- CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)
Power meter (branch circuit monitoring) · Modbus register map
ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP) Modbus register map
Updated 19 November 2026
The CMS-700 control unit measures mains voltage, current, power and energy and collects up to 96 open-core or solid-core branch current sensors. It serves everything over Modbus RTU (RS-485) and Modbus TCP on port 8001. Branch currents are 16-bit values in 0.01 A; mains values and branch power/energy are 32-bit, high word first.
This page lists 59 Modbus registers for the ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ABB’s own free documentation (linked below) and checked against it.
- Manufacturer
- ABB
- Model
- CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)
- Equipment type
- Power meter (branch circuit monitoring)
- Registers
- 59 (5 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Default serial
- 19200 baud, 8E1
- TCP port
- 8001
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- CMS-700, CMS700, ABB CMS-700, CMS-700 control unit
Integration notes: ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)
Read 0000h-005Fh for all branch TRMS currents in one block (0.01 A) and 9002h-90C4h for the mains. Branch power and energy come from 2200h and 2300h.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | TRMS current, sensor 1 | UINT16 | Branch 1 TRMS current | Read |
| HR 36866 | Voltage L1-N | UINT32 ABCD | Mains voltage L1-N | Read |
| HR 36880 | Line current L1 | UINT32 ABCD | Mains current L1 | Read |
| HR 36910 | Total active power | INT32 ABCD | Mains total active power | Read |
| HR 37044 | Total active energy (100 Wh steps) | UINT32 ABCD | Mains active energy (100 Wh) | Read |
| HR 8960 | Active energy, sensor 1 | UINT32 ABCD | Branch 1 energy | Read |
Enable Modbus control & writes
Set Modbus ID, baud rate and parity in the web UI (Settings > Communication / Modbus). Modbus TCP can be switched on or off there and its port changed; the standard port is 8001.
Byte order & addressing
- Modbus TCP uses port 8001 by default, not 502.
- Reads use function 03 and single writes use 06; the manual says not to use other functions (the table also lists 10 for names and polarity).
- 16-bit branch values use 7FF0h-7FFFh as status codes.
Network setup
- Default 19200 baud, even parity.
- Add a 120 ohm terminator on units with serial number after 700K1820000 if needed.
Watch out for
- Below about 60 mA CT secondary current the mains current reads 0 and power factor reads 1.
- The FAQ gives 429,496 kWh as the maximum energy value for the mains and each branch.
ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 0000h (0) | TRMS current, sensor 1 | Sensor n: add n-1 (n = 1-96). | UINT16 | × 0.01 | A | Read | ||
| HR | 1doc 0001h (1) | TRMS current, sensor 2 | UINT16 | × 0.01 | A | Read | |||
| HR | 95doc 005Fh (95) | TRMS current, sensor 96 | UINT16 | × 0.01 | A | Read | |||
| HR | 256doc 0100h (256) | AC current, sensor 1 | Sensor n: add n-1 (n = 1-96). | UINT16 | × 0.01 | A | Read | ||
| HR | 512doc 0200h (512) | DC current, sensor 1 | Sensor n: add n-1 (n = 1-96). Signed. | INT16 | × 0.01 | A | Read | ||
| HR | 1024doc 0400h (1024) | TRMS minimum, sensor 1 | Sensor n: add n-1 (n = 1-96). | UINT16 | × 0.01 | A | Read | ||
| HR | 2048doc 0800h (2048) | TRMS maximum, sensor 1 | Sensor n: add n-1 (n = 1-96). | UINT16 | × 0.01 | A | Read | ||
