Easy Modbus
  1. Home
  2. Modbus register maps
  3. ABB
  4. CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)

Power meter (branch circuit monitoring) · Modbus register map

ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP) Modbus register map

Updated 19 November 2026

Short answer

The CMS-700 control unit measures mains voltage, current, power and energy and collects up to 96 open-core or solid-core branch current sensors. It serves everything over Modbus RTU (RS-485) and Modbus TCP on port 8001. Branch currents are 16-bit values in 0.01 A; mains values and branch power/energy are 32-bit, high word first.

This page lists 59 Modbus registers for the ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ABB’s own free documentation (linked below) and checked against it.

Manufacturer
ABB
Model
CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)
Equipment type
Power meter (branch circuit monitoring)
Registers
59 (5 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Default serial
19200 baud, 8E1
TCP port
8001
Documented addressing
hexadecimal, 0-based
32-bit word order
ABCD high word first (big-endian)
Also known as
CMS-700, CMS700, ABB CMS-700, CMS-700 control unit
Source document
CMS-700 User manual - Circuit Monitoring System · 2CCC481011M0201 Rev. C · rev. 2018-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)

Integration in brief

Read 0000h-005Fh for all branch TRMS currents in one block (0.01 A) and 9002h-90C4h for the mains. Branch power and energy come from 2200h and 2300h.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0TRMS current, sensor 1UINT16Branch 1 TRMS currentRead
HR 36866Voltage L1-NUINT32 ABCDMains voltage L1-NRead
HR 36880Line current L1UINT32 ABCDMains current L1Read
HR 36910Total active powerINT32 ABCDMains total active powerRead
HR 37044Total active energy (100 Wh steps)UINT32 ABCDMains active energy (100 Wh)Read
HR 8960Active energy, sensor 1UINT32 ABCDBranch 1 energyRead

Enable Modbus control & writes

Set Modbus ID, baud rate and parity in the web UI (Settings > Communication / Modbus). Modbus TCP can be switched on or off there and its port changed; the standard port is 8001.

