- Home
- Modbus register maps
- IME
- Nemo D4-Le with Rogowski coil input (KRNEMOD4)
Power meter (DIN-rail) · Modbus register map
IME Nemo D4-Le with Rogowski coil input (KRNEMOD4) Modbus register map
Updated 17 November 2026
Rogowski-coil version of the Nemo D4-Le DIN-rail meter with an RS-485 Modbus/JBUS port. Voltages and currents are integers in mV/mA; a fixed-unit block gives signed powers, power factors and Wh/MWh energy counters.
This page lists 149 Modbus registers for the IME Nemo D4-Le with Rogowski coil input (KRNEMOD4) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from IME’s own free documentation (linked below) and checked against it.
- Manufacturer
- IME
- Model
- Nemo D4-Le with Rogowski coil input (KRNEMOD4)
- Equipment type
- Power meter (DIN-rail)
- Registers
- 149 (0 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- KRNEMOD4
Integration notes: IME Nemo D4-Le with Rogowski coil input (KRNEMOD4)
Read holding registers (function 03) from 0x1000 for voltages and currents in mV/mA, and from 0x1500 (or 0x1700) for signed powers and energies in fixed units. Double words are high word first.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 4096 | Phase 1: phase voltage | UINT32 ABCD | Phase 1 voltage | Read |
| HR 4102 | Phase 1: current | UINT32 ABCD | Phase 1 current | Read |
| HR 4134 | Frequency | UINT16 | Frequency | Read |
| HR 4132 | 3-phase: power factor | INT16 | 3-phase power factor | Read |
| HR 5400 | Signed 3-ph Active Power | INT32 ABCD | Signed 3-phase active power | Read |
| HR 5376 | Positive Active Energy - Low | UINT32 ABCD | Positive active energy (Wh part) | Read |
| HR 5378 | Positive Active Energy - High | UINT32 ABCD | Positive active energy (MWh part) | Read |
Enable Modbus control & writes
Set the address, baud rate and parity on the meter (both are programmable). Only functions 03 and 0x10 are used. Setup writes need the unlock key 0x5AA5 written to 0x2700 first.
Byte order & addressing
- Only functions 03 and 0x10 are supported (no function 04).
- A single request may ask for at most 240 bytes of data.
- Voltages and currents are in mV and mA.
Network setup
- Baud rate and parity are programmable on the device; 8 data bits and 1 stop bit.
Watch out for
- Power registers in the 0x10xx block change scale with the CT/VT ratio; prefer the 0x15xx block.
IME Nemo D4-Le with Rogowski coil input (KRNEMOD4) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 4096doc 0x1000 | Phase 1: phase voltage | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 4098doc 0x1002 | Phase 2: phase voltage | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 4100doc 0x1004 | Phase 3: phase voltage | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 4102doc 0x1006 | Phase 1: current | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 4104doc 0x1008 | Phase 2: current | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 4106doc 0x100a | Phase 3: current | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 4108doc 0x100c | Neutral current | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 4110doc 0x100e | Chained voltage: L1-L2 | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 4112doc 0x1010 | Chained voltage: L2-L3 | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 4114doc 0x1012 | Chained voltage: L3-L1 | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 4122doc 0x101a | 3-phase: sign of active power | UINT16 | Read | 0 = Positive; 1 = Negative | ||||
| HR | 4123doc 0x101b | 3-phase: sign of reactive power | UINT16 | Read | 0 = Positive; 1 = Negative | ||||
| HR | 4132doc 0x1024 | 3-phase: power factor | INT16 | × 0.01 | Read | ||||
