Power meter · Modbus register map
Circutor CVM-C10 Modbus register map
Updated 17 November 2026
The CVM-C10 is a 96x96 mm panel power analyzer from Circutor with an RS-485 port that speaks Modbus RTU or BACnet MS/TP. Measurements are 32-bit integers in register pairs with fixed scaling (V x10, mA, W, Hz x100) read with function 03 or 04. Energies come as a kWh register plus a Wh remainder per tariff. This map covers voltages, currents, reactive and apparent power, THD, demand, total energy, status words, the main setup registers and the reset commands.
This page lists 103 Modbus registers for the Circutor CVM-C10 — 20 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Circutor’s own free documentation (linked below) and checked against it.
- Manufacturer
- Circutor
- Model
- CVM-C10
- Equipment type
- Power meter
- Registers
- 103 (20 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- CVM-C10-ITF-485, CVM-C10-MC-485, CVM-C10-mV-485, CVM-C10-ITF-IN-485
- Source document
- CVM-C10 Power analyzer Instruction Manual · M001B01-03-23A
Integration notes: Circutor CVM-C10
Read the instantaneous block from 0x0000 with function 04 (up to 20 variables = 40 registers per frame). Each value is a 32-bit integer, high word first, with the scale shown in the table.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | L1 Phase voltage | UINT32 ABCD | L1 phase voltage (V x10) | Read |
| IR 2 | L1 Current | UINT32 ABCD | L1 current (mA) | Read |
| IR 54 | Apparent three-phase power | UINT32 ABCD | Three-phase apparent power | Read |
| IR 60 | L1 Frequency | UINT32 ABCD | Frequency (Hz x100) | Read |
| IR 220 | Total consumed active energy (kWh) | UINT32 ABCD | Total consumed active energy kWh | Read |
| IR 2001 | Power status | BITMAP16 | Power status (consumed/generated quadrant) | Read |
Enable Modbus control & writes
Set Protocol (0x2742) to Modbus (factory default), then peripheral number, speed and framing either from the front panel or via the 0x2743-0x2747 registers. Reset the device for changes to apply.
Byte order & addressing
- A frame may carry at most 20 variables (40 registers).
- Energy is split into a whole-unit register (kWh) and a remainder register (Wh); combine both for full resolution.
- Reset commands use function 05 (write coil) with FF00.
Network setup
- Defaults: peripheral number 1, 9600 baud, no parity, 8 data bits, 1 stop bit.
- Only 9600 and 19200 baud are available.
- Program voltage and current transformer ratios together; voltage ratio x current ratio must stay below 600000.
Watch out for
- The one RS-485 port runs either Modbus or BACnet, chosen by the Protocol setting (0x2742).
Circutor CVM-C10 Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 2100doc 834 | Delete energies | Write FF00 with function 05. | BIT | Write | ||||
| CO | 2104doc 838 | Delete max and min values | Write FF00 with function 05. | BIT | Write | ||||
| CO | 2105doc 839 | Start maximum demand | Write FF00 with function 05. | BIT | Write | ||||
| CO | 2109doc 83D | Delete hour counters (all tariffs) | Write FF00 with function 05. | BIT | Write | ||||
| CO | 2111doc 83F | Delete maximum of maximum demand | Write FF00 with function 05. | BIT | Write | ||||
| CO | 2120doc 848 | Delete energies, max demand and max/min | Write FF00 with function 05. | BIT | Write | ||||
| IR | 0doc 00-01 | L1 Phase voltage | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 2doc 02-03 | L1 Current | Instantaneous value. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 6doc 06-07 | L1 Inductive Power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 8doc 08-09 | L1 Capacitive Power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 10doc 0A-0B | L1 Apparent Power | Instantaneous value. | UINT32 | ABCD | VA | Read | ||
| IR | 16doc 10-11 | L2 Phase voltage | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 18doc 12-13 | L2 Current | Instantaneous value. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 22doc 16-17 | L2 Inductive Power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 24doc 18-19 | L2 Capacitive Power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 26doc 1A-1B | L2 Apparent Power | Instantaneous value. | UINT32 | ABCD | VA | Read | ||
