Actuator / valve (6-way pressure-independent change-over valve) · Modbus register map

Belimo 6-way EPIV Modbus RTU (EP..R-R6+BAC) Modbus register map

Updated 28 October 2026

Short answer

Belimo's 6-way EPIV serves two circuits (sequence 1 and sequence 2) through one valve and controls the flow in each with its own flow sensor. Over Modbus RTU one setpoint register covers both sequences (0-33 % and 67-100 %, with a closed dead band in between); the map also gives position, flow in three units, the active sequence, Vmax per sequence and fault flags.

This page lists 25 Modbus registers for the Belimo 6-way EPIV Modbus RTU (EP..R-R6+BAC) — 7 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Belimo’s own free documentation (linked below) and checked against it.

Manufacturer
Belimo
Model
6-way EPIV Modbus RTU (EP..R-R6+BAC)
Equipment type
Actuator / valve (6-way pressure-independent change-over valve)
Registers
25 (7 writable)
Transport
Modbus RTU
Default unit ID
10
Default serial
38400 baud, 8N2
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
CDAB low word first (word-swapped)
Also known as
EP..R-R6+BAC, 6-way pressure-independent valve
Source document
Modbus Register - 6-way EPIV · 6-way EPIV Modbus Register en-gb 2024-01 · rev. 2024-01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Belimo 6-way EPIV Modbus RTU (EP..R-R6+BAC)

Integration in brief

Set the address (factory 10) and frame with the Belimo Assistant app, write Setpoint source No. 119 = 1 (Bus), then write No. 1: 0-33 % runs sequence 1, 67-100 % sequence 2, 34-66 % closes. Poll No. 17 (active sequence), No. 7/10 (flow) and No. 105 (faults).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 118Setpoint sourceUINT16Setpoint source = Bus (default Analog)Read/write
HR 0SetpointUINT16Setpoint across both sequencesRead/write
HR 16Active sequenceUINT16Active sequenceRead
HR 9Absolute volumetric flow (l/h)UINT32 CDABFlow l/hRead
HR 4Relative positionUINT16Relative positionRead
HR 104Malfunction and service informationBITMAP16Fault flagsRead

Enable Modbus control & writes

Configure address and frame with the Belimo Assistant app, then write No. 119 = 1 so the valve follows the bus setpoint (factory setting is Analog).

Byte order & addressing

Network setup

Watch out for

Belimo 6-way EPIV Modbus RTU (EP..R-R6+BAC) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

