Power meter (static reactive energy regulator) · Modbus register map
Circutor Computer SMART III FAST Modbus register map
Updated 19 November 2026
The Computer SMART III FAST is a power factor regulator that switches capacitor stages with static (thyristor) outputs and measures the network like an analyzer. Its RS-485 port speaks Modbus RTU; measurements are 32-bit integer register pairs read with function 04 and the setup block at 0x1071-0x1190 is read with 04 and written with 0x10. This map covers currents, reactive and apparent power, frequency, leakage current, energies, stage and output status, and the main setup registers.
This page lists 89 Modbus registers for the Circutor Computer SMART III FAST — 37 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Circutor’s own free documentation (linked below) and checked against it.
- Manufacturer
- Circutor
- Model
- Computer SMART III FAST
- Equipment type
- Power meter (static reactive energy regulator)
- Registers
- 89 (37 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- Computer SMART III FAST 6, Computer SMART III FAST 12
Integration notes: Circutor Computer SMART III FAST
Read the measurement block from 0x0000 with function 04, keeping each frame at or under 80 bytes (at most 37 registers per read). Values are 32-bit integers, high word first; currents are in mA.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 80 | Three-phase current | UINT32 ABCD | Three-phase current | Read |
| IR 90 | Three-phase apparent power | UINT32 ABCD | Three-phase apparent power | Read |
| IR 92 | Three-phase reactive power consumed | UINT32 ABCD | Three-phase reactive power consumed | Read |
| IR 104 | Frequency | UINT32 ABCD | Frequency (Hz x10) | Read |
| IR 136 | Active energy consumed | UINT32 ABCD | Active energy consumed (kWh) | Read |
| IR 1536 | Relay variable | BITMAP16 | Which capacitor stages are switched in | Read |
| IR 114 | Leakage current | UINT32 ABCD | Leakage current | Read |
Enable Modbus control & writes
Set the peripheral number, speed, parity and stop bits in the RS-485 communications setup screen or with registers 0x1071-0x1075.
Byte order & addressing
- Frames longer than 80 bytes in either direction are rejected, so split large reads.
- Energies are a whole-unit register plus a remainder register; combine both.
- Digital output bits in the output status word read 1 when the output is OFF.
Network setup
- Defaults: peripheral 1, 19200 baud, no parity, 8 data bits, 1 stop bit.
- Only 9600 and 19200 baud are offered on the RS-485 Modbus port.
Watch out for
- Writing the stage status registers (0x1110-0x111B) forces capacitor stages on or off; return them to Auto (0) afterwards.
Circutor Computer SMART III FAST Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 2doc 02-03 | L1 Current | Instantaneous value; the manual prints the unit as mA. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 6doc 06-07 | L1 Inductive reactive power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 8doc 08-09 | L1 Capacitive reactive power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 12doc 0C-0D | L1 Apparent power | Instantaneous value. | UINT32 | ABCD | VA | Read | ||
| IR | 14doc 0E-0F | L1 Reactive power consumed | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 16doc 10-11 | L1 Reactive power generated | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 22doc 16-17 | L1 kW sign | Sign that goes with the power factor and cos phi. | INT32 | ABCD | Read | 1 = Positive; -1 = Negative | ||
| IR | 24doc 18-19 | L1 kvar sign | Sign that goes with the power factor and cos phi. | INT32 | ABCD | Read | 1 = Positive; -1 = Negative | ||
| IR | 28doc 1C-1D | L2 Current | Instantaneous value; the manual prints the unit as mA. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 32doc 20-21 | L2 Inductive reactive power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 34doc 22-23 | L2 Capacitive reactive power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 38doc 26-27 | L2 Apparent power | Instantaneous value. | UINT32 | ABCD | VA | Read | ||
