- Excel XR series electronic metering pump (Modbus RTU)
Pump (chemical metering pump) · Modbus register map
LMI Excel XR series electronic metering pump (Modbus RTU) Modbus register map
Updated 19 November 2026
The Excel XR is a stepper-driven chemical metering pump from LMI (Milton Roy). Its Modbus RTU version exposes coils for on/off, prime and mode selection, holding registers for flow setpoints and I/O configuration, input registers for live flow, analog I/O and totalizers, and discrete inputs for status and alarms. This map covers the control, live-value and alarm points plus the main mode settings.
This page lists 104 Modbus registers for the LMI Excel XR series electronic metering pump (Modbus RTU) — 50 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from LMI’s own free documentation (linked below) and checked against it.
- Manufacturer
- LMI
- Model
- Excel XR series electronic metering pump (Modbus RTU)
- Equipment type
- Pump (chemical metering pump)
- Registers
- 104 (50 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- Excel XR, LMI Excel XR, Milton Roy Excel XR, Excel XR Modbus
Integration notes: LMI Excel XR series electronic metering pump (Modbus RTU)
Set slave address, bit rate, parity and stop bits on the pump's Communication Settings screen. Read input register 3 for live flow and discrete inputs 1 and 101 for running and global alarm; set the flow with holding register 1 and start/stop with coil 1.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 2 | Current flow rate | UINT16 | Current flow rate | Read |
| IR 3 | Flow percentage | UINT16 | Flow percentage | Read |
| DI 0 | Running status | BIT | Running status | Read |
| DI 100 | Global alarm | BIT | Global alarm | Read |
| HR 0 | Flow rate for manual mode | UINT16 | Manual mode flow setpoint | Read/write |
| CO 0 | On/Off | BIT | On/off toggle | Read/write |
| CO 5 | Manual operation mode | BIT | Select manual mode | Read/write |
Enable Modbus control & writes
Modbus settings are on the pump display under Settings > Communication Settings: slave address 1-125, bit rate 9600/19200/38400/115200 or Auto, parity none/even/odd, 1 or 2 stop bits, internal line termination on/off.
Byte order & addressing
- Coil 1 toggles on/off rather than setting a state; read discrete input 1 to know the result.
- Flow values are four-digit integers with two implied decimals (1234 = 12.34).
Network setup
- With Auto bit rate the pump hunts for the speed, so the first messages may fail; set the rate explicitly when known.
- Enable internal termination on the last device on the bus. Connection is an M12 5-pin B-coded connector (pin 2 D0, pin 4 D1, pin 3 DGND).
Watch out for
- Function code 07 (read exception status) and 17 (report server ID) are also supported.
LMI Excel XR series electronic metering pump (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 1 (0x0001) | On/Off | Write ON to toggle the pump on/off state. | BIT | Read/write | ||||
| CO | 1doc 2 (0x0002) | Prime | ON starts the prime sequence, OFF ends it. | BIT | Read/write | ||||
| CO | 2doc 3 (0x0003) | 100 % run | ON runs the pump at 100 %. | BIT | Read/write | ||||
| CO | 3doc 4 (0x0004) | Force internal/external mode | ON forces internal control mode, OFF external. | BIT | Read/write | ||||
| CO | 4doc 5 (0x0005) | Force home screen | BIT | Read/write | |||||
| CO | 5doc 6 (0x0006) | Manual operation mode | ON selects manual mode. | BIT | Read/write | ||||
| CO | 6doc 7 (0x0007) | Analog operation mode | ON selects analog (mA) mode. | BIT | Read/write | ||||
