- Thermal Energy Meter (TEM) DN 15-50, Version 4 (Modbus RTU / TCP)
Energy meter (thermal / BTU meter) · Modbus register map
Belimo Thermal Energy Meter (TEM) DN 15-50, Version 4 (Modbus RTU / TCP) Modbus register map
Updated 17 November 2026
Ultrasonic thermal energy (BTU) meter with flow and two temperature sensors, readable over Modbus RTU or Modbus TCP. One flat register table carries flow, supply/return temperatures, delta T, glycol, heating and cooling power and energy, volume, nominal values, unit selection and a health bitmask.
This page lists 45 Modbus registers for the Belimo Thermal Energy Meter (TEM) DN 15-50, Version 4 (Modbus RTU / TCP) — 7 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Belimo’s own free documentation (linked below) and checked against it.
- Manufacturer
- Belimo
- Model
- Thermal Energy Meter (TEM) DN 15-50, Version 4 (Modbus RTU / TCP)
- Equipment type
- Energy meter (thermal / BTU meter)
- Registers
- 45 (7 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- 1
- Default serial
- 38400 baud, 8N2
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- 22PE-1U, 22PEM-1UC, 22PE..-1U.., 22PF, Belimo Thermal Energy Meter, Belimo TEM
Integration notes: Belimo Thermal Energy Meter (TEM) DN 15-50, Version 4 (Modbus RTU / TCP)
Poll Nos. 20-24 (temperatures and delta T), 8 (flow), 28/34 (cooling/heating power) and 66/72 (energy) with FC03, decoding 32-bit values low word first. Check No. 105 for sensor and flow faults.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 7 | Absolute volumetric flow | UINT16 | Flow l/s | Read |
| HR 19 | Temperature 1 (remote) | INT16 | Remote temperature | Read |
| HR 21 | Temperature 2 (flow body) | INT16 | Flow-body temperature | Read |
| HR 23 | Delta temperature | UINT16 | Delta T | Read |
| HR 27 | Absolute power cooling | UINT32 CDAB | Cooling power kW | Read |
| HR 33 | Absolute power heating | UINT32 CDAB | Heating power kW | Read |
| HR 65 | Absolute energy cooling | UINT32 CDAB | Cooling energy kWh | Read |
| HR 71 | Absolute energy heating | UINT32 CDAB | Heating energy kWh | Read |
| HR 104 | Malfunction and service information | BITMAP16 | Fault bitmask | Read |
Enable Modbus control & writes
Modbus is the native interface; set address, baud rate and frame format with Belimo Assistant 2 or the built-in web server.
Byte order & addressing
- 32-bit values are low word first (CDAB).
- Register No. vs Address: subtract 1 for the wire address.
- On MID models (22PEM) register 205 picks certified vs lifetime counters; switching it changes what the energy registers show.
Network setup
- RTU defaults: address 1, 38400 baud, 8-N-2; also 8-N-1, 8-E-1, 8-O-1 and 9600-115200 baud.
- Up to 32 nodes without repeater; internal 120 ohm terminator set by tool.
Watch out for
- The certified meter register resets when the sensor module is replaced; avoid toggling register 205, as it disturbs data logging.
Belimo Thermal Energy Meter (TEM) DN 15-50, Version 4 (Modbus RTU / TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 3doc 4 | Device type | UINT16 | Read | 0 = Device not connected; 1 = Air/Water; 2 = VAV / EPIV; 3 = Fire; 4 = Energy Valve / Energy Meter; 5 = 6-way EPIV | ||||
| HR | 6doc 7 | Relative volumetric flow | Flow as a share of nominal flow qp. | UINT16 | × 0.01 | % | Read | ||
| HR | 7doc 8 | Absolute volumetric flow | UINT16 | × 0.01 | l/s | Read | |||
| HR | 8doc 9 | Absolute volumetric flow (gpm) | UINT16 | × 0.1 | gpm | Read | |||
| HR | 12doc 13 | Sensor 1 value | Raw reading of the extra sensor input on Y3. | UINT16 | mV | Read | |||
| HR | 13doc 14 | Sensor 1 temperature | INT16 | × 0.01 | °C | Read | |||
| HR | 14doc 15 | Sensor 1 temperature (°F) | INT16 | × 0.01 | °F | Read | |||