| HR | 3072doc 0C00h (3072) | TRMS hold value, sensor 1 | Captured by the trigger-hold command. Sensor n: add n-1 (n = 1-96). | UINT16 | × 0.01 | A | Read | ||
| HR | 8192doc 2000h (8192) | DC polarity, sensor 1 | Bit 12: 0 = direct, 1 = reverse. Sensor n: add n-1 (n = 1-96). | BITMAP16 | Read/write | bit 12 = DC polarity reverse | |||
| HR | 8704doc 2200h (8704) | Active power, sensor 1 | Calculated branch power. Sensor n: add 2 x (n-1) (n = 1-96). | UINT32 | ABCD | W | Read | ||
| HR | 8960doc 2300h (8960) | Active energy, sensor 1 | Calculated branch energy. Sensor n: add 2 x (n-1) (n = 1-96). | UINT32 | ABCD | × 0.1 | Wh | Read | |
| HR | 9216doc 2400h (9216) | Active power, group 1 | Group n: add 2 x (n-1) (n = 1-96). | UINT32 | ABCD | W | Read | ||
| HR | 12304doc 3010h (12304) | Trigger hold / reset min-max | Bit 4 = trigger hold, bit 0 = reset min/max. | BITMAP16 | Write | bit 0 = Reset min and max values; bit 4 = Trigger hold measurement | |||
| HR | 29440doc 7300h (29440) | Power factor, sensor 1 | Configured PF used for branch power. Sensor n: add n-1 (n = 1-96). | UINT16 | × 0.01 | Read/write | |||
| HR | 32768doc 8000h (32768) | Number of current alarms | UINT16 | Read | |||||
| HR | 32769doc 8001h (32769) | Alarm status, branch 1 | Branch n: add n-1 (8001h-8060h). | UINT16 | Read | ||||
| HR | 36866doc 9002h (36866) | Voltage L1-N | UINT32 | ABCD | × 0.01 | V | Read | ||
| HR | 36868doc 9004h (36868) | Voltage L2-N | UINT32 | ABCD | × 0.01 | V | Read | ||
| HR | 36870doc 9006h (36870) | Voltage L3-N | UINT32 | ABCD | × 0.01 | V | Read | ||
| HR | 36880doc 9010h (36880) | Line current L1 | UINT32 | ABCD | × 0.01 | A | Read | ||
| HR | 36882doc 9012h (36882) | Line current L2 | UINT32 | ABCD | × 0.01 | A | Read | ||
| HR | 36884doc 9014h (36884) | Line current L3 | UINT32 | ABCD | × 0.01 | A | Read | ||
| HR | 36888doc 9018h (36888) | Power factor L1 | INT32 | ABCD | × 0.01 | Read | |||
| HR | 36890doc 901Ah (36890) | Power factor L2 | INT32 | ABCD | × 0.01 | Read | |||
| HR | 36892doc 901Ch (36892) | Power factor L3 | INT32 | ABCD | × 0.01 | Read | |||
| HR | 36902doc 9026h (36902) | Total apparent power | UINT32 | ABCD | VA | Read | |||
| HR | 36904doc 9028h (36904) | Apparent power L1 | UINT32 | ABCD | VA | Read | |||
| HR | 36906doc 902Ah (36906) | Apparent power L2 | UINT32 | ABCD | VA | Read | |||
| HR | 36908doc 902Ch (36908) | Apparent power L3 | UINT32 | ABCD | VA | Read | |||
| HR | 36910doc 902Eh (36910) | Total active power | INT32 | ABCD | W | Read | |||
| HR | 36912doc 9030h (36912) | Active power L1 | INT32 | ABCD | W | Read | |||
| HR | 36914doc 9032h (36914) | Active power L2 | INT32 | ABCD | W | Read | |||
| HR | 36916doc 9034h (36916) | Active power L3 | INT32 | ABCD | W | Read | |||
| HR | 36918doc 9036h (36918) | Total reactive power | INT32 | ABCD | VAr | Read | |||
| HR | 36920doc 9038h (36920) | Reactive power L1 | INT32 | ABCD | VAr | Read | |||
| HR | 36922doc 903Ah (36922) | Reactive power L2 | INT32 | ABCD | VAr | Read | |||
| HR | 36924doc 903Ch (36924) | Reactive power L3 | INT32 | ABCD | VAr | Read | |||
| HR | 36926doc 903Eh (36926) | Total active energy | UINT32 | ABCD | × 0.01 | Wh | Read | ||
| HR | 36928doc 9040h (36928) | Total reactive energy | UINT32 | ABCD | × 0.01 | varh | Read | ||
| HR | 36980doc 9074h (36980) | Active energy L1 | UINT32 | ABCD | × 0.01 | Wh | Read | ||