| IR | 32doc 20-21 | L3 Phase voltage | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 34doc 22-23 | L3 Current | Instantaneous value. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 38doc 26-27 | L3 Inductive Power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 40doc 28-29 | L3 Capacitive Power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 42doc 2A-2B | L3 Apparent Power | Instantaneous value. | UINT32 | ABCD | VA | Read | ||
| IR | 50doc 32-33 | Inductive Three-phase power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 52doc 34-35 | Capacitive Three-phase Power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 54doc 36-37 | Apparent three-phase power | Instantaneous value. | UINT32 | ABCD | VA | Read | ||
| IR | 60doc 3C-3D | L1 Frequency | Instantaneous value. | UINT32 | ABCD | × 0.01 | Hz | Read | |
| IR | 62doc 3E-3F | L1-L2 Voltage | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 64doc 40-41 | L2-L3 Voltage | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 66doc 42-43 | L3-L1 Voltage | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 68doc 44-45 | Neutral Current N | Instantaneous value. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 70doc 46-47 | L1 voltage % THD | Instantaneous value. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 72doc 48-49 | L2 voltage % THD | Instantaneous value. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 74doc 4A-4B | L3 voltage % THD | Instantaneous value. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 76doc 4C-4D | L1 current % THD | Instantaneous value. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 78doc 4E-4F | L2 current % THD | Instantaneous value. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 80doc 50-51 | L3 current % THD | Instantaneous value. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 84doc 54-55 | Maximum demand kVA III | Present maximum-demand value. | UINT32 | ABCD | VA | Read | ||
| IR | 86doc 56-57 | Maximum demand I AVG | Present maximum-demand value. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 88doc 58-59 | Maximum demand I L1 | Present maximum-demand value. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 90doc 5A-5B | Maximum demand I L2 | Present maximum-demand value. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 92doc 5C-5D | Maximum demand I L3 | Present maximum-demand value. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 220doc DC-DD | Total consumed active energy (kWh) | All tariffs. Full value = kWh-type register plus the matching Wh-type remainder. | UINT32 | ABCD | kWh | Read | ||
| IR | 222doc DE-DF | Total consumed active energy (Wh) | All tariffs. Full value = kWh-type register plus the matching Wh-type remainder. | UINT32 | ABCD | Wh | Read | ||
| IR | 224doc E0-E1 | Total consumed inductive reactive energy (kvarhL) | All tariffs. Full value = kWh-type register plus the matching Wh-type remainder. | UINT32 | ABCD | kvarh | Read | ||
| IR | 226doc E2-E3 | Total consumed inductive reactive energy (varhL) | All tariffs. Full value = kWh-type register plus the matching Wh-type remainder. | UINT32 | ABCD | varh | Read | ||
| IR | 228doc E4-E5 | Total consumed capacitive reactive energy (kvarhC) | All tariffs. Full value = kWh-type register plus the matching Wh-type remainder. | UINT32 | ABCD | kvarh | Read | ||
| IR | 230doc E6-E7 | Total consumed capacitive reactive energy (varhC) | All tariffs. Full value = kWh-type register plus the matching Wh-type remainder. | UINT32 | ABCD | varh | Read | ||
| IR | 232doc E8-E9 | Total consumed apparent energy (kVAh) | All tariffs. Full value = kWh-type register plus the matching Wh-type remainder. | UINT32 | ABCD | kVAh | Read | ||
| IR | 234doc EA-EB | Total consumed apparent energy (VAh) | All tariffs. Full value = kWh-type register plus the matching Wh-type remainder. | UINT32 | ABCD | VAh | Read | ||
| IR | 240doc F0-F1 | Total generated active energy (kWh) | All tariffs. Full value = kWh-type register plus the matching Wh-type remainder. | UINT32 | ABCD | kWh | Read | ||
| IR | 242doc F2-F3 | Total generated active energy (Wh) | All tariffs. Full value = kWh-type register plus the matching Wh-type remainder. | UINT32 | ABCD | Wh | Read | ||
