Easy Modbus
  1. Home
  2. Modbus register maps
  3. LMI
  4. Excel XR series electronic metering pump (Modbus RTU)

Pump (chemical metering pump) · Modbus register map

LMI Excel XR series electronic metering pump (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The Excel XR is a stepper-driven chemical metering pump from LMI (Milton Roy). Its Modbus RTU version exposes coils for on/off, prime and mode selection, holding registers for flow setpoints and I/O configuration, input registers for live flow, analog I/O and totalizers, and discrete inputs for status and alarms. This map covers the control, live-value and alarm points plus the main mode settings.

This page lists 104 Modbus registers for the LMI Excel XR series electronic metering pump (Modbus RTU) — 50 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from LMI’s own free documentation (linked below) and checked against it.

Manufacturer
LMI
Model
Excel XR series electronic metering pump (Modbus RTU)
Equipment type
Pump (chemical metering pump)
Registers
104 (50 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Also known as
Excel XR, LMI Excel XR, Milton Roy Excel XR, Excel XR Modbus
Source document
Excel XR Series Electronic Metering Pump Modbus RTU Manual · 55312 Rev 04 · rev. 2020-03 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: LMI Excel XR series electronic metering pump (Modbus RTU)

Integration in brief

Set slave address, bit rate, parity and stop bits on the pump's Communication Settings screen. Read input register 3 for live flow and discrete inputs 1 and 101 for running and global alarm; set the flow with holding register 1 and start/stop with coil 1.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 2Current flow rateUINT16Current flow rateRead
IR 3Flow percentageUINT16Flow percentageRead
DI 0Running statusBITRunning statusRead
DI 100Global alarmBITGlobal alarmRead
HR 0Flow rate for manual modeUINT16Manual mode flow setpointRead/write
CO 0On/OffBITOn/off toggleRead/write
CO 5Manual operation modeBITSelect manual modeRead/write

Enable Modbus control & writes

Modbus settings are on the pump display under Settings > Communication Settings: slave address 1-125, bit rate 9600/19200/38400/115200 or Auto, parity none/even/odd, 1 or 2 stop bits, internal line termination on/off.

Byte order & addressing

Network setup

Watch out for

LMI Excel XR series electronic metering pump (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