| CO | 7doc 8 (0x0008) | Pulse operation mode | ON selects pulse mode. | BIT | Read/write | ||||
| CO | 8doc 9 (0x0009) | Batch operation mode | ON selects batch mode. | BIT | Read/write | ||||
| CO | 9doc 10 (0x000A) | Cycle timer operation mode | ON selects cycle timer mode. | BIT | Read/write | ||||
| CO | 10doc 11 (0x000B) | Timed event operation mode | ON selects timed event mode. | BIT | Read/write | ||||
| CO | 11doc 12 (0x000C) | Slow mode | ON enables slow mode. | BIT | Read/write | ||||
| CO | 12doc 13 (0x000D) | Metric/English units | ON = metric, OFF = English units. | BIT | Read/write | ||||
| CO | 13doc 14 (0x000E) | Reset user totalizer | ON resets the user totalizer. | BIT | Read/write | ||||
| CO | 15doc 16 (0x0010) | Start batch | ON starts a batch. | BIT | Read/write | ||||
| DI | 0doc 1 (0x0001) | Running status | 1 = running. | BIT | Read | ||||
| DI | 1doc 2 (0x0002) | Internal/external operating mode | 0 = internal, 1 = external. | BIT | Read | ||||
| DI | 2doc 3 (0x0003) | Tank low | BIT | Read | |||||
| DI | 3doc 4 (0x0004) | Tank empty | BIT | Read | |||||
| DI | 4doc 5 (0x0005) | Manual mode | BIT | Read | |||||
| DI | 5doc 6 (0x0006) | Analog mode | BIT | Read | |||||
| DI | 6doc 7 (0x0007) | Pulse mode | BIT | Read | |||||
| DI | 7doc 8 (0x0008) | Batch mode | BIT | Read | |||||
| DI | 8doc 9 (0x0009) | Cycle timer mode | BIT | Read | |||||
| DI | 9doc 10 (0x000A) | Timed event mode | BIT | Read | |||||
| DI | 10doc 11 (0x000B) | 100 % mode | BIT | Read | |||||
| DI | 11doc 12 (0x000C) | Prime mode | BIT | Read | |||||
| DI | 12doc 13 (0x000D) | Slow mode | BIT | Read | |||||
| DI | 13doc 14 (0x000E) | Metric/English units | 0 = English, 1 = metric. | BIT | Read | ||||
| DI | 14doc 15 (0x000F) | Pump calibrated | BIT | Read | |||||
| DI | 15doc 16 (0x0010) | Keypad locked | BIT | Read | |||||
| DI | 16doc 17 (0x0011) | Digital output 1 | 1 = switched. | BIT | Read | ||||
| DI | 17doc 18 (0x0012) | Digital output 2 | 1 = switched. | BIT | Read | ||||
| DI | 18doc 19 (0x0013) | Digital input 1 | 1 = switched. | BIT | Read | ||||
| DI | 19doc 20 (0x0014) | Digital input 2 | 1 = switched. | BIT | Read | ||||
| DI | 20doc 21 (0x0015) | Digital input 3 | 1 = switched. | BIT | Read | ||||
| DI | 21doc 22 (0x0016) | Digital input 4 | 1 = switched. | BIT | Read | ||||
| DI | 23doc 24 (0x0018) | Batch mode dosing | BIT | Read | |||||
| DI | 100doc 101 (0x0065) | Global alarm | ON if any alarm is active. | BIT | Read | ||||
| DI | 101doc 102 (0x0066) | User alarm | BIT | Read | |||||
| DI | 102doc 103 (0x0067) | Tank empty alarm | BIT | Read | |||||
| DI | 103doc 104 (0x0068) | Tank low alarm | BIT | Read | |||||
| DI | 104doc 105 (0x0069) | Internal system error alarm | BIT | Read | |||||
| DI | 105doc 106 (0x006A) | Motor stall alarm | BIT | Read | |||||
| DI | 106doc 107 (0x006B) | Analog loss of signal alarm | BIT | Read | |||||
| DI | 107doc 108 (0x006C) | Analog overrange alarm | BIT | Read | |||||
| DI | 108doc 109 (0x006D) | Motor homing error alarm | BIT | Read | |||||
| DI | 109doc 110 (0x006E) | Pulse signal not present alarm | BIT | Read | |||||
| DI | 110doc 111 (0x006F) | Pulse signal overrange alarm | BIT | Read | |||||
| IR | 0doc 1 (0x0001) | Model ID | Output code for pump size. | UINT16 | Read | 2 = 5.6 GPH (21.2 l/h) 175 psi; 3 = 14.0 GPH (53.0 l/h) 75 psi; 4 = 18.0 GPH (68.1 l/h) 50 psi | |||
| IR | 2doc 3 (0x0003) | Current flow rate | Flow in GPH or L/h (per the units setting), two decimals. 0000-9999. | UINT16 | × 0.01 | Read | |||
| IR | 3doc 4 (0x0004) | Flow percentage | 0.00-100.00 %. | UINT16 | × 0.01 | % | Read | ||
