Power meter · Modbus register map
Circutor CVM-E3-MINI Modbus register map
Updated 17 November 2026
The CVM-E3-MINI is a compact DIN-rail three-phase power analyzer from Circutor with an RS-485 port for Modbus RTU or BACnet. It exposes two parallel Modbus maps; this file uses Map 2, which follows the CVM-C10 layout shifted by 0x1000. Values are 32-bit integers with fixed scaling (V x10, mA, Hz x100) read with function 03/04. Included: voltages, currents, reactive and apparent power, THD, demand, total energies, status words, setup registers and reset commands.
This page lists 104 Modbus registers for the Circutor CVM-E3-MINI — 21 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Circutor’s own free documentation (linked below) and checked against it.
- Manufacturer
- Circutor
- Model
- CVM-E3-MINI
- Equipment type
- Power meter
- Registers
- 104 (21 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- Notes in the source distinguish software version v2.xx (higher baud rates, address limit 247).
- Also known as
- CVM-E3-MINI-ITF-RS485, CVM-E3-MINI-MC, CVM-E3-MINI-FLEX, CVM-E3-MINI-mV, CVM-E3-MINI-ITF-WiEth
Integration notes: Circutor CVM-E3-MINI
Read the Map 2 block from 0x1000 with function 04, at most 20 variables (40 registers) per frame. Each value is a 32-bit integer, high word first, scaled as listed.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 4096 | L1 Phase voltage | UINT32 ABCD | L1 phase voltage (V x10) | Read |
| IR 4098 | L1 Current | UINT32 ABCD | L1 current (mA) | Read |
| IR 4150 | Three-phase Apparent power | UINT32 ABCD | Three-phase apparent power | Read |
| IR 4156 | L1 Frequency | UINT32 ABCD | Frequency (Hz x100) | Read |
| IR 4316 | Total consumed active energy III (kWh) | UINT32 ABCD | Total consumed active energy kWh | Read |
| IR 2001 | Power status | BITMAP16 | Power status (consumed/generated) | Read |
Enable Modbus control & writes
Set Protocol (0x2742) to Modbus (the default), then peripheral number, baud and framing from the display setup or registers 0x2743-0x2747. Reset or exit setup to apply.
Byte order & addressing
- Firmware v2.xx needs a master timeout of at least 200 ms and at least 100 ms between frames.
- Energy is split into a whole-unit register and a remainder (Wh/varh/VAh) register.
- Reset commands use function 05 with value FF00.
Network setup
- Defaults: peripheral number 1, 19200 baud, no parity, 8 data bits, 1 stop bit.
- Baud rates 9600 and 19200; 38400-115200 only on firmware v2.xx.
- Voltage ratio is limited to 1000 and voltage ratio x current ratio to 300000.
Watch out for
- Two maps return the same data at different addresses; make sure the master uses Map 2 (0x1000 range) for measurement and energy values.
Circutor CVM-E3-MINI Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 2100doc 834 | Delete three-phase energies | Write FF00 with function 05. | BIT | Write | ||||
| CO | 2121doc 849 | Delete maximum values | Write FF00 with function 05. | BIT | Write | ||||
| CO | 2122doc 84A | Delete minimum values | Write FF00 with function 05. | BIT | Write | ||||
| CO | 2130doc 852 | Maximum demand initialization | Write FF00 with function 05. | BIT | Write | ||||
| CO | 2164doc 874 | Delete per-phase and three-phase energies | Write FF00 with function 05. | BIT | Write | ||||
| CO | 2180doc 884 | Delete digital input pulse counter | Write FF00 with function 05. | BIT | Write | ||||
| CO | 2200doc 898 | Delete all of the above | Write FF00 with function 05. | BIT | Write | ||||
| IR | 2001doc 7D1 | Power status | Quadrant flags. | BITMAP16 | Read | bit 0 = Consumed; bit 1 = Generated; bit 2 = Inductive; bit 3 = Capacitive | |||
| IR | 2005doc 7D5 | Incorrect rotation detected | UINT16 | Read | 0 = No fault; 1 = Fault detected | ||||
| IR | 4096doc 1000-1001 | L1 Phase voltage | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 4098doc 1002-1003 | L1 Current | Instantaneous value. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 4102doc 1006-1007 | L1 Inductive Power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 4104doc 1008-1009 | L1 Capacitive Power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 4106doc 100A-100B | L1 Apparent Power | Instantaneous value. | UINT32 | ABCD | VA | Read | ||