| HR | 36982doc 9076h (36982) | Active energy L2 | UINT32 | ABCD | × 0.01 | Wh | Read | ||
| HR | 36984doc 9078h (36984) | Active energy L3 | UINT32 | ABCD | × 0.01 | Wh | Read | ||
| HR | 36994doc 9082h (36994) | Voltage THD L1 | UINT32 | ABCD | × 0.01 | % | Read | ||
| HR | 36996doc 9084h (36996) | Voltage THD L2 | UINT32 | ABCD | × 0.01 | % | Read | ||
| HR | 36998doc 9086h (36998) | Voltage THD L3 | UINT32 | ABCD | × 0.01 | % | Read | ||
| HR | 37000doc 9088h (37000) | Current THD L1 | UINT32 | ABCD | × 0.01 | % | Read | ||
| HR | 37002doc 908Ah (37002) | Current THD L2 | UINT32 | ABCD | × 0.01 | % | Read | ||
| HR | 37004doc 908Ch (37004) | Current THD L3 | UINT32 | ABCD | × 0.01 | % | Read | ||
| HR | 37030doc 90A6h (37030) | Total apparent energy | UINT32 | ABCD | × 0.01 | VAh | Read | ||
| HR | 37038doc 90AEh (37038) | Active energy L1 (100 Wh steps) | UINT32 | ABCD | × 100 | Wh | Read | ||
| HR | 37040doc 90B0h (37040) | Active energy L2 (100 Wh steps) | UINT32 | ABCD | × 100 | Wh | Read | ||
| HR | 37042doc 90B2h (37042) | Active energy L3 (100 Wh steps) | UINT32 | ABCD | × 100 | Wh | Read | ||
| HR | 37044doc 90B4h (37044) | Total active energy (100 Wh steps) | UINT32 | ABCD | × 100 | Wh | Read | ||
| HR | 37052doc 90BCh (37052) | Total reactive energy (100 varh steps) | UINT32 | ABCD | × 100 | varh | Read | ||
| HR | 37060doc 90C4h (37060) | Total apparent energy (100 VAh steps) | UINT32 | ABCD | × 100 | VAh | Read | ||
| HR | 37632doc 9300h (37632) | CT ratio L1/L2/L3 | Range 0.1-6000. | UINT16 | × 0.1 | Read/write | |||
| HR | 37633doc 9301h (37633) | CT ratio N | Range 0.1-6000. | UINT16 | × 0.1 | Read/write | |||
| HR | 37634doc 9302h (37634) | Line current L4/N | UINT32 | ABCD | × 0.01 | A | Read | ||
| HR | 37636doc 9304h (37636) | Current THD L4/N | UINT32 | ABCD | × 0.01 | % | Read |
Notes on this map
- The manual says multi-register data has the most significant part in the lowest address (high word first).
- Per-sensor blocks repeat for sensors 1-96: TRMS 0000h-005Fh, AC 0100h-015Fh, DC 0200h-025Fh, min 0400h+, max 0800h+, hold 0C00h+, polarity 2000h+, power factor 7300h+ (one register each); branch power 2200h+ and energy 2300h+ (two registers each). Only the first entries are listed.
- Special values: 7FF0h = data pending, 7FFCh = sensor not reachable, 7FFDh = data type disabled, 7FFEh = overload, 7FFFh = no such sensor (FFFF7FFxh for 32-bit values).
- The table has a few misprints in its summary rows (the last AC sensor row shows 005F for 351; the group 2 energy row repeats 9'472); this map lists only rows whose hex and decimal agree.
- The frame description lists 1 stop bit; parity can be even (default), odd or none. Data bits are not stated.
- Left out: sensor serial/version blocks (1000h+), branch and group names, phase/group assignment registers and the threshold alarm block (8100h+).
- Group energy (2500h+, 100 Wh steps) is left out because the table prints the same decimal address (9'472) for groups 1 and 2.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)
What Modbus registers does the ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP) have?
This map lists 59 registers: 59 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The mapping table prints each address in hex (with the decimal beside it), and sensor 1 sits at 0000h, so the printed value is the request address with no offset. The manual has no example frame.