| IR | 4doc 5 (0x0005) | Analog input 1 | 0.0-20.0 mA. | UINT16 | × 0.1 | mA | Read | ||
| IR | 5doc 6 (0x0006) | Analog input 2 | 0.0-20.0 mA. | UINT16 | × 0.1 | mA | Read | ||
| IR | 6doc 7 (0x0007) | Analog output | 0.0-20.0 mA. | UINT16 | × 0.1 | mA | Read | ||
| IR | 7doc 8 (0x0008) | Totalizer user strokes | UINT32 | ABCD | Read | ||||
| IR | 9doc 10 (0x000A) | Totalizer user volume | Gallons or litres per the units setting. | UINT64 | ABCD | Read | |||
| IR | 13doc 14 (0x000E) | Totalizer user hours | Motor run hours. | UINT32 | ABCD | h | Read | ||
| IR | 15doc 16 (0x0010) | Totalizer user power cycles | UINT16 | Read | |||||
| IR | 16doc 17 (0x0011) | Totalizer unit strokes | Lifetime count. | UINT32 | ABCD | Read | |||
| IR | 18doc 19 (0x0013) | Totalizer unit volume | Lifetime; gallons or litres per the units setting. | UINT64 | ABCD | Read | |||
| IR | 22doc 23 (0x0017) | Totalizer unit hours | Lifetime motor run hours. | UINT32 | ABCD | h | Read | ||
| IR | 24doc 25 (0x0019) | Totalizer unit power cycles | UINT16 | Read | |||||
| IR | 25doc 26 (0x001A) | Calibrated volume | Volume of one stroke from calibration. | UINT16 | × 0.01 | mL | Read | ||
| IR | 26doc 27 (0x001B) | Batch mode remaining volume | Gallons or litres per the units setting. | UINT32 | ABCD | Read | |||
| IR | 28doc 29 (0x001D) | Batch mode remaining dosing time | UINT32 | ABCD | s | Read | |||
| IR | 30doc 31 (0x001F) | Cycle mode startup delay left | UINT32 | ABCD | s | Read | |||
| IR | 32doc 33 (0x0021) | Cycle mode run time left | UINT32 | ABCD | s | Read | |||
| IR | 39doc 40 (0x0028) | Main firmware version | Read as hex digits X.X.X.X. | UINT16 | Read | ||||
| HR | 0doc 1 (0x0001) | Flow rate for manual mode | Flow in GPH or L/h (per the units setting), two decimals. 0000-9999. | UINT16 | × 0.01 | Read/write | |||
| HR | 1doc 2 (0x0002) | Flow rate for prime mode | Flow in GPH or L/h (per the units setting), two decimals. | UINT16 | × 0.01 | Read/write | |||
| HR | 2doc 3 (0x0003) | Prime mode duration | 1-3600 s. | UINT16 | s | Read/write | |||
| HR | 3doc 4 (0x0004) | Power loss mode | UINT16 | Read/write | 0 = Resume operation; 1 = Stay idle; 2 = Run at configured speed | ||||
| HR | 4doc 5 (0x0005) | Power loss resume speed | Flow in GPH or L/h (per the units setting), two decimals. | UINT16 | × 0.01 | Read/write | |||
| HR | 5doc 6 (0x0006) | Slow mode setpoint | 10-90 % in steps of 10. | UINT16 | % | Read/write | |||
| HR | 11doc 12 (0x000C) | Pulse mode count | Pulses received per delivery, 1-10000. | UINT16 | Read/write | ||||
| HR | 18doc 19 (0x0013) | Batch mode time | Dosing time for batch mode, 1-86400 s. | UINT32 | ABCD | s | Read/write | ||
| HR | 23doc 24 (0x0018) | Analog mode P1 flow | Flow in GPH or L/h (per the units setting), two decimals. | UINT16 | × 0.01 | Read/write | |||
| HR | 24doc 25 (0x0019) | Analog mode P1 current | 0.0-20.0 mA. | UINT16 | × 0.1 | mA | Read/write | ||
| HR | 25doc 26 (0x001A) | Analog mode P2 flow | Flow in GPH or L/h (per the units setting), two decimals. | UINT16 | × 0.01 | Read/write | |||
| HR | 26doc 27 (0x001B) | Analog mode P2 current | 0.0-20.0 mA. | UINT16 | × 0.1 | mA | Read/write | ||
| HR | 27doc 28 (0x001C) | Cycle mode cycle time | 1-1439 min. | UINT16 | min | Read/write | |||
| HR | 28doc 29 (0x001D) | Cycle mode duration | Inactive period, 1-1439 min. | UINT16 | min | Read/write | |||
| HR | 29doc 30 (0x001E) | Cycle mode delay | First inactive period before cycling, 0-1439 min. | UINT16 | min | Read/write | |||