104 of 104 shown
LMI Excel XR series electronic metering pump (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 1 (0x0001)On/OffWrite ON to toggle the pump on/off state.BITRead/write
CO1doc 2 (0x0002)PrimeON starts the prime sequence, OFF ends it.BITRead/write
CO2doc 3 (0x0003)100 % runON runs the pump at 100 %.BITRead/write
CO3doc 4 (0x0004)Force internal/external modeON forces internal control mode, OFF external.BITRead/write
CO4doc 5 (0x0005)Force home screenBITRead/write
CO5doc 6 (0x0006)Manual operation modeON selects manual mode.BITRead/write
CO6doc 7 (0x0007)Analog operation modeON selects analog (mA) mode.BITRead/write
CO7doc 8 (0x0008)Pulse operation modeON selects pulse mode.BITRead/write
CO8doc 9 (0x0009)Batch operation modeON selects batch mode.BITRead/write
CO9doc 10 (0x000A)Cycle timer operation modeON selects cycle timer mode.BITRead/write
CO10doc 11 (0x000B)Timed event operation modeON selects timed event mode.BITRead/write
CO11doc 12 (0x000C)Slow modeON enables slow mode.BITRead/write
CO12doc 13 (0x000D)Metric/English unitsON = metric, OFF = English units.BITRead/write
CO13doc 14 (0x000E)Reset user totalizerON resets the user totalizer.BITRead/write
CO15doc 16 (0x0010)Start batchON starts a batch.BITRead/write
DI0doc 1 (0x0001)Running status1 = running.BITRead
DI1doc 2 (0x0002)Internal/external operating mode0 = internal, 1 = external.BITRead
DI2doc 3 (0x0003)Tank lowBITRead
DI3doc 4 (0x0004)Tank emptyBITRead
DI4doc 5 (0x0005)Manual modeBITRead
DI5doc 6 (0x0006)Analog modeBITRead
DI6doc 7 (0x0007)Pulse modeBITRead
DI7doc 8 (0x0008)Batch modeBITRead
DI8doc 9 (0x0009)Cycle timer modeBITRead
DI9doc 10 (0x000A)Timed event modeBITRead
DI10doc 11 (0x000B)100 % modeBITRead
DI11doc 12 (0x000C)Prime modeBITRead
DI12doc 13 (0x000D)Slow modeBITRead
DI13doc 14 (0x000E)Metric/English units0 = English, 1 = metric.BITRead
DI14doc 15 (0x000F)Pump calibratedBITRead
DI15doc 16 (0x0010)Keypad lockedBITRead
DI16doc 17 (0x0011)Digital output 11 = switched.BITRead
DI17doc 18 (0x0012)Digital output 21 = switched.BITRead
DI18doc 19 (0x0013)Digital input 11 = switched.BITRead
DI19doc 20 (0x0014)Digital input 21 = switched.BITRead
DI20doc 21 (0x0015)Digital input 31 = switched.BITRead
DI21doc 22 (0x0016)Digital input 41 = switched.BITRead
DI23doc 24 (0x0018)Batch mode dosingBITRead
DI100doc 101 (0x0065)Global alarmON if any alarm is active.BITRead
DI101doc 102 (0x0066)User alarmBITRead
DI102doc 103 (0x0067)Tank empty alarmBITRead
DI103doc 104 (0x0068)Tank low alarmBITRead
DI104doc 105 (0x0069)Internal system error alarmBITRead
DI105doc 106 (0x006A)Motor stall alarmBITRead
DI106doc 107 (0x006B)Analog loss of signal alarmBITRead
DI107doc 108 (0x006C)Analog overrange alarmBITRead
DI108doc 109 (0x006D)Motor homing error alarmBITRead
DI109doc 110 (0x006E)Pulse signal not present alarmBITRead
DI110doc 111 (0x006F)Pulse signal overrange alarmBITRead
IR0doc 1 (0x0001)Model IDOutput code for pump size.UINT16Read2 = 5.6 GPH (21.2 l/h) 175 psi; 3 = 14.0 GPH (53.0 l/h) 75 psi; 4 = 18.0 GPH (68.1 l/h) 50 psi
IR2doc 3 (0x0003)Current flow rateFlow in GPH or L/h (per the units setting), two decimals. 0000-9999.UINT16× 0.01Read
IR3doc 4 (0x0004)Flow percentage0.00-100.00 %.UINT16× 0.01%Read
IR4doc 5 (0x0005)Analog input 10.0-20.0 mA.UINT16× 0.1mARead
IR5doc 6 (0x0006)Analog input 20.0-20.0 mA.UINT16× 0.1mARead
IR6doc 7 (0x0007)Analog output0.0-20.0 mA.UINT16× 0.1mARead
IR7doc 8 (0x0008)Totalizer user strokesUINT32ABCDRead
IR9doc 10 (0x000A)Totalizer user volumeGallons or litres per the units setting.UINT64ABCDRead
IR13doc 14 (0x000E)Totalizer user hoursMotor run hours.UINT32ABCDhRead
IR15doc 16 (0x0010)Totalizer user power cyclesUINT16Read
IR16doc 17 (0x0011)Totalizer unit strokesLifetime count.UINT32ABCDRead
IR18doc 19 (0x0013)Totalizer unit volumeLifetime; gallons or litres per the units setting.UINT64ABCDRead
IR22doc 23 (0x0017)Totalizer unit hoursLifetime motor run hours.UINT32ABCDhRead
IR24doc 25 (0x0019)Totalizer unit power cyclesUINT16Read
IR25doc 26 (0x001A)Calibrated volumeVolume of one stroke from calibration.UINT16× 0.01mLRead
IR26doc 27 (0x001B)Batch mode remaining volumeGallons or litres per the units setting.UINT32ABCDRead
IR28doc 29 (0x001D)Batch mode remaining dosing timeUINT32ABCDsRead
IR30doc 31 (0x001F)Cycle mode startup delay leftUINT32ABCDsRead
IR32doc 33 (0x0021)Cycle mode run time leftUINT32ABCDsRead
IR39doc 40 (0x0028)Main firmware versionRead as hex digits X.X.X.X.UINT16Read