What byte order does the ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)?
Start with HR 0 TRMS current, sensor 1 (Branch 1 TRMS current); HR 36866 Voltage L1-N (Mains voltage L1-N); HR 36880 Line current L1 (Mains current L1); HR 36910 Total active power (Mains total active power); HR 37044 Total active energy (100 Wh steps) (Mains active energy (100 Wh)); HR 8960 Active energy, sensor 1 (Branch 1 energy).
How do I enable Modbus control of the ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)?
Set Modbus ID, baud rate and parity in the web UI (Settings > Communication / Modbus). Modbus TCP can be switched on or off there and its port changed; the standard port is 8001.
Where is the official ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP) Modbus documentation?
The source is CMS-700 User manual - Circuit Monitoring System (2CCC481011M0201 Rev. C), revision 2018-09, published free by ABB at https://library.e.abb.com/public/ae914775dba84d5ea4ed896c6c0378f9/CMS%20Manual_web.pdf.
More ABB Modbus register maps
- Variable frequency drive
ABB ACH480 HVAC drive (embedded Modbus RTU)
ACH480 drives running the ACH480 HVAC control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000247134 Rev E.
Also known as: ACH480-04, ACH480 HVAC control program - Variable frequency drive
ABB ACH550-UH HVAC drive (embedded Modbus RTU)
ACH550-UH HVAC drives using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AUA0000081823 Rev F.
Also known as: ACH550-UH, ACH550 - Variable frequency drive
ABB ACH580 HVAC drive (embedded Modbus RTU)
ACH580 drives running the ACH580 HVAC control program, embedded fieldbus (EFB) set to Modbus RTU, addressing mode 0 (default).
Also known as: ACH580-01, ACH580-07, ACH580-31, ACH580-34, ACH580 HVAC control program - Variable frequency drive
ABB ACQ580 water and wastewater drive (embedded Modbus RTU)
ACQ580 drives running the ACQ580 pump control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000035867 Rev H.
Also known as: ACQ580-01, ACQ580-04, ACQ580-07, ACQ580-31, ACQ580-34, ACQ580 pump control program - Variable frequency drive
ABB ACS180 machinery drive (embedded Modbus RTU)
ACS180 drives running the machinery control program, built-in EIA-485 Modbus RTU terminal (embedded fieldbus, EFB), addressing mode 0 (default); firmware manual 3AXD50000467860 Rev D.
Also known as: ACS180-04, ACS180 machinery control program - Variable frequency drive
ABB ACS310 pump and fan drive (embedded Modbus RTU)
ACS310 drives (01E/01U/03E/03U) using the embedded fieldbus: Modbus RTU on the built-in EIA-485 terminals 23-26 or RS-232 on the panel connector; user's manual 3AUA0000044201 Rev D.
Also known as: ACS310-01E, ACS310-01U, ACS310-03E, ACS310-03U - Variable frequency drive
ABB ACS355 machinery drive (embedded Modbus RTU)
ACS355 drives with firmware 5.110 or later using the embedded fieldbus (Modbus RTU) over an FMBA-01 adapter on terminal X3 (EIA-485) or the panel port (RS-232).
Also known as: ACS355-01E, ACS355-03E, ACS355-01U, ACS355-03U, ACS355 with FMBA-01 - Variable frequency drive
ABB ACS380 machinery drive (embedded Modbus RTU)
ACS380 drives running the machinery control program with the BMIO-01 I/O and Modbus RTU module, embedded fieldbus (EFB), addressing mode 0 (default); firmware manual 3AXD50000029275 Rev J.
Also known as: ACS380-04, ACS380 machinery control program, BMIO-01 - Variable frequency drive
ABB ACS480 general purpose drive (embedded Modbus RTU)
ACS480 drives running the ACS480 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000047399 Rev G.
Also known as: ACS480-04, ACS480 standard control program - Variable frequency drive
ABB ACS550-01/U1 general purpose drive (embedded Modbus RTU)
ACS550-01 and ACS550-U1 drives (0.75-160 kW / 1-200 hp) using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AFE64804588 Rev H.
