73 V-phase RMS current (32-bit) | CDAB assumes 58.34 = LO-HI (default). | UINT32 | CDAB | × 0.01 | A | Read | |
| HR | 20347doc 420348 | 01.74 W-phase RMS current (32-bit) | CDAB assumes 58.34 = LO-HI (default). | UINT32 | CDAB | × 0.01 | A | Read | |
| HR | 21005doc 421006 | 05.03 Hours run (32-bit) | Motor run time in hours; CDAB assumes 58.34 = LO-HI (default). | UINT32 | CDAB | × 0.1 | h | Read |
Notes on this map
- The EIA-485 port is shared with the external control panel port; jumper J2 must be in 'Modbus Mode' for the EFB to work (J1 sets termination).
- Registers 400001-400006 are the factory defaults of Data I/O 1-6 (58.101-58.106) and can be re-pointed; 400007-400014 are user-selectable via 58.107-58.114 and are not listed.
- Control and status word bits are shown for the ABB Drives profile (58.25 = 0, default). In this manual 58.25 lists 0 = ABB Drives and 5 = DCU Profile; the DCU words use a different bit layout.
- Reference/actual registers are signed 16-bit; 20000 corresponds to the value of 46.01 Speed scaling or 46.02 Frequency scaling (46.03 torque), so their engineering value depends on drive settings and is left unscaled here.
- 32-bit registers follow 58.34 Word order; the default LO-HI sends the low word first (CDAB). With HI-LO the order becomes ABCD. Within each register the high byte is sent first.
- 16-bit scaling is the manual's FbEq16 column; 32-bit scaling is the FbEq32 column in the Additional parameter data chapter. Parameters whose 16-bit scaling is 'See par. 46.xx' (01.01, 01.03, 01.06, 01.07, 01.10, 01.14) are listed only in their 32-bit form; the 01.72-01.74 phase currents likewise appear only as 32-bit values (100 = 1 A).
- Left out: the error code registers 400090-400095. The heading of that table says 400090-400100 but its reference column numbers the rows 89-94, so the exact register of each row is not stated unambiguously in this manual.
- 58.16 Communication loss time (default 3.0 s, 0.0-6000.0 s) is left out: its 16-bit scaling is printed only as '1 = 1', so the unit of the integer is unclear.
- Left out: 06.xx control/status words, 05.10 control board temperature (unit depends on a setting), 01.50-01.53 hour/day kWh logs and configuration parameters other than the comm-loss settings. Coils and discrete inputs also exist but are omitted.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the ABB ACS180 machinery drive (embedded Modbus RTU)
What Modbus registers does the ABB ACS180 machinery drive (embedded Modbus RTU) have?
This map lists 46 registers: 46 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the ABB ACS180 machinery drive (embedded Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual uses 6-digit references 400001-465536 for the 65536 holding registers, so 400001 = wire address 0. Masters limited to 5 digits can use 40001-49999 for 400001-409999; 32-bit parameter registers (420000+) need 6-digit or raw addressing. With 58.33 Addressing mode = Mode 0 (default) a 16-bit parameter gg.ii sits at 400000 + 100*gg + ii (e.g. 01.11 -> 400111, wire 110) and a 32-bit copy at 420000 + 200*gg + 2*ii (e.g. 01.07 -> 420214, wire 20213). Mode 1 uses 400000 + 256*gg + ii and Mode 2 uses 400000 + 512*gg + 2*ii; this map assumes Mode 0. 32-bit registers are listed CDAB, which assumes 58.34 Word order = LO-HI, the default.
What byte order does the ABB ACS180 machinery drive (embedded Modbus RTU) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the ABB ACS180 machinery drive (embedded Modbus RTU)?
Start with HR 0 Control word (EFB CW) (Control word: start/stop/reset); HR 1 Reference 1 (EFB Ref1) (Reference 1 (speed/frequency setpoint, 20000 = 46.01/46.02)); HR 3 Status word (EFB SW) (Status word: ready/running/fault/remote); HR 4 Actual value 1 (EFB Act1) (Actual value 1 (speed/frequency feedback)); HR 110 01.11 DC voltage (01.11 DC voltage); HR 400 04.01 Tripping fault (04.01 Tripping fault code); HR 20211 01.06 Output frequency (32-bit) (01.06 Output frequency, 0.01 Hz (32-bit)); HR 20213 01.07 Motor current (32-bit) (01.07 Motor current, 0.01 A (32-bit)).