| HR | 4133doc 0x1025 | 3-phase: sector of power factor (cap or ind) | UINT16 | Read | 0 = PF = 1; 1 = Inductive; 2 = Capacitive | ||||
| HR | 4134doc 0x1026 | Frequency | UINT16 | × 0.1 | Hz | Read | |||
| HR | 4139doc 0x102b | Time counter for average power | UINT16 | min | Read | ||||
| HR | 4146doc 0x1032 | Phase 1: sign of active power | UINT16 | Read | 0 = Positive; 1 = Negative | ||||
| HR | 4147doc 0x1033 | Phase 2: sign of active power | UINT16 | Read | 0 = Positive; 1 = Negative | ||||
| HR | 4148doc 0x1034 | Phase 3: sign of active power | UINT16 | Read | 0 = Positive; 1 = Negative | ||||
| HR | 4155doc 0x103b | Phase 1: sign of reactive power | UINT16 | Read | 0 = Positive; 1 = Negative | ||||
| HR | 4156doc 0x103c | Phase 2: sign of reactive power | UINT16 | Read | 0 = Positive; 1 = Negative | ||||
| HR | 4157doc 0x103d | Phase 3: sign of reactive power | UINT16 | Read | 0 = Positive; 1 = Negative | ||||
| HR | 4164doc 0x1044 | Phase 1: power factor | INT16 | × 0.01 | Read | ||||
| HR | 4165doc 0x1045 | Phase 2: power factor | INT16 | × 0.01 | Read | ||||
| HR | 4166doc 0x1046 | Phase 3: power factor | INT16 | × 0.01 | Read | ||||
| HR | 4167doc 0x1047 | Phase 1: power factor sector | UINT16 | Read | 0 = PF = 1; 1 = Inductive; 2 = Capacitive | ||||
| HR | 4168doc 0x1048 | Phase 2: power factor sector | UINT16 | Read | 0 = PF = 1; 1 = Inductive; 2 = Capacitive | ||||
| HR | 4169doc 0x1049 | Phase 3: power factor sector | UINT16 | Read | 0 = PF = 1; 1 = Inductive; 2 = Capacitive | ||||
| HR | 4170doc 0x104a | Phase 1: THD V1 | UINT16 | × 0.1 | % | Read | |||
| HR | 4171doc 0x104b | Phase 2: THD V2 | UINT16 | × 0.1 | % | Read | |||
| HR | 4172doc 0x104c | Phase 3: THD V3 | UINT16 | × 0.1 | % | Read | |||
| HR | 4173doc 0x104d | Phase 1: THD I1 | UINT16 | × 0.1 | % | Read | |||
| HR | 4174doc 0x104e | Phase 2: THD I2 | UINT16 | × 0.1 | % | Read | |||
| HR | 4175doc 0x104f | Phase 3: THD I3 | UINT16 | × 0.1 | % | Read | |||
| HR | 4176doc 0x1050 | Phase 1: I1 average | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 4178doc 0x1052 | Phase 2: I2 average | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 4180doc 0x1054 | Phase 3: I3 average | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 4182doc 0x1056 | Phase 1: I1 peak maximum | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 4184doc 0x1058 | Phase 2: I2 peak maximum | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 4186doc 0x105a | Phase 3: I3 peak maximum | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 4188doc 0x105c | (I1+I2+I3)/3 | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 4190doc 0x105e | Phase 1: V1 min | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 4192doc 0x1060 | Phase 2: V2 min | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 4194doc 0x1062 | Phase 3: V3 min | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 4196doc 0x1064 | Phase 1: V1 max | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 4198doc 0x1066 | Phase 2: V2 max | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 4200doc 0x1068 | Phase 3: V3 max | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 4206doc 0x106e | Run hour meter | UINT16 | h | Read | ||||
| HR | 4220doc 0x107c | Run hour meter | UINT32 | ABCD | min | Read | |||
| HR | 5376doc 0x1500 | Positive Active Energy - Low | UINT32 | ABCD | Wh | Read | |||
| HR | 5378doc 0x1502 | Positive Active Energy - High | UINT32 | ABCD | MWh | Read | |||
| HR | 5380doc 0x1504 | Positive Reactive Energy - Low | UINT32 | ABCD | varh | Read | |||
| HR | 5382doc 0x1506 | Positive Reactive Energy - High | UINT32 | ABCD | Mvarh | Read | |||
| HR | 5384doc 0x1508 | Negative Active Energy - Low | UINT32 | ABCD | Wh | Read | |||