| IR | 40doc 28-29 | L2 Reactive power consumed | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 42doc 2A-2B | L2 Reactive power generated | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 48doc 30-31 | L2 kW sign | Sign that goes with the power factor and cos phi. | INT32 | ABCD | Read | 1 = Positive; -1 = Negative | ||
| IR | 50doc 32-33 | L2 kvar sign | Sign that goes with the power factor and cos phi. | INT32 | ABCD | Read | 1 = Positive; -1 = Negative | ||
| IR | 54doc 36-37 | L3 Current | Instantaneous value; the manual prints the unit as mA. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 58doc 3A-3B | L3 Inductive reactive power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 60doc 3C-3D | L3 Capacitive reactive power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 64doc 40-41 | L3 Apparent power | Instantaneous value. | UINT32 | ABCD | VA | Read | ||
| IR | 66doc 42-43 | L3 Reactive power consumed | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 68doc 44-45 | L3 Reactive power generated | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 74doc 4A-4B | L3 kW sign | Sign that goes with the power factor and cos phi. | INT32 | ABCD | Read | 1 = Positive; -1 = Negative | ||
| IR | 76doc 4C-4D | L3 kvar sign | Sign that goes with the power factor and cos phi. | INT32 | ABCD | Read | 1 = Positive; -1 = Negative | ||
| IR | 80doc 50-51 | Three-phase current | Instantaneous value; the manual prints the unit as mA. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 84doc 54-55 | Three-phase inductive power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 86doc 56-57 | Three-phase capacitive power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 90doc 5A-5B | Three-phase apparent power | Instantaneous value. | UINT32 | ABCD | VA | Read | ||
| IR | 92doc 5C-5D | Three-phase reactive power consumed | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 94doc 5E-5F | Three-phase reactive power generated | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 100doc 64-65 | Three-phase kW sign | Sign that goes with the power factor and cos phi. | INT32 | ABCD | Read | 1 = Positive; -1 = Negative | ||
| IR | 102doc 66-67 | Three-phase kvar sign | Sign that goes with the power factor and cos phi. | INT32 | ABCD | Read | 1 = Positive; -1 = Negative | ||
| IR | 104doc 68-69 | Frequency | Instantaneous value. | UINT32 | ABCD | × 0.1 | Hz | Read | |
| IR | 112doc 70-71 | Neutral current | Instantaneous value; the manual prints the unit as mA. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 114doc 72-73 | Leakage current | Instantaneous value; the manual prints the unit as mA. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 136doc 88-89 | Active energy consumed | Whole-unit counter. | UINT32 | ABCD | kWh | Read | ||
| IR | 138doc 8A-8B | Active energy consumed (Wh part) | Remainder below one whole unit. | UINT32 | ABCD | Wh | Read | ||
| IR | 140doc 8C-8D | Inductive energy consumed | Whole-unit counter. | UINT32 | ABCD | kvarh | Read | ||
| IR | 142doc 8E-8F | Inductive energy consumed (varh part) | Remainder below one whole unit. | UINT32 | ABCD | varh | Read | ||
| IR | 144doc 90-91 | Capacitive energy consumed | Whole-unit counter. | UINT32 | ABCD | kvarh | Read | ||
| IR | 146doc 92-93 | Capacitive energy consumed (varh part) | Remainder below one whole unit. | UINT32 | ABCD | varh | Read | ||
| IR | 148doc 94-95 | Apparent energy consumed | Whole-unit counter. | UINT32 | ABCD | kVAh | Read | ||
| IR | 150doc 96-97 | Apparent energy consumed (VAh part) | Remainder below one whole unit. | UINT32 | ABCD | VAh | Read | ||
| IR | 156doc 9C-9D | Inductive energy generated | Whole-unit counter. | UINT32 | ABCD | kvarh | Read | ||
| IR | 158doc 9E-9F | Inductive energy generated (varh part) | Remainder below one whole unit. | UINT32 | ABCD | varh | Read | ||