| HR | 30doc 31 (0x001F) | Cycle mode flow | Flow in GPH or L/h (per the units setting), two decimals. | UINT16 | × 0.01 | Read/write | |||
| HR | 56doc 57 (0x0039) | Digital input 1 config | UINT16 | Read/write | 0 = Disabled; 1 = Remote on/off; 2 = Float switch empty; 3 = Float switch low; 4 = Remote internal/external mode; 5 = Pacing pulse | ||||
| HR | 57doc 58 (0x003A) | Digital input 1 contact state | UINT16 | Read/write | 0 = Normally open; 1 = Normally closed | ||||
| HR | 58doc 59 (0x003B) | Digital input 2 config | UINT16 | Read/write | 0 = Disabled; 1 = Remote on/off; 2 = Float switch empty; 3 = Float switch low; 4 = Remote internal/external mode; 5 = Pacing pulse | ||||
| HR | 59doc 60 (0x003C) | Digital input 2 contact state | UINT16 | Read/write | 0 = Normally open; 1 = Normally closed | ||||
| HR | 60doc 61 (0x003D) | Digital input 3 config | UINT16 | Read/write | 0 = Disabled; 1 = Remote on/off; 2 = Float switch empty; 3 = Float switch low; 4 = Remote internal/external mode; 5 = Pacing pulse | ||||
| HR | 61doc 62 (0x003E) | Digital input 3 contact state | UINT16 | Read/write | 0 = Normally open; 1 = Normally closed | ||||
| HR | 62doc 63 (0x003F) | Digital input 4 config | UINT16 | Read/write | 0 = Disabled; 1 = Remote on/off; 2 = Float switch empty; 3 = Float switch low; 4 = Remote internal/external mode; 5 = Pacing pulse | ||||
| HR | 63doc 64 (0x0040) | Digital input 4 contact state | UINT16 | Read/write | 0 = Normally open; 1 = Normally closed | ||||
| HR | 64doc 65 (0x0041) | Analog input 1 config | UINT16 | Read/write | 0 = Disabled; 1 = Pacing; 2 = Level | ||||
| HR | 65doc 66 (0x0042) | Analog input 2 config | UINT16 | Read/write | 0 = Disabled; 1 = Pacing; 2 = Level | ||||
| HR | 66doc 67 (0x0043) | Digital output 1 config | UINT16 | Read/write | 0 = Disabled; 1 = Stroke pulse; 2 = Pump running; 3 = Pump standby; 4 = Alarm out; 5 = Internal/external mode; 6 = User alarm out; 7 = Pump stopped; 8 = Timed event | ||||
| HR | 67doc 68 (0x0044) | Digital output 1 contact state | UINT16 | Read/write | 0 = Normally open; 1 = Normally closed | ||||
| HR | 68doc 69 (0x0045) | Digital output 2 config | UINT16 | Read/write | 0 = Disabled; 1 = Stroke pulse; 2 = Pump running; 3 = Pump standby; 4 = Alarm out; 5 = Internal/external mode; 6 = User alarm out; 7 = Pump stopped; 8 = Timed event | ||||
| HR | 69doc 70 (0x0046) | Digital output 2 contact state | UINT16 | Read/write | 0 = Normally open; 1 = Normally closed | ||||
| HR | 70doc 71 (0x0047) | Analog output config | UINT16 | Read/write | 0 = Disabled; 1 = Flow; 2 = Mirror input | ||||
| HR | 71doc 72 (0x0048) | Remote internal mode | Mode used under internal control. | UINT16 | Read/write | 0 = Manual; 1 = Cycle timer; 2 = Weekly timer | |||
| HR | 72doc 73 (0x0049) | Remote external mode | Mode used under external control. | UINT16 | Read/write | 0 = mA; 1 = Pulse; 2 = Batch | |||
| HR | 73doc 74 (0x004A) | Keypad lock style | UINT16 | Read/write | 1 = No lock; 2 = All lock; 3 = All lock, power unlock; 4 = All lock, password | ||||
| HR | 75doc 76 (0x004C) | User alarm mask | Set a bit to route that alarm to the user alarm. | BITMAP16 | Read/write | bit 2 = Tank empty; bit 3 = Tank low; bit 4 = Internal system error; bit 5 = Motor stall; bit 6 = Analog loss of signal; bit 7 = Analog overrange; bit 8 = Motor homing error; bit 9 = Pulse signal not present; bit 10 = Pulse signal overrange |
Notes on this map
- LMI does not host this manual publicly as far as we could find; the linked copy is the unaltered LMI manual hosted by a distributor (Pumpworld).