| HR | 19doc 20 | Temperature 1 (remote) | INT16 | × 0.01 | °C | Read | |||
| HR | 20doc 21 | Temperature 1 (remote) (°F) | INT16 | × 0.01 | °F | Read | |||
| HR | 21doc 22 | Temperature 2 (flow body) | INT16 | × 0.01 | °C | Read | |||
| HR | 22doc 23 | Temperature 2 (flow body) (°F) | INT16 | × 0.01 | °F | Read | |||
| HR | 23doc 24 | Delta temperature | UINT16 | × 0.01 | K | Read | |||
| HR | 24doc 25 | Delta temperature (°F) | UINT16 | × 0.01 | °F | Read | |||
| HR | 25doc 26 | Glycol concentration | UINT16 | × 0.01 | % | Read | |||
| HR | 27doc 28-29 | Absolute power cooling | UINT32 | CDAB | × 0.001 | kW | Read | ||
| HR | 29doc 30-31 | Absolute power cooling (kBTU/h) | UINT32 | CDAB | × 0.001 | kBTU/h | Read | ||
| HR | 33doc 34-35 | Absolute power heating | UINT32 | CDAB | × 0.001 | kW | Read | ||
| HR | 35doc 36-37 | Absolute power heating (kBTU/h) | UINT32 | CDAB | × 0.001 | kBTU/h | Read | ||
| HR | 59doc 60-61 | Accumulated volume | Cannot be reset; follows register 205 choice. | UINT32 | CDAB | × 0.01 | m³ | Read | |
| HR | 61doc 62-63 | Accumulated volume (gal) | UINT32 | CDAB | gal | Read | |||
| HR | 65doc 66-67 | Absolute energy cooling | Follows the meter register chosen in register 205. | UINT32 | CDAB | kWh | Read | ||
| HR | 67doc 68-69 | Absolute energy cooling (kBTU) | UINT32 | CDAB | kBTU | Read | |||
| HR | 69doc 70-71 | Absolute energy cooling in selected unit | Unit set by register 151 (default kWh). | UINT32 | CDAB | Read | |||
| HR | 71doc 72-73 | Absolute energy heating | Follows the meter register chosen in register 205. | UINT32 | CDAB | kWh | Read | ||
| HR | 73doc 74-75 | Absolute energy heating (kBTU) | UINT32 | CDAB | kBTU | Read | |||
| HR | 75doc 76-77 | Absolute energy heating in selected unit | Unit set by register 151 (default kWh). | UINT32 | CDAB | Read | |||
| HR | 99doc 100 | Bus termination | 120 ohm terminator state, set with Belimo Assistant 2. | UINT16 | Read | 0 = Disabled; 1 = Enabled | |||
| HR | 100doc 101 | Series number 1st part | UINT16 | Read | |||||
| HR | 101doc 102 | Series number 2nd part | UINT16 | Read | |||||
| HR | 102doc 103 | Series number 4th part | UINT16 | Read | |||||
| HR | 103doc 104 | Firmware version | Communication module firmware, e.g. 402 = 4.02. | UINT16 | Read | ||||
| HR | 104doc 105 | Malfunction and service information | BITMAP16 | Read | bit 3 = Reverse flow; bit 6 = Flow above nominal flow; bit 7 = Flow measurement error; bit 8 = Remote temperature sensor error; bit 9 = Flow-body temperature sensor error; bit 10 = Communication to flow sensor interrupted; bit 11 = Freeze warning; bit 12 = Glycol detected; bit 14 = Device end of life reached (MID) | ||||
| HR | 110doc 111 | Nominal volumetric flow qp | UINT16 | × 0.01 | l/s | Read | |||
| HR | 111doc 112 | Nominal volumetric flow qp (gpm) | UINT16 | × 0.1 | gpm | Read | |||
| HR | 120doc 121 | Sensor 1 type | Index 2 is printed with a symbol only. | UINT16 | Read/write | 0 = None; 1 = Active; 3 = Passive; 4 = Switch | |||
| HR | 121doc 122 | Sensor 1 passive type | Used when register 121 = 3 (passive). | UINT16 | Read/write | 0 = Resistance measurement; 1 = PT1000; 2 = Ni1000; 7 = NTC10k2; 8 = NTC10k3 | |||
| HR | 147doc 148 | Unit selection flow | Default 4 (l/h). | UINT16 | Read/write | 0 = m³/s; 1 = m³/h; 2 = l/s; 3 = l/min; 4 = l/h; 5 = gpm; 6 = cfm | |||
| HR | 148doc 149 | Unit selection power | Default 1 (kW). | UINT16 | Read/write | 0 = W; 1 = kW; 2 = MW; 3 = BTU/h; 4 = kBTU/h; 5 = ton | |||
| HR | 149doc 150 | Unit selection volume | Default 0 (m³). | UINT16 | Read/write | 0 = m³; 1 = Litre; 2 = Gallon; 3 = cf | |||
| HR | 150doc 151 | Unit selection energy | Default 5 (kWh). | UINT16 | Read/write | 0 = J; 1 = kJ; 2 = MJ; 3 = GJ; 4 = Wh; 5 = kWh; 6 = MWh; 7 = BTU; 8 = kBTU; 9 = ton | |||