| IR | 244doc F4-F5 | Total generated inductive reactive energy (kvarhL) | All tariffs. Full value = kWh-type register plus the matching Wh-type remainder. | UINT32 | ABCD | kvarh | Read | ||
| IR | 246doc F6-F7 | Total generated inductive reactive energy (varhL) | All tariffs. Full value = kWh-type register plus the matching Wh-type remainder. | UINT32 | ABCD | varh | Read | ||
| IR | 248doc F8-F9 | Total generated capacitive reactive energy (kvarhC) | All tariffs. Full value = kWh-type register plus the matching Wh-type remainder. | UINT32 | ABCD | kvarh | Read | ||
| IR | 250doc FA-FB | Total generated capacitive reactive energy (varhC) | All tariffs. Full value = kWh-type register plus the matching Wh-type remainder. | UINT32 | ABCD | varh | Read | ||
| IR | 252doc FC-FD | Total generated apparent energy (kVAh) | All tariffs. Full value = kWh-type register plus the matching Wh-type remainder. | UINT32 | ABCD | kVAh | Read | ||
| IR | 260doc 104-105 | Total hours per tariff | All tariffs. | UINT32 | ABCD | s | Read | ||
| IR | 262doc 106-107 | L1 Phase voltage (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 264doc 108-109 | L1 Current (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 268doc 10C-10D | L1 Inductive Power (max) | Maximum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 270doc 10E-10F | L1 Capacitive Power (max) | Maximum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 272doc 110-111 | L1 Apparent Power (max) | Maximum recorded since last reset. | UINT32 | ABCD | VA | Read | ||
| IR | 278doc 116-117 | L2 Phase voltage (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 280doc 118-119 | L2 Current (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 284doc 11C-11D | L2 Inductive Power (max) | Maximum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 286doc 11E-11F | L2 Capacitive Power (max) | Maximum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 288doc 120-121 | L2 Apparent Power (max) | Maximum recorded since last reset. | UINT32 | ABCD | VA | Read | ||
| IR | 294doc 126-127 | L3 Phase voltage (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 296doc 128-129 | L3 Current (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 300doc 12C-12D | L3 Inductive Power (max) | Maximum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 302doc 12E-12F | L3 Capacitive Power (max) | Maximum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 304doc 130-131 | L3 Apparent Power (max) | Maximum recorded since last reset. | UINT32 | ABCD | VA | Read | ||
| IR | 312doc 138-139 | Inductive Three-phase power (max) | Maximum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 314doc 13A-13B | Capacitive Three-phase Power (max) | Maximum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 316doc 13C-13D | Apparent three-phase power (max) | Maximum recorded since last reset. | UINT32 | ABCD | VA | Read | ||
| IR | 322doc 142-143 | L1 Frequency (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.01 | Hz | Read | |
| IR | 324doc 144-145 | L1-L2 Voltage (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 326doc 146-147 | L2-L3 Voltage (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 328doc 148-149 | L3-L1 Voltage (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 330doc 14A-14B | Neutral Current N (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 332doc 14C-14D | L1 voltage % THD (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 334doc 14E-14F | L2 voltage % THD (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 336doc 150-151 | L3 voltage % THD (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 338doc 152-153 | L1 current % THD (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 340doc 154-155 | L2 current % THD (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 342doc 156-157 | L3 current % THD (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 2001doc 7D1 | Power status | Quadrant flags. | BITMAP16 | Read | bit 0 = Consumed; bit 1 = Generated; bit 2 = Inductive; bit 3 = Capacitive | |||
| IR | 2005doc 7D5 | Incorrect rotation detected | UINT16 | Read | 0 = No fault; 1 = Fault detected | ||||
| IR | 20000doc 4E20 | Digital input status | BITMAP16 | Read | bit 0 = Input 1 ON; bit 1 = Input 2 ON | ||||