25 of 25 shown
Belimo 6-way EPIV Modbus RTU (EP..R-R6+BAC) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1SetpointFlow control: 0-33 % runs sequence 1, 67-100 % sequence 2. Position control: plain 0-100 %.UINT16× 0.01%Read/write
HR1doc 2Override controlForces a fixed position or flow.UINT16Read/write0 = None; 1 = Open sequence 1 (0 %); 2 = Open sequence 2 (100 %); 3 = Close (50 %); 4 = Vmax sequence 1; 5 = Vmax sequence 2
HR3doc 4Actuator typeUINT16Read0 = Actuator not connected; 1 = Air / water; 2 = VAV / EPIV; 3 = Fire; 4 = Energy Valve; 5 = 6-way EPIV
HR4doc 5Relative positionUINT16× 0.01%Read
HR5doc 6Absolute positionUINT16× 0.01°Read
HR6doc 7Relative volumetric flowFlow as % of the active Vmax (Vmax1 or Vmax2).UINT16× 0.01%Read
HR7doc 8Absolute volumetric flow (selected unit)Unit set by No. 118.UINT32CDAB× 0.001see No. 118Read
HR9doc 10Absolute volumetric flow (l/h)UINT32CDAB× 0.001l/hRead
HR11doc 12Absolute volumetric flow (gpm)UINT32CDAB× 0.001gpmRead
HR13doc 14Flow setpoint (selected unit)Active absolute flow setpoint; unit set by No. 118.UINT32CDAB× 0.001see No. 118Read
HR15doc 16Setpoint analogAnalog control voltage when Setpoint source = Analog.UINT16× 0.01VRead
HR16doc 17Active sequenceUINT16Read0 = Sequence 1 (0-33 %); 1 = Sequence 2 (67-100 %); 2 = Dead band (34-66 %)
HR100doc 101Series number 1st partFirst block of the serial number on the housing label.UINT16Read
HR101doc 102Series number 2nd partSecond block of the serial number.UINT16Read
HR102doc 103Series number 4th partFourth block of the serial number (the third is not exposed).UINT16Read
HR103doc 104Firmware versionBus module firmware; 302 means version 3.02.UINT16Read
HR104doc 105Malfunction and service informationBit-coded fault flags; several can be set at once.BITMAP16Readbit 2 = Error flow sensor; bit 3 = Actuator cannot move; bit 4 = Flow with closed valve; bit 5 = Air bubbles (runs in position control until cleared); bit 6 = Flow not reached within 3 min; bit 9 = Gear disengaged
HR105doc 106Vmax sequence 1Max flow for sequence 1, 5-100 %; default 100 %.UINT16× 0.01%Read/write
HR106doc 107Vmax sequence 2Max flow for sequence 2, 5-100 %; default 100 %.UINT16× 0.01%Read/write
HR110doc 111Nominal volumetric flow (selected unit)Vnom; unit set by No. 118.UINT32CDAB× 0.001see No. 118Read
HR112doc 113Nominal volumetric flow (l/h)UINT32CDAB× 0.001l/hRead
HR114doc 115Nominal volumetric flow (gpm)UINT32CDAB× 0.001gpmRead
HR116doc 117Control modeDefault flow control.UINT16Read/write0 = Position control; 1 = Flow control
HR117doc 118Unit selection flowDefault l/h.UINT16Read/write0 = m3/s; 1 = m3/h; 2 = l/s; 3 = l/min; 4 = l/h; 5 = gpm; 6 = cfm
HR118doc 119Setpoint sourceAnalog = 0-10 V on wire 3; Bus = No. 1. Default Analog.UINT16Read/write0 = Analog; 1 = Bus

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Belimo 6-way EPIV Modbus RTU (EP..R-R6+BAC)

What Modbus registers does the Belimo 6-way EPIV Modbus RTU (EP..R-R6+BAC) have?

This map lists 25 registers: 25 holding registers. 7 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Belimo 6-way EPIV Modbus RTU (EP..R-R6+BAC) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Belimo prints each register twice: 'No.' counts from 1 and 'Address' from 0, and the documented value here is the No. column. Register No. 1 (setpoint) is wire address 0. Every value sits in one flat table, so holding-register reads (FC 3) and writes (FC 6/16) reach everything; FC 4 input-register reads of the same addresses also work.

What byte order does the Belimo 6-way EPIV Modbus RTU (EP..R-R6+BAC) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Belimo 6-way EPIV Modbus RTU (EP..R-R6+BAC)?

Start with HR 118 Setpoint source (Setpoint source = Bus (default Analog)); HR 0 Setpoint (Setpoint across both sequences); HR 16 Active sequence (Active sequence); HR 9 Absolute volumetric flow (l/h) (Flow l/h); HR 4 Relative position (Relative position); HR 104 Malfunction and service information (Fault flags).

How do I enable Modbus control of the Belimo 6-way EPIV Modbus RTU (EP..R-R6+BAC)?

Configure address and frame with the Belimo Assistant app, then write No. 119 = 1 so the valve follows the bus setpoint (factory setting is Analog).

Where is the official Belimo 6-way EPIV Modbus RTU (EP..R-R6+BAC) Modbus documentation?

The source is Modbus Register - 6-way EPIV (6-way EPIV Modbus Register en-gb 2024-01), revision 2024-01, published free by Belimo at https://www.belimo.com/mam/general-documents/system_integration/Modbus/belimo_Modbus-Register_6way-EPIV_en-gb.pdf.

More Belimo Modbus register maps

Source: Modbus Register - 6-way EPIV · 6-way EPIV Modbus Register en-gb 2024-01 · rev. 2024-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.