| IR | 160doc A0-A1 | Capacitive energy generated | Whole-unit counter. | UINT32 | ABCD | kvarh | Read | ||
| IR | 162doc A2-A3 | Capacitive energy generated (varh part) | Remainder below one whole unit. | UINT32 | ABCD | varh | Read | ||
| IR | 164doc A4-A5 | Apparent energy generated | Whole-unit counter. | UINT32 | ABCD | kVAh | Read | ||
| IR | 166doc A6-A7 | Apparent energy generated (VAh part) | Remainder below one whole unit. | UINT32 | ABCD | VAh | Read | ||
| IR | 1536doc 600 | Relay variable | Capacitor stage relays; bit set = relay on. | BITMAP16 | Read | bit 0 = Stage relay 1; bit 1 = Stage relay 2; bit 2 = Stage relay 3; bit 3 = Stage relay 4; bit 4 = Stage relay 5; bit 5 = Stage relay 6; bit 6 = Stage relay 7; bit 7 = Stage relay 8; bit 8 = Stage relay 9; bit 9 = Stage relay 10; bit 10 = Stage relay 11; bit 11 = Stage relay 12 | |||
| IR | 1552doc 610 | Status of the outputs | BITMAP16 | Read | bit 0 = Fan relay ON; bit 1 = Alarm relay ON; bit 2 = Digital output 1 OFF (0 = ON); bit 3 = Digital output 2 OFF (0 = ON) | ||||
| IR | 1557doc 615 | Status of the digital inputs | BITMAP16 | Read | bit 0 = Digital input 1 ON; bit 1 = Digital input 2 ON | ||||
| HR | 4209doc 1071 | Peripheral number | 1-254, default 1. | UINT16 | Read/write | ||||
| HR | 4210doc 1072 | RS-485 speed | UINT16 | Read/write | 0 = 9600; 1 = 19200 (default) | ||||
| HR | 4211doc 1073 | RS-485 parity | UINT16 | Read/write | 0 = None (default); 1 = Odd; 2 = Even | ||||
| HR | 4212doc 1074 | RS-485 data length | UINT16 | Read/write | 0 = 8 bits (default); 1 = 7 bits | ||||
| HR | 4213doc 1075 | RS-485 stop bits | UINT16 | Read/write | 0 = 1 bit (default); 1 = 2 bits | ||||
| HR | 4240doc 1090 | Current primary | 1-10000, default 5. | UINT16 | A | Read/write | |||
| HR | 4241doc 1091 | Current secondary | UINT16 | Read/write | 0 = 1 A; 1 = 5 A (default) | ||||
| HR | 4245doc 1095-1096 | Voltage primary | 1-99999, default 400. | UINT32 | ABCD | V | Read/write | ||
| HR | 4247doc 1097-1098 | Voltage secondary | 1-99999, default 400. | UINT32 | ABCD | V | Read/write | ||
| HR | 4352doc 1100 | Connection type | UINT16 | Read/write | 0 = 3U.3C (default); 1 = 3U.1C; 2 = 2U.1C | ||||
| HR | 4368doc 1110 | Stage C1 status | UINT16 | Read/write | 0 = Auto (default); 1 = On; 2 = OFF; 3 = OnNc | ||||
| HR | 4369doc 1111 | Stage C2 status | UINT16 | Read/write | 0 = Auto (default); 1 = On; 2 = OFF; 3 = OnNc | ||||
| HR | 4370doc 1112 | Stage C3 status | UINT16 | Read/write | 0 = Auto (default); 1 = On; 2 = OFF; 3 = OnNc | ||||
| HR | 4371doc 1113 | Stage C4 status | UINT16 | Read/write | 0 = Auto (default); 1 = On; 2 = OFF; 3 = OnNc | ||||
| HR | 4372doc 1114 | Stage C5 status | UINT16 | Read/write | 0 = Auto (default); 1 = On; 2 = OFF; 3 = OnNc | ||||
| HR | 4373doc 1115 | Stage C6 status | UINT16 | Read/write | 0 = Auto (default); 1 = On; 2 = OFF; 3 = OnNc | ||||
| HR | 4374doc 1116 | Stage C7 status | UINT16 | Read/write | 0 = Auto (default); 1 = On; 2 = OFF; 3 = OnNc | ||||
| HR | 4375doc 1117 | Stage C8 status | UINT16 | Read/write | 0 = Auto (default); 1 = On; 2 = OFF; 3 = OnNc | ||||
| HR | 4376doc 1118 | Stage C9 status | UINT16 | Read/write | 0 = Auto (default); 1 = On; 2 = OFF; 3 = OnNc | ||||
| HR | 4377doc 1119 | Stage C10 status | UINT16 | Read/write | 0 = Auto (default); 1 = On; 2 = OFF; 3 = OnNc | ||||
| HR | 4378doc 111A | Stage C11 status | UINT16 | Read/write | 0 = Auto (default); 1 = On; 2 = OFF; 3 = OnNc | ||||
| HR | 4379doc 111B | Stage C12 status | UINT16 | Read/write | 0 = Auto (default); 1 = On; 2 = OFF; 3 = OnNc | ||||
| HR | 4385doc 1121 | Voltage level | UINT16 | Read/write | 0 = Low voltage (default); 1 = Medium/High voltage | ||||
| HR | 4400doc 1130 | Target cos phi 1 | 50-100 raw (value x100), default 100 = 1.00. | UINT16 | × 0.01 | Read/write | |||
| HR | 4401doc 1131 | Target cos phi 2 | 50-100 raw (value x100), default 100 = 1.00. | UINT16 | × 0.01 | Read/write | |||
| HR | 4402doc 1132 | Target cos phi 3 | 50-100 raw (value x100), default 100 = 1.00. | UINT16 | × 0.01 | Read/write | |||