| IR | 20001doc 4E21 | Digital output status | BITMAP16 | Read | bit 0 = Output 1 ON; bit 1 = Output 2 ON; bit 2 = Output 3 ON; bit 3 = Output 4 ON | ||||
| HR | 10000doc 2710 - 2711 | Voltage primary | 1-599999, default 1. Program all ratio registers together. | UINT32 | ABCD | V | Read/write | ||
| HR | 10002doc 2712 | Voltage secondary | 1-999, default 1. | UINT16 | V | Read/write | |||
| HR | 10003doc 2713 | Current primary | 1-10000, default 5. | UINT16 | A | Read/write | |||
| HR | 10004doc 2714 | Current secondary | 1 = .../1 A, 5 = .../5 A (default 5). | UINT16 | A | Read/write | |||
| HR | 10050doc 2742 | Protocol | UINT16 | Read/write | 0 = Modbus (default); 1 = BACnet | ||||
| HR | 10051doc 2743 | Peripheral number (Modbus/BACnet address) | 0-255, default 1. | UINT16 | Read/write | ||||
| HR | 10052doc 2744 | Modbus baud rate | UINT16 | Read/write | 0 = 9600 (default); 1 = 19200 | ||||
| HR | 10053doc 2745 | Modbus parity | UINT16 | Read/write | 0 = No parity (default); 1 = Odd; 2 = Even | ||||
| HR | 10054doc 2746 | Modbus data bits | UINT16 | Read/write | 0 = 8 bits (default); 1 = 7 bits | ||||
| HR | 10055doc 2747 | Modbus stop bits | UINT16 | Read/write | 0 = 1 stop bit (default); 1 = 2 stop bits | ||||
| HR | 10060doc 274C | Max demand integration period | 1-60, default 15. | UINT16 | min | Read/write | |||
| HR | 11100doc 2B5C | Type of installation | UINT16 | Read/write | 0 = 3-phase 4-wire (default); 1 = 3-phase 3-wire; 2 = 3-phase 3-wire Aron; 3 = 2-phase 3-wire; 4 = 1-phase 2-wire phase-phase; 5 = 1-phase 2-wire phase-neutral | ||||
| HR | 11108doc 2B64 | Number of quadrants (max demand) | UINT16 | Read/write | 0 = 4 quadrants (default); 1 = 2 quadrants | ||||
| HR | 11142doc 2B86 | Measurement convention | UINT16 | Read/write | 0 = Circutor (default); 1 = IEC; 2 = IEEE |
Notes on this map
- Word order: the manual's function 04 example returns register 1 = 0000 and register 2 = 084D for 212.5 V, so 32-bit values are high word first (ABCD).
- Left out: active power (per phase and three-phase), power factor and cos phi, plus their max/min and the kW maximum demand. The manual shows generated power as negative on the display but does not say whether the Modbus value is signed, so the data type cannot be fixed from the document.
- Voltages, currents, reactive/apparent powers, frequency, THD and energies are non-negative quantities and are typed UINT32.
- Left out: minimum values, per-tariff energies, harmonics tables, CO2/cost, alarm/pulse programming, BACnet and password registers, to keep the map to what integrators normally poll. All are in the manual's tables 19-38.
- Left out: 'Generated apparent energy (VAh)' total because its address is printed FE-EF (a misprint for FE-FF).
- Configuration registers: the manual lists function 0x04 for reading them and 0x10 for writing; changes take effect only after the device is reset, and out-of-range values silently revert to the default.
- Reset commands are written with function 05 and value FF00. The manual's 0x05 example labels register 0834 as deleting max/min values, but its deleting-parameters table lists 834 as delete energies and 838 as delete max/min; the table is followed here.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Circutor CVM-C10
What Modbus registers does the Circutor CVM-C10 have?
This map lists 103 registers: 6 coils, 83 input registers, 14 holding registers. 20 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Circutor CVM-C10 Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. All Modbus map addresses in the manual are hexadecimal wire addresses. The manual's example reads L1 voltage at initial register 0000 and receives 0000 084D (= 2125, 212.5 V), confirming the offset and scaling.
What byte order does the Circutor CVM-C10 use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Circutor CVM-C10?
Start with IR 0 L1 Phase voltage (L1 phase voltage (V x10)); IR 2 L1 Current (L1 current (mA)); IR 54 Apparent three-phase power (Three-phase apparent power); IR 60 L1 Frequency (Frequency (Hz x100)); IR 220 Total consumed active energy (kWh) (Total consumed active energy kWh); IR 2001 Power status (Power status (consumed/generated quadrant)).