| HR | 159doc 160-161 | Nominal power P'nom | UINT32 | CDAB | × 0.001 | kW | Read | ||
| HR | 161doc 162-163 | Nominal power P'nom (kBTU/h) | UINT32 | CDAB | × 0.001 | kBTU/h | Read | ||
| HR | 200doc 201-202 | Energy meter serial number first digits | Production order number. | UINT32 | CDAB | Read | |||
| HR | 202doc 203-204 | Energy meter serial number last digits | Production sequence number. | UINT32 | CDAB | Read | |||
| HR | 204doc 205 | Select meter register | Chooses which counters registers 60-77 show. | UINT16 | Read/write | 0 = Certified meter register (MID models 22PEM only); 1 = Lifetime meter register |
Notes on this map
- Word order: the manual says 32-bit values use two consecutive registers with the least significant word first (register No. x = low word, x+1 = high word); both must be written together with FC16. Mapped as CDAB.
- Values are unsigned unless marked signed; the signed ones are the sensor 1 temperature and temperature 1/2 registers. Unsupported registers read 65535.
- Left out: flow, power, volume and nominal-flow/power registers 'in selected unit' (Nos. 10/11, 32/33, 38/39, 64/65, 113/114, 164/165), because the printed scale applies to several units at once and does not map cleanly to every unit choice. Energy in selected unit (70/71, 76/77) is listed since its scale is 1 for every unit.
- The power-cooling-in-selected-unit row is printed as 'No. 32, Address 30' in the description table but 'No. 32, Address 31' in the overview; it is omitted anyway.
- Registers above No. 100 that are writable are stored permanently; do not write them cyclically.
- The PDF was downloaded for checking from a distributor mirror (zotsupply.com) that carries the same edition; the link above is Belimo's own copy.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Belimo Thermal Energy Meter (TEM) DN 15-50, Version 4 (Modbus RTU / TCP)
What Modbus registers does the Belimo Thermal Energy Meter (TEM) DN 15-50, Version 4 (Modbus RTU / TCP) have?
This map lists 45 registers: 45 holding registers. 7 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Belimo Thermal Energy Meter (TEM) DN 15-50, Version 4 (Modbus RTU / TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Belimo lists 'No.' (from 1) and 'Address' (from 0) for each register; 'documented' is the No. column, so No. 8 is wire address 7. All data sit in one table, reachable with FC03 reads and FC06/FC16 writes; FC04 and FC02 also work as alternatives.
What byte order does the Belimo Thermal Energy Meter (TEM) DN 15-50, Version 4 (Modbus RTU / TCP) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Belimo Thermal Energy Meter (TEM) DN 15-50, Version 4 (Modbus RTU / TCP)?
Start with HR 7 Absolute volumetric flow (Flow l/s); HR 19 Temperature 1 (remote) (Remote temperature); HR 21 Temperature 2 (flow body) (Flow-body temperature); HR 23 Delta temperature (Delta T); HR 27 Absolute power cooling (Cooling power kW); HR 33 Absolute power heating (Heating power kW); HR 65 Absolute energy cooling (Cooling energy kWh); HR 71 Absolute energy heating (Heating energy kWh); HR 104 Malfunction and service information (Fault bitmask).
How do I enable Modbus control of the Belimo Thermal Energy Meter (TEM) DN 15-50, Version 4 (Modbus RTU / TCP)?
Modbus is the native interface; set address, baud rate and frame format with Belimo Assistant 2 or the built-in web server.
Where is the official Belimo Thermal Energy Meter (TEM) DN 15-50, Version 4 (Modbus RTU / TCP) Modbus documentation?
The source is Modbus Interface Description - Thermal Energy Meter (TEM), DN 15...50 (Version 4) (V4.2.0, EN 2025-11/B), revision 2025-11, published free by Belimo at https://www.belimo.com/mam/general-documents/system_integration/Modbus/belimo_Modbus-Register_TEM_V4_2_en-gb.pdf.