| HR | 5386doc 0x150A | Negative Active Energy - High | UINT32 | ABCD | MWh | Read | |||
| HR | 5388doc 0x150C | Negative Reactive Energy - Low | UINT32 | ABCD | varh | Read | |||
| HR | 5390doc 0x150E | Negative Reactive Energy - High | UINT32 | ABCD | Mvarh | Read | |||
| HR | 5392doc 0x1510 | Partial Active Energy - Low | UINT32 | ABCD | Wh | Read | |||
| HR | 5394doc 0x1512 | Partial Active Energy - High | UINT32 | ABCD | MWh | Read | |||
| HR | 5396doc 0x1514 | Partial Reactive Energy - Low | UINT32 | ABCD | varh | Read | |||
| HR | 5398doc 0x1516 | Partial Reactive Energy - High | UINT32 | ABCD | Mvarh | Read | |||
| HR | 5400doc 0x1518 | Signed 3-ph Active Power | INT32 | ABCD | W | Read | |||
| HR | 5402doc 0x151A | Signed 3-ph Reactive Power | INT32 | ABCD | var | Read | |||
| HR | 5404doc 0x151C | Signed Phase1 Active Power | INT32 | ABCD | W | Read | |||
| HR | 5406doc 0x151E | Signed Phase2 Active Power | INT32 | ABCD | W | Read | |||
| HR | 5408doc 0x1520 | Signed Phase3 Active Power | INT32 | ABCD | W | Read | |||
| HR | 5410doc 0x1522 | Signed Phase1 Reactive Power | INT32 | ABCD | var | Read | |||
| HR | 5412doc 0x1524 | Signed Phase2 Reactive Power | INT32 | ABCD | var | Read | |||
| HR | 5414doc 0x1526 | Signed Phase3 Reactive Power | INT32 | ABCD | var | Read | |||
| HR | 5416doc 0x1528 | Signed 3-ph Power Factor | INT32 | ABCD | × 0.001 | Read | |||
| HR | 5418doc 0x152A | Signed Phase1 Power Factor | INT32 | ABCD | × 0.001 | Read | |||
| HR | 5420doc 0x152C | Signed Phase2 Power Factor | INT32 | ABCD | × 0.001 | Read | |||
| HR | 5422doc 0x152E | Signed Phase3 Power Factor | INT32 | ABCD | × 0.001 | Read | |||
| HR | 5426doc 0x1532 | 3-phase: active average power | UINT32 | ABCD | W | Read | |||
| HR | 5428doc 0x1534 | 3-phase: reactive average power | UINT32 | ABCD | var | Read | |||
| HR | 5430doc 0x1536 | 3-phase: apparent average power | UINT32 | ABCD | VA | Read | |||
| HR | 5432doc 0x1538 | 3-phase: active PMD power | UINT32 | ABCD | W | Read | |||
| HR | 5434doc 0x153a | 3-phase: reactive PMD power | UINT32 | ABCD | var | Read | |||
| HR | 5436doc 0x153c | 3-phase: apparent PMD power | UINT32 | ABCD | VA | Read | |||
| HR | 5504doc 0x1580 | Phase 1: phase voltage crest factor | UINT16 | × 0.001 | Read | ||||
| HR | 5505doc 0x1581 | Phase 2: phase voltage crest factor | UINT16 | × 0.001 | Read | ||||
| HR | 5506doc 0x1582 | Phase 3: phase voltage crest factor | UINT16 | × 0.001 | Read | ||||
| HR | 5507doc 0x1583 | Phase 1: current crest factor | UINT16 | × 0.001 | Read | ||||
| HR | 5508doc 0x1584 | Phase 2: current crest factor | UINT16 | × 0.001 | Read | ||||
| HR | 5509doc 0x1585 | Phase 3: current crest factor | UINT16 | × 0.001 | Read | ||||
| HR | 5510doc 0x1586 | Chained voltage: L1-L2 crest factor | UINT16 | × 0.001 | Read | ||||
| HR | 5511doc 0x1587 | Chained voltage: L2-L3 crest factor | UINT16 | × 0.001 | Read | ||||
| HR | 5512doc 0x1588 | Chained voltage: L3-L1 crest factor | UINT16 | × 0.001 | Read | ||||
| HR | 5632doc 0x1600 | phase displacement V1-V2 (V12-V23) | UINT16 | × 0.1 | ° | Read | |||
| HR | 5633doc 0x1601 | phase displacement V2-V3 (V23-V31) | UINT16 | × 0.1 | ° | Read | |||
| HR | 5634doc 0x1602 | phase displacement V3-V1 (V31-V12) | UINT16 | × 0.1 | ° | Read | |||
| HR | 5635doc 0x1603 | phase displacement I1-I2 | UINT16 | × 0.1 | ° | Read | |||
| HR | 5636doc 0x1604 | phase displacement I2-I3 | UINT16 | × 0.1 | ° | Read | |||
| HR | 5637doc 0x1605 | phase displacement I3-I1 | UINT16 | × 0.1 | ° | Read | |||
| HR | 5638doc 0x1606 | phase displacement V1-I1 | UINT16 | × 0.1 | ° | Read | |||
| HR | 5639doc 0x1607 | phase displacement V2-I2 | UINT16 | × 0.1 | ° | Read | |||
