Power meter · Modbus register map

IME Nemo 96HD multifunction meter (MF96001 / MF96021) Modbus register map

Updated 17 November 2026

Short answer

The Nemo 96HD is a modular 96x96 multifunction meter; with an RS-485 module it speaks Modbus/JBUS with functions 03 and 0x10. This map lists the integer measurement registers with fixed units: voltages and currents in mV/mA, power factor, frequency, THD and status values.

This page lists 40 Modbus registers for the IME Nemo 96HD multifunction meter (MF96001 / MF96021) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from IME’s own free documentation (linked below) and checked against it.

Manufacturer
IME
Model
Nemo 96HD multifunction meter (MF96001 / MF96021)
Equipment type
Power meter
Registers
40 (0 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
hexadecimal, 0-based
32-bit word order
ABCD high word first (big-endian)
Also known as
MF96001, MF96021, Nemo 96HD
Source document
Communication Modbus protocol PR106 - MF96001/021 Nemo 96HD · PR106 rev. B · rev. 2016-10-20
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: IME Nemo 96HD multifunction meter (MF96001 / MF96021)

Integration in brief

Read holding registers (function 03) from 0x1000 for voltages and currents in mV/mA, power factor, frequency and THD. Double words are high word first.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 4096Phase 1: phase voltageUINT32 ABCDPhase 1 voltageRead
HR 4102Phase 1: currentUINT32 ABCDPhase 1 currentRead
HR 4134FrequencyUINT16FrequencyRead
HR 41323-phase: power factorINT163-phase power factorRead

Enable Modbus control & writes

Set the address, baud rate and parity on the meter (both are programmable). Only functions 03 and 0x10 are used. Setup writes need the unlock key 0x5AA5 written to 0x2700 first.

Byte order & addressing

Network setup

Watch out for

IME Nemo 96HD multifunction meter (MF96001 / MF96021) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

40 of 40 shown
IME Nemo 96HD multifunction meter (MF96001 / MF96021) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR4096doc 0x1000Phase 1: phase voltageUINT32ABCD× 0.001VRead
HR4098doc 0x1002Phase 2: phase voltageUINT32ABCD× 0.001VRead
HR4100doc 0x1004Phase 3: phase voltageUINT32ABCD× 0.001VRead
HR4102doc 0x1006Phase 1: currentUINT32ABCD× 0.001ARead
HR4104doc 0x1008Phase 2: currentUINT32ABCD× 0.001ARead
HR4106doc 0x100aPhase 3: currentUINT32ABCD× 0.001ARead
HR4108doc 0x100cNeutral currentUINT32ABCD× 0.001ARead
HR4110doc 0x100eChained voltage: L1-L2UINT32ABCD× 0.001VRead
HR4112doc 0x1010Chained voltage: L2-L3UINT32ABCD× 0.001VRead
HR4114doc 0x1012Chained voltage: L3-L1UINT32ABCD× 0.001VRead
HR4132doc 0x10243-phase: power factorINT16× 0.01Read
HR4133doc 0x10253-phase: sector of power factor (cap or ind)UINT16Read0 = PF = 1; 1 = Inductive; 2 = Capacitive
HR4134doc 0x1026FrequencyUINT16× 0.1HzRead
HR4139doc 0x102bTime counter for average powerUINT16minRead
HR4164doc 0x1044Phase 1: power factorINT16× 0.01Read
HR4165doc 0x1045Phase 2: power factorINT16× 0.01Read
HR4166doc 0x1046Phase 3: power factorINT16× 0.01Read
HR4167doc 0x1047Phase 1: power factor sectorUINT16Read0 = PF = 1; 1 = Inductive; 2 = Capacitive
HR4168doc 0x1048Phase 2: power factor sectorUINT16Read0 = PF = 1; 1 = Inductive; 2 = Capacitive
HR4169doc 0x1049Phase 3: power factor sectorUINT16Read0 = PF = 1; 1 = Inductive; 2 = Capacitive
HR4170doc 0x104aPhase 1: THD V1UINT16× 0.1%Read
HR4171doc 0x104bPhase 2: THD V2UINT16× 0.1%Read
HR4172doc 0x104cPhase 3: THD V3UINT16× 0.1%Read
HR4173doc 0x104dPhase 1: THD I1UINT16× 0.1%Read
HR4174doc 0x104ePhase 2: THD I2UINT16× 0.1%Read
HR4175doc 0x104fPhase 3: THD I3UINT16× 0.1%Read
HR4176doc 0x1050Phase 1: I1 averageUINT32ABCD× 0.001ARead
HR4178doc 0x1052Phase 2: I2 averageUINT32ABCD× 0.001ARead
HR4180doc 0x1054Phase 3: I3 averageUINT32ABCD× 0.001ARead
HR4182doc 0x1056Phase 1: I1 peak maximumUINT32ABCD× 0.001ARead
HR4184doc 0x1058Phase 2: I2 peak maximumUINT32ABCD× 0.001ARead
HR4186doc 0x105aPhase 3: I3 peak maximumUINT32ABCD× 0.001ARead
HR4188doc 0x105c(I1+I2+I3)/3UINT32ABCD× 0.001ARead
HR4190doc 0x105ePhase 1: V1 minUINT32ABCD× 0.001VRead
HR4192doc 0x1060Phase 2: V2 minUINT32ABCD× 0.001VRead
HR4194doc 0x1062Phase 3: V3 minUINT32ABCD× 0.001VRead
HR4196doc 0x1064Phase 1: V1 maxUINT32ABCD× 0.001VRead
HR4198doc 0x1066Phase 2: V2 maxUINT32ABCD× 0.001VRead
HR4200doc 0x1068Phase 3: V3 maxUINT32ABCD× 0.001VRead
HR4613doc 0x1205Voltages sequence diagnosticUINT16Read1 = OK; 2 = Error

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the IME Nemo 96HD multifunction meter (MF96001 / MF96021)

What Modbus registers does the IME Nemo 96HD multifunction meter (MF96001 / MF96021) have?

This map lists 40 registers: 40 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the IME Nemo 96HD multifunction meter (MF96001 / MF96021) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are the hex word addresses sent as 'first WORD address' in the function 03 request, so they go on the wire unchanged.

What byte order does the IME Nemo 96HD multifunction meter (MF96001 / MF96021) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the IME Nemo 96HD multifunction meter (MF96001 / MF96021)?

Start with HR 4096 Phase 1: phase voltage (Phase 1 voltage); HR 4102 Phase 1: current (Phase 1 current); HR 4134 Frequency (Frequency); HR 4132 3-phase: power factor (3-phase power factor).

How do I enable Modbus control of the IME Nemo 96HD multifunction meter (MF96001 / MF96021)?

Set the address, baud rate and parity on the meter (both are programmable). Only functions 03 and 0x10 are used. Setup writes need the unlock key 0x5AA5 written to 0x2700 first.

Where is the official IME Nemo 96HD multifunction meter (MF96001 / MF96021) Modbus documentation?

The source is Communication Modbus protocol PR106 - MF96001/021 Nemo 96HD (PR106 rev. B), revision 2016-10-20, published free by IME at https://assets.legrand.com/pim/NP-FT-GT/PR106FR.pdf.

More IME Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Communication Modbus protocol PR106 - MF96001/021 Nemo 96HD · PR106 rev. B · rev. 2016-10-20. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.