More Belimo Modbus register maps
- Actuator / valve (pressure-independent characterised control valve)
Belimo 2-way EPIV DN 15-50 (Version 4.2) Modbus RTU
Belimo 2-way EPIV DN 15-50 Version 4 (EP..R2+(K)BAC) on Modbus RTU, per interface description edition 2025-09 / V4.2.
Also known as: EP..R2+BAC, EP..R2+KBAC, Electronic pressure-independent valve - Actuator / valve (6-way pressure-independent change-over valve)
Belimo 6-way EPIV Modbus RTU (EP..R-R6+BAC)
Belimo 6-way EPIV EP..R-R6+BAC on Modbus RTU, per 6-way EPIV Modbus Register en-gb 2024-01 (general notes dated 16.12.2019).
Also known as: EP..R-R6+BAC, 6-way pressure-independent valve - Actuator / valve (damper and valve actuator)
Belimo Air/water actuators with Modbus RTU (..24A-MOD)
Belimo ..M(C)24A-MOD, ..R24A-MOD, ..V(K)24A-MOD, ..F24A-MOD, ..RF24A-MOD and ..H24A-MOD air/water actuators, per Modbus interface description edition 2026-05 / V3.08.
Also known as: LM24A-MOD, NM24A-MOD, SM24A-MOD, GM24A-MOD, LMC24A-MOD, NMC24A-MOD, NR24A-MOD, LR24A-MOD, NV24A-MOD, NVK24A-MOD, LF24A-MOD, NF24A-MOD, NRF24A-MOD, LRF24A-MOD, LH24A-MOD, SH24A-MOD - Actuator / valve (pressure-independent control valve with energy metering)
Belimo Energy Valve DN 15-50 (Version 4) Modbus RTU / TCP
Belimo Energy Valve Version 4, DN 15-50 (EV..R2+(K)BAC, EV..R2+MID, EV..R3+BAC), per Energy Valve Modbus interface description en-gb 2023-08.
Also known as: EV..R2+BAC, EV..R2+KBAC, EV..R2+MID, EV..R3+BAC, Energy Valve 4
Other power & energy meters register maps
- Energy meter (energy analyzer)
Carlo Gavazzi EM24-DIN (PFA, PFB and X models)
EM24-DIN three-phase energy analyzers, PFA/PFB (MID) and X models with the RS485 Modbus RTU port (IS option), protocol version 4 revision 0.
Also known as: EM24, EM24DIN, EM24DINAV93XISPFA, EM24DINAV93XISPFB, EM24DINAV93XISX, EM24DINAV53XISX, EM24DINAV23XISX, EM24 DIN AV9, EM24 DIN AV5 - Energy meter
Carlo Gavazzi EM530 / EM540 three-phase energy meters (RS485 Modbus)
EM530 (CT-connected) and EM540 (direct-connected) with the S1 RS485 port, X and MID (PFA/PFB/PFC) versions, protocol document version 1.3.
Also known as: EM530, EM540, EM530DINAV53XS1X, EM530DINAV53XS1PFA, EM530DINAV53XS1PFB, EM530DINAV53XS1PFC, EM540DINAV23XS1X, EM540DINAV23XS1PFA, EM540DINAV23XS1PFB, EM540DINAV23XS1PFC, EM500 series - Power meter (static reactive energy regulator)
Circutor Computer SMART III FAST
Circutor Computer SMART III FAST static reactive power regulators (6 and 12 stage), manual M021B01-03-21A.
Also known as: Computer SMART III FAST 6, Computer SMART III FAST 12 - Power meter
DENT Instruments PowerScout 3037 Power Meter
PowerScout 3037 serial (RS-485) and Ethernet meters in Modbus mode, per the November 9, 2017 PS3037 Operator's Guide.
Also known as: PS3037, PowerScout 3037 Ethernet, PS3037-E, PowerScout 3037 Serial - Energy meter
Eastron SDM230-Modbus
Eastron SDM230-Modbus (two-tariff SDM230-2T protocol) single-phase two-module DIN-rail meter, protocol V1.1.
Also known as: SDM230Modbus, SDM230-2T, SDM230-M - Sensor (electromagnetic flowmeter)
Endress+Hauser Proline Promag 300 electromagnetic flowmeter (Modbus RS485)
Promag 300 with the Modbus RS485 communication option, parameter description GP01053D/06/EN/04.22.
Also known as: Promag 300, Promag P 300, Promag H 300, Promag W 300
All power & energy meters Modbus register maps →
Source: Modbus Interface Description - Thermal Energy Meter (TEM), DN 15...50 (Version 4) · V4.2.0, EN 2025-11/B · rev. 2025-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.