| IR | 4112doc 1010-1011 | L2 Phase voltage | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 4114doc 1012-1013 | L2 Current | Instantaneous value. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 4118doc 1016-1017 | L2 Inductive Power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 4120doc 1018-1019 | L2 Capacitive Power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 4122doc 101A-101B | L2 Apparent Power | Instantaneous value. | UINT32 | ABCD | VA | Read | ||
| IR | 4128doc 1020-1021 | L3 Phase voltage | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 4130doc 1022-1023 | L3 Current | Instantaneous value. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 4134doc 1026-1027 | L3 Inductive Power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 4136doc 1028-1029 | L3 Capacitive Power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 4138doc 102A-102B | L3 Apparent Power | Instantaneous value. | UINT32 | ABCD | VA | Read | ||
| IR | 4146doc 1032-1033 | Three-phase Inductive power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 4148doc 1034-1035 | Three-phase Capacitive Power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 4150doc 1036-1037 | Three-phase Apparent power | Instantaneous value. | UINT32 | ABCD | VA | Read | ||
| IR | 4156doc 103C-103D | L1 Frequency | Instantaneous value. | UINT32 | ABCD | × 0.01 | Hz | Read | |
| IR | 4158doc 103E-103F | L1-L2 Voltage | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 4160doc 1040-1041 | L2-L3 Voltage | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 4162doc 1042-1043 | L3-L1 Voltage | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 4164doc 1044-1045 | Neutral Current | Instantaneous value. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 4166doc 1046-1047 | % L1 voltage THD | Instantaneous value. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 4168doc 1048-1049 | % L2 voltage THD | Instantaneous value. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 4170doc 104A-104B | % L3 voltage THD | Instantaneous value. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 4172doc 104C-104D | % L1 current THD | Instantaneous value. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 4174doc 104E-104F | % L2 current THD | Instantaneous value. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 4176doc 1050-1051 | % L3 current THD | Instantaneous value. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 4180doc 1054-1055 | Maximum demand kVA III | Present maximum-demand value. | UINT32 | ABCD | VA | Read | ||
| IR | 4184doc 1058-1059 | Maximum demand I L1 | Present maximum-demand value. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 4186doc 105A-105B | Maximum demand I L2 | Present maximum-demand value. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 4188doc 105C-105D | Maximum demand I L3 | Present maximum-demand value. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 4316doc 10DC-10DD | Total consumed active energy III (kWh) | All tariffs. Full value = whole-unit register plus the matching remainder register. | UINT32 | ABCD | kWh | Read | ||
| IR | 4318doc 10DE-10DF | Total consumed active energy III (Wh) | All tariffs. Full value = whole-unit register plus the matching remainder register. | UINT32 | ABCD | Wh | Read | ||
| IR | 4320doc 10E0-10E1 | Total consumed inductive reactive energy III (kvarhL) | All tariffs. Full value = whole-unit register plus the matching remainder register. | UINT32 | ABCD | kvarh | Read | ||
| IR | 4322doc 10E2-10E3 | Total consumed inductive reactive energy III (varhL) | All tariffs. Full value = whole-unit register plus the matching remainder register. | UINT32 | ABCD | varh | Read | ||
| IR | 4324doc 10E4-10E5 | Total consumed capacitive reactive energy III (kvarhC) | All tariffs. Full value = whole-unit register plus the matching remainder register. | UINT32 | ABCD | kvarh | Read | ||
| IR | 4326doc 10E6-10E7 | Total consumed capacitive reactive energy III (varhC) | All tariffs. Full value = whole-unit register plus the matching remainder register. | UINT32 | ABCD | varh | Read | ||
| IR | 4328doc 10E8-10E9 | Total consumed apparent energy III (kVAh) | All tariffs. Full value = whole-unit register plus the matching remainder register. | UINT32 | ABCD | kVAh | Read | ||