How do I enable Modbus control of the ABB ACS180 machinery drive (embedded Modbus RTU)?
Selecting the Modbus RTU control macro sets 20.01 Ext1 commands = Embedded fieldbus, 22.11 and 28.11 = EFB ref1 and 58.01 = Modbus RTU (and puts fault reset on DI1). Otherwise set them by hand, plus 58.03 node address, 58.04 baud and 58.05 parity, and apply with 58.06 Communication control = Refresh settings.
What happens when the ABB ACS180 machinery drive (embedded Modbus RTU) loses Modbus communication?
58.14 Communication loss action (default Fault; also No action / Last speed / Speed ref safe / Fault always / Warning) with 58.16 Communication loss time (default 3.0 s) and 58.15 Communication loss mode (default: only control word/reference writes reset the timer). A loss trips 6681 EFB comm loss or warns A7CE.
Where is the official ABB ACS180 machinery drive (embedded Modbus RTU) Modbus documentation?
The source is ACS180 machinery control program firmware manual (3AXD50000467860 Rev D), revision 2026-04-01, published free by ABB at https://search.abb.com/library/Download.aspx?DocumentID=3AXD50000467860&LanguageCode=en&DocumentPartId=1&Action=Launch.
More ABB Modbus register maps
- Variable frequency drive
ABB ACH480 HVAC drive (embedded Modbus RTU)
ACH480 drives running the ACH480 HVAC control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000247134 Rev E.
Also known as: ACH480-04, ACH480 HVAC control program - Variable frequency drive
ABB ACH550-UH HVAC drive (embedded Modbus RTU)
ACH550-UH HVAC drives using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AUA0000081823 Rev F.
Also known as: ACH550-UH, ACH550 - Variable frequency drive
ABB ACH580 HVAC drive (embedded Modbus RTU)
ACH580 drives running the ACH580 HVAC control program, embedded fieldbus (EFB) set to Modbus RTU, addressing mode 0 (default).
Also known as: ACH580-01, ACH580-07, ACH580-31, ACH580-34, ACH580 HVAC control program - Variable frequency drive
ABB ACQ580 water and wastewater drive (embedded Modbus RTU)
ACQ580 drives running the ACQ580 pump control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000035867 Rev H.
Also known as: ACQ580-01, ACQ580-04, ACQ580-07, ACQ580-31, ACQ580-34, ACQ580 pump control program - Variable frequency drive
ABB ACS310 pump and fan drive (embedded Modbus RTU)
ACS310 drives (01E/01U/03E/03U) using the embedded fieldbus: Modbus RTU on the built-in EIA-485 terminals 23-26 or RS-232 on the panel connector; user's manual 3AUA0000044201 Rev D.
Also known as: ACS310-01E, ACS310-01U, ACS310-03E, ACS310-03U - Variable frequency drive
ABB ACS355 machinery drive (embedded Modbus RTU)
ACS355 drives with firmware 5.110 or later using the embedded fieldbus (Modbus RTU) over an FMBA-01 adapter on terminal X3 (EIA-485) or the panel port (RS-232).
Also known as: ACS355-01E, ACS355-03E, ACS355-01U, ACS355-03U, ACS355 with FMBA-01 - Variable frequency drive
ABB ACS380 machinery drive (embedded Modbus RTU)
ACS380 drives running the machinery control program with the BMIO-01 I/O and Modbus RTU module, embedded fieldbus (EFB), addressing mode 0 (default); firmware manual 3AXD50000029275 Rev J.
Also known as: ACS380-04, ACS380 machinery control program, BMIO-01 - Variable frequency drive
ABB ACS480 general purpose drive (embedded Modbus RTU)
ACS480 drives running the ACS480 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000047399 Rev G.