HR0doc 1 (0x0001)Flow rate for manual modeFlow in GPH or L/h (per the units setting), two decimals. 0000-9999.UINT16× 0.01Read/write
HR1doc 2 (0x0002)Flow rate for prime modeFlow in GPH or L/h (per the units setting), two decimals.UINT16× 0.01Read/write
HR2doc 3 (0x0003)Prime mode duration1-3600 s.UINT16sRead/write
HR3doc 4 (0x0004)Power loss modeUINT16Read/write0 = Resume operation; 1 = Stay idle; 2 = Run at configured speed
HR4doc 5 (0x0005)Power loss resume speedFlow in GPH or L/h (per the units setting), two decimals.UINT16× 0.01Read/write
HR5doc 6 (0x0006)Slow mode setpoint10-90 % in steps of 10.UINT16%Read/write
HR11doc 12 (0x000C)Pulse mode countPulses received per delivery, 1-10000.UINT16Read/write
HR18doc 19 (0x0013)Batch mode timeDosing time for batch mode, 1-86400 s.UINT32ABCDsRead/write
HR23doc 24 (0x0018)Analog mode P1 flowFlow in GPH or L/h (per the units setting), two decimals.UINT16× 0.01Read/write
HR24doc 25 (0x0019)Analog mode P1 current0.0-20.0 mA.UINT16× 0.1mARead/write
HR25doc 26 (0x001A)Analog mode P2 flowFlow in GPH or L/h (per the units setting), two decimals.UINT16× 0.01Read/write
HR26doc 27 (0x001B)Analog mode P2 current0.0-20.0 mA.UINT16× 0.1mARead/write
HR27doc 28 (0x001C)Cycle mode cycle time1-1439 min.UINT16minRead/write
HR28doc 29 (0x001D)Cycle mode durationInactive period, 1-1439 min.UINT16minRead/write
HR29doc 30 (0x001E)Cycle mode delayFirst inactive period before cycling, 0-1439 min.UINT16minRead/write
HR30doc 31 (0x001F)Cycle mode flowFlow in GPH or L/h (per the units setting), two decimals.UINT16× 0.01Read/write
HR56doc 57 (0x0039)Digital input 1 configUINT16Read/write0 = Disabled; 1 = Remote on/off; 2 = Float switch empty; 3 = Float switch low; 4 = Remote internal/external mode; 5 = Pacing pulse
HR57doc 58 (0x003A)Digital input 1 contact stateUINT16Read/write0 = Normally open; 1 = Normally closed
HR58doc 59 (0x003B)Digital input 2 configUINT16Read/write0 = Disabled; 1 = Remote on/off; 2 = Float switch empty; 3 = Float switch low; 4 = Remote internal/external mode; 5 = Pacing pulse
HR59doc 60 (0x003C)Digital input 2 contact stateUINT16Read/write0 = Normally open; 1 = Normally closed
HR60doc 61 (0x003D)Digital input 3 configUINT16Read/write0 = Disabled; 1 = Remote on/off; 2 = Float switch empty; 3 = Float switch low; 4 = Remote internal/external mode; 5 = Pacing pulse
HR61doc 62 (0x003E)Digital input 3 contact stateUINT16Read/write0 = Normally open; 1 = Normally closed
HR62doc 63 (0x003F)Digital input 4 configUINT16Read/write0 = Disabled; 1 = Remote on/off; 2 = Float switch empty; 3 = Float switch low; 4 = Remote internal/external mode; 5 = Pacing pulse
HR63doc 64 (0x0040)Digital input 4 contact stateUINT16Read/write0 = Normally open; 1 = Normally closed
HR64doc 65 (0x0041)Analog input 1 configUINT16Read/write0 = Disabled; 1 = Pacing; 2 = Level
HR65doc 66 (0x0042)Analog input 2 configUINT16Read/write0 = Disabled; 1 = Pacing; 2 = Level
HR66doc 67 (0x0043)Digital output 1 configUINT16Read/write0 = Disabled; 1 = Stroke pulse; 2 = Pump running; 3 = Pump standby; 4 = Alarm out; 5 = Internal/external mode; 6 = User alarm out; 7 = Pump stopped; 8 = Timed event
HR67doc 68 (0x0044)Digital output 1 contact stateUINT16Read/write0 = Normally open; 1 = Normally closed
HR68doc 69 (0x0045)Digital output 2 configUINT16Read/write0 = Disabled; 1 = Stroke pulse; 2 = Pump running; 3 = Pump standby; 4 = Alarm out; 5 = Internal/external mode; 6 = User alarm out; 7 = Pump stopped; 8 = Timed event
HR69doc 70 (0x0046)Digital output 2 contact stateUINT16Read/write0 = Normally open; 1 = Normally closed
HR70doc 71 (0x0047)Analog output configUINT16Read/write0 = Disabled; 1 = Flow; 2 = Mirror input
HR71doc 72 (0x0048)Remote internal modeMode used under internal control.UINT16Read/write0 = Manual; 1 = Cycle timer; 2 = Weekly timer
HR72doc 73 (0x0049)Remote external modeMode used under external control.UINT16Read/write0 = mA; 1 = Pulse; 2 = Batch
HR73doc 74 (0x004A)Keypad lock styleUINT16Read/write1 = No lock; 2 = All lock; 3 = All lock, power unlock; 4 = All lock, password
HR75doc 76 (0x004C)User alarm maskSet a bit to route that alarm to the user alarm.BITMAP16Read/writebit 2 = Tank empty; bit 3 = Tank low; bit 4 = Internal system error; bit 5 = Motor stall; bit 6 = Analog loss of signal; bit 7 = Analog overrange; bit 8 = Motor homing error; bit 9 = Pulse signal not present; bit 10 = Pulse signal overrange