| IR | 4330doc 10EA-10EB | Total consumed apparent energy III (VAh) | All tariffs. Full value = whole-unit register plus the matching remainder register. | UINT32 | ABCD | VAh | Read | ||
| IR | 4336doc 10F0-10F1 | Total generated active energy III (kWh) | All tariffs. Full value = whole-unit register plus the matching remainder register. | UINT32 | ABCD | kWh | Read | ||
| IR | 4338doc 10F2-10F3 | Total generated active energy III (Wh) | All tariffs. Full value = whole-unit register plus the matching remainder register. | UINT32 | ABCD | Wh | Read | ||
| IR | 4340doc 10F4-10F5 | Total generated inductive reactive energy III (kvarhL) | All tariffs. Full value = whole-unit register plus the matching remainder register. | UINT32 | ABCD | kvarh | Read | ||
| IR | 4342doc 10F6-10F7 | Total generated inductive reactive energy III (varhL) | All tariffs. Full value = whole-unit register plus the matching remainder register. | UINT32 | ABCD | varh | Read | ||
| IR | 4344doc 10F8-10F9 | Total generated capacitive reactive energy III (kvarhC) | All tariffs. Full value = whole-unit register plus the matching remainder register. | UINT32 | ABCD | kvarh | Read | ||
| IR | 4346doc 10FA-10FB | Total generated capacitive reactive energy III (varhC) | All tariffs. Full value = whole-unit register plus the matching remainder register. | UINT32 | ABCD | varh | Read | ||
| IR | 4348doc 10FC-10FD | Total generated apparent energy III (kVAh) | All tariffs. Full value = whole-unit register plus the matching remainder register. | UINT32 | ABCD | kVAh | Read | ||
| IR | 4358doc 1106-1107 | L1 Phase voltage (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 4360doc 1108-1109 | L1 Current (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 4364doc 110C-110D | L1 Inductive Power (max) | Maximum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 4366doc 110E-110F | L1 Capacitive Power (max) | Maximum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 4368doc 1110-1111 | L1 Apparent Power (max) | Maximum recorded since last reset. | UINT32 | ABCD | VA | Read | ||
| IR | 4374doc 1116-1117 | L2 Phase voltage (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 4376doc 1118-1119 | L2 Current (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 4380doc 111C-111D | L2 Inductive Power (max) | Maximum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 4382doc 111E-111F | L2 Capacitive Power (max) | Maximum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 4384doc 1120-1121 | L2 Apparent Power (max) | Maximum recorded since last reset. | UINT32 | ABCD | VA | Read | ||
| IR | 4390doc 1126-1127 | L3 Phase voltage (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 4392doc 1128-1129 | L3 Current (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 4396doc 112C-112D | L3 Inductive Power (max) | Maximum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 4398doc 112E-112F | L3 Capacitive Power (max) | Maximum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 4400doc 1130-1131 | L3 Apparent Power (max) | Maximum recorded since last reset. | UINT32 | ABCD | VA | Read | ||
| IR | 4408doc 1138-1139 | Three-phase Inductive power (max) | Maximum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 4410doc 113A-113B | Three-phase Capacitive Power (max) | Maximum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 4412doc 113C-113D | Three-phase Apparent power (max) | Maximum recorded since last reset. | UINT32 | ABCD | VA | Read | ||
| IR | 4418doc 1142-1143 | L1 Frequency (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.01 | Hz | Read | |
| IR | 4420doc 1144-1145 | L1-L2 Voltage (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 4422doc 1146-1147 | L2-L3 Voltage (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 4424doc 1148-1149 | L3-L1 Voltage (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 4426doc 114A-114B | Neutral Current (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 4428doc 114C-114D | % L1 voltage THD (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 4430doc 114E-114F | % L2 voltage THD (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 4432doc 1150-1151 | % L3 voltage THD (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 4434doc 1152-1153 | % L1 current THD (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 4436doc 1154-1155 | % L2 current THD (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 4438doc 1156-1157 | % L3 current THD (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 4608doc 1200-1201 | Maximum demand kvarL III | Present maximum-demand value. | UINT32 | ABCD | var | Read | ||