| HR | 4403doc 1133 | Target cos phi 4 | 50-100 raw (value x100), default 100 = 1.00. | UINT16 | × 0.01 | Read/write | |||
| HR | 4404doc 1134 | Target cos phi 1 type | UINT16 | Read/write | 0 = Capacitive; 1 = Inductive (default) | ||||
| HR | 4405doc 1135 | Target cos phi 2 type | UINT16 | Read/write | 0 = Capacitive; 1 = Inductive (default) | ||||
| HR | 4406doc 1136 | Target cos phi 3 type | UINT16 | Read/write | 0 = Capacitive; 1 = Inductive (default) | ||||
| HR | 4407doc 1137 | Target cos phi 4 type | UINT16 | Read/write | 0 = Capacitive; 1 = Inductive (default) | ||||
| HR | 4408doc 1138 | C/K factor | 0-100 raw (value x100), default 100 = 1.00. | UINT16 | × 0.01 | Read/write | |||
| HR | 4409doc 1139 | Program | Stage ratio program 1111-1999, default 1111. | UINT16 | Read/write | ||||
| HR | 4410doc 113A | Operation type | UINT16 | Read/write | 0 = FCP (default); 1 = Total; 2 = Sim | ||||
| HR | 4411doc 113B | Number of stages | 0-6 (FAST 6) or 0-12 (FAST 12). | UINT16 | Read/write | ||||
| HR | 4412doc 113C | Connection time | 0-999 network cycles, default 10. | UINT16 | Read/write | ||||
| HR | 4413doc 113D | Reconnection time | 0-999 network cycles, default 50. | UINT16 | Read/write |
Notes on this map
- Word order: the function 04 example returns 0000 then 084D for one 2-register value, so 32-bit values are high word first (ABCD).
- Left out: all voltage registers. The table prints the unit V/100 but the worked example decodes the same register as V x10 (212.5 V), so the scaling is contradictory.
- Left out: active power, the signed reactive power rows, power factor and cos phi. The manual pairs PF and cos phi with separate kW/kvar sign registers but gives no type or scale for them and does not say whether the power values carry a sign.
- Left out: THD (unit printed as % with no scale), temperature (signedness not stated), harmonics, the 32-bit alarm word at 605-606 (its bit numbering is printed inconsistently), alarm thresholds, the deleting-parameters commands (the value is printed only as FF with no function code) and identification registers.
- Left out: registers 98-99 and 9A-9B. The table labels them active energy consumed (kWh and Wh), the same label as 88-89 and 8A-8B, although they sit in the generated-energy block; the manual does not say which they are.
- Currents and leakage current are printed in mA; they are given here in A with scale 0.001.
- The kW/kvar sign registers are typed INT32 because their documented values are +1 and -1.
- The 12Vdc version has its own manual (M100B01-03-21A) whose tables are numbered differently; it was not checked register by register, so it is not covered here.
- Setup registers are read with function 04 and written with function 0x10; they are listed as holding registers. Frames longer than 80 bytes are rejected.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Circutor Computer SMART III FAST
What Modbus registers does the Circutor Computer SMART III FAST have?
This map lists 89 registers: 52 input registers, 37 holding registers. 37 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Circutor Computer SMART III FAST Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. All Modbus tables print hexadecimal wire addresses. The manual's example reads initial log 0000 with function 04 and gets 0000 084D back for L1 phase voltage, which confirms that table addresses go on the wire unchanged.
What byte order does the Circutor Computer SMART III FAST use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Circutor Computer SMART III FAST?
Start with IR 80 Three-phase current (Three-phase current); IR 90 Three-phase apparent power (Three-phase apparent power); IR 92 Three-phase reactive power consumed (Three-phase reactive power consumed); IR 104 Frequency (Frequency (Hz x10)); IR 136 Active energy consumed (Active energy consumed (kWh)); IR 1536 Relay variable (Which capacitor stages are switched in); IR 114 Leakage current (Leakage current).