| HR | 5640doc 0x1608 | phase displacement V3-I3 | UINT16 | × 0.1 | ° | Read | |||
| HR | 5641doc 0x1609 | phase displacement 3-ph | UINT16 | × 0.1 | ° | Read | |||
| HR | 5888doc 0x1700 | Positive Active Energy - Low | UINT32 | ABCD | Wh | Read | |||
| HR | 5890doc 0x1702 | Positive Active Energy - High | UINT32 | ABCD | MWh | Read | |||
| HR | 5892doc 0x1704 | Positive Reactive Energy - Low | UINT32 | ABCD | varh | Read | |||
| HR | 5894doc 0x1706 | Positive Reactive Energy - High | UINT32 | ABCD | Mvarh | Read | |||
| HR | 5896doc 0x1708 | Negative Active Energy - Low | UINT32 | ABCD | Wh | Read | |||
| HR | 5898doc 0x170A | Negative Active Energy - High | UINT32 | ABCD | MWh | Read | |||
| HR | 5900doc 0x170C | Negative Reactive Energy - Low | UINT32 | ABCD | varh | Read | |||
| HR | 5902doc 0x170E | Negative Reactive Energy - High | UINT32 | ABCD | Mvarh | Read | |||
| HR | 5904doc 0x1710 | Partial+ Active Energy - Low | UINT32 | ABCD | Wh | Read | |||
| HR | 5906doc 0x1712 | Partial+ Active Energy - High | UINT32 | ABCD | MWh | Read | |||
| HR | 5908doc 0x1714 | Partial+ Reactive Energy - Low | UINT32 | ABCD | varh | Read | |||
| HR | 5910doc 0x1716 | Partial+ Reactive Energy - High | UINT32 | ABCD | Mvarh | Read | |||
| HR | 5912doc 0x1718 | Partial- Active Energy - Low | UINT32 | ABCD | Wh | Read | |||
| HR | 5914doc 0x171a | Partial- Active Energy - High | UINT32 | ABCD | MWh | Read | |||
| HR | 5916doc 0x171c | Partial- Reactive Energy - Low | UINT32 | ABCD | varh | Read | |||
| HR | 5918doc 0x171e | Partial- Reactive Energy - High | UINT32 | ABCD | Mvarh | Read | |||
| HR | 5920doc 0x1720 | Signed 3-ph active power | INT32 | ABCD | W | Read | |||
| HR | 5922doc 0x1722 | Signed 3-ph reactive power | INT32 | ABCD | var | Read | |||
| HR | 5924doc 0x1724 | Signed phase1 active power | INT32 | ABCD | W | Read | |||
| HR | 5926doc 0x1726 | Signed phase2 active power | INT32 | ABCD | W | Read | |||
| HR | 5928doc 0x1728 | Signed phase3 active power | INT32 | ABCD | W | Read | |||
| HR | 5930doc 0x172A | Signed phase1 reactive power | INT32 | ABCD | var | Read | |||
| HR | 5932doc 0x172C | Signed phase2 reactive power | INT32 | ABCD | var | Read | |||
| HR | 5934doc 0x172E | Signed phase3 reactive power | INT32 | ABCD | var | Read | |||
| HR | 28673doc 0x7001 | Current phase 1 - 2nd harmonic (percentage) | UINT16 | × 0.1 | % | Read | |||
| HR | 28721doc 0x7031 | Current phase 1 - 50th harmonic (percentage) | UINT16 | × 0.1 | % | Read | |||
| HR | 28737doc 0x7041 | Current phase 2 - 2nd harmonic (percentage) | UINT16 | × 0.1 | % | Read | |||
| HR | 28785doc 0x7071 | Current phase 2 - 50th harmonic (percentage) | UINT16 | × 0.1 | % | Read | |||
| HR | 28801doc 0x7081 | Current phase 3 - 2nd harmonic (percentage) | UINT16 | × 0.1 | % | Read | |||
| HR | 28849doc 0x70B1 | Current phase 3 - 50th harmonic (percentage) | UINT16 | × 0.1 | % | Read | |||
| HR | 28913doc 0x70F1 | Voltage phase 1 (V12) - 50th harmonic (percentage) | UINT16 | × 0.1 | % | Read | |||
| HR | 28929doc 0x7101 | Voltage phase 2 (V23) - 2nd harmonic (percentage) | UINT16 | × 0.1 | % | Read | |||
| HR | 28977doc 0x7131 | Voltage phase 2 (V23) - 50th harmonic (percentage) | UINT16 | × 0.1 | % | Read | |||
| HR | 28993doc 0x7141 | Voltage phase 3 (V31) - 2nd harmonic (percentage) | UINT16 | × 0.1 | % | Read | |||
| HR | 29041doc 0x7171 | Voltage phase 3 (V31) - 50th harmonic (percentage) | UINT16 | × 0.1 | % | Read | |||
