Actuator / valve (damper and valve actuator) · Modbus register map

Belimo Air/water actuators with Modbus RTU (..24A-MOD) Modbus register map

Updated 28 October 2026

Short answer

Belimo's standard damper and valve actuators in the -MOD version speak Modbus RTU on RS-485 directly. The map is small and flat: a position setpoint, an override, position feedback and an optional sensor input in registers 1-13, then identity, fault flags, Min/Max limits, the bus watchdog and the setpoint source from register 100 up. Everything is a 16-bit unsigned value.

This page lists 22 Modbus registers for the Belimo Air/water actuators with Modbus RTU (..24A-MOD) — 11 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Belimo’s own free documentation (linked below) and checked against it.

Manufacturer
Belimo
Model
Air/water actuators with Modbus RTU (..24A-MOD)
Equipment type
Actuator / valve (damper and valve actuator)
Registers
22 (11 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
38400 baud, 8N2
Documented addressing
1-based (subtract 1 for the wire address)
Also known as
LM24A-MOD, NM24A-MOD, SM24A-MOD, GM24A-MOD, LMC24A-MOD, NMC24A-MOD, NR24A-MOD, LR24A-MOD, NV24A-MOD, NVK24A-MOD, LF24A-MOD, NF24A-MOD, NRF24A-MOD, LRF24A-MOD, LH24A-MOD, SH24A-MOD
Source document
Modbus Interface Description - Air/water actuators (General actuators for air and water) · Edition 2026-05 / V3.08 · rev. 2026-05
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Belimo Air/water actuators with Modbus RTU (..24A-MOD)

Integration in brief

Wire to the RS-485 terminals, set address and frame with the Belimo Assistant app (or the Address button quick-addressing), then write the position in 0.01 % to register 1 (wire address 0) and poll registers 5 and 105. Leave Setpoint source (No. 119) at Bus, its default.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0SetpointUINT16Position setpoint, 0.01 %Read/write
HR 1Override controlUINT16Override (open/close/min/mid/max)Read/write
HR 4Relative positionUINT16Relative position feedbackRead
HR 104Malfunction and service informationBITMAP16Fault and service flagsRead
HR 118Setpoint sourceUINT16Setpoint source must be BusRead/write
HR 108Bus fail positionUINT16Bus fail positionRead/write
HR 109Timeout for bus watchdogUINT16Bus watchdog timeoutRead/write

Enable Modbus control & writes

Modbus is active out of the box on -MOD actuators; Setpoint source (No. 119) defaults to Bus. Address (1-247), baud rate and frame are set with the Belimo Assistant 2 app or tool, and the address can also be set with the Address and Adaption buttons (see the product datasheet).

Communication loss & watchdog

Not monitored by default. Set Bus fail position (No. 109) and Timeout for bus watchdog (No. 110, 0-3600 s; 0 = off, 120 s default once a fail position is set). If neither No. 1 nor No. 2 is written within the timeout, the actuator goes to the fail position and bit 10 of No. 105 is set. In hybrid mode (Setpoint source = Analog) bus monitoring is not active.

Byte order & addressing

Network setup

Watch out for

Belimo Air/water actuators with Modbus RTU (..24A-MOD) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