| IR | 4610doc 1202-1203 | Maximum demand kvarC III | Present maximum-demand value. | UINT32 | ABCD | var | Read | ||
| IR | 20000doc 4E20 | Digital input status | BITMAP16 | Read | bit 0 = Input 1 ON | ||||
| IR | 20001doc 4E21 | Digital output status | BITMAP16 | Read | bit 0 = Output 1 ON | ||||
| HR | 10000doc 2710 - 2711 | Voltage primary | 1-599999, default 1. Read/write the ratio group at once. | UINT32 | ABCD | V | Read/write | ||
| HR | 10002doc 2712 | Voltage secondary | 1-999, default 1. | UINT16 | V | Read/write | |||
| HR | 10003doc 2713 | Current primary | 1-10000, default 5 (ITF/MC models). | UINT16 | A | Read/write | |||
| HR | 10004doc 2714 | Current secondary | ITF models only. | UINT16 | Read/write | 0 = .../1 A; 1 = .../5 A (default) | |||
| HR | 10050doc 2742 | Protocol | UINT16 | Read/write | 0 = Modbus (default); 1 = BACnet | ||||
| HR | 10051doc 2743 | Peripheral number | Default 1; fw v2.xx limits Modbus addresses to 247. | UINT16 | Read/write | ||||
| HR | 10052doc 2744 | Baud rate | Shared by Modbus and BACnet. | UINT16 | Read/write | 0 = 9600; 1 = 19200 (default); 2 = 38400 (fw v2.xx); 3 = 57600 (fw v2.xx); 4 = 115200 (fw v2.xx) | |||
| HR | 10053doc 2745 | Modbus parity | UINT16 | Read/write | 0 = No parity (default); 1 = Odd; 2 = Even | ||||
| HR | 10054doc 2746 | Modbus data bits | UINT16 | Read/write | 0 = 8 bits (default); 1 = 7 bits | ||||
| HR | 10055doc 2747 | Modbus stop bits | UINT16 | Read/write | 0 = 1 stop bit (default); 1 = 2 stop bits | ||||
| HR | 10060doc 274C | Max demand integration period | 0 = no demand calculation (default), 1-60 minutes. | UINT16 | min | Read/write | |||
| HR | 11100doc 2B5C | Measurement system | UINT16 | Read/write | 0 = 3-phase 4-wire (default); 1 = 3-phase 3-wire; 2 = 3-phase 3-wire Aron; 3 = 2-phase 3-wire; 4 = 1-phase 2-wire phase-phase; 5 = 1-phase 2-wire phase-neutral | ||||
| HR | 11108doc 2B64 | Number of quadrants | UINT16 | Read/write | 0 = 4 quadrants (default); 1 = 2 quadrants | ||||
| HR | 11142doc 2B86 | Measurement convention | UINT16 | Read/write | 0 = Circutor (default); 1 = IEC; 2 = IEEE |
Notes on this map
- Word order: the manual's read example returns register 1 = 0000, register 2 = 084D for 212.5 V, so 32-bit values are high word first (ABCD).
- Map 1 (CVM-MINI compatible addresses) is not listed; the manual recommends Map 2 for new integrations. Map 1 also contains printing errors (e.g. min average current printed 106-417, frequency scale x10 vs x100).
- Left out: active power, reactive power (signed), power factor and cos phi, and kW maximum demand. The document does not say whether the Modbus values are signed, so the data type cannot be fixed.
- Left out: per-tariff and per-phase energies, harmonics, CO2/cost, alarm and pulse programming, password and BACnet registers; all are in tables 62-79 of the manual.
- Left out: the 'Generated apparent energy (VAh)' total, whose address is misprinted (10FE-10EF).
- Configuration changes made over Modbus apply only after a device reset; the ratio registers must be written as one group.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Circutor CVM-E3-MINI
What Modbus registers does the Circutor CVM-E3-MINI have?
This map lists 104 registers: 7 coils, 83 input registers, 14 holding registers. 21 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Circutor CVM-E3-MINI Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. All addresses in the manual are hexadecimal wire addresses. Its function 04 example reads L1 voltage at 0000 (Map 1) and gets 0000 084D = 212.5 V. Map 2 adds 0x1000 to the CVM-C10 addresses, so L1 voltage is 0x1000 here.
What byte order does the Circutor CVM-E3-MINI use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Circutor CVM-E3-MINI?