| HR | 29184doc 0x7200 | Current phase 1 - fundamental (rms) | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 29282doc 0x7262 | Current phase 1 - 50th harmonic (rms) | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 29312doc 0x7280 | Current phase 2 - fundamental (rms) | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 29440doc 0x7300 | Current phase 3 - fundamental (rms) | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 29568doc 0x7380 | Voltage phase 1 (V12) - fundamental (rms) | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 29666doc 0x73E2 | Voltage phase 1 (V12) - 50th harmonic (rms) | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 29696doc 0x7400 | Voltage phase 2 (V23) - fundamental (rms) | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 29794doc 0x7462 | Voltage phase 2 (V23) - 50th harmonic (rms) | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 29824doc 0x7480 | Voltage phase 3 (V31) - fundamental (rms) | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 29922doc 0x74E2 | Voltage phase 3 (V31) - 50th harmonic (rms) | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 29952doc 0x7500 | THD I1 | UINT16 | × 0.1 | % | Read | |||
| HR | 29953doc 0x7501 | THD I2 | UINT16 | × 0.1 | % | Read | |||
| HR | 29954doc 0x7502 | THD I3 | UINT16 | × 0.1 | % | Read | |||
| HR | 29955doc 0x7503 | THD V1 (V12) | UINT16 | × 0.1 | % | Read | |||
| HR | 29956doc 0x7504 | THD V2 (V23) | UINT16 | × 0.1 | % | Read | |||
| HR | 29957doc 0x7505 | THD V3 (V31) | UINT16 | × 0.1 | % | Read |
Notes on this map
- Double-word values (UD_WORD/SD_WORD) are sent most significant word first; the protocol notes the meter can be set to big endian, little endian or swapped words, so check that setting if values look wrong.
- Left out: power and energy registers whose unit is footnote (3) or (4); their scale depends on the CT x VT ratio (for example W/100 below a ratio product of 5000). The 0x15xx/0x17xx blocks give the same quantities in fixed units (W, var, Wh plus MWh).
- Left out: setup parameters, device configuration words, the per-slot data areas, and any row whose printed unit does not fit the quantity (for example apparent power printed in W).
- Energy in fixed units is split in two double words: a low part in Wh (varh) and a high part in MWh (Mvarh); total = high x 1,000,000 + low.
- Left out: the printed last-harmonic addresses 0x72E4 and 0x7364 for phase 2 and 3 current, because they break the two-word step used everywhere else in the harmonic tables (0x72E2/0x7362 would be expected).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the IME Nemo D4-Le with Rogowski coil input (KRNEMOD4)
What Modbus registers does the IME Nemo D4-Le with Rogowski coil input (KRNEMOD4) have?
This map lists 149 registers: 149 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the IME Nemo D4-Le with Rogowski coil input (KRNEMOD4) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are the hex word addresses sent as 'first WORD address' in the function 03 request, so they go on the wire unchanged.
What byte order does the IME Nemo D4-Le with Rogowski coil input (KRNEMOD4) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the IME Nemo D4-Le with Rogowski coil input (KRNEMOD4)?
Start with HR 4096 Phase 1: phase voltage (Phase 1 voltage); HR 4102 Phase 1: current (Phase 1 current); HR 4134 Frequency (Frequency); HR 4132 3-phase: power factor (3-phase power factor); HR 5400 Signed 3-ph Active Power (Signed 3-phase active power); HR 5376 Positive Active Energy - Low (Positive active energy (Wh part)); HR 5378 Positive Active Energy - High (Positive active energy (MWh part)).
How do I enable Modbus control of the IME Nemo D4-Le with Rogowski coil input (KRNEMOD4)?
Set the address, baud rate and parity on the meter (both are programmable). Only functions 03 and 0x10 are used. Setup writes need the unlock key 0x5AA5 written to 0x2700 first.