- Multi-register values: the manual states the first register holds the high-order value, so 32- and 64-bit counters are high word first (ABCD).
- Pulse mode volume (13-14) and batch mode volume (17-18) are left out: the manual gives a decimal range for a two-register integer but no scale.
- Timed event, RTC, password and stay-prime registers are left out; stay-prime remaining time and weekly event time have no stated units or length conflicts.
- Flow values are in GPH or L/h and volumes in gallons or litres depending on the units setting (coil 13 / discrete input 14).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the LMI Excel XR series electronic metering pump (Modbus RTU)
What Modbus registers does the LMI Excel XR series electronic metering pump (Modbus RTU) have?
This map lists 104 registers: 15 coils, 34 discrete inputs, 20 input registers, 35 holding registers. 50 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the LMI Excel XR series electronic metering pump (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Every table says PLC addressing (base 1) is used and lists each point as decimal and hex (holding register 1 = 0x0001). Request address n-1 on the wire: manual flow rate (1) is wire address 0.
What byte order does the LMI Excel XR series electronic metering pump (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the LMI Excel XR series electronic metering pump (Modbus RTU)?
Start with IR 2 Current flow rate (Current flow rate); IR 3 Flow percentage (Flow percentage); DI 0 Running status (Running status); DI 100 Global alarm (Global alarm); HR 0 Flow rate for manual mode (Manual mode flow setpoint); CO 0 On/Off (On/off toggle); CO 5 Manual operation mode (Select manual mode).
How do I enable Modbus control of the LMI Excel XR series electronic metering pump (Modbus RTU)?
Modbus settings are on the pump display under Settings > Communication Settings: slave address 1-125, bit rate 9600/19200/38400/115200 or Auto, parity none/even/odd, 1 or 2 stop bits, internal line termination on/off.
Where is the official LMI Excel XR series electronic metering pump (Modbus RTU) Modbus documentation?
The source is Excel XR Series Electronic Metering Pump Modbus RTU Manual (55312 Rev 04), revision 2020-03. LMI doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.pumpworld.com/assets/lmi-excel-xr-chemical-pump-modbus-manual.pdf. It may be an older revision, so check it against the live unit.
Other power & energy meters register maps
- Energy meter (DIN-rail, single-phase, MID)
Lumel NMID11 / NMID12 / NMID13 single-phase energy meter
Modbus RTU versions of the NMID11, NMID12 and NMID13 meters (NMID11/NMID13 are the CT-connected models); the LITE and MBUS versions have no Modbus port.
Also known as: NMID11, NMID12, NMID13 - Power meter
Northern Design Cube 350 panel power meter (Modbus RTU option)
Cube 350 three-phase panel meters fitted with the RS-485 Modbus option, per the June 2010 comms manual.
Also known as: Cube350, ND Cube 350, Northern Design Cube350 - Energy meter module
Peacefair PZEM-014 / PZEM-016
Peacefair PZEM-014 (10 A shunt) and PZEM-016 (100 A CT) single-phase AC RS485 modules; the PZEM-004T V3.0 (TTL UART) datasheet prints the identical register map.
Also known as: PZEM-014, PZEM-016, PZEM-004T V3.0, PZEM-004T-10A, PZEM-004T-100A - Power meter
Rishabh Instruments RISH Delta Power NX multifunction power meter
Rishabh RISH Delta Power NX programmable panel meters with RS-485 Modbus RTU, per operating manual AMAN-00IM-0117 Rev. E.
Also known as: RISH Delta Power NX, Delta Power NX, RISH Delta Power - Energy meter
Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter
Rishabh RISH EM 3490 DS dual-source energy meters (separate utility and generator energy) with RS-485 Modbus, per manual Rev G.
Also known as: RISH EM 3490 DS, EM3490DS, EM 3490DS - Power meter
Rishabh Instruments RISH LM 1380 multifunction meter
Rishabh RISH LM 1380 panel multifunction instruments with RS-485 Modbus, per interface definition DMAN-00IM-0925 Rev. A (04/2022).
Also known as: RISH LM 1380, LM1380
All power & energy meters Modbus register maps →
Source: Excel XR Series Electronic Metering Pump Modbus RTU Manual · 55312 Rev 04 · rev. 2020-03 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.