Byte order & addressing

Network setup

Watch out for

ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

59 of 59 shown
ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 0000h (0)TRMS current, sensor 1Sensor n: add n-1 (n = 1-96).UINT16× 0.01ARead
HR1doc 0001h (1)TRMS current, sensor 2UINT16× 0.01ARead
HR95doc 005Fh (95)TRMS current, sensor 96UINT16× 0.01ARead
HR256doc 0100h (256)AC current, sensor 1Sensor n: add n-1 (n = 1-96).UINT16× 0.01ARead
HR512doc 0200h (512)DC current, sensor 1Sensor n: add n-1 (n = 1-96). Signed.INT16× 0.01ARead
HR1024doc 0400h (1024)TRMS minimum, sensor 1Sensor n: add n-1 (n = 1-96).UINT16× 0.01ARead
HR2048doc 0800h (2048)TRMS maximum, sensor 1Sensor n: add n-1 (n = 1-96).UINT16× 0.01ARead
HR3072doc 0C00h (3072)TRMS hold value, sensor 1Captured by the trigger-hold command. Sensor n: add n-1 (n = 1-96).UINT16× 0.01ARead
HR8192doc 2000h (8192)DC polarity, sensor 1Bit 12: 0 = direct, 1 = reverse. Sensor n: add n-1 (n = 1-96).BITMAP16Read/writebit 12 = DC polarity reverse
HR8704doc 2200h (8704)Active power, sensor 1Calculated branch power. Sensor n: add 2 x (n-1) (n = 1-96).UINT32ABCDWRead
HR8960doc 2300h (8960)Active energy, sensor 1Calculated branch energy. Sensor n: add 2 x (n-1) (n = 1-96).UINT32ABCD× 0.1WhRead
HR9216doc 2400h (9216)Active power, group 1Group n: add 2 x (n-1) (n = 1-96).UINT32ABCDWRead
HR12304doc 3010h (12304)Trigger hold / reset min-maxBit 4 = trigger hold, bit 0 = reset min/max.BITMAP16Writebit 0 = Reset min and max values; bit 4 = Trigger hold measurement
HR29440doc 7300h (29440)Power factor, sensor 1Configured PF used for branch power. Sensor n: add n-1 (n = 1-96).UINT16× 0.01Read/write
HR32768doc 8000h (32768)Number of current alarmsUINT16Read
HR32769doc 8001h (32769)Alarm status, branch 1Branch n: add n-1 (8001h-8060h).UINT16Read
HR36866doc 9002h (36866)Voltage L1-NUINT32ABCD× 0.01VRead
HR36868doc 9004h (36868)Voltage L2-NUINT32ABCD× 0.01VRead
HR36870doc 9006h (36870)Voltage L3-NUINT32ABCD× 0.01VRead
HR36880doc 9010h (36880)Line current L1UINT32ABCD× 0.01ARead
HR36882doc 9012h (36882)Line current L2UINT32ABCD× 0.01ARead
HR36884doc 9014h (36884)Line current L3UINT32ABCD× 0.01ARead
HR36888doc 9018h (36888)Power factor L1INT32ABCD× 0.01Read
HR36890doc 901Ah (36890)Power factor L2INT32ABCD× 0.01Read
HR36892doc 901Ch (36892)Power factor L3INT32ABCD× 0.01Read
HR36902doc 9026h (36902)Total apparent powerUINT32ABCDVARead
HR36904doc 9028h (36904)Apparent power L1UINT32ABCDVARead
HR36906doc 902Ah (36906)Apparent power L2UINT32ABCDVARead
HR36908doc 902Ch (36908)Apparent power L3UINT32ABCDVARead
HR36910doc 902Eh (36910)Total active powerINT32ABCDWRead
HR36912doc 9030h (36912)Active power L1INT32ABCDWRead
HR36914doc 9032h (36914)Active power L2INT32ABCDWRead
HR36916doc 9034h (36916)Active power L3INT32ABCDWRead
HR36918doc 9036h (36918)Total reactive powerINT32ABCDVArRead
HR36920doc 9038h (36920)Reactive power L1INT32ABCDVArRead
HR36922doc 903Ah (36922)Reactive power L2INT32ABCDVArRead
HR36924doc 903Ch (36924)Reactive power L3INT32ABCDVArRead
HR36926doc 903Eh (36926)Total active energyUINT32ABCD× 0.01WhRead
HR36928doc 9040h (36928)Total reactive energyUINT32ABCD× 0.01varhRead
HR36980doc 9074h (36980)Active energy L1UINT32ABCD× 0.01WhRead
HR36982doc 9076h (36982)Active energy L2UINT32ABCD× 0.01WhRead
HR36984doc 9078h (36984)Active energy L3UINT32ABCD× 0.01WhRead
HR36994doc 9082h (36994)Voltage THD L1UINT32ABCD× 0.01%Read
HR36996doc 9084h (36996)Voltage THD L2UINT32ABCD× 0.01%Read
HR36998doc 9086h (36998)Voltage THD L3UINT32ABCD× 0.01%Read
HR37000doc 9088h (37000)Current THD L1UINT32ABCD× 0.01%Read
HR37002doc 908Ah (37002)Current THD L2UINT32ABCD× 0.01%Read
HR37004doc 908Ch (37004)Current THD L3UINT32ABCD× 0.01%Read
HR37030doc 90A6h (37030)Total apparent energyUINT32ABCD× 0.01VAhRead
HR37038doc 90AEh (37038)Active energy L1 (100 Wh steps)UINT32ABCD× 100WhRead
HR37040doc 90B0h (37040)Active energy L2 (100 Wh steps)UINT32ABCD× 100WhRead
HR37042doc 90B2h (37042)Active energy L3 (100 Wh steps)UINT32ABCD× 100WhRead
HR37044doc 90B4h (37044)Total active energy (100 Wh steps)UINT32ABCD× 100WhRead
HR37052doc 90BCh (37052)Total reactive energy (100 varh steps)UINT32ABCD× 100varhRead
HR37060doc 90C4h (37060)Total apparent energy (100 VAh steps)UINT32ABCD× 100VAhRead
HR37632doc 9300h (37632)CT ratio L1/L2/L3Range 0.1-6000.UINT16× 0.1Read/write
HR37633doc 9301h (37633)CT ratio NRange 0.1-6000.UINT16× 0.1Read/write
HR37634doc 9302h (37634)Line current L4/NUINT32ABCD× 0.01ARead
HR37636doc 9304h (37636)Current THD L4/NUINT32ABCD× 0.01%Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)

What Modbus registers does the ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP) have?

This map lists 59 registers: 59 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The mapping table prints each address in hex (with the decimal beside it), and sensor 1 sits at 0000h, so the printed value is the request address with no offset. The manual has no example frame.

What byte order does the ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)?

Start with HR 0 TRMS current, sensor 1 (Branch 1 TRMS current); HR 36866 Voltage L1-N (Mains voltage L1-N); HR 36880 Line current L1 (Mains current L1); HR 36910 Total active power (Mains total active power); HR 37044 Total active energy (100 Wh steps) (Mains active energy (100 Wh)); HR 8960 Active energy, sensor 1 (Branch 1 energy).

How do I enable Modbus control of the ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)?

Set Modbus ID, baud rate and parity in the web UI (Settings > Communication / Modbus). Modbus TCP can be switched on or off there and its port changed; the standard port is 8001.

Where is the official ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP) Modbus documentation?

The source is CMS-700 User manual - Circuit Monitoring System (2CCC481011M0201 Rev. C), revision 2018-09, published free by ABB at https://library.e.abb.com/public/ae914775dba84d5ea4ed896c6c0378f9/CMS%20Manual_web.pdf.

More ABB Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: CMS-700 User manual - Circuit Monitoring System · 2CCC481011M0201 Rev. C · rev. 2018-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.