Also known as: ACS480-04, ACS480 standard control program - Variable frequency drive
ABB ACS550-01/U1 general purpose drive (embedded Modbus RTU)
ACS550-01 and ACS550-U1 drives (0.75-160 kW / 1-200 hp) using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AFE64804588 Rev H.
Also known as: ACS550-01, ACS550-U1 - Variable frequency drive
ABB ACS580 general purpose drive (embedded Modbus RTU)
ACS580 drives running the ACS580 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default).
Also known as: ACS580-01, ACS580-04, ACS580-07, ACS580 standard control program - Variable frequency drive
ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link)
ACS800 drives running Standard Control Program 7.x with an RMBA-01 Modbus Adapter in option slot 1 or 2 (Standard Modbus Link, RTU only), ABB Drives communication profile.
Also known as: ACS800-01, ACS800-02, ACS800-04, ACS800-07, ACS800-11, ACS800-17, ACS800-31, ACS800-37, RMBA-01, ACS800 Standard Control Program - Variable frequency drive
ABB ACS880 industrial drive, primary control program (embedded Modbus RTU)
ACS880 drives running the primary control program (AINLX) 3.4x or later, embedded fieldbus (EFB) Modbus RTU on terminal XD2D, 58.33 Addressing mode = Mode 0 (default).
Also known as: ACS880-01, ACS880-04, ACS880-07, ACS880-11, ACS880-17, ACS880-31, ACS880-37, AINLX, ACS880 primary control program - Power meter (branch circuit monitoring)
ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)
ABB CMS-700 control unit with up to 96 CMS branch current sensors, per the CMS-700 user manual (Modbus and SNMP mapping chapter).
Also known as: CMS-700, CMS700, ABB CMS-700, CMS-700 control unit - Variable frequency drive (DC drive)
ABB DCS880 DC drive (embedded Modbus RTU)
DCS880 DC drives, firmware manual revision E, embedded fieldbus (EFB) Modbus RTU on control-board terminal XD2D, ABB Drives profile, 58.33 Addressing mode = Mode 0.
Also known as: DCS880-S01, DCS880-S02, DCS880-H, DCS880-R - Energy meter
ABB EQ meter A41 / A42 (Modbus RTU)
ABB EQ A41 (direct connected) and A42 (transformer connected) DIN meters whose RS-485 port is set to Modbus.
Also known as: A41, A42, EQ A41, EQ A42 - Energy meter
ABB EQ meter A43 / A44 (Modbus RTU)
ABB EQ A43 (direct connected) and A44 (transformer connected) three-phase DIN meters whose RS-485 port is set to Modbus.
Also known as: A43, A44, EQ A43, EQ A44 - Energy meter
ABB EQ meter B21 (Modbus RTU)
ABB EQ B21 single-phase 65 A DIN meter with the RS485 interface set to Modbus.
Also known as: B21, EQ B21 - Energy meter
ABB EQ meter B23 / B24 (Modbus RTU)
ABB EQ B23 (direct, 65 A) and B24 (CT-connected) three-phase DIN meters fitted with the RS485 interface set to Modbus.
Also known as: B23, B24, EQ B23, EQ B24 - Power meter (network analyzer)
ABB M4M 20 / M4M 30 network analyzer
ABB M4M 20 and M4M 30 network analyzers, Modbus RTU and Modbus TCP versions, map v1.3O; items marked M4M 30 only are absent on M4M 20.
Also known as: M4M 20, M4M 30, M4M 20 Modbus, M4M 30 Modbus, M4M 20 Ethernet, M4M 30 Ethernet, M4M 20 I/O, M4M 30 I/O, M4M 2X, M4M 30-M, M4M 32 - Process controller (sensor / PID controller)
ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)
ABB Protronic 100/500/550 and Digitric 500 universal process controllers with the RS-485/RS-232 Modbus interface module, interface description 42/62-50040 EN Rev. 04.
Also known as: Protronic 100, Protronic 500, Protronic 550, Digitric 500 - Soft starter (motor control)
ABB PSE softstarter (internal Modbus RTU)
ABB PSE18...PSE370 softstarters using the internal Modbus RTU interface (Modbus RTU adaptor on the front fieldbus connector), document 1SFC132367M0201 Rev B.