Where is the official IME Nemo D4-Le with Rogowski coil input (KRNEMOD4) Modbus documentation?
The source is Communication Modbus protocol PR140 - KRNEMOD4 Nemo D4-Le Rogowski coil input (PR140 rev. B), revision 2016-10-20, published free by IME at https://assets.legrand.com/pim/NP-FT-GT/PR140FR.pdf.
More IME Modbus register maps
- Energy meter (DIN-rail, single-phase)
IME Conto D1 single-phase energy meter (CE111)
IME Conto D1 single-phase meter, code CE111, per protocol PR133 (2025-02-24).
Also known as: CE111, Conto D1 - Power meter
IME Nemo 72Le multifunction meter (MF724)
IME Nemo 72Le 72x72 panel meter MF724 with RS-485, per protocol PR141 (software 1.04).
Also known as: MF724, Nemo 72Le - Power meter
IME Nemo 96HD multifunction meter (MF96001 / MF96021)
IME Nemo 96HD panel meters MF96001 and MF96021 with an RS-485 module, per protocol PR106 (software 3.18).
Also known as: MF96001, MF96021, Nemo 96HD - Power meter
IME Nemo 96HDe multifunction meter (MF96E06)
IME Nemo 96HDe panel meter MF96E06 with RS-485, per protocol PR145.
Also known as: MF96E06, Nemo 96HDe - Power meter
IME Nemo 96HDLe multifunction meter (MF964)
IME Nemo 96HDLe panel meter MF964 with RS-485, per protocol PR130 (software 5.08).
Also known as: MF964, Nemo 96HDLe - Power meter
IME Nemo 96HDLe with Rogowski coil input (KRNEMOHD)
IME Nemo 96HDLe for Rogowski coils, code KRNEMOHD, per protocol PR139 (software 1.03).
Also known as: KRNEMOHD - Power meter (DIN-rail)
IME Nemo D4-Le multifunction meter (MFD44)
IME Nemo D4-Le DIN-rail meter MFD44 with RS-485, per protocol PR129 (software 2.05).
Also known as: MFD44, Nemo D4-Le
Other power & energy meters register maps
- Energy meter
inepro Metering PRO380-Eichrecht three-phase energy meter
PRO380-Eichrecht direct-connected 3x230/400 V, 40 A meter (MID + German MessEV calibration law, for EV chargers), user manual version 1.45, September 2025.
Also known as: PRO380 Eichrecht, PRO380-E, inepro PRO380 Eichrecht - Power meter (power quality analyser)
Janitza UMG 512-PRO power quality analyser (Modbus RTU / Modbus TCP)
UMG 512-PRO power quality analyser, per address list 1.054.016.3.k (08/2023).
Also known as: UMG512-PRO, UMG 512, UMG512, UMG 512 PRO, Janitza UMG512-PRO - Power meter (power analyser)
Janitza UMG 96RM-E power analyser (Ethernet, Modbus TCP / RTU)
UMG 96RM-E from firmware 3.01 / hardware release 104, per address list 1.040.085.8.n (06/2024).
Also known as: UMG96RM-E, UMG 96 RM-E, UMG96RME, Janitza UMG96RM-E - Energy meter
Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus)
Legrand 2-module DIN energy meters cat. no. 046 77 and 046 79 with RS485 (Modbus/JBUS), per the 'Communication protocol' sheet dated 01/07/2011.
Also known as: 04677, 04679, 046 77, 046 79, Legrand 4 677, Legrand 4 679 - Power meter (panel network parameter meter)
Lumel ND31LITE network parameter meter
Lumel ND31LITE panel meter with RS-485 Modbus RTU, per user manual ND31LITE-09.
Also known as: ND31LITE - Power meter
Northern Design Cube & Rail IP Meter (Ethernet, Modbus TCP)
V2 Ethernet versions of the Cube 350I, Cube 350V, Cube 400I and Cube 400V (label 'IP.Ver: V2') and the Rail 350V, per manual revision 1.07p (December 2013).
Also known as: Cube 350I IP, Cube 350V IP, Cube 400I IP, Cube 400V IP, Rail 350V IP, Cube IP meter V2
All power & energy meters Modbus register maps →
Source: Communication Modbus protocol PR140 - KRNEMOD4 Nemo D4-Le Rogowski coil input · PR140 rev. B · rev. 2016-10-20. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.