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the LMI Excel XR series electronic metering pump (Modbus RTU)

What Modbus registers does the LMI Excel XR series electronic metering pump (Modbus RTU) have?

This map lists 104 registers: 15 coils, 34 discrete inputs, 20 input registers, 35 holding registers. 50 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the LMI Excel XR series electronic metering pump (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Every table says PLC addressing (base 1) is used and lists each point as decimal and hex (holding register 1 = 0x0001). Request address n-1 on the wire: manual flow rate (1) is wire address 0.

What byte order does the LMI Excel XR series electronic metering pump (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the LMI Excel XR series electronic metering pump (Modbus RTU)?

Start with IR 2 Current flow rate (Current flow rate); IR 3 Flow percentage (Flow percentage); DI 0 Running status (Running status); DI 100 Global alarm (Global alarm); HR 0 Flow rate for manual mode (Manual mode flow setpoint); CO 0 On/Off (On/off toggle); CO 5 Manual operation mode (Select manual mode).

How do I enable Modbus control of the LMI Excel XR series electronic metering pump (Modbus RTU)?

Modbus settings are on the pump display under Settings > Communication Settings: slave address 1-125, bit rate 9600/19200/38400/115200 or Auto, parity none/even/odd, 1 or 2 stop bits, internal line termination on/off.

Where is the official LMI Excel XR series electronic metering pump (Modbus RTU) Modbus documentation?

The source is Excel XR Series Electronic Metering Pump Modbus RTU Manual (55312 Rev 04), revision 2020-03. LMI doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.pumpworld.com/assets/lmi-excel-xr-chemical-pump-modbus-manual.pdf. It may be an older revision, so check it against the live unit.

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Excel XR Series Electronic Metering Pump Modbus RTU Manual · 55312 Rev 04 · rev. 2020-03 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.