Also known as: ACS550-01, ACS550-U1 - Variable frequency drive
ABB ACS580 general purpose drive (embedded Modbus RTU)
ACS580 drives running the ACS580 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default).
Also known as: ACS580-01, ACS580-04, ACS580-07, ACS580 standard control program - Variable frequency drive
ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link)
ACS800 drives running Standard Control Program 7.x with an RMBA-01 Modbus Adapter in option slot 1 or 2 (Standard Modbus Link, RTU only), ABB Drives communication profile.
Also known as: ACS800-01, ACS800-02, ACS800-04, ACS800-07, ACS800-11, ACS800-17, ACS800-31, ACS800-37, RMBA-01, ACS800 Standard Control Program - Variable frequency drive
ABB ACS880 industrial drive, primary control program (embedded Modbus RTU)
ACS880 drives running the primary control program (AINLX) 3.4x or later, embedded fieldbus (EFB) Modbus RTU on terminal XD2D, 58.33 Addressing mode = Mode 0 (default).
Also known as: ACS880-01, ACS880-04, ACS880-07, ACS880-11, ACS880-17, ACS880-31, ACS880-37, AINLX, ACS880 primary control program - Variable frequency drive (DC drive)
ABB DCS880 DC drive (embedded Modbus RTU)
DCS880 DC drives, firmware manual revision E, embedded fieldbus (EFB) Modbus RTU on control-board terminal XD2D, ABB Drives profile, 58.33 Addressing mode = Mode 0.
Also known as: DCS880-S01, DCS880-S02, DCS880-H, DCS880-R - Energy meter
ABB EQ meter A41 / A42 (Modbus RTU)
ABB EQ A41 (direct connected) and A42 (transformer connected) DIN meters whose RS-485 port is set to Modbus.
Also known as: A41, A42, EQ A41, EQ A42 - Energy meter
ABB EQ meter A43 / A44 (Modbus RTU)
ABB EQ A43 (direct connected) and A44 (transformer connected) three-phase DIN meters whose RS-485 port is set to Modbus.
Also known as: A43, A44, EQ A43, EQ A44 - Energy meter
ABB EQ meter B21 (Modbus RTU)
ABB EQ B21 single-phase 65 A DIN meter with the RS485 interface set to Modbus.
Also known as: B21, EQ B21 - Energy meter
ABB EQ meter B23 / B24 (Modbus RTU)
ABB EQ B23 (direct, 65 A) and B24 (CT-connected) three-phase DIN meters fitted with the RS485 interface set to Modbus.
Also known as: B23, B24, EQ B23, EQ B24 - Power meter (network analyzer)
ABB M4M 20 / M4M 30 network analyzer
ABB M4M 20 and M4M 30 network analyzers, Modbus RTU and Modbus TCP versions, map v1.3O; items marked M4M 30 only are absent on M4M 20.
Also known as: M4M 20, M4M 30, M4M 20 Modbus, M4M 30 Modbus, M4M 20 Ethernet, M4M 30 Ethernet, M4M 20 I/O, M4M 30 I/O, M4M 2X, M4M 30-M, M4M 32 - Process controller (sensor / PID controller)
ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)
ABB Protronic 100/500/550 and Digitric 500 universal process controllers with the RS-485/RS-232 Modbus interface module, interface description 42/62-50040 EN Rev. 04.
Also known as: Protronic 100, Protronic 500, Protronic 550, Digitric 500 - Soft starter (motor control)
ABB PSE softstarter (internal Modbus RTU)
ABB PSE18...PSE370 softstarters using the internal Modbus RTU interface (Modbus RTU adaptor on the front fieldbus connector), document 1SFC132367M0201 Rev B.
Also known as: PSE18, PSE25, PSE30, PSE37, PSE45, PSE60, PSE72, PSE85, PSE105, PSE142, PSE170, PSE210, PSE250, PSE300, PSE370 - Soft starter (motor control)
ABB PSTX softstarter (built-in Modbus RTU)
ABB PSTX30...PSTX1250 softstarters using the built-in Modbus RTU interface on terminals 23/24 (Com3), document 1SFC132089M0201 Rev F.