How do I enable Modbus control of the Circutor Computer SMART III FAST?
Set the peripheral number, speed, parity and stop bits in the RS-485 communications setup screen or with registers 0x1071-0x1075.
Where is the official Circutor Computer SMART III FAST Modbus documentation?
The source is Computer SMART III FAST (Static operation) Reactive Energy Regulator - Instruction Manual (M021B01-03-21A), published free by Circutor at https://docs.circutor.com/docs/M021B01-03.pdf.
More Circutor Modbus register maps
- Power meter (power factor regulator with network analyzer)
Circutor Computer SMART III
Circutor Computer SMART III reactive energy regulators (6 and 12 step models), RS-485 Modbus RTU, manual M015B01-03-25B.
Also known as: Computer SMART III 6, Computer SMART III 12, SMART III - Power meter
Circutor CVM-C10
Circutor CVM-C10 panel power analyzer, RS-485 versions (ITF, MC, mV, ITF-IN), manual M001B01-03-23A.
Also known as: CVM-C10-ITF-485, CVM-C10-MC-485, CVM-C10-mV-485, CVM-C10-ITF-IN-485 - Power meter
Circutor CVM-C5
Circutor CVM-C5 panel power analyzer, RS-485 Modbus RTU versions (ITF-485, MC-485, mV-485), manual M026B01-03.
Also known as: CVM-C5-ITF-485, CVM-C5-MC-485, CVM-C5-mV-485 - Power meter
Circutor CVM-E3-MINI
Circutor CVM-E3-MINI DIN-rail power analyzer, RS-485 Modbus RTU (Map 2 / CVM-C10-compatible addresses), manual M170B01-03-25B.
Also known as: CVM-E3-MINI-ITF-RS485, CVM-E3-MINI-MC, CVM-E3-MINI-FLEX, CVM-E3-MINI-mV, CVM-E3-MINI-ITF-WiEth - Power meter (earth leakage breaker with reclosing and metering)
Circutor RECmax-CVM
Circutor RECmax-CVM earth-leakage circuit breaker with automatic reclosing and built-in analyzer, manual M175B01-03-22A.
Other power & energy meters register maps
- Power meter
DENT Instruments PowerScout 3037 Power Meter
PowerScout 3037 serial (RS-485) and Ethernet meters in Modbus mode, per the November 9, 2017 PS3037 Operator's Guide.
Also known as: PS3037, PowerScout 3037 Ethernet, PS3037-E, PowerScout 3037 Serial - Energy meter
Eastron SDM230-Modbus
Eastron SDM230-Modbus (two-tariff SDM230-2T protocol) single-phase two-module DIN-rail meter, protocol V1.1.
Also known as: SDM230Modbus, SDM230-2T, SDM230-M - Sensor (electromagnetic flowmeter)
Endress+Hauser Proline Promag 300 electromagnetic flowmeter (Modbus RS485)
Promag 300 with the Modbus RS485 communication option, parameter description GP01053D/06/EN/04.22.
Also known as: Promag 300, Promag P 300, Promag H 300, Promag W 300 - Energy meter
Fronius Fronius Smart Meter via Datamanager (SunSpec meter model int+SF)
An energy meter wired to a Fronius Datamanager (or Hybridmanager) over Modbus RTU and republished by it, with SunSpec Model Type set to int+SF (meter model 201/202/203).
Also known as: Fronius Smart Meter 63A, Fronius Smart Meter 50kA, Fronius Smart Meter TS, SunSpec meter model 201/202/203 - Power meter
IME Nemo 96HDLe multifunction meter (MF964)
IME Nemo 96HDLe panel meter MF964 with RS-485, per protocol PR130 (software 5.08).
Also known as: MF964, Nemo 96HDLe - Energy meter
inepro Metering PRO2 single-phase energy meter (2026 PRO line)
PRO2-Mod (art. 1201) and PRO2-Mod-Ba (art. 1202, with RTC tariffs) from the 2026 PRO2 user manual version 1.3; the PRO2-S has no Modbus.
Also known as: PRO2-Mod, PRO2-Mod-Ba, PRO2 1U AC 100A Mod T MID, PRO2 1U AC 100A Mod T Ba MID, 1201, 1202
All power & energy meters Modbus register maps →
Source: Computer SMART III FAST (Static operation) Reactive Energy Regulator - Instruction Manual · M021B01-03-21A. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.