Also known as: PSE18, PSE25, PSE30, PSE37, PSE45, PSE60, PSE72, PSE85, PSE105, PSE142, PSE170, PSE210, PSE250, PSE300, PSE370 - Soft starter (motor control)
ABB PSTX softstarter (built-in Modbus RTU)
ABB PSTX30...PSTX1250 softstarters using the built-in Modbus RTU interface on terminals 23/24 (Com3), document 1SFC132089M0201 Rev F.
Also known as: PSTX30, PSTX37, PSTX45, PSTX60, PSTX72, PSTX85, PSTX105, PSTX142, PSTX170, PSTX210, PSTX250, PSTX300, PSTX370, PSTX470, PSTX570, PSTX720, PSTX840, PSTX1050, PSTX1250 - Power meter (DC circuit breaker trip unit)
ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU)
ABB SACE PR122DC and PR123DC DC protection trip units with the PR120/D-M communication module, document rev 02 (04/04/2014, SW 3.01 and later).
Also known as: PR122DC, PR123DC, PR120/D-M, Emax DC, SACE Emax DC - Power meter (circuit breaker trip unit)
ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU)
ABB SACE PR122/P and PR123/P (Emax) and PR332/P and PR333/P (Emax X1, Tmax T7, Tmax T8) protection releases with the Modbus RTU communication module, per 1SDH000556R0001.
Also known as: PR122/P, PR123/P, PR332/P, PR333/P, PR120/D-M, PR330/D-M, Emax PR122, Emax PR123, Tmax T7 PR332, Emax X1 PR333, Tmax T8 PR332 - Power meter (circuit breaker trip unit)
ABB SACE Tmax PR223DS trip unit (Modbus RTU)
ABB SACE PR223DS electronic trip unit (Tmax moulded-case breakers), software version 02.02, per 1SDH000658R0001.
Also known as: PR223DS, Tmax PR223DS, SACE PR223DS
Other variable frequency drives register maps
- Variable frequency drive
AutomationDirect GS1 series AC drive
All GS1 drives; status addresses and P9.xx serial-communication parameters from chapter 5 of the user manual.
Also known as: GS1-10P2, GS1-10P5, GS1-20P2, GS1-20P5, GS1-21P0, GS1-22P0 - Variable frequency drive
Danfoss VLT AutomationDrive FC 360 (Modbus RTU)
VLT AutomationDrive FC 360 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC360, FC-360, VLT AutomationDrive FC 360 - Variable frequency drive (HVAC)
Eaton H-Max HVAC drive (embedded Modbus RTU / TCP)
H-Max HVAC drives with the application described in application manual MN04008006E (January 2012).
Also known as: HMX, H-Max HVAC, HMX32, HMX34 - Pump (circulator / E-pump / pump drive)
Grundfos E-pumps (MAGNA3, TPE, CRE, CUE) via CIM 200 / CIM 500
Grundfos E-pumps (CRE/CRNE/CRIE, MTRE, CHIE, CME, TPE, TPE Series 2000, NBE/NKE), CUE drives and MAGNA3 with a CIM/CIU 200, CIM/CIU 500 or built-in SoftCIM.
Also known as: MAGNA3, TPE, TPE Series 2000, CRE, CRNE, CRIE, MTRE, CHIE, CME, NBE, NKE, CUE, MGE, CIM 200, CIU 200, CIM 500, CIU 500, SoftCIM Modbus RTU - Variable frequency drive
Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU)
Invertek Optidrive E3 (ODE-3) IP20 drives on the RJ45 Modbus RTU port, per user guide 82-E3I20-IN V1.05.
Also known as: ODE-3, Optidrive E3, ODE-3 IP20, Optidrive ODE-3 - Variable frequency drive
INVT Goodrive270 (GD270) fan and pump VFD
INVT Goodrive270 fan and pump drives using the built-in RS-485 Modbus RTU port, per the GD270 manual V1.4 (chapter 9).
Also known as: GD270, Goodrive270, GD270 fan and pump drive, GD270 HVAC drive
All variable frequency drives Modbus register maps →
Source: ACS180 machinery control program firmware manual · 3AXD50000467860 Rev D · rev. 2026-04-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.