Also known as: PSTX30, PSTX37, PSTX45, PSTX60, PSTX72, PSTX85, PSTX105, PSTX142, PSTX170, PSTX210, PSTX250, PSTX300, PSTX370, PSTX470, PSTX570, PSTX720, PSTX840, PSTX1050, PSTX1250 - Power meter (DC circuit breaker trip unit)
ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU)
ABB SACE PR122DC and PR123DC DC protection trip units with the PR120/D-M communication module, document rev 02 (04/04/2014, SW 3.01 and later).
Also known as: PR122DC, PR123DC, PR120/D-M, Emax DC, SACE Emax DC - Power meter (circuit breaker trip unit)
ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU)
ABB SACE PR122/P and PR123/P (Emax) and PR332/P and PR333/P (Emax X1, Tmax T7, Tmax T8) protection releases with the Modbus RTU communication module, per 1SDH000556R0001.
Also known as: PR122/P, PR123/P, PR332/P, PR333/P, PR120/D-M, PR330/D-M, Emax PR122, Emax PR123, Tmax T7 PR332, Emax X1 PR333, Tmax T8 PR332 - Power meter (circuit breaker trip unit)
ABB SACE Tmax PR223DS trip unit (Modbus RTU)
ABB SACE PR223DS electronic trip unit (Tmax moulded-case breakers), software version 02.02, per 1SDH000658R0001.
Also known as: PR223DS, Tmax PR223DS, SACE PR223DS
Other power & energy meters register maps
- Energy meter (thermal / BTU meter)
Belimo Thermal Energy Meter (TEM) DN 15-50, Version 4 (Modbus RTU / TCP)
Belimo Thermal Energy Meter DN 15...50 version 4 (22PE..-1U.., 22PF-..U..), interface description V4.2.0 edition 2025-11.
Also known as: 22PE-1U, 22PEM-1UC, 22PE..-1U.., 22PF, Belimo Thermal Energy Meter, Belimo TEM - Energy meter (energy analyzer)
Carlo Gavazzi EM24-DIN (PFA, PFB and X models)
EM24-DIN three-phase energy analyzers, PFA/PFB (MID) and X models with the RS485 Modbus RTU port (IS option), protocol version 4 revision 0.
Also known as: EM24, EM24DIN, EM24DINAV93XISPFA, EM24DINAV93XISPFB, EM24DINAV93XISX, EM24DINAV53XISX, EM24DINAV23XISX, EM24 DIN AV9, EM24 DIN AV5 - Energy meter
Carlo Gavazzi EM530 / EM540 three-phase energy meters (RS485 Modbus)
EM530 (CT-connected) and EM540 (direct-connected) with the S1 RS485 port, X and MID (PFA/PFB/PFC) versions, protocol document version 1.3.
Also known as: EM530, EM540, EM530DINAV53XS1X, EM530DINAV53XS1PFA, EM530DINAV53XS1PFB, EM530DINAV53XS1PFC, EM540DINAV23XS1X, EM540DINAV23XS1PFA, EM540DINAV23XS1PFB, EM540DINAV23XS1PFC, EM500 series - Power meter (static reactive energy regulator)
Circutor Computer SMART III FAST
Circutor Computer SMART III FAST static reactive power regulators (6 and 12 stage), manual M021B01-03-21A.
Also known as: Computer SMART III FAST 6, Computer SMART III FAST 12 - Power meter
DENT Instruments PowerScout 3037 Power Meter
PowerScout 3037 serial (RS-485) and Ethernet meters in Modbus mode, per the November 9, 2017 PS3037 Operator's Guide.
Also known as: PS3037, PowerScout 3037 Ethernet, PS3037-E, PowerScout 3037 Serial - Energy meter
Eastron SDM230-Modbus
Eastron SDM230-Modbus (two-tariff SDM230-2T protocol) single-phase two-module DIN-rail meter, protocol V1.1.
Also known as: SDM230Modbus, SDM230-2T, SDM230-M
All power & energy meters Modbus register maps →
Source: CMS-700 User manual - Circuit Monitoring System · 2CCC481011M0201 Rev. C · rev. 2018-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.