How do I enable Modbus control of the Circutor CVM-C10?
Set Protocol (0x2742) to Modbus (factory default), then peripheral number, speed and framing either from the front panel or via the 0x2743-0x2747 registers. Reset the device for changes to apply.
Where is the official Circutor CVM-C10 Modbus documentation?
The source is CVM-C10 Power analyzer Instruction Manual (M001B01-03-23A), published free by Circutor at https://docs.circutor.com/docs/M001B01-03.pdf.
More Circutor Modbus register maps
- Power meter (power factor regulator with network analyzer)
Circutor Computer SMART III
Circutor Computer SMART III reactive energy regulators (6 and 12 step models), RS-485 Modbus RTU, manual M015B01-03-25B.
Also known as: Computer SMART III 6, Computer SMART III 12, SMART III - Power meter (static reactive energy regulator)
Circutor Computer SMART III FAST
Circutor Computer SMART III FAST static reactive power regulators (6 and 12 stage), manual M021B01-03-21A.
Also known as: Computer SMART III FAST 6, Computer SMART III FAST 12 - Power meter
Circutor CVM-C5
Circutor CVM-C5 panel power analyzer, RS-485 Modbus RTU versions (ITF-485, MC-485, mV-485), manual M026B01-03.
Also known as: CVM-C5-ITF-485, CVM-C5-MC-485, CVM-C5-mV-485 - Power meter
Circutor CVM-E3-MINI
Circutor CVM-E3-MINI DIN-rail power analyzer, RS-485 Modbus RTU (Map 2 / CVM-C10-compatible addresses), manual M170B01-03-25B.
Also known as: CVM-E3-MINI-ITF-RS485, CVM-E3-MINI-MC, CVM-E3-MINI-FLEX, CVM-E3-MINI-mV, CVM-E3-MINI-ITF-WiEth - Power meter (earth leakage breaker with reclosing and metering)
Circutor RECmax-CVM
Circutor RECmax-CVM earth-leakage circuit breaker with automatic reclosing and built-in analyzer, manual M175B01-03-22A.
Other power & energy meters register maps
- Energy meter (heat / cooling meter)
Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module
Modbus RTU plug-in communication module (Sylop M/N 11024, firmware 1.0) in a Diehl SHARKY 775 compact heat meter or SCYLAR INT 8 calculator.
Also known as: SHARKY 775, SCYLAR INT 8, Sylop M/N 11024, Diehl Modbus RTU module - Energy meter
Eastron SDM630-DI
Eastron SDM630-DI three-phase DIN-rail meter (100 A direct, two digital inputs, RS485 Modbus RTU), manual V1.02.
Also known as: SDM630 DI - Sensor (electromagnetic flowmeter)
Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485)
Proline Promag 400 transmitters with the Modbus RS485 output, as described in GP01045D/06/EN/02.21.
Also known as: Promag D 400, Promag L 400, Promag W 400, Proline 400 Modbus RS485 - Energy meter
Fronius Fronius Smart Meter via GEN24 / Tauro inverter (SunSpec meter model int+SF)
A Fronius Smart Meter wired to a GEN24 or Tauro inverter over Modbus RTU and republished by the inverter over Modbus TCP, with SunSpec Model Type set to int+SF (meter model 201/202/203).
Also known as: Fronius Smart Meter 63A, Fronius Smart Meter 50kA, Fronius Smart Meter TS, SunSpec meter model 201/202/203 - Power meter
IME Nemo 96HDLe with Rogowski coil input (KRNEMOHD)
IME Nemo 96HDLe for Rogowski coils, code KRNEMOHD, per protocol PR139 (software 1.03).
Also known as: KRNEMOHD - Energy meter
inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6)
PRO2-Mod of the PRO2 series (PRO2-S/-2T/-Mb/-Mod), register map of user manual version 2.18-6.
Also known as: PRO2-Mod, PRO2 Mod, PRO2 MID, inepro PRO2 legacy
All power & energy meters Modbus register maps →
Source: CVM-C10 Power analyzer Instruction Manual · M001B01-03-23A. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.