22 of 22 shown
Belimo Air/water actuators with Modbus RTU (..24A-MOD) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1SetpointPosition setpoint 0-100 %, scaled between Min (No. 106) and Max (No. 107).UINT16× 0.01%Read/write
HR1doc 2Override controlForces a fixed position instead of the setpoint.UINT16Read/write0 = None; 1 = Open; 2 = Close; 3 = Min; 4 = Mid; 5 = Max; 6 = Fast open; 7 = Fast close
HR2doc 3CommandStarts a service function; reads back 0 once accepted. 4 clears No. 105.UINT16Read/write0 = None; 1 = Adaption; 2 = Test; 3 = Sync; 4 = Reset
HR3doc 4Actuator typeUINT16Read0 = Actuator not connected; 1 = Air / water; 2 = VAV / EPIV; 3 = Fire; 4 = Energy Valve; 5 = 6-way EPIV
HR4doc 5Relative positionUINT16× 0.01%Read
HR5doc 6Absolute positionDegrees for rotary actuators, mm for linear actuators.UINT16° / mmRead
HR8doc 9Sensor 1 valueRaw reading of sensor input 1; meaning and scale follow No. 108 (see notes).UINT16Read
HR12doc 13Analog setpointSetpoint seen on the 0-10 V input when Setpoint source = Analog.UINT16× 0.01%Read
HR99doc 100Bus terminationShows whether the built-in 120 ohm terminator is on (set with the tool).UINT16Read0 = Inactive; 1 = Active
HR100doc 101Series number 1st partFirst block of the serial number on the housing label.UINT16Read
HR101doc 102Series number 2nd partSecond block of the serial number.UINT16Read
HR102doc 103Series number 4th partFourth block of the serial number (the third is not exposed).UINT16Read
HR103doc 104Firmware versionBus module firmware; 302 means version 3.02.UINT16Read
HR104doc 105Malfunction and service informationBit-coded fault and status flags; clear with Command = 4.BITMAP16Readbit 1 = Mechanical travel increased (moved outside adapted range); bit 2 = Actuator cannot move (overload / blocked); bit 8 = Internal activity (test run, adaption); bit 9 = Gear train disengaged (manual override pressed); bit 10 = Bus watchdog triggered
HR105doc 106MinLower position limit; must stay at least 20 % below Max. Default 0.UINT16× 0.01%Read/write
HR106doc 107MaxUpper position limit; must stay at least 20 % above Min. Default 100 %.UINT16× 0.01%Read/write
HR107doc 108Sensor 1 typeWhat is wired to sensor input 1; restart may be needed after a change.UINT16Read/write0 = None; 1 = Active; 2 = Passive_1K; 3 = Passive_20K; 4 = Switch; 5 = PT1000_C; 6 = NI1000_C; 7 = NTC10K2_C; 8 = PT1000_F; 9 = NI1000_F; 10 = NTC10K2_F
HR108doc 109Bus fail positionWhere the actuator goes when the bus watchdog expires.UINT16Read/write0 = None / last setpoint; 1 = Fast close; 2 = Fast open; 3 = Mid position (parametrised)
HR109doc 110Timeout for bus watchdog0 disables; defaults to 120 s once a bus fail position is set.UINT16sRead/write
HR118doc 119Setpoint sourceBus = No. 1 drives the actuator; Analog = 0-10 V on wire 3. Default Bus.UINT16Read/write0 = Analog; 1 = Bus
HR189doc 190Fail-safe bridging timeDelay before the fail-safe move after power loss (electronic fail-safe types only).UINT16sRead/write
HR190doc 191Fail-safe positionPosition taken on power loss (electronic fail-safe types; knob on 'Tool').UINT16× 0.01%Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Belimo Air/water actuators with Modbus RTU (..24A-MOD)

What Modbus registers does the Belimo Air/water actuators with Modbus RTU (..24A-MOD) have?

This map lists 22 registers: 22 holding registers. 11 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Belimo Air/water actuators with Modbus RTU (..24A-MOD) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Belimo prints each register twice: 'No.' counts from 1 and 'Address' from 0, and the documented value here is the No. column. Register No. 1 (setpoint) is wire address 0. Every value sits in one flat table, so holding-register reads (FC 3) and writes (FC 6/16) reach everything; FC 4 input-register reads of the same addresses also work.

What are the minimum Modbus registers to integrate the Belimo Air/water actuators with Modbus RTU (..24A-MOD)?

Start with HR 0 Setpoint (Position setpoint, 0.01 %); HR 1 Override control (Override (open/close/min/mid/max)); HR 4 Relative position (Relative position feedback); HR 104 Malfunction and service information (Fault and service flags); HR 118 Setpoint source (Setpoint source must be Bus); HR 108 Bus fail position (Bus fail position); HR 109 Timeout for bus watchdog (Bus watchdog timeout).

How do I enable Modbus control of the Belimo Air/water actuators with Modbus RTU (..24A-MOD)?

Modbus is active out of the box on -MOD actuators; Setpoint source (No. 119) defaults to Bus. Address (1-247), baud rate and frame are set with the Belimo Assistant 2 app or tool, and the address can also be set with the Address and Adaption buttons (see the product datasheet).

What happens when the Belimo Air/water actuators with Modbus RTU (..24A-MOD) loses Modbus communication?

Not monitored by default. Set Bus fail position (No. 109) and Timeout for bus watchdog (No. 110, 0-3600 s; 0 = off, 120 s default once a fail position is set). If neither No. 1 nor No. 2 is written within the timeout, the actuator goes to the fail position and bit 10 of No. 105 is set. In hybrid mode (Setpoint source = Analog) bus monitoring is not active.

Where is the official Belimo Air/water actuators with Modbus RTU (..24A-MOD) Modbus documentation?

The source is Modbus Interface Description - Air/water actuators (General actuators for air and water) (Edition 2026-05 / V3.08), revision 2026-05, published free by Belimo at https://www.belimo.com/mam/general-documents/system_integration/Modbus/belimo_Modbus-Register_AirWater_V3_8_en-gb.pdf.

More Belimo Modbus register maps

Source: Modbus Interface Description - Air/water actuators (General actuators for air and water) · Edition 2026-05 / V3.08 · rev. 2026-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.