Start with IR 4096 L1 Phase voltage (L1 phase voltage (V x10)); IR 4098 L1 Current (L1 current (mA)); IR 4150 Three-phase Apparent power (Three-phase apparent power); IR 4156 L1 Frequency (Frequency (Hz x100)); IR 4316 Total consumed active energy III (kWh) (Total consumed active energy kWh); IR 2001 Power status (Power status (consumed/generated)).
How do I enable Modbus control of the Circutor CVM-E3-MINI?
Set Protocol (0x2742) to Modbus (the default), then peripheral number, baud and framing from the display setup or registers 0x2743-0x2747. Reset or exit setup to apply.
Where is the official Circutor CVM-E3-MINI Modbus documentation?
The source is CVM-E3-MINI Power analyzer Instruction Manual (M170B01-03-25B), published free by Circutor at https://docs.circutor.com/docs/M170B01-03.pdf.
More Circutor Modbus register maps
- Power meter (power factor regulator with network analyzer)
Circutor Computer SMART III
Circutor Computer SMART III reactive energy regulators (6 and 12 step models), RS-485 Modbus RTU, manual M015B01-03-25B.
Also known as: Computer SMART III 6, Computer SMART III 12, SMART III - Power meter (static reactive energy regulator)
Circutor Computer SMART III FAST
Circutor Computer SMART III FAST static reactive power regulators (6 and 12 stage), manual M021B01-03-21A.
Also known as: Computer SMART III FAST 6, Computer SMART III FAST 12 - Power meter
Circutor CVM-C10
Circutor CVM-C10 panel power analyzer, RS-485 versions (ITF, MC, mV, ITF-IN), manual M001B01-03-23A.
Also known as: CVM-C10-ITF-485, CVM-C10-MC-485, CVM-C10-mV-485, CVM-C10-ITF-IN-485 - Power meter
Circutor CVM-C5
Circutor CVM-C5 panel power analyzer, RS-485 Modbus RTU versions (ITF-485, MC-485, mV-485), manual M026B01-03.
Also known as: CVM-C5-ITF-485, CVM-C5-MC-485, CVM-C5-mV-485 - Power meter (earth leakage breaker with reclosing and metering)
Circutor RECmax-CVM
Circutor RECmax-CVM earth-leakage circuit breaker with automatic reclosing and built-in analyzer, manual M175B01-03-22A.
Other power & energy meters register maps
- Energy meter
Eastron SDM120-Modbus
Eastron SDM120Modbus single-phase DIN-rail meter (direct connected), protocol implementation V2.4.
Also known as: SDM120M, SDM120Modbus, SDM120-M - Energy meter
Eastron SDM630MCT
Eastron SDM630MCT three-phase CT-connected DIN-rail meter with RS485 Modbus RTU, protocol implementation V1.7.
Also known as: SDM630 MCT - Sensor (ultrasonic gas flowmeter)
Endress+Hauser Proline Prosonic Flow G 500 ultrasonic gas flowmeter (Modbus RS485)
Prosonic Flow G 500 with the Modbus RS485 communication option, parameter description GP01133D/06/EN/02.24-00.
Also known as: Prosonic Flow G 500 - Energy meter (DIN-rail, single-phase)
IME Conto D1 single-phase energy meter (CE111)
IME Conto D1 single-phase meter, code CE111, per protocol PR133 (2025-02-24).
Also known as: CE111, Conto D1 - Power meter (DIN-rail)
IME Nemo D4-Le with Rogowski coil input (KRNEMOD4)
IME Nemo D4-Le for Rogowski coils, code KRNEMOD4, per protocol PR140 (software 1.01).
Also known as: KRNEMOD4 - Energy meter
inepro Metering PRO380-Eichrecht three-phase energy meter
PRO380-Eichrecht direct-connected 3x230/400 V, 40 A meter (MID + German MessEV calibration law, for EV chargers), user manual version 1.45, September 2025.
Also known as: PRO380 Eichrecht, PRO380-E, inepro PRO380 Eichrecht
All power & energy meters Modbus register maps →
Source: CVM-E3-MINI Power analyzer Instruction Manual · M170B01-03-25B. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.